Reactive power compensation: a basic overview

Similar documents
The Contactor. Antonino Daviu, Jose Alfonso Departamento de Ingeniería Eléctrica. Universitat Politècnica de València

Pump ED 101. Power Factor (Part 2) - - Electricity Behaving Better

Eskisehir Light Train- Correcting Capacitive

Chapter 3.1: Electrical System

Power Factor Correction

INVESTIGATION ONE: WHAT DOES A VOLTMETER DO? How Are Values of Circuit Variables Measured?

AGN Unbalanced Loads

Chapter 21 Practical Electricity

EPRLAB FAQ v1.0 Page 1 / 8 Copyright EPRLAB December 2015

POWER FACTOR CORRECTION OF FAST DYNAMICS INDUSTRIAL LOADS

HomeCap: Residential Power Factor Correction

ELECTRIC POWER AND HOUSEHOLD CIRCUITS

Reactive Power Compensation using 12 MVA Capacitor Bank in 132/33 KV Distribution Substation

Advanced Protective Relay Training

DC CIRCUITS ELECTROMAGNETISM

Power Quality Luis Vargas Research Engineer 9/18/2008

A Review on Reactive Power Compensation Technologies

Higher National Unit Specification. General information for centres. Electrical Motors and Motor Starting. Unit code: DV9M 34

Safe, fast HV circuit breaker testing with DualGround technology

Power Quality. Power Factor Wiring and Service. Background. Introduction. bchydro.com

The Language of Physics

Microcontroller Based Power Factor Correction Using SCR

HOKKIM. Control & Protection Relays. giving you control. Utilization: Power Factor Regulator : 14-STEP CYCLIC POWER FACTOR REGULATOR.

Electrical Power Systems 2014/15

10. Starting Method for Induction Motors

POWER FACTOR REBATE-BOLD DECISION FROM REGULATOR

The Wound-Rotor Induction Motor Part I

ITT Technical Institute. ET3480T Power Systems Onsite Course SYLLABUS

American Journal of Science, Engineering and Technology

Working Principle of Power Saver as per Manufacture:

STEP Motor Control Centers

Date: Name: ID: LABORATORY EXPERIMENT NO. 8 INDUCTION MOTOR/GENERATOR 8-1

FLUORESCENT INDUCTION

Iowa State University Electrical and Computer Engineering. E E 452. Electric Machines and Power Electronic Drives

EFFECT OF CAPACITOR ON STARTING & RUNNING OF SINGLE PHASE INDUCTION MOTOR

Effect of prime mover speed on power factor of Grid Connected low capacity Induction Generator (GCIG)

R07 SET - 1

Application of AC Three-Phase Induction Motor of Squirrel Cage AEL-ACINA

Module 9. DC Machines. Version 2 EE IIT, Kharagpur

ELECTRIC CURRENT. Name(s)

MU MMMREV.2 09/01 UNI EN ISO ELECTRONIC POWER FACTOR REGULATOR type QR INSTRUCTION MANUAL PAG. 7

Maximizing the Power Efficiency of Integrated High-Voltage Generators

Electricity Course. Part B Course Outline

Section 6 HOW ARE VALUES OF CIRCUIT VARIABLES MEASURED?

CHAPTER 3 TRANSIENT STABILITY ENHANCEMENT IN A REAL TIME SYSTEM USING STATCOM

Concepts And Application Of Flexible Alternating Current Transmission System (FACTS) In Electric Power Network

THE BEST ELECTRICAL CONTROLS BUSINESS ON THE PLANET! Unmatched Service Superior Product Quality Advantage Pricing

Is Uncorrected Power Factor Costing You Money?

Application of AC Dahlander Three-Phase Induction Motor AEL-ACDHA

EXPERIMENT CALIBRATION OF 1PHASE ENERGY METER

Dynamics of Machines. Prof. Amitabha Ghosh. Department of Mechanical Engineering. Indian Institute of Technology, Kanpur. Module No.

Fachpraktikum Elektrische Maschinen. Experiments with a 400/ 690 V Squirrel Cage Induction Machine

DESIGN CONSIDERATIONS FOR APPLICATION OF SHUNT CAPACITORS IN HEAVY HATER PLANT (TUTICORIN)

Electrical Machines II. Week 5-6: Induction Motor Construction, theory of operation, rotating magnetic field and equivalent circuit

Electrical Power System Essentials

Overview of Flexible AC Transmission Systems

ABB n.v Power Quality in LV installations

Power Conditioning of Microgrids and Co-Generation Systems

INTRODUCTION. I.1 - Historical review.

