TABLE I 60 CYCLE BURDEN OF THE CVD RELAY AT CONTINUOUS RATING

Similar documents
P. Sub 4 184A404. Sub 3 876A220

Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) E

41-747G. Figure 1: Type DGF Relay without case (Photo)

2.0 CONSTRUCTION AND OPERATION 3.0 CHARACTERISTICS K. CO (HI-LO) Overcurrent Relay

Type CRN-1 Reverse Power Relay 50 and 60 Hertz

A - Add New Information C - Change Existing Information D - Delete Information. Page 7. Delete the fourth paragraph beginning CAUTION

L. Photo. Figure 2: Types CA-16 Relay (rear view) Photo. Figure 1: Types CA-16 Relay (front view)

3.0 CHARACTERISTICS E Type CO-4 Step-Time Overcurrent Relay

C. Figure 1. CA-16 Front View Figure 2. CA-16 Rear View

B CW POWER RELAY

4.0 OPERATION Type ITH-T Relay

TYPE KF UNDER-FREQUENCY RELAY A. Figure 1: Type KF Relay for 60 Hertz without Case. (Front & Rear View.) Front View Rear View

COM Overcurrent Relay

3. OPERATION 2.1. RESTRAINT CIRCUIT 2.6. INDICATING CIRCUIT 2.2. OPERATING CIRCUIT 2.7. SURGE PROTECTION CIRCUIT 2.3.

ABB ! CAUTION. Type KRV Directional Overcurrent Relay E 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION. Instruction Leaflet

ABB. Type CRQ Directional Negative Sequence Relay for Ground Protection B 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION CAUTION

ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065

ABB Power T&D Company Inc. Relay Division Coral Springs, FL Allentown, PA. Non-Directional, Single Phase Adjustable Time Delay Device No.

2.0 CONSTRUCTION 3.0 OPERATION. SA-1 Generator Differential Relay - Class 1E 2.5 TRIP CIRCUIT

ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA

INSTRUCTIONS. seconds. the tween the end of the bearing screw and the. top of the shaft. The moving contact is a small silver hemisphere

Type SOQ Negative Sequence Time Overcurrent Relay

www. ElectricalPartManuals. com INSTRUCTIONS TYPE CO CONTACT MAKING AMMETER INSTALLATION OPERATION MAINTENANCE I.. L APPLICATION

www. ElectricalPartManuals. com Type CO Overcurrent Relays E ABB Power T&D Company Inc. Relay Division Coral Springs, FL Allentown, PA

Inverse-Time Overcurrent & E/F Relays. Type ICM 21, ICM 21B. Station Automation & Protection. ABB Substation Automation Products

HGA. Hinged Armature Auxiliary. Hinged armature auxiliary relay to perform auxiliary functions in AC and DC circuits.

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

www. ElectricalPartManuals. com INSTRUCTIONS Westinghouse 1. L F TYPE CVQ RELAY OPERATION MAINTENANCE INSTALLATION APPLICATION

www. ElectricalPartManuals. com INSTRUCTIONS TYPE CT TEMPERATURE-OVERLOAD RELAY INSTALLATION OPERATION MAINTENANCE I.L

Type CDG 14 Extremely Inverse Time Overcurrent and Earth Fault Relay

INSTRUCTIONS. GEI-38974A Supersedes GEI INSTANTANEOUS CURRENT RELAY TYPE PJC2OA GENERALS ELECTRIC

Inverse-Time Overcurrent & E/F Relays. Type ICM 21, ICM 21B

INSTRUCTIONS SYNCHRONISM-CHECK RELAYS. GE Meter and Control. 205 Great Valley Parkway Malvern, PA Types IJS51A.

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

www. ElectricalPartManuals. com INSTRUCTIONS TYPE HQS PHASE SELECTOR RELAY FOR INSTALLATION OPERATION MAINTENANCE APPLICATION

ELECTRICAL MAINTENANCE

www. ElectricalPartManuals. com INSTRUCTIONS "INERTEEN AND OIL INSULATED FEEDER SWITCHES DESCRIPTION INSTALLATION MAINTENANCE

INSTRUCTIONS. GE Protection and Control. 205 Great Valley Parkway Malvern, PA UNDERVOL TAGE RELAYS TYPES: IAV54E IAV55C IAV54F IAV55F

Stir-Guard Operation. Instructions Design III Stir-Guard Option

POWER METER. my2010 (c)

SURE-TRIP OEM RELACEMENT TRIP UNIT

Lincolnweld AC-1000 POWER SOURCE

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

Century Style Analog Panel Meters

GEK41931B INSTRUCTIONS MULTI-CONTACT AUXILIARY RELAYS TYPE HFA73K. GE Protection and Control 205 Great Valley Parkway Malvern, PA

CHEC"'- INSTRUCTION UNION SWITCH & SIGNAL.. SWISSVALE, PA. DIVISION OF WESTINGHOUSE AIR BRAKE COMPANY

Instructions for A200, A210, A250 size 6, two- or three-pole non-reversing or reversing motor controllers

