Valves. Rapid opening and closing solenoid valves VMR (E1110 rev /11/2012)

Similar documents
Valves. Slow opening and rapid closing solenoid valves VM-L (E1111 rev /11/2012)

Orifice Flow Meters POP-S (E5720 rev /03/2013)

Burners. Pilot Heads BTC & BTSA (E3121 rev /04/2018)

Burners. Pilot Heads BTC & BTSA (E3121 rev /09/2010)

Burners. Ribbon linear flame burners AB & ABM (E3010 rev /11/2017)

Free flame burners EMB (E3004 rev /02/2015)

Burners. Metallic free flame burners. EMB (E3004 rev /02/2010)

Valves. Double stage and modulant motorized butterfly valves MRBV & MRBV-CMAP (E1302 rev /04/2011)

Burners. High velocity LOW NOx combustion air burners EMB-SIK-NxT (E3507 rev /11/2016)

Burners. Self-recuperative burners high speed with flat flame REKO-SIK-SW (E3903 rev /06/2015)

Radiant tube burners RT (E3900 rev /01/2018)

OIL REGULATORS RFG SERIES FEATURES APPLICATIONS DESCRIPTION INSTALLATION. Bulletin E5301 rev03 02/04/03. Body and valve seat: Shutter seat:

Electronics. Permanent operation microprocessor burner control device ESA GENIO-S (E7021 rev /05/2015)

Burners. Self-recuperative burners high speed free flame REKO-SIK-FF (E3901FF rev /05/2009)

VML. elektrogas.com. Safety solenoid valves for gas Slow opening and fast closing type DN10 DN80 EE

VMH. www. delta-elektrogas.com. Safety shut off valves for gas with hydraulic actuator DN65 DN200 EE

Electronics. Permanent operation microprocessor burner control device ESA GENIO-PRS (E7022 rev /05/2015)

VMH. delta-elektrogas.com. Safety shut off valves for gas with hydraulic actuator DN65 DN EE

PCS. Proof of closure switch for safety gas valves. delta-elektrogas.com EE

Electronics. Permanent Operation Microprocessor Burner Control ESA ESTRO-PO (E7014PO rev /05/2013)

Safety. Operating instructions Solenoid valve for gas VG 6 VG 15/10 DANGER. Contents WARNING CAUTION. Changes to edition 07.15

SOLENOID VALVES FOR REFRIGERATING SYSTEMS

VQ400M SERIES CLASS A COMBINATION VALVES PRODUCT HANDBOOK APPLICATION

Installation and Operating Instructions DDM-DS11 DDM-DS11-MS1 DDM-DS11-MS2

USE AND MAINTENANCE MANUAL

822 NOVAMIX GAS FLOW RATE ADJUSTMENT AS A FUNCTION OF THE AIR FLOW GAS/AIR RATIO 1:1 DOUBLE AUTOMATIC SOLENOID SHUT-OFF VALVE

RS/M SERIES. Modulating Gas Burners FIRING RATES

VE4000 & VE5000 SERIES

VQ400M SERIES CLASS A COMBINATION VALVES PRODUCT HANDBOOK APPLICATION

RS SERIES. Two Stage Progressive Gas Burners FIRING RATES

Solenoid System. The coil is also in conformity with 94/9/EC ATEX for electrical apparatus of group II, category 3 (Ex na II 3 GD T4 or T5).

Operating and Installation Instructions Diaphragm Gas Sampling Pumps

RS/1 SERIES. One Stage Gas Burners RS 34/1 MZ RS 44/1 MZ kw kw GAS

Safety. Operating instructions Solenoid valve VGP DANGER. Contents WARNING CAUTION. Changes to edition Elster GmbH Edition 10.

VF VFH. elektrogas.com. Butterfly valves DN40 DN150 EE155-11/11

Installation and Service Instructions for Self Adjust Brakes 81,000 Series

ELECTRIC ACTUATOR MOD. VB015 MAINTENANCE AND INSTALLATION INSTRUCTIONS OF VALBIA ELECTRIC ACTUATORS

US - UP2/OIL 12V US - UP2/OIL 24V

CIRCLE SEAL CONTROLS

Installation and Service Instructions for Self Adjust Brakes 82,000 Series

RS/E-EV MZ SERIES. Modulating Gas Burners FIRING RATES

INSTALLATION, OPERATION AND MAINTENANCE TECHNICAL MANUAL

B21 Series BASOTROL Gas Valve

USER s MANUAL 1. GENERAL INFORMATION 2. PRODUCT IDENTIFICATION

ONE STAGE GAS BURNERS RDBS SERIES

BAH series Use and Maintenance Manual

CO 3-WAY PNEUMATIC VALVE INSTRUCTION MANUAL 2080

Mounting and Operating Instructions EB 8222 EN. Type 3310/AT and Type 3310/3278 Pneumatic Control Valves. Type 3310 Segmented Ball Valve