INSTALLATION OF CAPACITOR BANK IN 132/11 KV SUBSTATION FOR PARING DOWN OF LOAD CURRENT

ELECTRICAL FUNDAMENTALS

1 Low-voltage Power-factor Correction capacitors KNK APPLICATION DESIGN

II/IV B.Tech(Regular) DEGREE EXAMINATION. Electronics & Instrumentation Engineering

Lab Electrical Power Engineering I

OBJECTIVE: GENERAL ASPECTS ABOUT ENGINES MECHANISM:

THE ELECTRICAL CIRCUIT

SILICONES GLOBAL SOLUTIONS

A Practical Guide to Free Energy Devices

DRAFT. Guidelines on Power quality & safety issues in usage of roof-top solar pv system CENTRAL ELECTRICITY AUTHORITY

LUNERA BALLASTLED TECHNOLOGY AND POWER FACTOR

Energy Transfer Model

Electrical Power Electric power electrical electric power Electric power electric electric

Lecture PowerPoints. Chapter 21 Physics: Principles with Applications, 7th edition, Global Edition Giancoli

INTRODUCTION. In today s highly complex and interconnected power systems, mostly made up of thousands of buses and hundreds of generators,

AE105 PRINCIPLES OF ELECTRICAL ENGINEERING JUNE 2014

Class X Chapter 09 Electrical Power and Household circuits Physics

The Physics of the Automotive Ignition System

Galapagos San Cristobal Wind Project. VOLT/VAR Optimization Report. Prepared by the General Secretariat

Regulation: R16 Course & Branch: B.Tech EEE

A Dual Stator Winding-Mixed Pole Brushless Synchronous Generator (Design, Performance Analysis & Modeling)

Supercapacitor Based Power Conditioning System for Power Quality Improvement in Industries

Intext Exercise 1 Question 1: Why does a compass needle get deflected when brought near a bar magnet?

Study of Fault Clearing by A Circuit Breaker In Presence of A Shunt Capacitor Bank

Implementation of FC-TCR for Reactive Power Control

RESISTANCE : A STUDY

Name Date Period. MATERIALS: Light bulb Battery Wires (2) Light socket Switch Penny

QCF level: 4 Credit value: 15

LUNERA BALLASTLED TM TECHNOLOGY AND POWER FACTOR

14 Single- Phase A.C. Motors I

ESO 210 Introduction to Electrical Engineering

Impact of Plug-in Electric Vehicles on the Supply Grid

RL Circuits Challenge Problems

Induction Generator: Excitation & Voltage Regulation

MYRON ZUCKER CALMANUAL POWER FACTOR CORRECTION APPLICATION GUIDE INC.

Application of AC Three-Phase Induction Motor of Wound Rotor AEL-ACWRA

Goals. Introduction (4.1) R = V I

COPYRIGHTED MATERIAL SYSTEM OVERVIEW, TERMINOLOGY, AND BASIC CONCEPTS CHAPTER OBJECTIVES HISTORY OF ELECTRIC POWER

Sunny Island Generator - White Paper

Modelling and Analysis of Thyristor Controlled Series Capacitor using Matlab/Simulink

EE 742 Chap. 7: Wind Power Generation. Y. Baghzouz Fall 2011

Transcription:

Reactive power compensation: a basic overview Surnames, name Antonino Daviu, Jose Alfonso (joanda@die.upv.es) Department Centre Departamento de Ingeniería Eléctrica Universitat Politècnica de València 1

1 Summary The aim of this paper is to present a basic overview of the reactive power compensation. More specifically, we try to provide satisfactory responses to the following questions: - Which are the problems caused by the generation and transmission of reactive power? - How do the electric utilities penalize the reactive power consumption? - How can the customers avoid these penalties? - Which are the physical bases of the reactive power compensation? - Which are the basic elements of a reactive power compensation system? - Which are the modalities of reactive power compensation? - Which are the guidelines for the basic design of a reactive power compensation system? This work is devoted to students or researchers interested in obtaining a basic and quick vision of the area, without deepening in complex or accessory details. 2 Introduction In the industrial environments, we can find two main types of loads. On the one hand, there are pure resistive loads (R) that only demand active power (P) due to their pure resistive characteristic (e.g. heaters, incandescent lamps ). On the other hand, there are also resistive-inductive loads (R-L) that demand a certain amount of active power (P) but also consume reactive power (Q) during their normal operation; this is the case of induction motors, most discharge lamps or transformers. Hence, an industrial customer will demand two types of energy: active and reactive. Both of them must be supplied by the electric utility. As a consequence, the phasor of the current circulating through the transmission and distribution lines (I) (from the generation plants toward the customers) will have two components: a real component (active current, Ia) and an imaginary component (reactive current, IL), as depicted in Fig. 1. G R loads R-L loads Figure 1. Schematic representation of the line current phasor The generation, transmission and distribution of the reactive power (Q) cause several problems to the electric utility: 2

