21st European Photovoltaic Solar Energy Conference, 4-8 September 2006, Dresden, Germany

Similar documents
Solar Power. Demonstration Site. Annual Performance Report 2017

Field Verification and Data Analysis of High PV Penetration Impacts on Distribution Systems

MULTI-OBJECTIVE OPTIMIZATION OF STORAGE BATTERY OPERATION IN CLUSTERED RESIDENTIAL GRID-INTERCONNECTED PV

Combination control for photovoltaic-battery-diesel hybrid micro grid system

Impact Analysis of Fast Charging to Voltage Profile in PEA Distribution System by Monte Carlo Simulation

Investigation of CO 2 emissions in usage phase due to an electric vehicle - Study of battery degradation impact on emissions -

Construction of power supply system using electric vehicle for stable power delivery from PV generation

POWER QUALITY IMPROVEMENT BASED UPQC FOR WIND POWER GENERATION

Behaviour of battery energy storage system with PV

Rate Impact of Net Metering. Jason Keyes & Joseph Wiedman Interstate Renewable Energy Council April 6, 2010

Dynamic Modelling of Hybrid System for Efficient Power Transfer under Different Condition

Island Smart Grid Model in Hawaii Incorporating EVs

Development of Higher-voltage Direct Current Power Feeding System for ICT Equipment

Figure 1b: Daily Production Profile Non Power Limiting Day

New York Science Journal 2017;10(3)

The evaluation of endurance running tests of the fuel cells and battery hybrid test railway train

Power Optimization and Monitoring in Photovoltaic Systems. Perry Tsao, Ph.D. January 20, 2010

Remarkable CO 2 Reduction of the Fixed Point Fishing Plug-in Hybrid Boat

Peak power shaving using Vanadium Redox Flow Battery for large scale grid connected Solar PV power system

Kazuyuki Takada Representative NEDO Representative office in Washington DC

Why array oversizing makes financial sense

Designing Stand Alone Systems. Overview, components and function, Elements in Design

Figure 1 I-V characteristics of PV cells. Meenakshi Dixit, Dr. A. A. Shinde IJSRE Volume 3 Issue 12 December 2015 Page 4687

AEC PHOTOVOLTAIC TEST FACILITY FIRST YEAR TEST DATA

International Journal of Advanced Research in Electrical, Electronics and Instrumentation Engineering. (An ISO 3297: 2007 Certified Organization)

Increasing PV Hosting Capacity in Distribution Networks: Challenges and Opportunities. Dr Andreas T. Procopiou

INTELLIGENT DC MICROGRID WITH SMART GRID COMMUNICATIONS: CONTROL STRATEGY CONSIDERATION AND DESIGN

Analysis of Grid Connected Solar Farm in ETAP Software

Title Goes Here and Can Run Solar Photovoltaic up to 3 lines as shown here Systems as you see

Analysis of Impact of Mass Implementation of DER. Richard Fowler Adam Toth, PE Jeff Mueller, PE

Total number of PV modules: 42 Energy usability factor: 99.9 % Number of PV inverters: 1

Design and Implementation of Reactive Power with Multi Mode Control for Solar Photovoltaic Inverter in Low Voltage Distribution System

Design and Installation of A 20.1 kwp Photovoltaic-Wind Power System

A.Arun 1, M.Porkodi 2 1 PG student, 2 Associate Professor. Department of Electrical Engineering, Sona College of Technology, Salem, India

FAULT ANALYSIS OF AN ISLANDED MICRO-GRID WITH DOUBLY FED INDUCTION GENERATOR BASED WIND TURBINE

There are several technological options to fulfill the storage requirements. We cannot use capacitors because of their very poor energy density.

Design of Active and Reactive Power Control of Grid Tied Photovoltaics

OKLAHOMA CORPORATION COMMISSION REGULATED ELECTRIC UTILITIES 2017 RELIABILITY SCORECARD

Guideline for Using IEEE 1547 for Solar PV Interconnection Page 1

DISTRIBUTED GENERATION FROM SMALL HYDRO PLANTS. A CASE STUDY OF THE IMPACTS ON THE POWER DISTRIBUTION NETWORK.