WATERFLUX 3070 Quick Start

TECHNICAL CATALOGUE BALL VALVES: PARIS

SERIES 2000 GAS SAFETY SHUT OFF VALVE

SOLENOID VALVES FOR REFRIGERATING SYSTEMS

TECHNICAL CATALOGUE BLOCK CHECK AND FOOT VALVES

VALVES WITH SA03 ELECTRIC ACTUATOR

These installation and maintenance instructions must be read in full and completely understood before the installation!

Installation and Service Instructions for 87,000 Series Manual Adjust Brakes (rev. B)

VALVES WITH NA ELECTRIC ACTUATOR

Operating and Installation Instructions Diaphragm Vacuum Pumps and Compressors

TECHNICAL CATALOGUE EUROPA CHECK AND FOOT VALVES

VALVES WITH SA ELECTRIC ACTUATOR

ATTENTION: Industrial machinery for professional use. These instructions are for qualified personnel USE AND MAINTENANCE MANUAL

VE Series. Class "A" Gas Valves. Product handbook APPLICATION CONTENTS. General. Technical. Installation and operation. Various

BCV30 DN20 - Blowdown Control Valve Installation and Maintenance Instructions

Swing Piston Compressors and Vacuum Pumps

INSTALLATION INSTRUCTION & TECHNICAL MANUAL FLOWMETER

ILED Dorado. User Manual

Diaphragm Vacuum Pumps and Compressors

Honeywell VV, VP, VB & MS SERIES FOR VQ400M CLASS A VALVES PRODUCT HANDBOOK APPLICATION

Introduction. System Components

APT10-2 Automatic Pump Trap

USERS MA UAL Bellow sealed valve Fig.229, 230, 234, 235 Edition: 1/2008

Mounting and Operating Instructions EB 3913 EN. Electropneumatic Converters i/p Converter Type

VALVE WITH SA ELECTRIC ACTUATOR

Boiler room components 0459EN October 2013 Safety pressure switch with manual reset

Installation and Service Instructions for 87,000 & 87,100 Series Self-Adjust Brakes (rev. B)

Installation and operating manual Quick closing valve (Bellow sealed) LK product no:

Diaphragm Vacuum Pumps and Compressors

EC4 SERIES CRYOGENIC VALVES 1/4 2 Sizes

Installation, Operation, and Maintenance Manual

USE AND MAINTENANCE MANUAL

Installation, Operation, and Maintenance Manual Full Port Y-Pattern, Bolted Bonnet, Globe and Check Valves

NEOTECHA NTB-NTC BALL VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS

Automatic concealed bollards 275 H600 and 275 H800 with pit

Motorized Two-Way Ball Valve with Screwed-End Connection

TECHNICAL CATALOGUE BALL VALVES: IDEAL

E Series CE Approved Intermittent Pilot Ignition Control

UNA 13 UNA 15 UNA 15 Stainless Steel Design. Installation Instructions Steam Traps UNA 13, UNA 15

D4BL. Protective Doors Are Locked Until Machines Completely Stop Operating. Guard Lock Safety-door Switch. Model Number Structure.

INSTALLATION AND MAINTENANCE OF TOP LOADING ARM

USE AND MAINTENANCE MANUAL

Installation and operating manual

TECHNICAL CATALOGUE GAS BALL VALVES: BERLIN

Gas Pressure Governors

VARIFUEL MAINTENANCE AND REPAIR INSTRUCTIONS

OPTIFLUX 2000 Quick Start

VALVES WITH UM ELECTRIC ACTUATOR

VARIFUEL MAINTENANCE AND REPAIR INSTRUCTIONS

PNEUMATIC PUMP Series

Double motor belt grinding machine

Installation and Service Instructions for 87,000 & 87,100 Series Self-Adjust Brakes (rev. B)

Transcription:

Valves Rapid opening and closing solenoid valves VMR (E1110 rev. 03-19/11/2012)

