A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system.

SPECIFICATION FOR THREE-PHASE PAD MOUNT TRANSFORMERS. D. Dead Front, loop feed design shall be employed.

C. System Design and Performance Requirements

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-115

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS

MATERIAL SPECIFICATION ELECTRIC OPERATIONS ORGANIZATION. M3902 ****Supercedes BECo Standard E and ComElectric Spec ****

GENERAL INFORMATION POLE MOUNT TRANSFORMER SINGLE PHASE PAD MOUNT TRANSFORMER SINGLE PHASE POLE MOUNT TRANSFORMER THREE PHASE 17

MATERIAL STANDARD ELECTRIC OPERATIONS ORGANIZATION. ****Supercedes BECo Standard E and ComElectric Spec ****

1500 kva Pad Mount Transformer GRDY/14400V Primary - 208Y/120 Wye Secondary - Oil Cooled

SERIES 802 / 812 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTERS AND FUSE ASSEMBLIES

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

DISTRIBUTION TRANSFORMERS SPECIFICATION #

Drive Duty Transformer Specification Virginia Transformer Corp. Power Up! Selecting the Right Transformer

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

Underground Distribution Switchgear

500 kva Pad Mount Transformer V Delta Primary - 208Y/120 Secondary - NEMA 4X - Oil Cooled

1TSF /CD Attachment B. City and County of San Francisco Office of Contract Administration

Distribution Transformers

Solid Dielectric Load Break Switch SPECIFICATION. 25kV, 630A, 4 WAYS, 4 WAYS SWITCHED PADMOUNTED VACUUM LOAD INTERRUPTER

Distribution Transformers

100 / 110 DRYWELL FUSE SPECIFICATION

SUBSTATION TYPE TRANSFORMER - MINERAL OIL FILLED THREE PHASE OISC 65 C RISE 60 HERTZ

Underground Distribution Switchgear

Single Phase Padmounted Transformers kva

Fixed, Medium-Voltage, Pad-Mounted, Three-Phase Power Capacitor Bank Guide Form Specification

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008

SPECIFICATION FOR THREE PHASE PAD-MOUNT DISTRIBUTION TRANSFORMERS

Unit Substation Transformers 5 and 15 KV Class

Operation & Maintenance Manual PAD-OM200. Single Phase & Three Phase Pad-mount Liquid Compartmental Transformer

H1 H2 H3 X0 X1 X2 X3

www. ElectricalPartManuals. com Substation Transformers Primary or Secondary Open

Padmount. Small Power Transformers 2500 kva Through 20,000 kva 5 kv Through 46 kv Primary Voltage 120V Through 25 kv Secondary Voltage

Automatic, Medium-Voltage, Pad-Mounted, Three-Phase Power Capacitor Bank Guide Form Specification

NEW Solutions for Underground System Growth

Medium Voltage Metal-Enclosed Switches

HPS EnduraCoil. Cast Resin Transformer

MIRUS International Inc. TYPICAL SPECIFICATION ULLTRA & ULLTRA-H1E 31 Sun Pac Blvd., Brampton, Ontario, Canada L6S 5P6

Guide Specification. Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break

Switchgear Skid, C1192

Power IT Liquid Filled Single Phase Padmounted Transformers kva

Figure 1. Two and Three-phase MagneX.

DISTRIBUTION TRANSFORMERS Single-Phase Pad-Mounted

INSTRUCTION MANUAL #103

Single-Phase, Liquid-Filled, Compartmental-Type, Pad-Mounted Transformers Class 7230

Three-Phase Ventilated

www. ElectricalPartManuals. com Substation Transformers Primary or Secondary Unit

TGK Prefabricated Substation Technical Data

"#$%&'(%)*#$ Installation, Operation, and Maintenance of Three-Phase Padmounted Distribution Transformers 45 kva through 10,000 kva

Three Phase Padmounted Transformers kva

Outdoor Power Transmission & Distribution

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

Technical Specification for Pole Mounted Capacitor Rack

Single-Phase Step Voltage Regulator

CONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS

TECHNICAL SPECIFICATIONS OIL FILLED PADMOUNTED THREE PHASE WYE-WYE TRANSFORMERS

Figure 1. Single-phase pad-mounted voltage regulator. STANDARD FEATURES

www. ElectricalPartManuals. com WeSTinghouse Secondary Unit Substation Transformers (Power Centers) Descriptive Bulletin Page 1

www. ElectricalPartManuals. com Westinghouse PLAZAPADTM Tamper-Resistant Transformers For Underground Power Distribution 750 Thru 2500 Kva

Medium Voltage Metal-Enclosed Switches

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents

Proudly Made In America

C1000 Series Automatic Cap Bank

Issued Revised Approved Reviewed October 31, 1984 October 22, 2002 J. Ross J. Fuller

Underground Distribution Switchgear

RPS Station. Solutions for the North American Solar Market

SECTION PANELBOARDS

Substation Transformers

ABB Transformadores para aplicaciones solares y eolicas

Specification Pad-Mounted Capacitor Bank with Dual Fusing Integral Load-Interrupter on Line-Side Fuse Mountings

University of Houston Master Construction Specifications Insert Project Name

A. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified.