NaS (sodium sulfura) battery modelling

Energy Management for Regenerative Brakes on a DC Feeding System

Available online at ScienceDirect. Energy Procedia 36 (2013 )

Planning Guidelines SMA SMART HOME

Ahmet Aktas, Koray Erhan, Engin Ozdemir, Sule Ozdemir. University of Kocaeli, Kocaeli

Implementation of Bidirectional DC/AC and DC/DC Converters for Automotive Applications

Impacts of distributed photovoltaic generation on Jenin distribution network: voltage level, power losses, power factor and power quality

Yield vs simulation of Canadian Solar modules October 2012 QUALITY I VALUE I INNOVATION

Solar Powered System - 2

RECONFIGURATION OF RADIAL DISTRIBUTION SYSTEM ALONG WITH DG ALLOCATION

OKLAHOMA CORPORATION COMMISSION REGULATED ELECTRIC UTILITIES 2018 RELIABILITY SCORECARD

Impact of Reflectors on Solar Energy Systems

BIDIRECTIONAL DC-DC CONVERTER FOR INTEGRATION OF BATTERY ENERGY STORAGE SYSTEM WITH DC GRID

Electric Vehicles Coordinated vs Uncoordinated Charging Impacts on Distribution Systems Performance

Improved PV Module Performance Under Partial Shading Conditions

HOMER OPTIMIZATION BASED SOLAR WIND HYBRID SYSTEM 1 Supriya A. Barge, 2 Prof. D.B. Pawar,

Applicability for Green ITS of Heavy Vehicles by using automatic route selection system

Productive. Reliable. Smart. Safe. Brandon J. Pierquet. The Impact of Microinverters in Photovoltaic Systems Enphase Energy

A Novel GUI Modeled Fuzzy Logic Controller for a Solar Powered Energy Utilization Scheme

Data Analytics of Real-World PV/Battery Systems

NEDO Case Studies of Project in New Mexico, US

Technology from the New Product SANUPS K for a Smart Grid Society

Using Opal-RT Real-Time Simulation and HIL System in Power and Energy Systems Research

Off-grid Power for Wireless Networks. Training materials for wireless trainers

Where Space Design see the future of renewable energy in the home

Reference: Photovoltaic Systems, p References: Photovoltaic Systems, Chap. 7 National Electrical Code (NEC), Articles 110,

DYNAMIC BEHAVIOUR OF SINGLE-PHASE INDUCTION GENERATORS DURING DISCONNECTION AND RECONNECTION TO THE GRID

Module-Integrated Power Electronics for Solar Photovoltaics. Robert Pilawa-Podgurski Power Affiliates Program 33rd Annual Review Friday, May 4th 2012

OVERSIZING WHITEPAPER

PES Cook Islands KEMA Grid Study Final Report

Impact of Active Power Curtailment on Overvoltage Prevention and Energy Production of PV Inverters Connected to Low Voltage Residential Feeders

Using energy storage for modeling a stand-alone wind turbine system

Journal of American Science 2015;11(11) Integration of wind Power Plant on Electrical grid based on PSS/E

Yield Reduction Due to Shading:

Development of control unit for smart power supply system using battery energy storages and residential PV-PCSs

Net Metering Service. Customer Information Package

Power Quality and Power Interruption Enhancement by Universal Power Quality Conditioning System with Storage Device

Georgia Transmission Corporation Georgia Systems Operations Corporation

Modeling and Comparison of Dynamics of AC and DC Coupled Remote Hybrid Power Systems

Simulation of real and reactive power flow Assessment with UPFC connected to a Single/double transmission line

The Effect Of Distributed Generation On Voltage Profile and Electrical Power Losses Muhammad Waqas 1, Zmarrak Wali Khan 2

Smart community clustering for sharing local green energy. Yoshiki Yamagata, Hajime Seya and Sho Kuroda

CHAPTER 3 FINANCIAL ANALYSIS OF SOLAR PV PUMPS

3 MWp vertical E-W oriented system in Germany. Dipl. Ing. Heiko Hildebrandt

Available online at ScienceDirect. Procedia Engineering 170 (2017 )

ISES Solar Charging Station

Application of energy storage systems for DC electric railways

Train Group Control for Energy-Saving DC-Electric Railway Operation

Technology of Estimating Short Circuit Current and Ground Fault for Direct Current Distribution Systems

Solar for Aquaponics. Extension. Design and size an off-grid, ground-mounted solar PV system to sustainably power an aquaponics system.

