SOUND-RETARDANT- VERTICAL LIFT DOORS

Similar documents
VERTICAL LIFT FIRE/BLAST DOORS

A. This Section includes the following types of sectional overhead doors:

SECTION HYDRAULIC FOUR FOLD DOORS MODEL 48 LOUVERS

Construct Compressed Air Building Near Bldg SECTION OVERHEAD COILING DOORS 07/07

SECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS

A. Products shall be designed, manufactured, tested, and installed in compliance with the following standards:

RADIAL GATES USES CONSTRUCTION FEATURES FACE PLATE SEALS

SECTION AXIAL HVAC FANS

SECTION CENTRIFUGAL HVAC FANS

SECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS

Multi-Institutional Academic Health Science & Research Center Evansville, IN

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

ROLLER GATES. Waterman Industries of Egypt. Roller gates are nominated for heavy duty service where large loads and sizes are going to be encountered.

Overhead Crane Specification prepared by SVEDA CRANES SPECIFICATION. * (Top/Under) running * (single/double) girder crane

AlumaView AV200. A. Section Metal Fabrications: Miscellaneous for steel supports.

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

1. Division 26 Section "Elevator Shunt-Trip Fused Disconnect Switches".

radial GATES Waterman Industries of Egypt

Design Standard. Purpose: Design Standard:

SECTION ENCLOSED CONTROLLERS

SECTION LIFT ARM PARKING GATES

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types:

BUSWAY Low Voltage (Pow-R-Flex)

SECTION OVERHEAD COILING DOORS PART 1 - GENERAL 1.1 RELATED DOCUMENTS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

IN2 Enclosed Switches and Circuit Breakers

University of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL

SECTION GENERAL-SERVICE AIR COMPRESSOR PART 1 - GENERAL

Electric Coil [Make-Up Air / Displacement Ventilation / Space Heating] System

SECTION [ ] HIGH PERFORMANCE OVERHEAD HIGH SPEED DOORS. Display hidden notes to specifier. (Don't know how?

SECTION (15444) - DOMESTIC WATER PACKAGED BOOSTER PUMPS

SECTION GENERAL MOTOR REQUIREMENTS FOR PLUMBING EQUIPMENT

SteelForm S-24C SECTIONAL OVERHEAD DOORS

SECTION HVAC POWER VENTILATORS

J.R. Clancy, Inc. Phone: , Interstate Island Road Fax: Syracuse, New York

A. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified.

65141_Teledoor_r3-06 3/2/06 9:28 AM Page 1. Teledoor. Telescoping Door. The Ultimate Solution to Security and Space Allocation

SECTION MOTOR REQUIREMENTS for HVAC

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

MECHANICAL AND ELECTRICAL COORDINATION SECTION MECHANICAL AND ELECTRICAL COORDINATION PART 1 - GENERAL

PROJ. NO SECTION HYDRONIC PUMPS

East Central College

SECTION RAPIDVIEW MODEL 999. Copyright ARCAT, Inc. All rights reserved

SECTION FIRST RESPONDER SERIES HEAVY DUTY PERSONNEL LOCKERS DEBOURGH MFG. CO. 10/15/2013

1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces.

Health & Safety Policy and Procedures Manual SECTION 22 CRANE SUSPENDED PERSONNEL PLATFORMS

B. Fabricate in accordance with ASHRAE handbooks and SMACNA duct manuals. A. Submit in accordance with Division-1 and Section

STATE OF NORTH CAROLINA D DEPARTMENT OF ADMINISTRATION MARCH 20, 1995 PURCHASE AND CONTRACT DIVISION 7125-LM-2C November 9, 1989

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

SECTION [ ] SECURITY GRILLES. Display hidden notes to specifier. (Don't know how? Click Here)

SPECIFICATIONS - DETAILED PROVISIONS Section Vertical Hollowshaft Electric Motors C O N T E N T S

Model H/HB Heavy-Duty Industrial Drawbar Door Operator Safety, Installation and Service Manual

SECTION COILING DOORS AND GRILLES

SECTION COMMON MOTOR REQUIREMENTS FOR HVAC EQUIPMENT

An Investment in Plant Floor Safety. 802C Safety Cable Pull Switches 802E Hinge Safety Interlock Switches 802F Safety Interlock Switches