Design Standard. Purpose: Design Standard:

Detail Bill of Material Page 1 of 1 Project Name: Amphi School - MVS Replacement Negotiation No: TU700213X7K2 General Order

Distribution transformers Efficiency over life-cycle

35-kV Safefront SuperWell Mini-Switch Source Isolated Pad-Mounted Switchgear 50 Amp (Max) Clip-Mounted Current Limiting Fuses

9. Non-Residential Services (Commercial, Industrial, and Agricultural)

10 Commercial, Industrial, Agricultural Services

ABB Ltd. FACTORY IN HANOI

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

Installation, Operation, and Maintenance of Single-Phase Pad-Mounted Compartmental-Type Distribution Transformers

BUSWAY Low Voltage (Pow-R-Flex)

SECTION 27 - PAD-MOUNTED TRANSFORMERS TABLE OF CONTENTS

Single-phase pad-mounted step voltage regulator

Instructions (HI-110) Installation, Operation, and Maintenance of Secondary Network Transformers. Howard Industries Distribution Transformer Division

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

REVISIONS App PC. App Sud. App Thom TC 2014/03/25

56-SDMS-07 REV. 01 SPECIFICATIONS FOR

FIXED POWER FACTOR CORRECTION EQUIPMENT 5KV CLASS MEDIUM VOLTAGE SECTION Z

Totally Enclosed Non-Ventilated

Minera. Oil distribution transformers up to kva. eco design. Minera at a glance. Standards

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

Three-Phase Pole Mounted Recloser

35-kV Safefront 200 Amp SuperWell Primary Capacitor Station Pad-Mounted Outdoor

A. Motors shall be designed, built, and tested in accordance with the latest revision of the following standard documents.

15-kV Wall-Mount Switchgear Three-Phase Indoor/Outdoor 600 Amp S&C Mini-Rupter Switch

Transcription:

SECTION 26 12 19.01 PADMOUNT TRANSFORMER - OIL FILLED PART 1 GENERAL 1.1 DESCRIPTION: Padmount Transformers and Insulating Oil with underground primary and secondary connections for use in distribution system. 1.2 INCORPORATED DOCUMENTS: Latest applicable NEMA and ANSI standards for padmount, dead front, oil filled distribution transformers. Including: NEMA TP-1 Guide for Determining Energy Efficiency for Distribution Transformers ANSI/IEEE C57.12.00-2006 IEEE Standard for Standard General Requirements for Liquid- Immersed Distribution, Power, and Regulating Transformers C57.12.22-1993 American National Standard for Transformers- Pad-Mounted, Compartmental-Type, Self-Cooled Three-Phase Distribution Transformers 10CFR431 Part III, ENERGY EFFICIENCY PROGRAM FOR CERTAIN COMMERCIAL AND INDUSTRIAL EQUIPMENT 1.3 SUBMITTALS: A. Submit shop drawings containing information of dimensions, weight, sound level, impedance, voltage regulation, efficiency, and fabrication details. B. Submit manufacturers test report of the transformer furnished PART 2 PRODUCTS 2.1 GENERAL DESCRIPTION: Padmount Compartmental Type, Self-cooled, Three Phase Distribution Transformer, with disconnect switch and fuses. Acceptable manufactures: Pacific Crest Transformer, Medford, OR (suggested vendor: Ormond Associates, phone (925) 377-7070) December 2012 Page 1 of 5 2018 FDG Section 26 12 19.01

