COOPER POWER SERIES. Edison Modular Fuse (EMF) Installation Instructions. Fusing Equipment MN132031EN

Similar documents
COOPER POWER SERIES. QD5 Quik-Drive tap-changer reversing neutral stationary contact asssembly kit A26 installation instructions

Effective June 2016 New Issue

Effective November 2016 Supersedes September 1998 (S )

COOPER POWER SERIES. Testing a motor capacitor on a voltage regulator procedure instructions. Voltage Regulators MN225064EN

COOPER POWER SERIES. Current-Limiting Type NXC (C-Rated) Fuse Installation Instructions. Fusing Equipment MN132014EN

COOPER POWER SERIES. 200 A loadbreak junction 15 and 25 kv class installation instructions. Loadbreak Connectors MN650015EN

COOPER POWER SERIES. 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions. Loadbreak/Deadbreak Connectors MN650016EN

COOPER POWER SERIES. S.T.A.R. Hot line voltage indicator installation instructions. Fault Indicators MN320011EN. Indicator boot.

COOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN

Effective March 2015 Supersedes S August 2012

COOPER POWER SERIES. High-voltage primary bushings installation instructions. OEM Equipment MN800008EN

COOPER POWER SERIES. ELSG Full-Range Current-Limiting Fuse Re-Fusing Instructions. Fusing Equipment MN132017EN

COOPER POWER SERIES. UltraSIL polymer-insulated D-73P disconnect switches installation instructions. Switches MN008004EN

COOPER POWER SERIES. S.T.A.R. type LVR faulted circuit indicator installation instructions. Fault Indicators MN320005EN

COOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing

COOPER POWER. SERIES CMU Medium voltage power fuse installation instructions. Fusing Equipment MN132032EN

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. KA1169R Closing Coil Transfer-Switch Accessory Operation. Reclosers MN280069EN

COOPER POWER SERIES. RTE EL-BAY-O-NET FUSE Re-Fusing Instructions. Fusing Equipment MN132024EN

COOPER POWER SERIES. 200 A Fused Loadbreak Elbow Connector Replacement Fuse Installation Instructions. Fusing Equipment MN132021EN

COOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. HX-CB loadbreak fuse cutout installation instructions. Fusing Equipment MN132011EN

COOPER POWER SERIES. KA662R tank-lifting windlass assembly and installation instructions. Recloser Mountings MN280071EN

High-voltage primary bushings installation instructions

Effective November 2016 Supersedes February 2012 (S )

COOPER POWER SERIES. Pad-mounted Switchgear MN285019EN. Effective March 2017 Supersedes February 2007 (S )

COOPER POWER SERIES. Dielectric grease application to recloser cable instructions. Reclosers MN280070EN

COOPER POWER SERIES. Expulsion fuse installation instructions. Capacitors MN230005EN. Effective November 2016 Supersedes November 2001 (S )

COOPER POWER SERIES. Types 4H single-phase and 6H three-phase vacuum interrupter conversion kits. Reclosers MN280014EN

COOPER POWER SERIES. Quick Connect Assembly (QCA) Retrofit Kit, General Electric Installation Instructions. Voltage Regulators MN225075EN

COOPER POWER SERIES. Mercury switch to microswitch retrofit kit KA349WE installation instructions. Reclosers MN280022EN

Type NR oil switch installation and operation instructions

COOPER POWER SERIES. KA146W5 single pole-mounting hanger; KA146W2 tank lifting windlass assembly and installation instructions. Reclosers MN280039EN

Effective May 2017 Supersedes December 2004 (S )

COOPER POWER SERIES. KA716L7001 adjustable control valve kit for Types L, E, 4E, V4E, and V4L reclosers installation and adjustment instructions

COOPER POWER SERIES. Electronic control battery testing, charging, and replacement instructions. Reclosers MN280074EN

Effective May 2017 Supersedes January 2003 (S )

COOPER POWER SERIES. 600 A 15/25 kv class BOL-T and separable splice connector assembly installation instructions

COOPER POWER SERIES. Surge arrester interchangeable fuse cutout combination installation instructions. Surge Arresters MN235004EN

S Voltage Regulators GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage. Standards

COOPER POWER SERIES. 600 A 15 kv and 25 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650004EN

COOPER POWER SERIES. 600 A 35 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650003EN

COOPER POWER SERIES. Fused loadbreak elbow connector installation instructions. Loadbreak Apparatus Connectors MN650014EN

S Voltage Regulators PRODUCT INFORMATION GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage.