Technical Information Average Efficiency of the SMA Flexible Storage System

NAS batteries for Technical Challenges with Renewable Energy

A Study of Lead-Acid Battery Efficiency Near Top-of-Charge and the Impact on PV System Design

Exercise 3. Battery Charging Fundamentals EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Charging fundamentals

Hardware Testing of Photovoltaic Inverter Loss of Mains Protection Performance

Design Modeling and Simulation of Supervisor Control for Hybrid Power System

Development of Catenary and Batterypowered

Experimental Evaluation of New Magnetic Movement Converter for Linear Oscillatory Actuator

Strategy and Roadmap for PV Systems in Japan

DANGER. The Conext products below can utilize Load Shedding and Load Shifting:

Transcription:

PERFORMANCE ANALYSES OF BATTERY INTEGRATED GRID-CONNECTED RESIDENTIAL SYSTEMS Yuzuru Ueda 1, Kosuke Kurokawa 1, Takamitsu Itou 2, Kiyoyuki Kitamura 2, Katsumi Akanuma 3, Masaharu Yokota 3, Hiroyuki Sugihara 3, Atsushi Morimoto 4 1 Tokyo University of Agriculture and Technology, 2-24-16 Naka-cho, Koganei, Tokyo 184-8588, Japan email: yzrueda@cc.tuat.ac.jp 2 MEIDENSHA CORPORATION, Riverside Building, 36-2 Nihonbashi Hakozakicho, Chuo-Ku, Tokyo 103-8515, Japan 3 Kandenko Co., Ltd., 4-8-33 Shibaura, Minato-ku, Tokyo 108-8533, Japan 4 Matsushita Ecology Systems Co., Ltd., 4017 Shimonakata Takaki-cho, Kasugai-city, Aichi 486-8522, Japan ABSTRACT: Grid connected systems will feed electric power to the power distribution network. Voltage at the connecting point to the grid will become higher along with the reverse power flow increasing. PCS output power is restricted by the grid voltage so the significant amount of the possible energy output will be lost if the grid voltage is too high. To avoid this output energy loss due to the high grid voltage, battery integrated systems are developed in the Demonstrative research on clustered systems. More than 550 residential systems are installed in the demonstrative research area. Annual performance analysis results of commercial systems without battery and battery integrated systems are summarized in this paper. Variation of the output energy loss due to the grid voltage is observed in commercial systems due to the difference of the regulating method. Approximately 8% of additional performance loss is observed in battery integrated systems. Active power regulations due to the high grid voltage are successfully avoided in some cases. Keywords: Grid-Connected, System, Performance 1 INTRODUCTION Grid connected-residential photovoltaic () systems such as roof mounted systems feed electric power to the power distribution line. Since radial power distribution system is designed for a power flow from the high voltage (HV) side to the low voltage (LV) side, reverse power flow from the end of LV side may cause voltage rise of LV line. [1](see Figure 1) To prevent the over voltage of the power distribution line, Japanese system s power conditioning subsystems (PCS) have a function to regulate output power when the voltage of the grid is too high. Because of this function, significant amount of electric power will be lost. [2] Demonstrative research on clustered systems is being conducted from December, 2002 by NEDO to investigate about the voltage problem and other potential issues of grid-connected systems. Approximately 550 systems are installed on the roofs of houses and connected to the commercial power grid in the demonstrative research area in Oota, Japan. A total of nominal system power is more than 2[MW] and all the systems are connected to the same power distribution network. [3] Voltage Transformer End of line Figure 1: Voltage rising of power distribution line Upper Limit Lower Limit 2 BATTERY INTEGRATED SYSTEMS 2.1 Overview of battery integrated system To minimize the output energy loss due to the high grid voltage and maintain the power quality of the grid, battery integrated systems are developed in the demonstrative research. Lead acid battery with a capacity of 49 [Ah] for single cell are used for the systems, 96 cells are series connected and installed in the outdoor storage box for each systems. Two types of charge controller are developed in the demonstrative research. One is the unified PCS for and battery and the other is the additional charge controller for commercial systems. Installation of the unified PCS is started from January, 2005. Additional charge controllers for the installed commercial systems are started in a year later. 2.2 Unified PCS for and battery The unified PCS is composed of a DC/DC booster, DC/DC charge controller and DC/AC inverter. Figure 2 shows a schematic view of the battery integrated system with the unified PCS. Only the power from the array will be charged to the battery, the charged power will be used in the inhouse load. Unified PCS monitors a power flow at the connecting point, more than 150[W] of forward power flow are required for discharging in order to prevent the reverse power flow from the battery to the grid. array PCS - - - ~ - - Lead acid battery In-house load Figure 2: Schematic view of the battery integrated system with the unified PCS Grid 2580