SURE TRIP RETRO KITS

RELAYS HAVING NO KS DESIGNATIONS WARD LEONARD COMPANY, ALLEN-BRADLEY COMPANY AND WESTINGHOUSE CORPORATION REQUIREMENTS AND ADJUSTING PROCEDURES

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES UNIT OBJECTIVES 3/21/2012

www. ElectricalPartManuals. com INS T R U c.t I 0 N S Westinghouse OPER.ATION MAINTENANCE INSTALLATION SWITCHBOARD INSTRUMENTS SIX-INCH CLASSIFICATION

CONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS

Type IMC Indoor current transformer

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector

A. Submit manufacturer's literature and technical data before starting work.

THERMAL OVER CURRENT RELAY

Protectors. Manual motor. Types MS116, MS132, MS45x, MS49x. MS Series. Manual motor protectors. Type MS116. Type MS132. Type MS45x.

Voltmeter. for Experiments with the fischertechnik Expansion Kit. Order No

SECTION MOTOR CONTROL

Instructions for Replacing

File E14900 Project 98NK January 11, 1999 REPORT MOTOR CONTROLLERS MAGNETIC. Siemens Energy & Automation Inc. Batavia, IL

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

Utilization of Electric Power Laboratory 3 rd Year G2: Testing & Characteristic of MCCB Used in Commercial and Industrial Applications

ELECTRO LIFT, INC. 204 SARGEANT AVENUE, P.O. BOX 827, CLIFTON NJ TELEPHONE FAX NUMBER

GEK 45484B INSTRUCTIONS MULTI-CONTACT AUXILIARY RELAY HFA151 TYPE. GE Protection and Control 205 Great Valley Parkway Malvern, PA

INSTRUCTIONS GEK G HIGH-SPEED DIFFERENTIAL RELAYS TYPES CFD22A AND CFD22B. GE Protection and Control

INSTRUCTIONS HAA 15A / 15B / 15C / 15D / 15E / 15F / 15G / 15H AUXILIARY CURRENT RELAYS

DIVISION 26 ELECTRICAL SECTION CIRCUIT BREAKERS

www. ElectricalPartManuals. com INSTRUCTIONS TYPE SX TOGGLE RELAY Westinghouse I.L C INSTALLATION OPERATION MAINTENANCE APPLICATION

INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR THREE PHASE INDUCTION MOTORS. Frames 143T - 449T

Product Specifications for Phase Over Phase GOABS(r)

201 S. Anaheim Blvd. Page No Anaheim, CA RULE NO. 2 DESCRIPTION OF SERVICE

AC Relays. Type IC5182. Ordering Information. Control Power Requirements. Contact Ratings (Amperes)

EKT112 Principles of Measurement and Instrumentation. Power Measurement

www. ElectricalPartManuals. com INSTRUCTIONS TYPE KLF LOSS-OF-FIELD RELAY Westinghouse I.L B INSTALLATION OPERATION MAINTENANCE

www. ElectricalPartManuals. com lncoming-6900 through 69,000 volts Outgoing-2400 through 13,800 volts Ratings:

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

Design Standard. Purpose: Design Standard:

contactor may be required to interrupt up to 200% current. The N.O. contacts are equipped with permanent magnet blowouts to meet this requirement.

Westingh'ouse Steam Turbines-I. B (Rev. 3) GOVERNOR, GOVERNING VALVE

Components for EEx e Panels

Motor Protection. Presented By. Scott Peele PE

AUTOTRANSFORMER-TYPE STARTERS ALLEN-BRADLEY COMPANY REPLACEMENT PARTS AND PROCEDURES

Q-04: Replace Brake Shoes/Adjust Brakes

PERFORMANCE LOAD HP AMPERES RPM % % SPEED TORQUE RPM TORQUE TORQUE AMPERES % FULL LOAD LB-FT

A. Provide variable frequency drives to operate variable torque loads as shown on the Drawings and as specified herein.

Renewable Energy Systems 14

ADDITIONAL INFORMATION. BE1-50/51B SELF POWERED TIME OVERCURRENT RELAY and RETROFIT KITS. FEATURES and APPLICATION Page 2

SPECIFICATIONS ULTIMAX SUB-SURFACE DIRECTIONAL AERATION SYSTEM

Multiquip Submersible Pump Model ST-3050D

Module 2 CONTROL SYSTEM COMPONENTS. Lecture - 4 RELAYS

Programmable Logic Controller. Mat Nor Mohamad

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

GEF Renewal Pans. low Vohage Power Circuit Breakers. Type AKR-30S and AKRU-30S. www. ElectricalPartManuals. com

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

SIEMENS Transmission and Distribution

Trouble Shooting Guide EWA, 3-phase (D2422)

UNION SERVICE SPECIFICATION NUMBER SU A

SafeGear TM Motor Control Center Arc resistant metal-clad construction Motor Control Center Descriptive bulletin