S Voltage Regulators GENERAL. PRODUCT INFORMATION Introduction. Contents. Acceptance and Initial Inspection. Handling and Storage.

S Voltage Regulators PRODUCT INFORMATION GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage

S Fault Indicators. S.T.A.R. Type TPR Faulted Circuit Indicator Installation Instructions. Contents INSTALLATION PROCEDURES

COOPER POWER SERIES. Types D and DV recloser installation instructions. Reclosers MN280030EN

COOPER POWER SERIES. Manually-Operated M-Force Switch Installation and Operation Instructions. Switches and Disconnects MN008003EN

Figure 1. Kearney Type HX cutout.

This Kit Is for Use with Types RE, RVE, WE, WVE, VWE, VWVE27, and VWVE38 Reclosers.

Factory Authorized Mechanism Enhancement (FAME)

COOPER POWER SERIES. Metal-enclosed, pad-mounted capacitor banks installation instructions. Power Capacitors MN230009EN

COOPER POWER SERIES. Metal-enclosed capacitor banks installation instructions. Power Capacitors MN230010EN

GWI Rev. 1 October 2007 Supersedes Rev. 0 Dated February 2004

COOPER POWER SERIES. Instructions for oil-filled, single-phase overhead distribution transformers. Distribution Transformers MN201003EN

Removal/installation instructions for Series NRX (IZMX) drawout levering (racking) mechanism

Edison modular fuse, vault application products

Two-way cable interlock kit for Magnum fixed circuit breakers

CCP2-FLR1-21_ flange-rod operating mechanism

Two-way cable interlock kit for Magnum drawout circuit breakers

3-way multi-family drawout cable interlock kit - type 32 - RF

Instruction Booklet IB E. Contents

Installation and removal instructions for Series NRX RF fixed breaker three-way Type 32 cable interlock kit

Installation Instructions for Interlocking Trip Indicator with Remote Reset for Magnum Low Voltage Circuit Breakers

Installation Instructions For Motor Control Center (MCC) Units

Reprogramming guide. Power Defense ICCB. Instructional Leaflet IL EN WARNING WARNING. Instructions apply to:

COOPER POWER SERIES. Externally fused block banks installation instructions. Capacitors MN230004EN

Instructions for VCP-W Simple Electrical Ground & Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version

COOPER POWER SERIES. VFI tester operating instructions. Underground Distribution Switchgear MN285001EN

Effective October 2016 Supersedes January 2014 (S )

Installation Instructions for R-Frame G-Series (RG) 310+ Trip Unit

O & M Manual for the EATON Generator Ready Loadcenter

ELB ELB

Installation Instructions for KPS and KPH Circuit Breakers and Molded Case Switches

KFE10010-E. Reclosers. Contents. Type KFVE and KFVME (27kV) Bus Bar Kit KRK710-1 Installation Instructions. Cooper Power Systems

BC Brake Caliper. (i) MEX (55) QRO (442) MTY (81) DIST. AUTORIZADO

SIEMENS. XJ-L Busway Systems. Storage, Installation and Maintenance Instructions for... Piece No. 32-J Rev 3

S Voltage Regulators. Contents. QD3 Quik-Drive Voltage Regulator Tap-Changer Manual. Figure 1B. QD3 Tap-changer. Figure 1A. QD3 Tap-changer.