GENERAL WARNINGS: DISPOSAL: ¾ All installation, maintenance, ignition and setting must be performed by qualified staff, respecting the norms present at the time and place of the installation. ¾ To avoid damage to people and things, it is essential to observe all the points indicated in this handbook. The reported indications do not exonerate the Client/User from observing general or specific laws concerning accidents and environmental safeguarding. ¾ The operator must wear proper DPI clothing (shoes, helmets...) and respect the general safety, prevention and precaution norms. ¾ To avoid the risks of burns or high voltage electrocution, the operator must avoid all contact with the burner and its control devices during the ignition phase and while it is running at high temperatures. ¾ All ordinary and extraordinary maintenance must be performed when the system is stopped. ¾ To assure correct and safe use of the combustion plant, it is of extreme importance that the contents of this document be brought to the attention of and be meticulously observed by all personnel in charge of controlling and working the devices. ¾ The functioning of a combustion plant can be dangerous and cause injuries to persons or damage to equipment. Every burner must be provided with certified combustion safety and supervision devices. To dispose of the product, abide by the local legislations regarding it. GENERAL NOTES: ¾ In accordance to the internal policy of constant quality improvement, ESA-PYRONICS reserves the right to modify the technical characteristics of the present document at any time and without warning. ¾ It is possible to download technical sheets which have been updated to the latest revision from the www.esapyronics.com website. ¾ The products manufactured by ESA-PYRONICS have been created in conformity to the UNI EN 746-2:2010 Norms: Equipment for industrial thermal process - Part 2: Safety requirements for combustion and the movement and treatment of combustible elements. This norm is in harmony with the Machine Directive 2006/42/CE. It is certified that the products in question respect all the requirements prescribed by the above mentioned Norms and Directives. ¾ Certified in conformity with the UNI EN ISO 9001 Norm by DNV GL. CERTIFICATIONS: ¾ The burner must be installed correctly to prevent any type of accidental/undesired heat transmission from the flame to the operator or the equipment. ¾ The performances indicated in this technical document regarding the range of products are a result of experimental tests carried out at ESA-PYRONICS. The tests have been performed using ignition systems, flame detectors and supervisors developed by ESA-PYRO- NICS. The respect of the above mentioned functioning conditions cannot be guaranteed if equipment, which is not present in the ESA-PYRONICS catalogue, is used. The valves comply with the UNI EN 161 Norm: Automatic isolating valves for gas burners and gas-user equipment, in Class A, group 2, certificate n. CE 0063AQ1350. CONTACTS / ASSISTANCE: Headquarters: Esa S.p.A. Via Enrico Fermi 40 24035 Curno (BG) - Italy Tel +39.035.6227411 Fax +39.035.6227499 esa@esacombustion.it The products conform to the requests for the Euroasia market (Russia, Belarus and Kazakhstan). www.esapyronics.com International Sales: Pyronics International s.a. Zoning Industriel, 4ème rue B-6040 Jumet - Belgium Tel +32.71.256970 Fax +32.71.256979 marketing@pyronics.be www.esapyronics.com 2

The VMR is an electromagnetic mono-stage valve. It opens and closes rapidly and is a normally closed valve complying with the UNI EN 161 Norm. APPLICATIONS ¾Gas interception on decompression units. ¾Air/gas interception for burners. ¾Special gases interception BIOGAS and COG. GENERAL: CHARACTERISTICS ¾Working pressure: 200/360 mbar ¾Fluid temperature: < 40 C ¾Adjustable capacity: 0-100 % ¾Voltage rating: 110/230 V 50/60 Hz ¾Voltage (on request): 24/12 VAC/DC ¾Tension tolerance: from -15% to +10% ¾Working temperature: from 15 C to +60 C ¾Opening time: < 1 second ¾Closing time: < 1 second ¾Coil direction: 360 ¾Protection: IP 54 (EN 60529) ¾Cable gland: M20 x 1,5 ¾Dust filter: incorporated ¾Limit switch: on request ¾Mounting: in any position except with coil facing downwards ¾Manufactured in accordance to the EN161 Norm (EC certificate n. 0063AQ1350) in class A group 2. F1110I03 MATERIAL COMPOSITION: ¾Valve body: ¾Seals: DESCRIPTION aluminum, copper, steel PTFE, NBR, FPM F1110I04 The VMR series solenoid valves are interception devices operating with auxiliary electrical energy suited for block maneuvers and gas or air supply in burners at atmospheric or blown air pressures, for furnaces and other applications that use gas as fuel. When the coil is not powered, the spring acts on the shutter, keeping the gas passage closed (intrinsic safety). In this condition, gas is present at line pressure in the inlet chamber and by pushing against the shutter it increases the sealing force. When the coil is powered, the valve opens rapidly, overcoming the force of the spring and gas pressure. The valve stroke (and thus the flow) can be regulated by the special regulation screw (see section regarding regulation). If power is cut off from the coil, the valve closes rapidly, interrupting the gas passage. F1110I05 www.esapyronics.com 3

