A. This section includes unit capacitors for power factor correction.

Similar documents
A. This section includes enclosed dry type transformers for lighting and power loads, with primaries and secondaries rated 600 volts and less.

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

A. Submit manufacturer's literature and technical data before starting work.

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

A. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified.

SECTION PANELBOARDS

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

Generator Fire Safety: Generator assemblies should be located outside the building.

SECTION MOTOR CONTROL

Medium Voltage Metal-Enclosed Switches

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents

Medium Voltage Metal-Enclosed Switches

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

Low Voltage Switchgear Type WL Low Voltage Metal-Enclosed Switchgear

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

10 Commercial, Industrial, Agricultural Services

www. ElectricalPartManuals. com Section 13 Switchgear Low Voltage

SECTION SWITCHGEAR. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

Busway Construction. Bus Bars

WARREN COUNTY, N.Y. M/E REFERENCE

Chapter 6 Generator-Voltage System

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

CONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS

CHAPTER V RESIDENTIAL WIRING

Design Standard. Purpose: Design Standard:

Applications. Trim are flat gauge steel per code. Standard painted finish ANSI 61 gray. Directory card with plastic cover on front of trim

1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces.

SECTION ELECTRICAL DESIGN AND CONSTRUCTION STANDARDS _ February A. Use heavy duty type fused and non-fused, enclosed switches only.

16.13 Unit Substation to 15kV Construction Standards Page 1 of 7

Critical Power Switchboards. Selection and Application Guide

DIVISION 26 ELECTRICAL SECTION CIRCUIT BREAKERS

Specification Number: Product Name: GROUP MOUNTED MAIN FUSIBLE SWITCH, GROUP MOUNTED BRANCH FUSIBLE SWITCH (LONG) SECTION

7. SERVICES OVER 600 VOLTS

Metering and Service Installation:

IN2 Enclosed Switches and Circuit Breakers

TEMPORARY ELECTRIC WIRING FOR CARNIVALS, CONVENTIONS, EXHIBITIONS, FAIRS AND SIMILAR USES

Service Entrance Methods

Customer Requirements Downtown Secondary Network Service

Quik-Spec Coordination Panelboard Specifications

A. Provide a complete system of overcurrent protective devises as indicated on the drawings, and as specified herein.

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

SECTION ELECTRIC DISTRIBUTION

Issued Revised Approved Reviewed October 31, 1984 October 22, 2002 J. Ross J. Fuller

SWITCHGEAR DIVISION PRODUCT PROFILES

Eielson AFB Electrical Design Standard 09 September 2016

SECTION LOW VOLTAGE SWITCHBOARDS - Spectra Bolt-On

1. Field verify measurements and circuiting arrangements as shown on as-built drawings.

COMMERCIAL QUICK REFERENCE

GE 8000-Line Motor Control Centers

Corrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections

SECTION LOW VOLTAGE SWITCHBOARDS - SPECTRA. A. The requirements of the Contract, Division 1, and Division 16 apply to work in this Section.

AREA OF WORK ENERGY

University of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL

Thomas R. Proctor High School

Three-Phase Pole Mounted Recloser

9. Non-Residential Services (Commercial, Industrial, and Agricultural)

2010 PM CM ELECTRICAL. The High-Velocity Edge: Achieving Operational Excellence. 21st Annual Conference

CONTENTS. B. System Design and Performance Requirements

9/7/2010. Objectives. Article 90. Introduction NEC Significant Changes. Review significant revisions in the 2011 NEC

Spring Test 10 due 05/11/2013

1. Division 26 Section "Elevator Shunt-Trip Fused Disconnect Switches".

SECTION V SWITCHBOARD I 4 Engine/Gen Control Cubicles II 1 Synchronizing System III 1 Ground Detection Network IV 1 600V Feeder Section V 2

ENTRANCE EQUIPMENT ER D PAGE 1 OF 5

Mar H: SUPPLEMENTAL PARALLELING GEAR (16315-H)

9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc.