** NOTE TO SPECIFIER ** Overhead Door Corporation; High performance overhead coiling door products.

SECTION HIGH PERFORMANCE OVERHEAD COILING DOORS

DIVISION 14 CONVEYING EQUIPMENT

A. Submit manufacturer's literature and technical data before starting work.

SPECIAL SPECIFICATION 8676 Solar Panel Power Supply System

SECTION MOTOR CONTROLLERS

ThermaSeal TM220 SECTIONAL OVERHEAD DOORS

MODEL JH JACKSHAFT INDUSTRIAL DOOR OPERATOR INSTALLATION MANUAL. OPERATOR SPECIALTY COMPANY, INC. P.O. Box 128 Casnovia, MI 49318

EXTRUDED ALUMINUM BALANCED DOORS AND ENTRANCES

SECTION METAL ATHLETIC SPORT LOCKERS

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

FREE STANDING WORK STATION JIB CRANE

WARREN COUNTY, N.Y. M/E REFERENCE A. Submit manufacturer's product data on all motors and adjustable speed drives.

D. Operation and Maintenance Data. In addition to items specified in Division 1 Section "Operation and Maintenance Data," include the following:

AUTOMATIC ENTRANCES SLIDING GILDOR, INC. SECTION [08460] MODEL SLM SERIES TYPE COM

SECTION SWITCHGEAR. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

StopGate TM Barrier Arm GENERAL SPECIFICATIONS

SECTION HVAC CONTROL SYSTEM PART 1 GENERAL 1.01 SUMMARY. A. Section Includes:

STANDBY EMERGENCY CNG/LPG GENERATOR

.3 Section Vibration Isolation and Seismic Control..2 ANSI/AMCA 210/ASHRAE 51 Laboratory Methods of Testing Fans for Rating.

SECTION WIRING DEVICES

1. Wiring Diagrams: Power, signal, and control wiring.

SECTION VIII. (Sub-section 430) Wastewater Valves and Appurtenances. 1. General thru Gate Valves thru 430-3

.1 The following is a list of standards which may be referenced in this Section: .2 B30.11, Monorails and Underhung Cranes.

READ AND SAVE THESE INSTRUCTIONS. Centrifugal Downblast Exhaust Fan Belt Driven for Roof & Wall Mounting

CEILING MOUNTED WORK STATION STEEL BRIDGE CRANE

SECTION VistaGard ROLLING GRILLES CLEAR PANEL DESIGN

SECTION HIGH PERFORMANCE OVERHEAD COILING DOORS

A. Motors shall be designed, built, and tested in accordance with the latest revision of the following standard documents.

WARREN COUNTY, N.Y. M/E REFERENCE

ISIMET/MAPA, LLC, an affiliate of WCM Industries, Inc. 103 CJ Wise Parkway Naples, TX (903) fax (903)

SECTION AIR TERMINAL UNITS

SECTION HIGH PERFORMANCE OVERHEAD COILING DOORS

Model JG Industrial Gearhead Jackshaft Door Operator Safety, Installation, and Service Manual

SECTION MOTORS AND VARIABLE FREQUENCY DRIVES

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES

University of Houston Master Construction Specifications Insert Project Name

SECTION COMPRESSED-AIR PIPING FOR LABORATORY FACILITIES

A. Fan motors and associated equipment shall be sized to operate at 110% of calculated loads and capacities.

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards

Ice Rink Renovation & New Clubhouse

SPECIAL SPECIFICATION 5066 Packaged Engine Generator System

Transcription:

International Door, Inc. 8001 Ronda Drive Canton, MI 48187 (800) 231-9521 Website: www.international-door.com Sales Dept. E-Mail: sales@international-door.com Engineering Dept. E-Mail: engineering@international-door.com SOUND-RETARDANT- VERTICAL LIFT DOORS Section 08348-Vertical Lift Doors- Sound-Retardant Part 1-General 1.1 Related Document: Drawing and general provisions of contract, including general and supplementary conditions and division 1 specification section, apply to this section. 1.2 Work Included: A. Provide all labor, equipment, materials and services required to execute and complete all items of work in connection with Furnishing and Installing the Sound-Retardant Vertical Lift Doors described herein. All work shall be in accordance with the specifications and drawings. B. Related Sections include the following: 1.3 Definitions 1. Division 8 Section Door Hardware for lock cylinders and keying. 2. Division 9 Section Painting for field-applied paint finish. 3. Division 16 Section Conductors and Cables for electrical service and connections for powered operators and accessories. 4. Division 16 Section Disconnect Switches and Circuit Breakers for disconnect switches and circuit breakers for powered operators. are Operation Cycle: One complete cycle of a door begins with the door in the closed position. The door is then moved to the open position and back to the closed position. B. Sound Rating: STC (Sound Transmission Class) is a numerical measure of how efficiently the door assembly reduces noise levels. IDI S Vertical Lift Doors designed to reflect OR Absorb sound

Performance Requirements A. Structural Performance: Provide vertical lift doors capable of withstanding the effects Of gravity loads and the following loads and stresses without evidencing permanent deformation of door components: 1.4 Guarantee 1. Wind Load: Uniform pressure (velocity pressure) of 25lbf/sq. ft. (1.2Kpa) acting. Inward and outward Provide to the Owner a written guarantee, warranting the doors against any defects or materials and/or workmanship for the new door for a period of 1 year. With proper maintenance, commencing from the date of final acceptance of the project. Motors shall be guaranteed for a period of 1 year. State that all door and control work that becomes defective during the guarantee period shall be repaired promptly, to the requirements of these Specifications and at no cost to the Owner. 1.5 Quality Assurance Installation work shall only be carried out by the unit manufacturer or by an approved installation specialist properly licensed or franchised for installation work. B. Source Limitations: Obtain sound retardant vertical lift doors through one source from a single manufacturer. 1. Obtain operators and controls from the vertical lift door manufacturer. 2. Inserts & Anchorages: General Contractor shall furnish and install inserts and anchorages that must be built into the masonry for door installation. Door manufacturer shall provide drawings, templates and installation directions. 1.6 Requirements of Regulatory Agencies Equipment and installation shall comply with local, state and federal laws and with other mandatory requirements. Be responsible to insure an installation which is in compliance with such laws and regulations and all changes or alterations required by the authorized inspector or the authority having jurisdiction to be made without increase of subcontract price. Systems shall bear labeling for electrical equipment form the following standards; 1. Underwriters Laboratory 508 Electrical standards. 1.8 Product Delivery, Storage and Handling A. Deliver materials in sequence to meet the installation schedule and arrange ahead for off-the-ground, covered storage locations. Only materials scheduled to be erected within 24 hours may be stored on site. Other materials will have to be stored off site. B. Handle components with care. Protect against damage, dirt, disfigurement and weather

1.9 Submittals A. Submit detailed shop drawings of all work, and list the location in the building for each door. Clearly show and describe in detail, detailed door assemblies, and adjacent construction, including elevations, sections, and details of door, track, hardware, and operating components, dimensions, finishes and relationship of door, frames, track, hardware and operating components to adjacent construction. B. Submit printed operation instructions and maintenance data for the doors as follows: 1. Wiring diagrams: as built straight line wiring and schematic diagrams showing electrical connections and control circuitry. 2. Instructions showing operation. 3. Lubrication chart indicating lubrication points and type of lubricant recommended for equipment. 4. Provide Design calculations to justify the door system meets the required STC value. Part 2-Products 2.1 Manufacturers and Products Manufacturer: Subject to compliance with requirements. Provide products as manufactured by International Door, Inc. (734) 459-3000, designed to reflect or absorb sound with ratings up to STC 55. A. Model # XXX-VLSR-DSI-S (XXX:= 100,200,300,OR400) B. Vertical Lift Doors shall be one, two, three or four leaf types as indicated on contract drawings. 2.2 Door Design Design doors to withstand horizontal wind loads in closed position of 25 pounds per square foot positive and negative wind load. Maximum deflection under full design load shall be 1/120 of the span. B. Design door system including perimeter seals to meet the required Sound Transmission Loss (STC) when tested to satisfy the requirements of ASTM E90-90 and ASTM E413-87 2.3 Materials