FLOWCHART 10000 VMR95 DN150 VMR93 DN125 3000 2000 VMR9 DN100 1000 500 400 VMR8 DN80 VMR7 DN65 VMR6 Rp.2 VMR4 Rp. 1.1/2 300 Natural gas flow @ 20 C P.S.= 1 [Nm 3 /h] 200 100 50 40 30 20 10 9 7 8 6 5 4 3 VMR3 Rp.1 VMR2 Rp. 3/4 VMR1 Rp. 1/2 VMR0 Rp. 3/8 2 1 0.5 0.1 0.5 1 2 3 4 5 10 50 100 200 Pressure drop [mbar] G1110I01 www.esapyronics.com 4

WARNINGS ¾Make sure that the working pressure and fluid temperature are lower than the maximum values allowed. ¾Check correct installation of the valve before starting the flow in the pipes. ¾In case of valve malfunctioning, follow the indications in the present manual at the Maintenance chapter or contact ESA-PYRONICS assistance. ¾Any modification or repair done by third parties could compromise the application safety and cause the general warrantee conditions to automatically expire. Do not expose the valve to direct sunlight, heat sources or near combustion products, liquids, solvents or corrosive gases. INSTALLATION ¾Check that the line pressure is lower than the maximum working pressure allowed. ¾Check that the arrow on the valve body is pointing in the correct flow direction. ¾The valve may be installed in any position (coil can be horizontal or vertical), except with coil facing downwards. ¾Ensure that there are no foreign objects inside the valve before assembling. If necessary, blow with compressed air. ¾Check the correct alignment of the attachment pipes. Keep a certain distance from the walls allowing air to circulate freely. ¾Leave enough space above the solenoid valve to extract the coil in case of replacement. 02 01 02 THREADED MODELS: D1111I01 1 - Make sure that the threads conform to the valve that must be installed (pos. 01) according to the UNI ISO 7/1 Norm. 2 - Use thread-sealing paste on the male threads of the pipes (pos. 02) paying attention not to use too much as it could enter the valve and damage its seal. 3 - Screw the valve onto the pipe using an appropriate tool. Do not use the coil as a lever and only use the special seats on the body. 02 03 04 05 FLANGED MODELS: 1 - Weld the flanges (pos. 03) on the ends of the pipes, eliminating any welding burrs. 2 - Place the gaskets (pos. 02) between the flange (pos. 03) and the valve (pos. 01) and insert the bolts (pos. 04). 3 - Using appropriate tools, progressively tighten the bolts (pos. 04) crosswise. 4 - Avoid excessive tightening and mount without tension. 04 05 03 01 02 D1111I02 www.esapyronics.com 5

ELECTRIC WIRING D1110I03 Before making any electrical connection, ensure that the voltage and frequency of the solenoid valve correspond to the electrical supply available. 1 - Disconnect electrical supply and close the gas. 2 - Using a screwdriver unscrew the screws (pos. 04) of the protection cover (pos. 03) of the connection box. 3 - Unscrew the cablegrip (pos. 07) and remove the locking ring (pos. 09) and the cone shaped gasket (pos. 08). 4 - Insert the cable respectively into the cablegrip, inside the locking ring of the cable gland, therefore inside the appropriate hole in the cover. 5 - Connect power to the terminals (pos. 01) of the recti- fier circuit following the symbols indicated. In the case of valves powered at 12Vdc or 24Vdc, when the + terminals are used, do not invert polarity. 6 - Always make sure that the ground protection is connected to the related clamps (pos. 01). 7 - If the cable passage takes place through the hole that was originally closed, use the rubber pad under the cap to close the other hole if left open. 8 - Pull the wire and screw the cablegrip back on and then the cover, paying attention to position the gasket correctly (pos. 02). FLOW REGULATION The solenoid valves are supplied adjusted at maximum flow (regulation screw completely open). Regulation is carried out by the screw found under the coil fixing cap. Once the cap and grain are removed, regulation takes place using a 4mm allen wrench, each clockwise turn decreases the flow of about 25% on 1/2, il 6% on 2.1/2-3, il 15% on 1, il 12% on 1.1/2-1.1/4, il 10% on 2. Flow regulation is recommended on running burners. After regulating, screw the grain and cap back on. Regulation below 40% of the attachment pipe flow is not advised, as with line pressure variations this could created problems in the flow regime. D1110I04 www.esapyronics.com 6