CM52 Network Protector with Arc Flash Reduction Module

600 A 15 and 25 kv class Cleer grounding elbow

COOPER POWER SERIES. Types VWE, VWVE27, VWVE38X, WE, WVE27, and WVE38X; threephase electronically controlled; installation and operation instructions

COOPER POWER SERIES. RVAC Fluid-insulated Vacuum Switchgear; Installation, Operation, and Maintenance Instructions. Switchgear MN285005EN

Installation Instructions LINK---C

600 A 28 kv class Cleer loadbreak connector system

Raychem CSJA Safety Instructions. Safety Instructions. Customer Service. Kit Contents. Installation Instructions

Vacuum Circuit Breaker (Vehicle)

COOPER POWER SERIES. Type MOST Fluid-Insulated Switchgear; Installation, Operation, and Maintenance Instructions

TVSS Installation for RLCM/CHGENLC, RLCU, and CHGEN ATSs

Linear Actuator. Installation Manual. warranty installation parts list. Linear Actuator Installation Manual Page 1

Installation Instructions

Installation and Operation

Full Length Bed Rail - Model G29

600 A 15 kv class Cleer loadbreak connector system

ELB ES. Product Installation Instructions

Magnum Breaker Remote Racking Device (MRR1000)

38 kv Type VCPW-HD Simple Electrical Ground & Test Device (SEG&TD) lower terminal instruction booklet

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod

Flush Mount AIN ALPHA Meters. General. Hardware Kit

Transcription:

Fusing Equipment MN132031EN Effective November 2016 Supersedes July 2008 (S240-92-1) COOPER POWER Edison Modular Fuse (EMF) Installation Instructions SERIES

DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information, recommendations, descriptions and safety notations in this document are based on Eaton Corporation s ( Eaton ) experience and judgment and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser. THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or other-wise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and descriptions contained herein. The information contained in this manual is subject to change without notice. ii

Contents DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY... II SAFETY FOR LIFE... IV SAFETY INFORMATION... IV Safety instructions...iv PRODUCT INFORMATION.... 1 Introduction...1 Read this manual first...1 Acceptance and initial inspection...1 Handling and storage...1 Product description...1 ASSEMBLY AND INSTALLATION.... 2 Channel bases...2 Clamps...2 Pocket brackets...6 Adjustable foot bracket option...8 Installation...8 EMF FUSE REPLACEMENT.... 12 WELL-ADAPTER REPLACEMENT.... 13 DIMENSIONAL DRAWINGS.... 14 iii

! SAFETY FOR LIFE Safety for life Eaton s Cooper Power series products meet or exceed all applicable industry standards relating to product safety. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Eaton employees involved in product design, manufacture, marketing and service. We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around high-voltage lines and equipment and support our Safety For Life mission.! SAFETY FOR LIFE Safety information The instructions in this manual are not intended as a substitute for proper training or adequate experience in the safe operation of the equipment described. Only competent technicians, who are familiar with this equipment should install, operate, and service it. A competent technician has these qualifications: Is thoroughly familiar with these instructions. Is trained in industry-accepted high- and low-voltage safe operating practices and procedures. Is trained and authorized to energize, de-energize, clear, and ground power distribution equipment. Is trained in the care and use of protective equipment such as flash clothing, safety glasses, face shield, hard hat, rubber gloves, clampstick, hotstick, etc. Following is important safety information. For safe installation and operation of this equipment, be sure to read and understand all cautions and warnings. Hazard Statement Definitions This manual may contain four types of hazard statements: DANGER Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in equipment damage only. Safety instructions Following are general caution and warning statements that apply to this equipment. Additional statements, related to specific tasks and procedures, are located throughout the manual. DANGER Hazardous voltage. Contact with hazardous voltage will cause death or severe personal injury. Follow all locally approved safety procedures when working around high- and low-voltage lines and equipment. WARNING Before installing, operating, maintaining, or testing this equipment, carefully read and understand the contents of this manual. Improper operation, handling or maintenance can result in death, severe personal injury, and equipment damage. WARNING This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply may result in death, severe personal injury and equipment damage. WARNING Power distribution and transmission equipment must be properly selected for the intended application. It must be installed and serviced by competent personnel who have been trained and understand proper safety procedures. These instructions are written for such personnel and are not a substitute for adequate training and experience in safety procedures. Failure to properly select, install or maintain power distribution and transmission equipment can result in death, severe personal injury, and equipment damage. iv