ATLV MaxSG. Low Voltage Metal Enclosed Switchgear

Electrical Switchgear Replacement Montgomery County Community College

EMERGENCY GENERATOR SET

Approved Meter Sockets and Cabinets

SECTION DISTRIBUTION AND GROUNDING

Midwest Dry Type Transformers

GE 8000-Line Motor Control Centers Mains, Feeders, Incoming Lines C-1

Pretest Module 24 Three-phase Service Entrance

RESIDENTIAL SUBDIVISION SERVICE REQUIREMENTS SECTION VI RESIDENTIAL SUBDIVISION SERVICE REQUIREMENTS

QMB Panel boards Switchboards. 200,000A. short circuit rating. www. ElectricalPartManuals. com

Power Quality and Protective Device Coordination: Problems & Solutions Part 1 Undersizing of Utility Main Service Transformers

Approved Contractor Construction e-guide Residential Commercial

MEDIUM-VOLTAGE SWITCHGEAR

DRAFT. Western Michigan University Campus Facilities

UNDERGROUND SERVICES - SECONDARY

Electrical Depth. Josh Kreutzberger Lighting/Electrical

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position

Horizontal Circuit Switchers

University of California, San Diego Cal (IT) 2 Technical Assignment #2. Brian Smith

Horizontal Circuit Switchers

Outdoor Power Transmission & Distribution

SIGNAL WORDS QUALIFIED PERSON

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008

Transcription:

PART 1: GENERAL 1.01 Wiring Devices A. This section of the standard includes design requirements for wiring connections, including receptacles and switches to equipment specified in other sections. 1.02 Dry Type Transformers A. This section includes enclosed dry type transformers for lighting and power loads, with primaries and secondaries rated 600 volts and less. 1.03 LV Power Factor Capacitors A. This section includes unit capacitors for power factor correction. B. Reference Utility Specifications. 1.04 Disconnect Switches A. This section includes enclosed switches for use as disconnects in service and distribution systems rated 600 volts and less. 1.05 Metal Enclosed Distribution Switchgear A. This section includes metal enclosed switchgear for application at 600 volts and less. B. Reference Utility Specifications. 1.06 Panelboards A. This section includes enclosed fusible switch and circuit breaker panelboards for feeders, and circuit breaker type lighting and appliance branch circuit panelboards. 1.07 Busway A. This section includes feeder and plug-in busway in ratings 150 amperes to 5000 amperes, 600 volts and less. 1.08 Reference Standard A. Reference standard 6.26.05 Common Work Results for Electrical for related information on underground ducts and manholes, building wire and cable, raceways and boxes, cabletrays, full short circuit device, coordination and arc fault study, and enclosed switches. PART 2: PRODUCTS Design & Construction Standards - Revised January 2013 5.26.20-1

2.01 Wiring Devices A. Electrical Requirements B. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality. C. Minimum 20 ampere rated switches shall be used for lighting and power loads. In cases where wall dimmers are used, the dimmer shall be solid-state design with flicker noise control. Minimum accepted manufacturer and quality Lutron Nova T Series. D. Device faceplates shall be smooth finish hard plastic. Project Service Provide (PSP) shall coordinate color requirements with building architect. Use of vinyl faceplates is strictly prohibited. Galvanized face plates shall be used for all surface mounted devices. For Occupancy sensors and other lighting design control strategies, refer to Standard 5.26.50. 2.02 Dry Type Transformers A. Up to 5 kva: (1ph and 3ph) shall be totally enclosed, self-cooled dry-type with a 150 C insulation system that will not exceed a 80 C rise at a maximum ambient temperature of 40 degrees C. B. 5 kva to 25 kva: (1ph and 3ph) shall be totally enclosed, solid fill, self-cooled with a 180 C insulation system that will not exceed a 110 C rise at maximum ambient temperature of 40 degrees. C. 30 kva and above: shall be open, self-cooled dry-type, designed for free convection of air through the windings with a 220 C insulation system that will not exceed a 150 C rise at maximum ambient temperature of 40 C. D. Taps in the high voltage winding shall be four each 2-1/2% FCBN for the following ratings: 30 KVA and above, three phase; 5 KVA through 25 KVA, single phase. Taps shall be two each 5% FCBN for all other units except that units rated below 1.0 KVA do not require taps. Additional or smaller taps may be supplied (10% total BN required) if it is the manufacturer s standard. E. Transformers used to supply 120 volt lighting or other circuits from 277 volt lighting circuits shall have a Bussmann type HPC fuse holder mounted in the terminal connection compartment, connected to the primary, with a properly rated Bussmann type KTK fuse, removable from outside the connection compartment. F. Transformer windings can be copper or aluminum. 2.03 LV Power Factor Capacitors Design & Construction Standards - Revised January 2013 5.26.20-2

