LV Capacitor CLMD03 Power Module Instruction manual

Similar documents
MODVAR Low voltage reactive power compensation modules Installation manual

LV Capacitor CLMD Reliability for Power Factor Correction

CLMD Low-voltage capacitors for reliable power factor correction

APC03 capacitor bank series The ABB comprehensive solution for automatic power factor correction

Low voltage capacitors CLMD Improving power factor and enhancing power quality of your network

LV Capacitor Bank APC

LV Capacitor Bank APC

Technical brochure. The Vector series The ABB comprehensive solution for automatic power factor correction

DYNACOMP. The top-class reactive power compensator

LCL FILTERS INSTRUCTIONS MANUAL (M A) (c) CIRCUTOR S.A.

Chapter 08 Dynamic power factor correction systems (real time PFC) Dynamic power factor correction systems (real time PFC) Optimised, thermal design

CP Automatic capacitor bank

AUTOMATIC CAPACITOR BANK WITH CONTACTOR OPERATIONS

High Reliable Components for Power Factor Correction and Power Quality

PhiCap Capacitors for Power Factor Correction

Three Phase Capacitors KNK

FRANKE. Power Factor Correction GMKP ENERGY. GMKPg Low Voltage Capacitors by Gas Technology Save energy and reduce carbon dioxide emission!

High Reliable Components for Power Factor Correction and Power Quality

multicond Power capacitors Data sheet: multicond

LV Capacitors QCap-L series Capacitors for power factor correction

PhaseCap Premium PFC Capacitors Gas-impregnated n Dry type n Concentric winding n Wavy cut n Triple safety system

HARMONIC FILTER REACTOR

FUSES. Safety through quality

Capacitor Switching Contactors Type K3...-A, K3...-K

PQdynaC High speed, flexibility and modularity

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL

C1000 Series Automatic Cap Bank

NH fuse-links gg 500VAC size 000, 00, 0, 1, 2, 3

Transforming Energy.. For Advanced Technology

PQstorI One stop solution for energy storage and power quality

HHD HIGH VOLTAGE FUSES GERMAN DIN STANDARD. The temperature limiting function of the fuse striker pin. Design and construction.

Automatic capacitor banks

EMPAC Metal enclosed capacitor bank for wind applications

INSTRUCTION MANUAL (M A)

SOLSTART Instruction Manual

LV CAPACITOR BANKS WITH STATIC SWITCHING EMK SERIES

REFERENCE MANUAL FORM: MX-TRM-E REL REV MTE

Film Capacitors Power Factor Correction

Sr. No. Details Page No. 1 MV Capacitor Unit Drawings 3. 2 Technical Perticular for Capacitor Unit 4. 3 MV Surge Capacitor Unit Drawings 6

Capacitors. Individual & fixed bank. Individual & fixed capacitor banks. Low Voltage Network Quality

CTU 02. Thyristor switching module for fast PF compensation. User manual

Power System Solutions (PSS)

AIR CORE REACTORS. Phoenix Electric Corporation

Bussmann series NH catalogue. Leadership in circuit protection

Model Number Structure

MADE IN GERMANY. Components for reactive power compensation. Components for reactive power compensation. Power Quality. Reactive power controllers

Installation and Start-up Guide. ACS-BRK Brake Units

Film Capacitors Power Factor Correction

Medium Voltage Capacitors

NH fuse-links am 690VAC top indicator/live tags size 4, 4a

www. ElectricalPartManuals. com Instruction Bulletin ALTIVAR FLEX58 TRX Adjustable Speed Chassis Drive Controllers Installation Guide

Automatic COSYS PFC. Automatic power factor correction system NEW

Power Factor Correction Equipment

System pro E power Capacitor Bank

PF Guard Power Factor Capacitor Bank Installation, Operation, and Maintenance Manual

amp ramp Operators Manual Page 1 Saftronics 2S Ltd Turnbridge Mills Quay Street Huddersfield West Yorkshire HD1 6QT

Appendix: Safety and application notes for... 15

LINEAR LED DRIVERS. ComfortLine Selectable Current (Output Terminal) ComfortLine SELECTABLE CURRENT (OUTPUT TERMINAL)

Medium Voltage Metal Enclosed Thyristor Switched Harmonic Filter Banks

HIB Enclosed Inverter User Guide

Medium Voltage. Power Factor Correction Reactive Compensation Harmonic Filters. Electrical Power Quality Management at its best.