Cooper Power Systems. 2.2 ELECTRICAL CHARACTERISTICS: See purchase order for specific model and rating information. A. Self cooled rating: KVA, 3-Phase, 60 Hz. B. Insulating Liquid: Mineral Oil, ASTM D-3487. C. Primary Voltage: [4,160] [12,470] Delta. D. Secondary Voltage: [208/120] [480/277] Four wire. E. Impedance: 4.5%, Minimum. F. Taps: Two - 2.5% full capacity above and below normal; externally operable no-load tap changer. G. Temperature rise: 65 ºC. 2.3 PRIMARY TERMINATION AND EQUIPMENT A. Loop Feed 1) Provide six (6) externally clamped 200 Amp bushing wells and inserts and parking stands. The face of the parking stand shall extend from the tank wall a minimum of 1.75-inch. 2) Provide three (3), OFF-ON, 200 Amp LBOR switches (feed left, feed right and isolate transformer) with eyes for hot stick operation in the primary section. 3) Provide primary protection by bay-o-net fuses with internal current-limiting backup fuses. Interlock the bay-o-net fuses so that transformer switch ( MAIN ) must be in the off position before the bay-o-net fuses can be removed. Fuses shall be Cooper Power System or approved equal. Spare bay-o-net fuses, in their original carton, shall be provided with the transformer, in a metal pocket on the inside of the primary compartment door. B. Radial Feed 1) Provide three (3) externally clamped 200 Amp bushing wells and inserts and parking stands. The face of the parking stand shall extend from the tank wall a minimum of 1.75-inch. 2) Provide one (1), OFF-ON, 200 Amp LBOR switch with eye for hot stick operation in December 2012 Page 2 of 5 2018 FDG Section 26 12 19.01

the primary section. 3) Provide primary protection by bay-o-net fuses with internal current-limiting backup fuses. Interlock the bay-o-net fuses so that transformer switch ( MAIN ) must be in the off position before the bay-o-net fuses can be removed. Fuses shall be Cooper Power System or approved equal. Spare bay-o-net fuses, in their original carton, shall be provided with the transformer, in a metal pocket on the inside of the primary compartment door. 2.4 LOW VOLTAGE TERMINATION AND EQUIPMENT Low voltage connections shall be by blade type spade terminals with NEMA standard hole spacing. Low voltage spades, 8-hole and above, shall be provided with phenolic cross bracing under the outside end of the bushing. 2.5 CONSTRUCTION: A. Construction shall be dead front primary with a steel barrier separating the high and low voltage sections. B. The transformer tank is to be provided with a domed welded lid with a minimum 16- inch diameter bolted, tamperproof hand-hole. C. The high and low voltage compartments shall be side-by-side with the low voltage compartment on the right facing the transformer. The doors shall be tamperproof, secured by a pentahead bolt and padlock arrangement. The lid is to be hinged on the tank to allow removal and insertion of the bay-o-net fuses. The high and low voltage compartments shall be side-by-side with the low voltage compartment on the right facing the transformer. The doors shall be tamperproof, secured by a pentahead bolt and padlock arrangement. D. Provide lifting lugs and provisions for jacking, rolling, and skidding. E. Provide lugs, attached at the bottom of the transformer tank, for bolting the transformer to the pad. The lugs shall be designed for UBC (California 1997) Seismic Zone 4 earthquake forces. F. Provide the following accessories: 1) Pressure relief valve 2) One inch drain valve with sampling device 3) Upper filter press connection 4) Liquid level gauge 5) Ground pad 6) NEMA standard padmount warning label on door to primary section. December 2012 Page 3 of 5 2018 FDG Section 26 12 19.01

7) Thermometer 8) Pressure/Vacuum Gauge 9) Gas Sample/Pressure Test Valve 10) Non PCB Label. 11) Units rated 2000 kva and above are to be provided with a phenolic cross brace for secondary cable support located approximately on-half the way between the bottom of the low voltage bushings and the pad, and one-half the way between the end of the bushings and the compartment door. G. Transformer to be five-legged, wound core design. H. Paint and Finish: Finish the transformer according to ANSI standard (C57.12.28/29) for surface preparation, primer, and paint durability. Exterior color: Kelly Moore DTM 5725 569 Wrought Iron Black. 2.6 FACTORY TESTS: A. Perform factory tests on each transformer according to ANSI C57.12.90 and submit certified test reports to the Owner prior to shipment of the transformer. B. Include the following test results in the report: 1) Winding-to-winding and winding-to-ground resistance 2) Ratio tests on rated voltage and all tap connections 3) Polarity and phase relation test on rated voltage connection 4) No load loss 5) Exciting Current 6) Impedance and load loss at full load 7) Applied potential test 8) Induced potential test 9) Impulse test (one full wave, QC on all units) 10) Pressure leak test. PART 3 EXECUTION 3.1 SHIPPING AND DELIVERY: A. Ship the transformer on a flat-bed truck and secured to a pallet suitable for unloading by forklift. B. Notify the Owner 24 hours prior to delivery at the phone number provided in the Purchase Order. December 2012 Page 4 of 5 2018 FDG Section 26 12 19.01

3.2 WARRANTY The manufacturer shall warrant the product for a period of not less than eighteen (18) months from the date of shipment or twelve (12) months from the date of energization, whichever occurs earliest. END OF SECTION December 2012 Page 5 of 5 2018 FDG Section 26 12 19.01