Provide electrically operated, insulated with safety controls and provision for manual operation in case of power failure. 2.4 Door Material and Construction A. Stiles and rails shall be of structural steel sections, not smaller than three-inch channels, with all joints welded and ground smooth. Bracing shall consist of horizontal and vertical structural sections, to adequately stiffen the door panels. B. Door leaves shall be faced on the exterior and interior with 14-gauge sheet steel attached to stiles, rails with screws and sound absorbing material between the sheet steel and the door framing members. All sound retardant doors shall be fully insulated with mineral wool sound insulation full thickness of panel and lined inside both faces with ½ thick gypsum board and coated with sound deadening paste. C. Equipment: 1. Vertical Lift Door guides and counterweight box shall be fabricated from structural steel shapes or plates bolted or welded together to give ample strength at their connections in performing their proper functions. Counterweights shall be guided by UHMW for full travel of height. Access to the counter weight box shall be furnished by removable # 14 GA HRS flatsheet covers up to 8-0 high. 2. Provisions shall be made on the leaves for application of any attached hardware. 3. Door leaves shall be suspended on plow steel wire rope from machined steel sheaves and lifting drums to counterweights located at one side of the opening. 4. Sheaves, rollers and drums shall have anti-friction sealed bearings. 5. Wire rope shall have the capacity to sustain the dead weight of the door with an allowance of 25 percent of impact all with a minimum safety factor of 10. D. Provide safety latches on all door leaves that will prevent the door from falling in case of failure of one or more of the supporting cables. When these devices are actuated they must not cause and damage to the door panel or door guides and be reusable. E. Sound Seals: Provide continuous fabric reinforced rubber or neoprene bulb type sound seals at top, meeting rails, bottom and sides. Size sound seals to compress to minimum 50% of original size when door is fully closed. Seals are secured with bolts and continuous steel retainers for easy replacement. Door bottom weather seal shall be a safety type as specified under Reversing Fail Safe Safety Edge F. There shall be no steel to steel contact between door and the guides. Rollers with sealed ball bearings shall guide all panels and support the door leaves against wind and/or side thrust loads.

2.5 Finishes General A. Finish: Gray primer for exposed steel surfaces. 2.4 Electric Door Operators General: Provide electric door operator assembly of size and capacity recommended and provided by door manufacturer for door and operational life specified with electric motor and factory-prewired motor controls, starter, gear-reduction unit, solenoid-operated brake, clutch, remote-control stations, control devices, integral gearing for locking door, sheaves, racks, levers, cables, brakes and accessories required for proper operation. A. Comply with NFPA 70 and NEC 96 B. Furnish all labor and material required for the complete installation of electric door operator for each door, including motor, speed reducers with all gears running in oil, sheaves, cables and brakes. C. Motor shall be 220/440 volt, 3 phase, 60 cycle, totally enclosed, ball bearing, continuous duty and of capacity sufficient to operate the door at specified speed without exceeding a temperature rise of 55 degrees Celsius. Braking device to be operated automatically by a solenoid and be adjustable to suit the requirements of the door. D. Operating mechanism shall include a safety friction clutch, that must be set to allow only slightly more than enough power to reach the door raising mechanism than is required to lift door. If door should become stalled, the clutch must slip free, eliminating the chance for a motor burnout. Clutch must be adjusted to slip slightly each time the motor starts so as to cushion starting and reversing loads. E. Door operator is to be equipped with a disconnecting device, chain or lever operated, which will disconnect the driving unit and engage a chain hoisting arrangement to facilitate the easy operation of the door when the power is off. Motor, brake, hand operation disconnect switch, and open and close limit switches are to be factory mounted and pre-wired to a terminal block n a NEMA 12 enclosure mounted on door operator. All materials necessary for the pre-wired assembly shall conform to J.I.C. electrical standards for equipment and connections. The door contractor shall furnish and install the electric door operator including the motor, with open-close limit switches, hand chain disconnect switched, solenoid, brake, all pre-wired to a terminal box mounted adjacent to the motor. F. Remote-Control Station: Provide momentary-contact, three-button station with pushbutton controls labeled Open, Close and Stop.