NEW. Heavy Duty Capacitors. Power Factor Correction Capacitors Type LKT. It s all about saving your money! Features that matter:

Essential equipment for all your requirements

PQactiF Higher flexibility and modularity for improved power quality

B kv T&D GAS INSULATED SWITCHGEAR

Low Voltage Products. Low Voltage Capacitors Power Factor Correction Solutions

INDUSTRIAL POWER SUPPLIES SFL-SERIES

43-SDMS-04 REV. 00 SPECIFICATIONS FOR

POWER FACTOR CORRECTION MOTOR LOAD (ML) FIXED CAPACITOR

NH fuse-links gg 400VAC double indicator/live gripping-lugs size 000, 00, 1, 2, 3

CALTRAP INSTALLATION AND OPERATIONS MANUAL

Power Factor Correction Capacitors Type LKT

Braking Devices BR 230/ Assembly- and Commissioning Instructions

Latch for Contactors 4-pole see page 36. Ratings Rated Aux. Contacts Type Coil voltage 2) AC2 Current Built-in Additional 24 24V= DC 5

RVS-AX Instruction Manual

(with Class-1 AC resistive load) 3. G3PB-215B-2N-VD kW max. (25 A) G3PB-225B-3N-VD 2. G3PB-225B-2N-VD kw max. (35 A) G3PB-235B-3N-VD 2

Manual for Inverter system type PCI05

RSC09 RSC16 RSC22 RSC38 RSC43 RSC63 RSC-AUX

Brake Chopper BC BC 4.1. Instruction and Operation Manual

dv Sentry TM 208V 600V INSTALLATION GUIDE Quick Reference ❶ How to Install Pages 6 14 ❷ Startup/Troubleshooting Pages WARNING

Power Factor Correction Capacitors Type LKT

HHD. High Voltage Fuses German DIN Standard. The temperature limiting function of the fuse striker pin. Design and construction.

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation

ARTECHE LOW VOLTAGE CAPACITOR BANKS. smartbat LV.

1ZSC AAA EN, REV. 7. Transformer bushings type GSBK Technical guide

Matrix AP 400V 690V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 20 ❷ Startup/Troubleshooting Pages WARNING

R.4. Automatic capacitor banks with static system. Power factor correction and harmonic filtering. Homepage :

Appendix: Safety and application notes for 19

1ZSC AAA en, Rev. 6. Resin impregnated paper bushing, oil to SF 6., type GSBK Technical guide

Index Low Voltage Network Quality. Low Voltage Network Quality

Domae. The right solution for distribution boards

Power Factor Correction Capacitors Type LKT

ACC Series Power Conditioner OPERATION & INSTALLATION MANUAL

Switch Disconnectors. SENTRON 3NP5 Fuse Switch Disconnectors up to 630 A. Introduction. 7/106 Siemens LV

ROBUST LED DRIVERS. EasyLine Industry. EasyLine INDUSTRY , , , , , , ,

ABB November 16, 2016 Slide 1

Power factor correction Harmonic filtering Dynamic flicker compensation

FIXED POWER FACTOR CORRECTION EQUIPMENT 5KV CLASS MEDIUM VOLTAGE SECTION Z

RE-PR1-F 1-Phase Din-Rail Mount 1.5, 3 & 6kW

Power Factor Correction Capacitors in sheet steel cases

Transcription:

LV Capacitor CLMD03 Power Module Instruction manual

Table of Contents 1 Safety... 3 2 Upon reception... 3 2.1 Inspection on reception... 3 2.2 Storage- transportation handling... 3 3 Hardware Description... 4 3.1 CLMD03 Power module layout... 4 3.2 CLMD03 power module dimensions... 5 4 Power module installation... 6 4.1 Mechanical installation... 6 4.2 Airflow and cooling requirement... 7 4.3 Electrical Installation... 9 4.3.1 Electrical connection overview... 9 4.3.2 Cable sizing... 9 4.3.3 Contactor for capacitor switching... 10 4.3.4 Earthing... 10 4.3.5 Fuses... 10 5 Commissioning... 11 6 Operation... 11 7 Maintenance... 11 8 Detailed technical specification... 12 2 Table of contents CLMD03 Power Module Instruction manual

Before installation, read this notice carefully and keep it at disposal of people in charge of installation, maintenance and operation. 1 Safety For a safe use of CLMD capacitor units, please ensure: Installation and maintenance are undertaken only by authorized and qualified personnel, in accordance with current local regulations; Isolate the equipment from the supply before working Wait 5 min. after isolating supply before handling. After 5 min, short-circuit the capacitor terminals with a piece of insulated cable to confirm discharge. Failure to respect the safety rules may lead to bodily injury, premature failure, or other material damage to installations. 2 Upon reception 2.1 Inspection on reception Inspect the packing and immediately report any damages Unpack the CLMD03 POWER MODULE and check that: 2.2 Storage- transportation handling data on the label correspond to those of your purchase order CLMD03 POWER MODULE is not damaged. Any loss or damage should be notified immediately to your closest ABB agent. Indoor, in dry, dust free and non-corrosive environments, protected from vibrations or shocks. Storage in initial packing is recommended Storage temperature: minimum: -40 C/-40 F. maximum: 75 C/167 F. CLMD03 Power Module Instruction manual Safety Upon reception 3

3 Hardware Description 3.1 CLMD03 Power module layout Two types of CLMD03 POWER MODULES exist: CLMD03 POWER MODULE to be connected with a reactor. CLMD03 POWER MODULE to be connected without reactor. CLMD03 Power Module to be connected with a reactor 1. Contactor 2. Cables from capacitor to contactor (provided) 3. Discharge resistor 4. Fuses & fuse holder 5. Capacitor CLMD03 Power Module to be connected without reactor 1. Contactor 2. Cables from contactor to fuse (provided) 3. Cables from capacitor to contactor (provided) 4. Discharge Resistor 5. Fuses & fuse holder 6. Capacitor Please refer to 4.3.1 for the electrical drawings that present the parts included or not for both versions of the product. 4 Hardware description CLMD03 Power Module Instruction manual

3.2 CLMD03 power module dimensions CLMD03 Power Module Instruction manual Hardware description 5

4 Power module installation 4.1 Mechanical installation CLMD03 Power Module must be fixed VERTICALLY so as to allow airflow circulation (see blue arrows in the figure below). CLMD03 POWER MODULE must be fixed on a rigid plate/frame with four M6 screws, nuts and washers (not provided). Make sure that the rigidity of the support and the screws are sufficient to bear the weight (about 9 kg) of the CLMD03 POWER MODULE(s). CLMD03 POWER MODULE can be mounted in 2 different positions: totally inside its enclosure or partly external to the enclosure as illustrated at the next page. Clearances: 25 mm to walls and flange to flange between modules. 6 Power module installation CLMD03 Power Module Instruction manual

CLMD03 Power Module totally mounted inside its enclosure The capacitor of the power module must be located in a specific air duct (vertical row) with forced ventilation (refer to 4.2 Airflow and cooling requirement) with cylindrical links vertical. The other components of the CLMD03 POWER MODULE (contactor, fuses, discharge resistor and cables) must be cooled with forced air cooling as well. Rules of good practice: When reactors are used they should be placed in such a way that they do not radiate heat directly on the capacitors. A thermal barrier is recommended CLMD03 Power Module mounted partly outside its enclosure In such mounting, Capacitor cylinders are located outside the enclosure. Cylinders are naturally air cooled as they are oriented outside the enclosure. Cylinders must not be heated by external source of heat. A clearance distance of minimum 25 mm must be respected between the cylinders and the wall. Inside the enclosure, the other components of the CLMD03 POWER MODULE (contactor, fuse, discharge resistor and cables) must also be cooled with forced air cooling (refer to 4.2 Airflow and cooling requirement) 4.2 Airflow and cooling requirement The service conditions specified in the IEC 60831 1 4 are applicable. As per IEC 60831-1 3.21, the ambient temperature for capacitors is the temperature around the capacitors itself and not around the cubicle. CLMD03 Power Module Instruction manual Power module installation 7