Figure 1. Typical horizontal vault installation, shown with Quick-Release Mounting Clamps, Top-Hat Channel Base, and Rotatable Stand-Off Pockets Product information Introduction Service Information MN132031EN provides instructions for installing and removing the Edison Modular Fuse (EMF). Read this manual first Read and understand the contents of this manual and follow all locally approved procedures and safety practices before installing or operating this equipment. Additional Information These instructions cannot cover all details or variations in the equipment, procedures, or process described nor provide directions for meeting every possible contingency during installation, operation, or maintenance. For additional information, contact your Eaton representative. Acceptance and initial inspection Each fuse is in good condition when accepted by the carrier for shipment. Upon receipt, inspect the shipping container for signs of damage. Unpack the kit and inspect it thoroughly for damage incurred during shipment. If damage is discovered, file a claim with the carrier immediately. Handling and storage Be careful during handling and storage of the fuse to minimize the possibility of damage. If the fuse is to be stored for any length of time prior to installation, provide a clean, dry storage area. Standards ISO 9001 Certified Quality Management System Product description Eaton s Cooper Power series Edison Modular Fuse (EMF) is a completely sealed, full-range, current-limiting fuse designed for dead-front, overhead, underground, or submersible cable distributions systems. Terminal connections consist of a 200 A bushing well, designed to IEEE 386-2006 standard, permitting the use of 200 A dead-break and load-break bushing inserts and elbows. Stainless steel base assemblies with optional parking stand and pocket can be used to mount the fuse easily with minimal support structure. Base assemblies can be mounted to vault walls or welded to an existing bracket system. All mounting assembly material and hardware are made of stainless steel. There are two base types: Standard Channel Base and Top-Hat Channel Base. There are also two different types of mounting clamps: the Quick-Release and the Bolted Mounting Clamp. If the fuse is securely mounted in the Quick-Release clamp, the fuse can be installed/removed by simply unfastening the mounting buckles. All mounting assemblies are equipped with a grounding nut. Table 1. Parts Description Kit Item # Part Quantity Channel Base Standard Channel Base 1 channel base 1 EMFBRKCB Top-Hat Channel Base 2 top-hat base 1 EMFBRKHB Clamps Quick-Release Channel Mounting Clamp EMFBRKQR 3 base bracket 2 4 clamp straps 2 5 3/8-16 x 1 cap screw 4 6 3/8 lock washer 4 7 cotter pin 2 Bolted Channel Mounting Clamp EMFBRKBC 8 base bracket 2 9 3/8-16 X 1 cap screw 6 10 3/8 lock washer 4 11 clamp bracket 2 12 3/8-16 lock nut 2 Pockets Rotatable Stand-Off Pocket EMFBRKS1 1

Table 1. Parts Description (continued) Kit Item # Part Quantity Note: For use with tophat 13 pocket 2 channel base only. 14 5/16-18 X 1/2 cap screw 2 15 detent 2 Extended Stand-Off Channel Bracket with Pocket EMFBRKS3 16 stand-off bracket 2 17 5/16-18 X 3/4 hex bolt 8 18 5/16 lock washer 8 19 pocket 2 20 5/16-18 X 1/2 cap screw 2 21 detent 2 Foot Brackets Note: For use with standard channel base only. Adjustable Foot Bracket 22 adjustable bracket 2 EMFBRKF1 23 5/16-18 X 5/8 hex bolt 8 24 5/16 lock washer 8 25 5/16 nut 4 26 foot bracket 2 Clamps Using the standard channel base (Item 1) or the top-hat channel base (Item 2), attach the clamps to the base. The options include the Quick-Release clamp and the bolted clamp. Quick-Release clamp option The Quick-Release Clamp is shipped with a cotter pin for securing the clamp. This is a small part. Locate the cotter pin in the shipping bag and retain for later use. 1. Site the base brackets (Item 3) to the base (Item 1 or 2) for placement. See Figures 4 and 5. 2. Attach the base bracket (Item 3) to the base (Item 1 or 2) with a hex-head wrench using 3/8-16 X 1 cap screws and 3/8 lock washers (Items 5 and 6). See Figure 6. Assembly and installation! WARNING High Voltage. All associated apparatus must be de-energized prior to any hands-on installation or maintenance of this equipment. Failure to do so could result in contact with high voltage, which will cause death or severe personal injury. Refer to Table 1 for parts description. Channel bases The standard channel base (CB) and the top-hat channel base (HB) are compatible with the quick-release clamp (QR), the bolted clamp (BC), and the extended stand-off channel bracket with pocket (S3). The rotatable stand-off pocket (S1) is used with the top-hat base only. The foot bracket (F1) is for use with the standard channel base only. The top-hat channel base is mounted without a foot bracket. Identify the channel base type. Refer to Figures 2 and 3. Figure 4. Base bracket placement on standard channel base Base bracket (item 3) Figure 2. Standard channel base (Item 1) Figure 3. Top-hat channel base (Item 2) Figure 5. Base bracket placement on top-hat channel base 2