A. The capacitor unit shall be indoor, metal enclosed, and factory assembled, prewired tested and ready for installation. B. Capacitor unit shall be sized such that the building will operate at no worse than 95% power factor. C. Capacitor bank shall be rated for a life expectancy of at least 20 years. The enclosure shall be freestanding type NEMA 12. The assembly shall be accessible from the front with a continuously hinged door with a three point locking handle mechanism. D. All capacitor cells shall be three phase industrial grade, metal encased, utilizing threaded type terminals installed with insulating plastic terminal plate. Only three phase units shall be furnished. Single phase units that have been interconnected shall not be allowed. The capacitors shall be specifically designed for power factor correction and continuous duty. E. The following control type items shall be included with each assembly: 1. A microprocessor based field programmable automatic power factor controller shall be provided and designed with the following features: a. Digital LED readout or meter indication of actual power factor and power factor setpoint. The setpoint shall be continually adjustable to settings that are leading or lagging from 0.7 inductive to 0.7 capacitive. b. Capacitor step display on number of steps activated and the number available. c. Automatic or manual mode of operation. 2. Instrument transformers shall be provided for the necessary inputs into the automatic controller. Control and potential transformers shall be appropriately fused on both sides of the primary and secondary. 3. Control power transformers shall be provided, if required, for the contractors and associated equipment. 2.04 Disconnect Switches A. Use heavy duty type non-fused, enclosed switches only. 2.05 Metal Enclosed Distribution Switchgear A. Switchgear shall be metal enclosed construction, front and rear access, NEMA 1 dripproof, ANSI C37/UL1558, rated 600V and shall operate on a 480/277 or 208/120 volt, three-phase, solidly grounded wye, 60 Hz system. The switchboard shall be designed in accordance with the latest NEMA, ANSI, and IEEE standards applicable to this equipment. These standards shall be referenced in the project specifications. B. Use only ANSI C37.15/UL1066, drawout mounted, power circuit breakers in the switchgear. Design & Construction Standards - Revised January 2013 5.26.20-3

C. Metering: 1. Coordinate location of metering requirements with The University. If metering at the distribution switchboard is required use the Square D Ion 8600. 2. Submetering shall be Square D PM820. D. Bussing 1. The bus shall be insulated copper with a current density of 1000A/ in2. The insulation shall be class B (130 degree C) rated material. Bus connections (including the tie bus) shall be accessible from the rear of the switchboard. All bussing shall be braced for the maximum available fault current. 2. Neutral bars shall be full capacity rated. 3. Provide a ground bus through the full length of each section of the switchboard. 4. Provide a disconnecting means for the neutral either in the form of a link, or similar conducting piece, designed to make connection between two suitable terminals or consisting of a terminal plate or stud provided with a suitable wire connection. Simple removal of bolts from a single bus bar is not acceptable. E. Professional Service Provider (PSP) shall require the manufacturer to provide a mimic bus. Show bussing, connections and devices in single line form using black laminated plastic strips securely attached on the front panels of the switchboard. F. Main and Tie section devices shall be individually mounted and compartmented. G. Distribution section devices shall be individually mounted and compartmented. H. Auxiliary section devices shall be individually mounted and compartmented. I. Provide switchboard on 4 housekeeping pad with suitable angle iron embedded in concrete to allow for proper alignment and anchoring as recommended by the manufacturer. J. Future provisions: Switchboard shall be designed with future spaces (15% minimum) equipped with breakers and such that the future additions may be readily made in the field. K. The power circuit breakers shall be equipped with a solid state tripping system consisting of individual phase monitoring current sensors, a solid state processing device, and a flux transfer shunt trip. The following protective modes or the equivalents shall be provided as a part of the solid state tripping: 1. All breakers shall have long-time pick-up of at least to 1.25 times sensor rating and a long time delay of at least 4 to 36 seconds at 6 times sensor rating. 2. All breakers shall have short time pick-up of at least 4 to 12 times sensor rating and a short delay time of at least to 0.05 seconds at 2.5 times short delay pick-up. 3. Only the feeder breakers shall have instantaneous pick-up (At least 4 to 12 times sensor rating). Instantaneous operation is not required on the Mains or Tie breakers. If provided instantaneous element must be capable of being disabled. Design & Construction Standards - Revised January 2013 5.26.20-4