CLMD03 Power Module totally mounted inside its enclosure The cross-section of air inlet and outlet must be adapted to the air flow. Air should flow from the bottom to the top of the cubicle as illustrated on the opposite picture. One fan per 6 PMOD03 columns blowing a minimum air flow of 420 m³/h is requested. Design guideline: Difference between ambient temperature outside the cubicle and measured temperature must be lower than 22.5 C. To meet that requirement, the temperature probe must be located at about 2/3 of the air duct, attached to the central cylinder of the CLMD03 POWER MODULE, as per (1) of present drawing. Internal capacitors rear view CLMD03 Power Module mounted partly outside its enclosure CLMD03 capacitor cylinders are natural air cooled. Air must circulate freely around the cylinders at least one meter below and above them without any other source of heat around them. Inside the cubicle, an air forced ventilation has to be ensured by a fan of 170 m³/h. External capacitors left view Note: The use of an over temperature protection can be performed by the RVT temperature probe in order to switch the bank off in case of fan failure or over temperature due to other causes. 8 Power module installation CLMD03 Power Module Instruction manual

4.3 Electrical Installation 4.3.1 Electrical connection overview CLMD03 Power Module to be connected without reactor CLMD03 Power Module to be connected without reactor 1. Capacitor 2. Cable from capacitor to contactor (provided) 3. Contactor 4. Cable from contactor to fuse (provided) 5. Fuse 1. Capacitor 2. Cable from capacitor to contactor (provided) 3. Contactor 4. Cable from contactor to reactor (not provided) 5. Reactor (not provided) 6. Cable from reactor to fuse (not provided) 7. Fuse 4.3.2 Cable sizing The cables must be sized for a current of 1.5 times nominal current (In) minimum. The nominal current can be calculated with the following formula: In = Qn Vn 3 Where: Qn is the capacitor rated reactive power Vn is the capacitor rated voltage The temperature around the cables must also be considered according to cable manufacturer. Note: In case of CLMD03 POWER MODULE connected without reactor, it is necessary to add additional inductance to attenuate the inrush peak current. A practical method for making additional inductance is simply made by winding the cables designed to connect CLMD03 Power Module Instruction manual Power module installation 9

the Power Module onto a cylinder. For more details please refer to the Attenuation of the Inrush Peak chapter of the ABB UA contactor manual. 4.3.3 Contactor for capacitor switching Capacitor switching leads to transient operating conditions. Therefore, the use of standard contactors is not acceptable and can be dangerous for the safety of people as well as the installations. The ABB UA50 and UA75 contactors are specially designed to control capacitors whose inrush current peaks are less than or equal to 100 times nominal rms current. Please refer to the ABB contactors for capacitor switching application guide for the conductor s dimensions as well as the additional inductance in case of inrush current peak. 4.3.4 Earthing Earthing is achieved through fixation points of the CLMD03 POWER MODULE. An extra cable between the CLMD03 POWER MODULE enclosure and the earthing contact of the installation is therefore required in case the CLMD03 POWER MODULE unit is fixed to an isolating material. 4.3.5 Fuses The fuses are made with non-isolated gripping lugs, double indicator and contact blades compliant to DIN VDE 0636 Part 201 and IEC 60269-2-1. The NH system is classed among plug-in fuse systems M8 cable shoes are fixed with M8 screw and nuts (both not provided) on the fuse terminal. While tightening the bolt, a dedicated torque must be applied for proper electrical connection according to the applicable standards. 10 Power module installation CLMD03 Power Module Instruction manual