Base Base bracket 5. Feed the serrated section of the clamp strap through the slots in the base bracket. Begin feeding the strap in the slot by the solid side of the bracket. The strap exits on the side of the bracket with the extra slot. See Figures 8 and 9. Lock washer (Item 6) Cap screw (item 5) Figure 6. Installing base bracket (top-hat channel base shown) Figure 9. Clamp strap in base bracket Drive screw Figure 7. Clamp straps Shipping tie 3. Remove the plastic shipping tie from the clamp straps (Item 4). See Figure 7. 4. Separate the clamp strap sections by unscrewing the drive screw until the sections release. See Figures 7 and 8. Serrated strap section Figure 10. Connecting straps at drive screw 6. Reconnect the clamp straps at the drive-screw: Thread serrated strap into the smooth strap at the drive screw; Tighten the drive screw just until engaged. The drive screw is tightened in a later step. See Figure 10. 7. Repeat assembly for the second set of base bracket and clamp straps. See Figure 11. Figure 8. Clamp strap sections Figure 11. Quick release brackets on base 3

Channel slot Cotter pin (item 7) Figure 14. Closed quick-release clamp Figure 12. Clamping fuse If either of the pocket options is used, assemble the pocket onto the base before installing the fuse. Refer to the Pocket Brackets section of this manual. Bolted clamp option 1. Site the base brackets (Item 8) to the base (Item 1 or 2) for placement. See Figures 15 and 16. 8. Place the EMF fuse on the base brackets. Align the clamp straps with the channel slots around the smallest diameter sections of the fuse. See Figures 12 and 13. The channel base and clamps assembly can be mounted in the installation before securing the fuse into the assembly. 9. Engage the clamp straps into the buckles and close the buckles. See Figure 12. 10. Tighten the drive screws on each clamp to conform the clamp around the fuse. See Figure 13. 11. Insert the cotter pins (Item 7) through the buckles and spread the ends to secure in place. See Figure 14. Base bracket (Item 8) Figure 15. Base bracket placement on standard channel base Base bracket (Item 8) Figure 13. Tighten clamp Figure 16. Base bracket placement on top-hat channel base 4

Lock washer Item #10 Cap screw Item #9 Figure 19. EMS fuse in bolted channel mounting clamp Figure 17. Bolted clamp base bracket 2. Attach the base bracket (Item 8) to the base (Item 1 or 2) with a hex-head wrench using 3/8-16 X 1 cap screws and 3/8 lock washers (Items 9 and 10). See Figure 17. 3. Insert the removable clamp strap into the outer slot of the base bracket. See Figure 18. 4. Repeat assembly for the second set of base bracket and clamp straps. If either of the pocket options is used, assemble the pocket onto the base before installing the fuse. Refer to the Pocket Brackets section of this manual. 5. Place the EMF fuse to rest on the base brackets. Align the clamp straps with the channel slots around the smallest diameter sections of the fuse. See Figure 19. The channel base and clamps assembly can be mounted in the installation before securing the fuse into the assembly. 6. Bolt the clamp straps using 3/8-16 X 1 cap screw and 3/8-16 lock nut (Items 9 and 12). See Figures 20 and 21. Lock nut Item #12 Cap screw Item #9 Figure 20. Bolted clamp straps Figure 18. Bolted clamp Figure 21. EMF fuse in bolted mounting on channel base 5

Pocket brackets Rotatable Stand-Off Pocket Option 1. Insert a detent (Item 15) into small hole at each end of the channel base. Refer to Figure 22. 2. Attach pocket (Item 13) to the base at the centered boss nut using 5/16-18 X 1/2 cap screw (Item 14). Refer to Figures 22 and 23. Finger tighten only. Tighten screw during installation after preferred positioning is determined. Cap screw Item #14 Detent Item #15 Pocket Item #13 Boss nut Figure 23. Stand-off pocket Extended stand-off channel bracket with pocket option Figure 22. Pocket mounting location Extended standoff bracket Item #16 Hex bolt Item #17 Lock washer Item #18 Figure 24. Boss nuts for mounting stand-off bracket 6