1. Provide interior units, full-guarded, surface-mounted, heavy-duty type, with NEMA ICS 6. Type 12 enclosure. 2. Provide exterior units, full-guarded, standard, surface-mounted, weatherproof type.nema ICS 6. Type 4 enclosure. 2.8 Reversing Fail Safe Safety Edge Door manufacturer shall provide and install rubber-encased, reverse action safety mechanism on the electrically-operated sound retardant vertical lift doors. The system is continuously energized and operates through the electrical system to stop the downward travel of the door on contact with an obstruction, providing an instantaneous reversal of the door travel to the full open position. Failure of any component prevents closing of door. A multi-conductor cord from an electrical junction box on the bottom door leaf is provided for the safety edge. The safety edge system shall be catalog # IDI-FSSE-S2K as manufactured by International Door, Inc. 2.9 Emergency Manual Operation A. Provide and install devices and make provisions for emergency manual operation in accordance with the following: emergency chain operation, including plated chain, reduction unit, sheaves, etc., required to provide complete operation from side of door to suit conditions. This device shall be so arranged that when set for manual operation the brake is automatically released and control circuit is broken, making it impossible to operate the doors electrically until the device is set for motor operation. B. Chain gear operators shall be approved type, designed for easy uniform effort. Plated chain shall be installed within easy reach of floor. C. Operators shall be so designed that the electric motor may be removed without affecting manual operation of the door by means of the chain operator. D. Limit Switches: Provide adjustable switches, interlocked with motor controls and set to automatically stop door at fully opened and fully closed positions. E. Pull-Cord Operation as an option: The doors may be operated by a pull-cord device which consists of a switch mounted overhead and away from the door so that a driver may open and close the door without leaving the vehicle. The switch shall be heavyduty, oiltight and weather proof. All relays and contacts to operate and sequence this device shall be included in the control panel. F. Fully Automatic controls as an option: Fully automatic electric control panel includes a flange-mounted, fusible disconnect switch, size 1 reversing starter, fail safe safety edge controls, loop detector amplifier, timers, relays, pilot lights, selector switches, terminal blocks, etc., all built in a NEMA 12 enclosure to conform to JIC automotive standards. Loop detector wires are embedded in floor on either side of

door to open door automatically. Modulated L.E.D. through beam electric eye beams are unbroken. Non-automatic, push button type control systems are available for openings with low volume traffic. G. Electrical power required for standard operators is 220/480 volts, 3 phase, 3 wire, 60 hertz and is to be provided by the electrical contractor Part 3- Execution 3.1 Installation A. Installation of the doors shall be by the manufacturer or a duly authorized agent who is qualified to do this installation. The door installer shall be responsible for mounting the door guides and hanging the door panels plumb and true,accurately counter balancing the door system, installing and adjusting the sound seals. The door installer will make the final adjustments of the limit switches and sound seals to ensure proper operation of the doors B. The door manufacturer shall have total responsibility for the installation of the vertical lift doors C. Koil Kords or S.O. Cords: The Fail Safe Safety Edge shall be wired with a 3 conductor koil kords or 3 conductor S.O. cords. Koil Kords or S.O. Cords shall be furnished by door manufacturer. D. Fully synchronize doors, with the hardware and cables designed so that the door sections move simultaneously, the upper section traveling at a fraction of the speed of the lower sections so that they reach the open or closed position at the same time. 3.2 Adjusting A. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment. B. Any repairs that required an account of faulty materials, workmanship, design or door construction shall be made at no additional charge to the owner. 3.4 Demonstration A. Startup Services: Engage a factory-authorized service representative to perform startup services and to train Owner s maintenance personnel as specified below: B. 1. Train Owner s maintenance personnel on procedures and schedules related to startup and shutdown, troubleshooting, servicing, preventive maintenance and procedures for testing and resetting release devices. 2. Review data in the maintenance manuals. Refer to Division! Section Contract Closeout 3. Schedule training with Owner with at least 7 days advance notice. END OF SECTION 08348