OUTPUT SHORT-CIRCUIT CURRENT BEARABLE BY THE UPS

Similar documents
ACTIVE ECO MODE IN SINGLE-PHASE UPS. Miguel Rascon AC Power Senior Product Manager

HIGH EFFICIENCY MODES OF OPERATION. Path toward highest energy efficiency without load availability trade-off

Active ECO Mode in Single-Phase UPS. By Miguel Rascon AC Power Senior Product Manager

Miniature circuit breaker Application guide

SITE PLANNING DATA LIEBERT EXM 3-PHASE UPS: KVA/KW, 60HZ, VAC, SINGLE INPUT

Characteristics of LV circuit breakers Releases, tripping curves, and limitation

Current Ratings. Standards & codes note 1. Introduction. interest. By Steve Hansen Sr. Field Engineer

Protistor size 14x51 ar 690VAC (IEC) / 700VAC (UL)

3.2. Current Limiting Fuses. Contents

Galaxy VX. 380 V, 400 V, 415, and 440 V UPS System Technical Specifications 12/

Liebert NX TM. 250kVA kVA Transformer-free. High Efficiency, Scalable On-line UPS

Reducing. with Current. arc flash note 2. points of interest. Why Use Current Limiting Fuses. By mike lang, Principal field engineer

Protistor size 70 gr 690VAC (IEC)

BS : C&G 2382 Outcomes 4

MOLDED CASE CIRCUIT BREAKER BASICS. David Castor, P.E.

Leadership in fusible circuit protection

Applying More Than One ArmorStart Motor Controller in a Single Branch Circuit on Industrial Machinery

Selective Coordination Enforcement:

Liebert. APS UPS 5-20 kva Flexible, efficient scalable UPS for room or row-based applications

Semiconductor (AC) fuses

MEDIUM VOLTAGE PRODUCTS. Fault Current Limiters I S. -limiter and FC-Protector The worldʼs fastest switching devices

Earthing Principles. Symmetra PX 250/500 kw

High Speed Fuses. Section Contents Page

NetSure 5100 ORDERING GUIDE. 48V & 24V DC Power System (40 A to 600 A)

kVA. Liebert NX. Enterprise-Scale UPS Protection For Medium And Large Data Centers

Semiconductor Fuses European Fuses

onlinecomponents.com

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL

Ultra-Rapid Fuse Links for the Protection of Semiconductor Rectifiers

Whad 0.8, 1, 1.5 kva. Manuel d installation Installation manual. Part. LE05733AA-07/12-01 GF

Est DCM Double Conversion Module 400kVA - 800kVA

2006 IEEE PES General Meeting June 2006, Montreal, Canada Paper 06GM0613. Fault Current Limiters - Report on the Activities of Cigre WG A3.

DELPHYS GP. Green Power 2.0 range 160 to 1000 kva/kw

High reliability against cyclic and peak current loads / age resistant due to high motor start up currents

GBPC15,25,35- Series. Features: Page <1> 10/08/10 V1.1

3NP1 Fuse Switch Disconnectors up to 630 A

Evaluating Selective Coordination Between Current-Limiting Fuses And Non Current-Limiting Circuit Breakers

Miniature Circuit-Breakers (MCBs)

Application Guide Effective June Protecting semiconductors with high speed fuses

Electrical Measuring Instruments

Features. Figure 1. EFIL-28 Connection Diagram

NEW SERIES OF ETIBREAK EB2 IN VIEW OF SELECTIVITY

DX 3 MCBs. Choice of DX 3 MCBs for capacitor banks. Technical data

1 Low-voltage Power-factor Correction capacitors KNK APPLICATION DESIGN

Miniature & Moulded Case

Eaton 93PS 8-40kW UPS Technical Specification Manufacturer s declaration in accordance with IEC

Evaluating Selective Coordination Between

Medium-voltage fuses 3 kv 40.5 kv, 0.4 A 315 A

Limitor -G General Purpose Fuses

Selective Coordination

Green Power 2.0 MASTERYS GP

Liebert Hipulse E The High-ECO-Availability UPS. AC Power Systems

Surge Current, I 2 t Value and Short - Circuit Protection of High Power Semiconductors.