1. Attach the extended stand-off bracket (Item 16) to the channel base at the four squared boss nuts using 5/16-18 X 3/4 hex bolt and 5/16 lock washer (Items 17 and 18). Refer to Figures 24 and 25. 2. Insert a detent (Item 21) into small hole at each end of the stand-off bracket. Refer to Figure 25. 3. Attach pocket (Item 19) to the stand-off bracket at the centered boss nut using 5/16-18 X 1/2 cap screw (Item 20). Refer to Figures 25 and 26. Finger tighten only. Tighten screw during installation after preferred positioning is determined. When installing the fuse, proceed carefully. The fuse will fit snugly between the stand-off brackets. Boss nut Detent location Figure 25. Pocket mounting location Cap screw Item #20 Pocket Item #19 Figure 26. Top-hat base assembled with extended stand-off channel bracket with pocket and bolted clamps 7

Adjustable foot bracket option The adjustable foot allows the base to be mounted at different angles to the mounting structure. The adjustable foot bracket is used with the standard channel base only. 1. Assemble the adjustable bracket (Item 22) to the foot bracket (Item 26) using 5/16-18 X 5/8 hex-head bolts, 5/16 lock washers, and 5/16 nut (Items 23, 24, and 25). Refer to Figure 27. Foot bracket Item #26 Hex bolt Item #23 Lock washer Item #24 Adjustable bracket Item #22 Nut Item #25 2. Attach the adjustable bracket (Item 22) to the standard channel base (Item 1) using 5/16-18 X 5/8 hex-head bolts, 5/16 lock washers, and 5/16 nut (Items 23, 24, and 25). Attach the bracket to the side of the base at the center hole and either the left or the right hole on the base. On the adjustable bracket, any of the holes along the perimeter can be used for positioning the foot.) Refer to Figure 28. Installation Figures 29 through 34 show typical installations of the EMF fuse. Figure 29 displays a typical horizontal installation; Figure 30 shows a typical vertical installation. Mount as typical installations or as specified by the utility. 1. Attach the mounting assembly to the wall or other support structure. A. For the standard base, mount the assembly using the holes on the foot bracket, making sure necessary clearances are maintained. The bracket has provisions for 5/16 mounting hardware. Mounting hardware is not supplied with the mounting assembly. B. For the top-hat base, mount the assembly using the mounting holes along the edge of the base, making sure necessary clearances are maintained. The mounting assembly has provisions for 1/2 mounting hardware. Mounting hardware is not supplied with the mounting assembly. Figure 27. Assembled adjustable foot bracket Channel base Item #1 2. Install the 200 A dead-break or load-break inserts and elbows as specified by the manufacturer. 3. The extended stand-off channel bracket can be rotated by 90 increments to fit specified configuration: Loosen the four mounting bolts that attach the bracket to the channel base; reposition the bracket; and tighten the mounting bolts. 4. The standoff pockets can also be rotated to fit the specified configuration: Loosen the mounting screw; rotate the pocket to the desired angle; and tighten the screw. The mounting assembly can be grounded to the grounding nut or as specified by the utility. Adjustable bracket Item #22 Figure 28. Adjustable foot bracket on standard channel base 8

Grounding nut Figure 29. Typical top-hat channel mounting Figure 30. Typical mounting with EMF fuse 9

18.00-24.00 (457.2-609.6) 18.00-24.00 (457.2-609.6) Figure 31. Typical horizontal vault installation (using Standard Channel base) Grounding nut located on all EMF fuse mounting assemblies. 18.00-24.00 (457.2-609.6) 18.00-24.00 (457.2-609.6) Figure 32. Typical vertical vault installation (using Standard Channel base) Grounding nut located on all EMF fuse mounting brackets 10