ORDINARY MAINTENANCE For correct maintenance of the VMR solenoid valves, scrupulously abide by the following instructions. Before carrying out maneuvers with the plant on, make sure that the process and operator safety is not compromised. If necessary check with plant off. INTEGRITY CHECK SOLENOID VALVE MOVEMENT ¾Checking for the presence of valve movement obstructions takes place by completely opening the valve and visually checking that there is nothing obstructing or limiting its stroke. ¾The integrity of the gaskets and threads can be checked visually. If necessary, used liquid gas detector. GENERAL MAINTENANCE PLAN Maintenance and installation must be carried out by technically qualified staff respecting the Norms in force. After installation has take place it is advisable to test the tightness of the threads or flange connections. Operation Type (*) Advised time Notes Gasket integrity O annual Check that there are no leaks outside Thread integrity O annual Check that there are no leaks outside Maintenance of the solenoid valve S annual Check the valve conditions NOTES: Key: O = Ordinary / E = Extraordinary (*) it is suggested that the gaskets are replaced every time the valve is disassembled. www.esapyronics.com 7

EXTRAORDINARY MAINTENANCE For correct maintenance of the VMR solenoid valves scrupulously follow the instructions with plant off. COIL REPLACEMENT Before proceeding with any type of installation or service, close the upstream gas supply and disconnect the power supply. BOLT TIGHTENING ¾ Checking the bolt tightening must take place when the plant is off. GASKET REPLACEMENT 1 - Progressively unscrew the screws that fix the solenoid valve crosswise. Extract the solenoid valve and check the conditions of its internal components. 2 - Clean the inside of the valve body with a clean cloth and compressed air. Do not use tools that could damage the internal parts. 3 - Check that the valve moves without friction. 4 - Replace the gaskets and reassemble the valve in its seat, according to the steps indicated in the INSTALLA- TION section. 5 - Finally check that the valve moves freely without any obstructions. COIL REPLACEMENT Malfunctioning coils must be replaced. Disconnect electric supply, remove the junction box cover. Disconnect the cables from the clamps, unscrew the fixing cap and replace the coil reassembling the valve following the sequence backwards. INTERNAL CLEANING Dust and possible foreign objects can easily be removed from the filter or from the gas passage seat. 1 - Close the ball valve upstream of the plant. 2 - Remove the coil as described previously. 3 - Progressively unscrew the screws that fix the upper flange crosswise. During this operation some residual gas could leak out from the valve body. 4 - Check the condition of the o-ring gasket on the flange. If it is worn, see to its replacement. 5 - Clean the inside of the sleeve using a clean cloth and compressed air. 6 - Remove the return spring and blow it with compressed air. Pay attention to the mounting direction of the spring, that must be placed in the same way when reassembling. D1110I05 7 - Clean the complete shutter assembly with a clean cloth and compressed air. 8 - Check the sealing gasket conditions. If it is damaged, replace it. 9 - Clean the sealing disc valve seat with a clean cloth. Do not use tools that could damage it. 10 - Remove the filter and blow it with compressed air. 11 - Reassemble the valve following the sequence backwards. www.esapyronics.com 8

OVERALL DIMENSIONS - VMR C C A B A B Current Standard Available Threaded Flanged A B C drawn working working Mass Model attachments attachments [mm] [mm] [mm] @230VAC pressure pressure [Kg] [W] [mbar] [mbar] VMR0 G - 3/8-88 77 126 20/25 500 200 1,4 VMR1 G - 1/2-88 77 126 20/25 500 200 1,4 VMR2 G - 3/4 88 96 145 45 500 200 2,5 VMR3 G - 1-88 96 145 45 500 200 2,5 VMR4 G - 1.1/2-120 153 191 20/80 (*) 500 200 5,7 VMR6 G - 2-106 156 195 20/80 (*) 500 200 6 VMR7 - DN65 PN16 200 305 266 60/240 (*) 200 360 14 VMR8 - DN80 PN16 200 305 266 60/240 (*) 200 360 14 VMR9 - DN100 PN16 252 350 352 80/320 (*) 200 360 36 VMR93 - DN125 PN16 310 460 430 90/360 (*) 200 360 58 VMR95 - DN150 PN16 310 460 430 90/360 (*) 200 360 60 (*) working / opening www.esapyronics.com 9

ORDERING CODE - VMR VMR - 01 02-03 - 04 Model 01 02 Voltage 3/8 Rp. (DN10) 1/2 Rp. (DN15) 3/4 Rp. (DN20) 1 Rp. (DN25) 1.1/2 Rp. (DN40) 2 Rp. (DN50) DN65 DN80 DN100 DN125 DN150 0 1 2 3 4 6 7 8 9 93 95 03 04 24 VDC 24 VAC +10-15% 115 VAC +10-15% 230 VAC +10-15% Not installed Present Limit switch * Special applications 24DC (*) 24 (*) 115 230 / PCS No special BIOGAS CokeOvenGas COG / J K (*) on request www.esapyronics.com 10