3 ANALYSIS METHOD One-minute averages of secondly measured data are used for the analysis. System yield [kwh/kw] and performance ratio are employed for the overall system performance analysis. In addition to these indexes, detailed loss analyses are performed to clarify the benefit of the battery integration. Deployed systems performance is highly depending on the various loss factors, i.e. temperature, shading, array configuration, grid voltage and so on. Expected output power which would be generated in the normal grid voltage condition and lost energy under the high voltage condition need to be quantified in order to quantify the energy which is saved by the battery. Some of the losses occur exclusively but some of them occur simultaneously, the following loss factors are considered and separately quantified in this paper. 1. Shading 2. Regular loss (Soil, Degradation, Array config.) 3. Incident Angle / Reflection 4. Module Temperature 5. Output restriction (over voltage) 6. PCS capacity shortage 7. MPP mismatch (high voltage side) 8. DC resistance 9. Inverter 10. PCS Off / PCS Standby 11. Fluctuation Input energy of the systems is irradiation. Irradiation is measured at the meteorological stations using pyranometer in this research. Shading, soil, degradation and incident angle are treated as factors to reduce the input irradiation of the array. Received irradiation will be used for the photovoltaic energy conversion. Module temperature, operation point on the I-V curve and array configuration are treated as factors to change the conversion efficiency of the array. Grid voltage, PCS capacity and MPP mismatch are considered as factors to determine the operation point on the I-V curve of the array. Loss due to the incident angle and DC circuit resistance are calculated using theoretical model. [4][5] Loss due to the module temperature and inverter are directly calculated using measured module temperature, array s output power and inverter s output power. Other losses are quantified for each factor using empirical models. [5][6][7] battery for battery integrated systems. As a result, fed power is less than half of the non battery integrated systems. Figure 3: Reference yield, system yield, fed power and performance ratio for commercial and battery integrated systems 4.2 Annual system performance Annual system performance and loss analysis results of commercial systems and those of battery integrated systems are shown in Figures 4 and 5 respectively. Data collected from March, 2005 to February, 2006 are used in these results. Numbers of systems used in these graphs are gradually increased during the evaluation period, numbers of commercial (non battery integrated) systems in March, 2005 are 134 and 140 in February, 2006. On the other hand, numbers of battery integrated systems are 19 in March and 197 in February. Both energy losses at the inverter and charge controller are included in a loss due to the unified PCS. Additional energy consumption of the measurement system and control system are also included. Looking at the results, all the loss factors showed almost the same values and seasonal trend except the loss due to the battery and PCS. Since commercial PCS and unified PCS have almost the same DC/AC conversion efficiency, 4.7% of the expected energy can be assumed as a loss at the charge controller of unified PCS and other additional losses. 3.3% of the expected power is also lost in the battery itself so that the total performance ratio is around 8% lower in the battery integrated systems. 4 RESULTS AND DISCUSSIONS 4.1 System yield and performance ratio Monthly averages of daily reference yield, daily system yield and daily fed power are summarized in Figure 3. Monthly performance ratios are also plotted in this figure as a right y-axis. In general, April has a longest reference yield but peak of the performance ratio is in winter. Performance ratio in summer is slightly lower because of the efficiency drop due to the module temperature increasing. systems with battery always result approximately 8% lower performance ratio due to the additional energy loss at the charge controller and battery. 30% of generated power is once charged in the Figure 4: Annual performance and loss analysis result of commercial (non battery integrated) systems 2581