18.00-24.00 (457.2-609.6) 18.00-24.00 (457.2-609.6) Figure 33. Typical horizontal vault installation (using Top-Hat Channel base) Grounding nut located on all EMF fuse mounting assemblies. 18.00-24.00 (457.2-609.6) 18.00-24.00 (457.2-609.6) Figure 34. Typical vertical vault installation (using Top-Hat Channel base) Grounding nut located on all EMF fuse mounting assemblies. 11

EMF Fuse replacement! WARNING High Voltage. All associated apparatus must be de-energized prior to any hands-on installation or maintenance of this equipment. Failure to do so could result in contact with high voltage, which will cause death or severe personal injury. When the Edison Modular Fuse operates, it can be replaced without removing the entire mounting assembly. Follow the appropriate steps when removing the fuse and re-fusing. 1. De-energize the system using the approved safety procedures. 2. Place the elbows in the pockets using the approved safety procedures. Figure 35. Closed quick-release clamp! CAUTION Personal Injury. The fuse is not secure when the clamps are released. Support the fuse during the replacement procedure. Failure to do so may result in personal injury. 3. Remove the old fuse. Bolt For the quick-release clamps, remove the cotter pin, release buckle, and remove the fuse. Refer to Figure 35. For the bolted clamps, loosen and remove the bolt and remove the fuse. Refer to Figure 36. 4. Replace with a new EMF fuse and secure per the installation instructions. Figure 36. Bolted clamp straps 12

Well-adapter replacement The EMF fuse has a thread adapter in each well for system connection. The EMF fuse adapter is available for replacement. The adapter is removed and installed using an EMF fuse socket attached to a standard 5/16 hex wrench.! WARNING High Voltage. All associated apparatus must be de-energized prior to any hands-on installation or maintenance of this equipment. Failure to do so could result in contact with high voltage, which will cause death or severe personal injury. 1. De-energize the system using the approved safety procedures. 2. Disconnect both sides of the fuse. Holes for locator pins Locator Pins Figure 38. Well adapter in fuse Wrench Adapter Figure 37. Socket and locator pins 3. Attach the socket to the wrench and align the locator pins toward the fuse. Refer to Figure 37. 4. Engage the adapter with the socket; gently rotate the socket as needed to engage the locator pins. Refer to Figure 38. 5. Turn the socket counter-clockwise to remove the well adapter. Refer to Figure 39. Figure 39. Turning well adapter with socket on wrench Threads 6. Attach the new well adapter to the socket. The 3/8-16 system side attaches to the socket. The 5/8-11 side screws into the fuse. 7. Using the socket, screw the well adapter into the fuse; torque to 20 N m (15 ft lbs). Refer to Figure 40. 8. Unscrew the socket from the adapter. Figure 40. Fuse with well adapter removed 13

Dimensional drawings 30.97 (786.61 mm) 27.77 (705.33 mm) 19.77 (502.16 mm) 5.40 (137.16 mm) 10.56 (268.30 mm) 6.83 (173.56 mm) 20.95 (532.20 mm) A Min. A Max. B Max. B Min. C Min. C Max. 34.63 (879.60 mm) Option A min. A max. B min. B max. C min. C max. Mounting options Length in. 22.77 25.91 25.97 29.61 29.67 33.10 Length mm 565.73 658.18 659.64 752.09 753.62 846.07 2.56 (65.02 mm) 3.18 (80.87 mm) 6.27 (159.38 mm) Figure 41. Standard channel base CB, clamp BC, pocket brackets S3, and foot F1 14

31.00 (787.4 mm) 27.00 (685.8 mm) 1.00 (25.4 mm) 8.00 (203.2 mm) 18.00 (457.2 mm) 6.80 (172.72 mm) 8.75 (222.25 mm) 19.77 (502.16 mm) 27.77 (705.33 mm) 9.06 (230.00 mm) 5.33 (135.26 mm) Figure 42. Top-hat channel base HB 15

! SAFETY FOR LIFE Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton s Power Systems Division 2300 Badger Drive Waukesha, WI 53188 United States Eaton.com/cooperpowerseries 2016 Eaton All Rights Reserved Printed in USA Publication No. MN132031EN / Rev. 00 November 2016 Eaton is a registered trademark. All trademarks are property of their respective owners. For Eaton's Cooper Power series product information call 1-877-277-4636 or visit: www.eaton.com/cooperpowerseries.