5 Commissioning With the equipment isolated from the supply, check: Cabling is properly connected (including earth) Ambient ventilation is adequate Correct tightness of the connections 6 Operation The CLMD03 POWER MODULE capacitor unit is delivered with factory-installed discharge resistors to comply with IEC 60831 and allow a decrease of the residual voltage to less than 50V after 1 min. disconnection from supply. During operation, make sure the delay before the CLMD03 is re-energized is not shorter than 40 sec. Failure to follow this rule may cause damage and reduce the lifetime of the capacitor. Like other standard capacitor units, CLMD03 POWER MODULE discharge devices are not suitable for use with rapid switching rates like thyristor switched banks (minimum off time: 40 sec). Additional external resistors are not a solution for such cases. Only specially designed capacitors must be used in such applications. Please contact ABB. Harmonics Installation of capacitors on networks disturbed by harmonics may require special precautions especially when there is a risk of resonance phenomena. Please ensure that your installation is as per the over current rating as per IEC 60831 Standard. Please contact ABB for technical support. 7 Maintenance Ensure safety procedures are completed (see paragraph Safety ) Maintenance frequency depends on working conditions. At least a yearly maintenance should include: Removal of dust deposits, cleaning of all parts; Check of tightness of all electrical connections; Check of ambient temperature; Check condition of discharge resistors. CLMD03 Power Module Instruction manual Commissioning Operation - Maintenance 11

8 Detailed technical specification Voltage range Connection Net output power Q N Discharge resistors Terminals Earth Case material Color Fixing Execution Protection degree (according to IEC 60529) Weight Maximum ambient temperature Minimum ambient temperature Fuse Contactor Clearance Capacitor losses Contactor and fuses losses 400V and 415V at 50Hz 380V and 480V at 60Hz For other values, please consult us Three-phase 25 or 50 kvar Included Discharge: less than 50V in 1 minute Fuse: M8 threaded terminals Contactor: UA50 and UA75 Earth connection on the enclosure flange M6 Aluminum Raw aluminum Four slots for M6 screws (12x7mm) on the upper flange Indoor IP00 Approx. 9 kg Class D according to IEC60831: Maximum average over 1 year: 35 C Maximum average over 24h: 45 C Maximum: 55 C -25 C ABB gg or gl 50, 63, 100 and 125 A ABB UA50 for 25kvar ABB UA75 for 50 kvar Control voltage: 230V at 50Hz 120V at 60Hz 25 mm minimum to walls Flange to flange between power modules Less than 0.5 W/kvar (discharge resistor losses included) With UA50 contactor: 0.53 W/kvar With UA75 contactor: 0.82 W/kvar Tolerance on capacitance 0% +10 % Capacitor voltage test Between terminals: 2.15xUn for 10 seconds Between terminals and earth: 3kV for 10 sec: Un 450V 4kV for 10 sec: Un > 450V Lightning impulse voltage : 8 kv: Un 690V 12 Detailed technical specification CLMD03 Power Module Instruction manual

Overload capability (according to IEC 60831) Altitude Overvoltage tolerance: 10% for maximum 8h in every 24h and 30% for maximum 1min Maximum permissible current: 1.3x In. Up to 1000m Compliance IEC 60831 part 1 & 2 CE marked Dimensions Cooling If the capacitors are placed externally: natural cooling for capacitors and forced air cooling for internal parts Label If the capacitors are placed internally: forced air cooling CLMD03 Power Module Instruction manual Detailed technical specification 13

Contact us ABB n.v. Power Quality Products Avenue Centrale 10 Zoning Industriel de Jumet B-6040 Charleroi (Jumet), Belgium Phone: +32(0) 71 250 811 Fax: +32 (0) 71 344 007 E-Mail: Power.Quality@be.abb.com www.abb.com/lowvoltage Copyright 2012 ABB.2GCS204011A0030 November 2012