Transcription:

the voltage unit contacts, this effect is negligible. 3.2 Trip Circuit The main contacts will close 30 amperes at 250 volts dc and the seal-in contacts of the indicating contactor switch (ICS) will carry this current long enough to trip a circuit breaker. The indicating contactor switch (ICS) has two taps that provide a pickup setting of 0.2 or 2 amperes. To change taps requires connecting the lead located in front of the desired setting by means of a screw connection. 4.0 ENERGY REQUIREMENTS See Table I. 5.0 SETTINGS 5.1 Voltage Unit These are independent relay adjustments. These are the high voltage and low voltage contact settings as described under Section 3, Characteristics. 5.2 Indicating Contactor Switch (ICS) No setting is required on the ICS unit except the selection of the 0.2 or 2.0 ampere tap setting. This selection is made by connecting the lead located in front of the tap block to the desired setting by means of the connecting screw. 6.0 INSTALLATION The relays should be mounted on switchboard panels or their equivalent in a location free from dirt, moisture, excessive vibration, and heat. Mount the relay vertically by means of the four mounting holes on the flange for semi-flush mounting or by means of the rear mounting stud or studs for projection mounting. Either a mounting stud or the mounting screws may be utilized for grounding the relay. The electrical connections may be made directly to the terminals by means of screws for steel panel mounting or to the terminal studs furnished with the relay for thick panel counting. The terminal studs may be easily removed or inserted by locking two nuts on the stud and then turning the proper nut with a wrench. For detailed FT Case Information refer to I.L. 41-076. 7.0 ADJUSTMENTS AND MAINTENANCE 7.1 Acceptance Check a. Contacts Set the left-hand adjustable contact in the center of the scale and adjust the voltage until the moving contact just makes. Set the left-hand contact back out of the way and bring the right-hand contact up until the contacts just make. The pointer should be within 1/32 inch of where the left-hand pointer was. b. Calibration Check Check the scale markings by setting either of the two contacts at a value marked on the scale, then alternately apply this voltage ±5%. Contacts should make and break respectively. TABLE I 60 CYCLE BURDEN OF THE CVD RELAY AT CONTINUOUS RATING Continuous Power Factor Range Rating Burden Angle Watts 15-60 65 volts 7.85 VA 70 2.68 30-120 132 volts 7.85 VA 70 2.68 40-160 176 volts 7.85 VA 70 2.68 80-320 352 volts 7.85 VA 70 2.68 105-135 148 volts 16.5 VA 78 3.43 180-320 254 volts 16.5 VA 78 3.43 210-270 296 volts 16.5 VA 78 3.43 Degrees current lags voltage. 2

8.0 CALIBRATION 8.1 Voltage Unit a. Contacts Apply sufficient voltage to the relay to make the disc float in the center of its travel. Move both of the adjustable contacts until they just make with the moving contacts. If the contact pointers do not meet at the same point on the scale, adjust the follow on both stationary contacts. Approximately the same follow should be in each of the adjustable stationary contacts. b. Calibration Check The adjustment of the spring tension in calibrating the relay is most conveniently made with the damping magnet removed. Set either of the adjustable stationary contacts in the center of its travel and apply this voltage to the relay. Wind up the spiral spring by means of the spring adjuster until the stationary contact and moving contact just makes. Check the other scale markings by setting the adjustable contact on these markings and applying the corresponding voltage to the relay. The contacts should make within ±5% of scale markings. c. Time-Curve Adjust the permanent magnet keeper to calibrate for the operate times (±5%) given in Table II. 8.2 Indicating Contactor Switch (ICS) Close the main relay contacts and pass sufficient dc current through the trip circuit to close the contacts of the ICS. This value of current should not be greater than the particular ICS setting being used. The indicator target should drop freely. For proper contact adjustment, insert a.030 feeler gauge between the core pin and the armature. Hold the armature closed against the core pin and gauge and adjust the stationary contacts such that they just make with the moving contact. Both stationary contacts should make at approximately the same time. The contact follow will be approximately 1/64 to 3/ 64. 9.0 RENEWAL PARTS Repair work can be done most satisfactorily at the factory. However, interchangeable parts can be furnished to the customers who are equipped for doing repair work. When ordering parts, always give the complete nameplate data. TABLE II Relay Rating Under Voltage Over Voltage Test Voltage Operate Time (Volts) Contact Setting Contact Setting From To (Seconds) 15-60 15 34 0 68 1.9 30-120 40 120 65 0 1.5 (1.5 sec.) 30-120 66 80 66 120 2.0 (2.0 sec.) 40-160 40 91 0 182 1.9 80-320 80 182 0 364 1.19 105-135 117 123 120 130 7.5 180-230 234 246 240 260 7.5 240 220 210-270 200 210 205 222 7.5 205 188 Allow relay to heat for 30 minutes. 3

Sub 1 184A176 Figure 1. Type CVD Voltage Relay in Type FT-11 Case 4

Sub 1 184A793 Figure 2. Type CVD Voltage Relay with ICS Unit in Type FT-11 Case 5

Sub 1 188A409 Figure 3. Type CVD Voltage Relay with Two (2) ICS Units in Type FT-11 Case 6

ABB IL 41-201.3 - New Information ABB Inc. 4300 Coral Ridge Drive Coral Springs, Florida 33065 Telephone: +1 954-752-6700 Fax: +1 954-345-5329 www.abb.com/substation automation