4. Ground fault protection is required and shall include zone interlocking between feeder circuits and the appropriate main breaker. L. A redundant and remote set of circuit breaker control switches, for the mains and tie circuit breakers, consisting of the following shall be provided: 2.06 Panelboards 1. 1 NEMA 12 hinged door enclosure, at one end of the switchgear, determined according to a safe egress route, containing wired, redundant, circuit breaker control switches, and comprised of the following: a. 3 ea. - Circuit breaker control switches. Westinghouse type W2, or equal; b. 3 ea. - Red "breaker on" light. Data Display Products, or equal; c. 3 ea.- Green "breaker off" light. Data Display Products, or equal; d. Necessary wiring, conduit, etc. to interconnect and provide remote operational circuit breaker control switching. A. Panelboard bus shall be 98% conductivity copper. Bus shall be installed completely throughout panel to permit addition of new bolt-on breakers in available space in future without modifying bus. B. All panelboards shall have door locks. The front cover shall be a door in door arrangement with the inner door hinged to allow breaker handle access. 2.07 Busway A. Provide copper busway only. B. Service entrance busway to be furnished with switchgear and include 240 volt rated space heaters to operate at 120 volts. PART 3: EXECUTION 3.01 Wiring Devices A. Modular Furniture Spine (no telecommunications outlets) shall not be connected to a general purpose receptacle and must be connected by a furniture whip. B. A typical single person office space should contain a minimum of two duplex receptacles and two communications outlets as shown in the diagram below. Locate the power and data outlets according to the typical office detail 6.26.20-1. 3.02 Wiring Devices A. A typical open office cubicle shall contain a minimum of two duplex receptacles and one communications outlet per workstation. Locate the power and data outlets according to the typical office detail 6.26.20-2. Design & Construction Standards - Revised January 2013 5.26.20-5

B. Locate power and communications outlets in interior walls shall be approved on a project specific basis. Do not locate any outlets on exterior walls under windows or on the exterior of the building. C. Mounting heights for devices shall be as follows: 1. Wall switches and dimmers -- 48 Aff. 2. Receptacles -- 18 Aff. 3. Heights are to center of outlet boxes 3.03 Dry Type Transformers A. Larger transformers for facilities shall be designed for location on the ground floor if possible. The PSP is responsible for coordinating maximum transformer weights and anticipated floor loading with the project structural engineer. B. Transformers installed in electrical rooms shall be designed and sized in coordination with architect and door dimensions. All transformers sized above 225 kva shall require double doors or doors in excess of standard 36 width. C. Transformers 15 kva and above are to be floor mounted. Up to 15 kva may be wall or trapeze mounted if appropriate for the room layout. D. PSP shall provide detail layouts of electrical rooms indicating transformer locations drawn to scale with special mounting instructions as appropriate. E. All transformers are to be given an alphanumeric label that will relate the transformer on the room detail to the transformer on the single line diagram. Design & Construction Standards - Revised January 2013 5.26.20-6

F. The single line diagram shall indicate the alphanumeric identifier, the transformer size (kva), and the primary and secondary voltages. G. Transformers for Non-Linear Loads (K-rated) shall be used at the PSP s discretion. 3.04 LV Power Factor Capacitors A. The PSP shall show on the single line diagram the planned locations for installing power factor correction capacitor banks. B. The drawings shall also indicate location of the capacitor banks in a detail of the electrical room layout. C. The capacitor assembly shall be installed a minimum of 200 feet measured along the electrical route from the nearest SCR drive or as indicated in the VFD manufacturer s Harmonic Analysis Study. 3.05 Disconnect Switches A. The top of the handle shall be no more than 6 6 above finished floor. 3.06 Metal Enclosed Distribution Switchgear A. PSP shall show equipment room layout, drawn to scale, indicating location of equipment and busway routing for interconnection. B. PSP shall label the switchboard consistently on the single-line diagram and the room layout. C. Single-line diagram shall indicate board size and required short circuit rating. D. PSP shall furnish a detailed specification indicating detailed control wiring, meter requirements and special construction requirements not outlined in the design standard. 3.07 Panelboards A. Branch circuit panelboards shall not serve loads on more than one level of a building. B. Molded case circuit breakers shall be bolt-on type only. Design & Construction Standards - Revised January 2013 5.26.20-7