reverse power flow (increasing reverse current) in clear sunny days caused higher grid voltage. Figure 5: Annual performance and loss analysis result of battery integrated systems It should be noted that charged energy have to go through the charge controller twice. When the generated electricity is being stored in the battery, current will go through DC/DC booster and DC/DC charge controller. During the discharging, current will go through DC/DC charge controller again and DC/AC inverter. Charging DC current are not the constant current but follow the array output, this is not the best way to charge the battery in terms of the efficiency stand point but necessary in the battery integrated systems. 4.3 Loss due to the grid voltage The voltage at the power distribution line needs to be controlled within 101V +- 6V or 202V +- 20V in Japan. Flowing current and line impedance are two major factors to determine the voltage at the connecting point. If the sending voltage of the transformer substation and tap positions are the same but different current in the same line impedance, more current cause more voltage drop in forward power flow case but results voltage increasing in reverse power flow case at the end of LV line. Thus reducing the feeding power to the grid is necessary to avoid the over voltage for the distributed generator such as grid connected systems. Battery integration is one of the options for systems to minimize the risk of over voltage without sacrificing the output energy by mean of storing the electricity in the battery. So far, energy loss due to the grid voltage is not so severe even in the non battery integrated systems. Percentage of the loss due to the grid voltage is less than 1% in annual average as shown in Figure 4. This is probably because of the good voltage control of the power grid. However, there are a few systems which tend to have more energy loss due to the grid voltage and amount of lost energy is sometimes more than 50% of the expected energy out. Figure 6 shows analysis result of the loss due to the grid voltage for commercial systems. Each data point represents the daily loss of one system and more than 3000 data are plotted in each month. Although most of the data are on the 0% line, some of the systems result significant energy loss on particular days. Most of these bad days are weekends and clear sunny days as shown in Figure 7. The results suggest that the reduced load (reducing forward current) in the power distribution network in weekends and more Figure 6: Daily loss ratio due to the high grid voltage for commercial (non battery integrated) systems Figure 7: Loss ratios due to the grid voltage as a function of the day of the week and daily expected output power Another factor to differentiate the amount of energy loss due to the grid voltage among the systems is the starting voltage of output regulation. Examples of the regulation methods, starting voltage and regulating speed are summarized in Table 1. Phase advance reactive power control will shift the phase of current and change the power factor between 1 and 0.85, active power control will regulate the output current in order to reduce the output power by shifting the operation point from MPP to the open circuit voltage. Since PCS is not monitoring the voltage at the connecting point but its own output terminal voltage and there is a voltage drop between PCS output terminal and connecting point due to the resistance of the drop wire, voltage at the connecting point might be lower than that at the PCS output terminal. Thus PCS may not need to start the regulation from 107V but can start from slightly higher voltage. This is one of the reasons why starting voltages of output regulation are not exactly the same among all the PCS. However, it is pointed out that this kind of variation may cause the concentration of output restriction in particular PCS so this variation should be minimized. [8] 2582

PCS Types Starting Voltage Speed Reactive power control 1 112V PF=1 to 0.85 in 2.5sec 2 None None 3 None None 4 107V PF=1 to 0.85 in 10sec 1 Active power control (Regulation) After PF reached 0.85 2A/sec, 100% to 0%=10sec 2 107V 43mA/4sec 3 109V Immediately 0% 4 109V 100% to 0% in 4 to 10sec Table 1: Examples of output regulation method Figure 8: Example of output regulation due to the high grid voltage. System #1 with commercial PCS type A Figure 9: Example of output regulation due to the high grid voltage. System #2 with commercial PCS type B high grid voltage. PCS output voltage1 and 2 are measured voltage at the single-phase three-wire PCS output terminals. Starting voltage of the active power regulation for system #1 s PCS is around 107.5[V]. On the other hand, that of system #2 s is around 109[V] and 110[V] for system #3 s PCS. As a result, around 69% of the expected power was lost due to the high grid voltage in system #1 while system #2 lost around 15% and no loss was observed in system #3. PCS output terminal voltages of system #3 are slightly higher than those of the others because #3 has more reverse power flow to the grid. However, this result does not mean that system #3 was in over voltage condition because these voltages are not the voltages at the connecting point. 4.4 Effect of battery Battery can be used as an output restriction avoidance system in grid connected systems. Charging battery with generated electricity can minimize the power fed to the grid in the daytime. Stored electricity will be used in the in-house load during the nighttime. Figures 11 and 12 are examples of the results how the battery worked as an output restriction avoidance system. Data are collected on March 25, 2006, Saturday. In addition to the data showed in Figures 8, 9 and 10, feeding power to the grid and charged power to the battery are plotted in these figures. Negative power of the feeding power means forward power flow from the grid to the in-house load, negative power of the battery power means charging battery. Bottom side of Figure 12 shows state of charge. (SOC) System #4 in Figure 11 resulted out put energy loss due to the high grid voltage in afternoon and lost energy was approximately 20% of the daily expected energy out. On the other hand, system #5 started charging battery around 10 a.m. so there is no fed power when the voltage is high in the afternoon. As a result, no electric power was lost due to the high grid voltage. Another example of battery integrated system is shown in Figure 13. The system started charging battery when the array started generation of electricity. Then battery was fully charged around noon so there was no more room to store the electric power when the voltage became high in the afternoon. The capacity of the battery should be minimized from the installation cost point of view, however, less capacity requires more intelligent method for charging and discharging battery. Further study will be continued to optimize the control pattern of the battery. Figure 10: Example of output regulation due to the high grid voltage. System #3 with commercial PCS type C Figures 8, 9 and 10 are examples of the output regulations due to the high grid voltage for three different commercial PCS. All the systems are connected under the same pole transformer, no battery are installed in these systems. Data are collected on April 9, 2005, Saturday. Peak power means expected system output power under the measured irradiation at the module temperature of 25 degree Celsius. Array output means actual output power from the array under the actual module temperature. Red area means lost energy mainly because of the restriction of the output power due to the Figure 11: Example of output regulation due to the high grid voltage. System #4 with commercial PCS type A 2583