CI-tronic Soft Start Motor Controller Type MCI 25B with Brake

Technical Section: Miniature Circuit Breakers

NH fuse-links am 690VAC top indicator/live tags size 4, 4a

FUSES. Safety through quality

C&D VRLA Batteries Extended Run Time for Small UPS Machines

Implementation of low inductive strip line concept for symmetric switching in a new high power module

Adapted from presentation developed by Scott Fausneaucht

CI-TI Contactors - VLT Frequency Converters

Lab Electrical Power Engineering I

2000 Cooper Bussmann, Inc. Page 1 of 9 10/04/00

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL MTE Corporation

NEOZED D0 fuse-links gg 400/440VAC

DNX 3 MCB 4500 A / 6 ka Phase + Neutral, neutral on left side

FUSE: SAFE & RELIABLE

AF series contactors (9 2650)

REFERENCE MANUAL FORM: MX-TRM-E REL REV MTE

Common Bus and Line Regeneration

FUSERBLOC CD. The universal Fuse Combination Switch FROM 20 TO 1250 A. Industrial Switching & Protection Systems

FUSE TECHNOLOGY Ambient temperature

SENTRON 3NP1 Fuse Switch Disconnectors up to 630 A

10 20KVA 3Ph/1Ph KVA 3Ph / 3Ph

NH fuse-links gg 400VAC double indicator/live gripping-lugs size 000, 00, 1, 2, 3

Recommended Procedures

NH Solid Blades 690 VAC sizes 000 to 3

NH fuse-links am VAC with striker, size 0, 1, 2, 3, 4

NH fuse-links gg 500VAC top indicator/live gripping-lugs size 4, 4a

TERMS AND DEFINITIONS

High-voltage high-breaking capacity VV fuse-links

Phase + Neutral, neutral on left side

Protection and Connection Motorized and automatic transfer switches IEC Technical guide

Protection of Power Electronic Multi Converter Systems in AC and DC Applications

Power System Stability Analysis on System Connected to Wind Power Generation with Solid State Fault Current Limiter

Optimizing Drive Systems for Energy Savings

POWR-SPEED FUSES TECHNICAL APPLICATIONS GUIDE

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation

, , PREPARATION - CONNECTION. Mounting:. On symmetrical EN rail or DIN 35 rail

Advanced Guide To Understanding Assembly Short-Circuit Current Rating WITH ENGINEERING SOLUTIONS AND OVERCURRENT PROTECTION DEVICES TO ENHANCE SCCR

Phase + Neutral, neutral on right side

E-15 Uninterruptible Power Systems (UPS)

M T E C o r p o r a t i o n. MTE Series RL. Line/ load Reactors USER MANUAL PART NO. INSTR -011 REL MTE Corporation

EPS Technical Specifications 06/2015.

NH fuse-links gg 690VAC top indicator/live gripping-lugs size 4 and 4a

MASTERYS IP+ 10 to 80 kva

the National PhotoVoltaic protection note 5 I rated Introduction points of interest When to Fuse, When Not to Fuse

Page 2 of 39 Report No. CTI PA Testing location:

ABB UPS 3. November 2014

AF series contactors (9 2650)

Transcription:

OUTPUT SHORT-CIRCUIT CURRENT BEARABLE BY THE UPS

Abstract According to the standards, an overcurrent is a current which exceeds its rated value. Overcurrents can arise in different modalities, depending on whether they are the result of an overload or a short-circuit. While the former is a normal situation for an electrical circuit, the latter occurs after a negligible impedance fault between two points of the circuit where there is a voltage in ordinary operating conditions. One of the features that must be carefully evaluated when choosing a UPS is its capability to properly withstand a short circuit current on its output for a certain amount of time. This capability depends on whether the output short circuit current is withstood solely by the inverter or by the source through the static bypass. In the first case the capability strictly depends on the UPS design, while in the second it also depends on the source prospective short circuit current (named Icp). The Icp is independent of the UPS and, because of its electrodynamic and thermal effects on the components, in some cases it is appropriate to define its limits and/or to implement particular solutions which allow limiting its extent within the UPS or the entire site. However, in other cases limiting the prospective short circuit current is necessary in order to stay within the limits of the protective devices downstream the UPS. All the choices mentioned above risk negatively affecting the short circuit current that the electrical distribution downstream the UPS requires to guarantee the correct coordination between the various site protective devices. Therefore you need to take into consideration how the maximum source-icp can be mitigated by the UPS while operating in double conversion mode. The aims of this white paper are to clarify the concept of prospective short circuit current bearable by the UPS, to explain the role of fuses and to indicate the requirements of the international standard IEC 62040-1. 2