C. Do not mount panelboards in hallways or other public spaces. Where an obsolete panel is being replaced in an existing public space, the new panel shall be flush mounted. D. Provide a separate panelboard for labs or other high density electrical utilization equipment spaces where the power requirements exceed 12 poles, and locate the panelboard near the entrance to and within the space. Provide door locks on all panelboards. E. Lighting panelboards shall serve only lighting loads and should contain 15% spare capacity in both load and circuit breaker count. F. Receptacle panelboards, power distribution panelboards, main switchboards and motor control centers should contain 25% minimum spare capacity in both load and circuit breaker count. G. Panelboards should be designed in the electrical room detail layout such that feeder piping is minimized and installed efficiently. Provide a minimum of two 1 empty conduits from each flush mounted panel to an accessible point above the ceiling. H. Panelboards shown on single line diagram shall indicate required short circuit amps interrupting capacity (AIC) rating. (May be shown in panel schedules if single-line diagram not appropriate.) I. Provide panel locations drawn to scale in electric room detail plans. J. Panelboards shall be labeled with a descriptor indicating location, reference voltage level, and primary loads served. K. Panel schedules shall be provided indicating panel size, AIC rating, whether main circuit breaker or main lug only style, main breaker size. Panel schedules shall indicate load information in kva per phase. L. Distribution panelboards (400A & up) shall have a minimum of 10 of gutter space on both sides. M. Label utilization equipment with circuit number. 3.08 Busway Design & Construction Standards - Revised January 2013 5.26.20-8

A. Clearly indicate bus duct ratings and locations on drawings Room Use Type of Fixture Lamps Fixture Efficiency Classroom, library, office Kitchen, machine shop, laboratory Conference room Lobby, lounge, reception, copy room, exhibit hall, dining, food court, locker, study and common area Lensed or louvered fluorescent Lensed or wrap around fixtures Lensed or louvered fluorescent Optional fluorescent wall washers Lensed or louvered fluorescent 2 T8, 28 watt, 2 to 3 T8, 28 watt, 2 T8, 28 watt, Recommended average light levels 80% or greater 45 to 55 foot candles at work surface 80% or greater 50 to 65 foot candles at work surface 80% or greater 35 to 45 foot candles at work surface CFL 60% or greater NA 2 T8, 28 watt, Restroom Lensed fluorescent 2 T8, 28 watt, Corridor with Lensed or louvered 2 T8, 28 watt, exhibit space fluorescent 80% or greater 20 to 35 foot candles at 30 AFF 80% or greater 20 to 25 foot candles at 30 AFF 80% or greater 30 to 40 foot 60% or greater candles at floor level Optional fluorescent wall CFL 60% or greater NA washers Stairway, corridor Commensurate with architectural finish of space 2 T8, 28 watt, 80% or greater 15 to 25 foot candles at floor level Storage, mech/elec room Industrial fluorescent 2 T8, 28 watt, 80% or greater 20 to 30 foot candles at 30 AFF Computer room 18 cell 3 parabolic i.e. 2 T8, 28 watt, 65% or greater Lithonia 2PM3N series Exhibit LED or fluorescent wall Varies Varies Varies wash or track Sidewalk Pole-mount with cut off LED or pulse start MH 1 to 2 foot candles at ground level Parking Pole-mount with cut off LED or pulse start MH 8 to 10 foot candles at ground level UT shuttle stops Varies Induction or pulse start MH 10 to 20 foot candles at ground High bay areas High bay fluorescent Varies-T8, 28 watt, 4100k level 80% or greater Varies based on function of space END OF STANDARD Design & Construction Standards - Revised January 2013 5.26.20-9