and battery operation. Further research will be continued in the Demonstrative research on clustered systems. ACKNOWLEDGEMENT Demonstrative research on clustered systems is a project of New Energy and Industrial Technology Development Organization (NEDO). Authors would like to acknowledge the financial support of NEDO and cooperative discussions with project members. Figure 12: Example of output restriction avoidance. System #5 with unified PCS with battery Figure 13: Example of the failure of output restriction avoidance. System #6 with unified PCS with battery 5 CONCLUSIONS Output energy loss due to the high grid voltage is analyzed in this paper. Without the battery, system s output energy is restricted by the grid voltage. Since the reverse power flow from the system to the grid is one of the causes of high grid voltage, battery integration is one of the options to reduce the risk of over voltage and minimize the energy loss due to the high grid voltage for system s user side. Although the frequency of the occurrence of active power regulation due to the high grid voltage is very low, some of the systems had significant amount of output energy loss in fewer load / more electricity generation condition such as weekend and sunny clear day. Different PCS have different starting voltage of the active power regulation so the amount of the lost energy is not the same among all the PCS. If the battery is appropriately operated, battery integrated system can avoid the output energy loss under the high grid voltage situation. However, battery integration results additional energy loss due to the charge controller and battery, saved energy should be larger than the additional loss in order to maximize the merit of system user. Amount of saved energy will be affected by the grid condition REFERENCES : [1] A F POVLSEN, Impacts of Penetration from Photovoltaic Systems in Distribution Networks, Report IEA PS T5-10 (2002) [2] Y.Ueda, T.Oozeki, K.Kurokawa, T.Itou, K.Kitamura, Y.Miyamoto, M.Yokota, H.Sugihara, S.Nishikawa, ANALYTICAL RESULTS OF OUTPUT RESTRICTION DUE TO THE VOLTAGE INCREASING OF POWER DISTRIBUTION LINE IN GRID-CONNECTED CLUSTERED SYSTEMS, 31st IEEE Photovoltaic Specialists Conference (2005) pp1631 [3] S.Nishikawa, K.Kato, DEMONSTRATIVE RESEARCH ON GRID-INTERCONNECTION OF CLUSTERED PHOTOVOLTAIC POWER GENERATION SYSTEMS, 3rd World Conference on Photovoltaic Energy Conversion (2003) 8LN-C- 03 [4] T Yamada, H Nakamura, T Sugiura, K Sakuta, K Kurokawa, Refection loss analysis by optical modeling of module Solar Energy Materials & Solar Cells, Vol.67 pp.405-413 (2001) [5] Y.Ueda, K.Kurokawa, T.Itou, K.Kitamura, Y.Miyamoto, M.Yokota, H.Sugihara, PERFORMANCE RATIO AND YIELD ANALYSIS OF GRID CONNECTED CLUSTERED SYSTEMS IN JAPAN, 4th World Conference on Photovoltaic Energy Conversion (2006) [6] Y.Ueda, T.Oozeki, K.Kurokawa, T.Itou, K.Kitamura, Y.Miyamoto, M.Yokota, H.Sugihara, Quantitative Analysis Method of Output Loss due to Restriction for Grid-connected Systems, IEE Japan Vol.125-B, No.12, pp1317-1326 (2005-12) [7] Y.Ueda, T.Oozeki, K.Kurokawa, T.Itou, K.Kitamura, Y.Miyamoto, M.Yokota, H.Sugihara, Advanced analysis of shading effect using minutely based measured data for systems, 15th International Photovoltaic Science and Engineering Conference, TECHNICAL DIGEST pp.444-445 (2005) [8] Kandenko Co., Ltd., FY2002 NEDO report Demonstrative research on clustered systems (2003) (in Japanese) 2584