Devices run across by short circuit current and their sizing Throughout the current path, between the bypass input and the UPS output, there are various components and devices which are run across by short circuit current. Among these we can mention cables, switching devices, static devices (named SCR after the acronym of Silicon Controlled Rectifiers ) and possible fuses (Figure1). Their sizing indirectly fixes a limit to the maximum perspective short circuit current of the source. There are mainly two guidelines for this sizing: 1. Protect as many devices as possible while accepting to penalize the maximum output current; 2. Achieve the maximum output current possible while accepting that the fault may spread over more than one device, but still guaranteeing their insulation. Maintenance Bypass QS3 Static Switch U1, V1, W1 QS2 Rectifier Inverter U, V, W QS1 QS4 U2, V2, W2 Battery converter N Battery N Figure 1: UPS block diagram. Short-circuit current effects Short-circuit current effects are both electro-dynamic and thermal. The thermal effects consist of heat dissipation over the conductors by Joule effect and, as short-circuit currents are much higher than rated current, the component overheats and degrades. On the contrary, the electro-dynamic effects are attractant or repulsive mechanical actions between the components and are function of the square of the current peak. Depending on the prospective short-circuit current of the source (Icp), the current peak value must be evaluated according to Table 7 of the international standard CEI EN 61439-1 here below: Up to a Icp 10kArms, Ipk max = 1.7 x Icp Up to a Icp 20kArms, Ipk max = 2.0 x Icp Up to a Icp 50kArms, Ipk max = 2.1 x Icp Up to a Icp 100kArms, Ipk max = 2.2 x Icp 3

High speed fuses When there is the need for maximum device protection, it is necessary to use high speed fuses, which are capable of limiting the prospective short circuit current peak whenever it rises above a certain level. Figure 2 portrays the curve of some high speed fuses which show the feature mentioned above. For example, the 1000 A fuse does not limit the maximum current peak up to the prospective short-circuit current of 5 ka, while above 5 ka the value gradually reduces so that in case the prospective short circuit current value is 100 ka it becomes equal to 31 ka only. If a UPS with a rated current of 1000 A is paired with a 1000 A high speed fuse, the UPS itself could be compatible with a source prospective short-circuit current of 45 ka if the peak current limit of the static bypass devices is higher than 24 ka, while it could be compatible with 100 ka if the peak current limit of the static bypass devices is higher than 31 ka. If the same UPS was paired with a 1250 A high speed fuse and the maximum peak current limit was still 31 ka, it could be compatible with a source prospective shortcircuit current of about 50 ka maximum, and not 100 ka as in the case of the 1000 A fuse. The use of high speed fuses inevitably reduces the current peak and its duration (which is usually some ms long), therefore the selectivity downstream can be accomplished for the short-circuit only by using some more high speed fuses or electromechanical devices, which are also capable to open the circuit with characteristics dependent on the I 2 t value. In these two cases the current peak will be mainly limited by the high speed fuses downstream of the device. How to increase the short-circuit current As fuses are not resettable after they intervene and Service intervention to replace them is always required, a valid solution to achieve a higher short-circuit current is to increase the fuse size at the expense of SCR protection. 100000 70000 50000 Im = 2.3 Ip 1400 A 1250 A 1100 A Max peak let trhu current (Im) (A) 30000 20000 10000 7000 5000 3000 1000 A 900 A 800 A 700 A 630 A 550 A 500 A 2000 1000 1000 2000 3000 5000 7000 10000 20000 30000 50000 70000 100000 200000 300000 500000 700000 1e + 06 Available current in RMS symmetrical amperes (Ip)(A) Figure 2: Short-circuit current peak limitation of a typical commercial high speed fuse 4

In this scenario, in the rare case of a short circuit taking place right at the UPS output, both fuses and SCR will need to be replaced. For example, if a 1400 A fuse is used then the maximum current peak becomes about 45 ka while the prospective short-circuit current is approximately equal to 100 ka; it is then clear that both the peak value and the I 2 t value are increased, but both values remain much lower than the maximum current peak value with no fuses, which is approximately equal to 220 ka in the worst case. Manual bypass short-circuit current The maximum current peak value without fuses, equal to 220 ka in the example above, is the value to be considered for any possible manual bypass, be it inside or outside the equipment, as a manual bypass is not typically protected by fuses. In this scenario it is the very switch, with its typical short-circuit withstand current (called Icw), to fix the limit of the maximum prospective short circuit current: when it is lower than the static bypass short circuit current It becomes the limit for the entire installation / site. In case of systems with a prospective current higher than the switch Icw, then one of the two following solutions is needed: yadding fuses on the manual bypass; yadding an inductance in series with the source whose value may be enough to lower the maximum prospective short-circuit current to the desired value. The inductances mentioned above are typically realized in the air, in order to avoid their saturation in short-circuit conditions. Their presence upstream of the UPS can give the opportunity to reconsider the static bypass fuse sizing as well. Short-circuit current in a parallel UPS system In those situations in which there are more UPS connected in parallel, once again considering just the short-circuit-tothe-output of the parallel system, the maximum prospective short-circuit current of the source may be considered equal to about 80% of that of the single UPS multiplied by the number of UPS in the parallel system (without considering any redundancy). 80% is a safety margin which takes into consideration that there can be a short-circuit current imperfect distribution due to asymmetries in the equipment connections both at the bypass input and at the system output. These asymmetries have always to be taken into consideration when balancing the UPS static bypasses in nominal operating conditions, in order to keep them within a 10% range. If the site layout does not allow symmetry between the bypass input and UPS output connections, solutions have to be implemented in order to compensate for these deviations. In case inductances are chosen as a solution, they must not saturate in a short circuit scenario. International standard IEC 62040-1 The international standard IEC 62040-1:2008 (EN 62040-1:2008-11) was published in 2008 under the name Uninterruptible Power Systems (UPS) - Part 1: General and Safety Requirements for UPS. In September 2011 it replaced the first editions of IEC 62040-1-1 and IEC 62040-1-2, published in 2004. This standard applies to UPS units which are movable, stationary, fixed or for building-in, for use in low-voltage distribution systems and intended to be installed in any operator accessible area or in restricted access locations as applicable. Amendment IEC 62040-1:2008/A1:2013 (Date of publication, DOP) must be taken into consideration mandatorily by law, in addition to the original standard as of 14/02/2016 (Date of withdrawal, DOW) in order to assess UPS safety conformity through harmonized standards. This amendment introduces requirements to the UPS output short-circuit withstand current. In particular, it forces the manufacturers to guarantee a minimum value depending on the UPS rating. Important final note When talking about prospective short-circuit current, considering only the source can be penalizing because the softening action carried out by the impedance of the connection between source and bypass input would be left out. The above mentioned impedance depends both on the distance between source and UPS, and, above all, on the connection type, (i.e. if this is made with a low impedance busbar or with cables). In the latter scenario, the way in which cables are arranged into the support conduit is another factor to be taken into consideration because it could cause significant impedance depending on the specific solution implemented. Therefore, the declared UPS performance has to be intended as a prospective short-circuit current available to the bypass input. 5

Conclusion With this whitepaper the concept of prospective short-circuit current withstand capability has been clarified for both a single UPS and a parallel system, by illustrating the role of fuses and by giving an indication about what the IEC 62040-1 international standard requirements are. All the topics above are important because one of the features to be carefully evaluated when choosing a UPS is its capability to bear a short circuit current to its output properly for a certain amount of time. 6

Notes: 7

VertivCo.com Emerson Network Power Limited, George Curl Way, Southampton, SO18 2RY, VAT Number: GB188146827 2016 Vertiv Co. All rights reserved. Vertiv, the Vertiv logo, and Vertiv Liebert UPS are trademarks or registered trademarks of Vertiv Co. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness herein, Vertiv Co. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications are subject to change without notice.