- First, it limits the active power (P) generation capacity: in the power plants, the generators have a limited apparent power (S) generation capacity. Indeed, the maximum apparent power of a three-phase generator (S= 3 U I) is limited by the maximum line voltage (V) and current (I) that the generator can withstand; the first is determined by the generator insulations, while the second is determined by the cross-sectional areas of its conductors. Therefore, taking into consideration the basic Equation 1, we can conclude that, for a certain apparent power S, the higher the reactive power (Q) to be generated (in order to the supplied to the customers), the lower the active power (P) that the generator can produce. In other words, the generation of Q limits the capacity of generating P. Equation 1. Basic power equation. - Second, the transmission and distribution of Q, increases the Joule losses in the lines as well as the voltage drops. Indeed, if the customers only demanded P, the line current would only have an active component (I=Ia) and, then, the Joule losses (R Ia 2 ) as well as the voltage drops would only be a function of Ia. However, since the electric utility must also supply Q, the line current is higher (see Equation 2) and, hence, the Joule losses and the voltage drops. Equation 2. Total line current as a function of its active and reactive components Due to all these problems, the electric utility takes into consideration the reactive power demanded by the industrial customers, increasing their electricity bill as their Q consumption does. Years ago, in Spain, the way to include this penalty in the bill was clear: industrial customers with power factors (cos ) higher than 0,9 were credited in the electricity bill, whereas customers with power factors lower than 0,9 were penalized, reaching surcharges of up to 47% [1]. Nowadays, due to the liberalization of the electricity market in Spain, the reactive power consumption penalization is still carried out, but in an indirect manner; the reactive power consumption is included in the price that the retailer must pay to the distributor, undergoing high increments as the demanded Q increases [1]. 3 Objetives Once the problems of reactive power generation, transmission and distribution have been exposed, we will proceed to describe the actions that the customers can adopt in order to avoid or minimize the corresponding penalization in the electricity bill. These actions are covered by the denomination reactive power compensation. In this context, three main goals are pursued: To explain the physical process underlying the reactive power compensation process. 3

To describe the industrial modalities for reactive power compensation, commenting their respective advantages and drawbacks. To design a basic reactive power compensation system. 4 Development 4.1 Reactive power compensation: foundations The intuitive idea underlying the reactive power compensation process is the following one: to avoid the penalties that the electric utility imposes due to the consumption of reactive power (Q) by the R-L loads, the customer installs capacitor banks. In that way, the customer can produce the reactive power that his plant needs, hence avoiding the supply of Q by the electric utility. More rigorously, the physical process taking place when the customer installs capacitor banks in parallel with the loads is described next: Let us suppose that there is no reactive power compensation (the customer does not install capacitor banks). The line current circulating through the distribution lines (I) will be equal to the total current demanded by the loads in the industrial plant and it will have two components; an active (Ia) and a reactive component (IL), as depicted in Fig. 1. The phasor diagram corresponding to this situation is depicted in Fig.2. I a I I L Figure 2. Phasor diagram of the line current in the situation of Figure 1 Let us suppose now that the customer installs capacitor banks (Fig. 3). Since the capacitor (C) is also a load, it demands a certain current for its operation. However, the phasor of the current demanded by a capacitor (IC) unlike the one demanded by a coil is forwarded 90º versus its voltage phasor. As a consequence, since the total current circulating through the distribution lines is the addition of the current demanded by the loads in the installation (Ia-j IL) and the current demanded by the capacitors (j Ic), the resulting phasor diagram will be the one depicted in Fig.4. Note there is a 180º phase displacement between the phasor of the reactive component of the current demanded by the loads (-j IL) and that of the capacitor current (j IC). Therefore, if the capacity (C) of the capacitor is selected in such a way that the magnitudes of IL and IC are equal, these two components would cancel each other in the phasor diagram and, hence, the total current circulating through the distribution lines would be I=Ia. In conclusion, the electric utility should only supply the active component (i.e. active power P), so we avoid the supply of the reactive one and, hence, the supply of Q from the grid. 4

G R loads R-L loads Figure 3. Schematic representation of the line current phasor when there is reactive power compensation I a I C I L Figure 4. Phasor diagram of the line current in the situation of Figure 3 Of course, the theoretical situation described above is not usual in practice. In real life, the magnitudes of IL and IC are not exactly the same. This is due to the fact that the capacity of the real capacitor banks is rarely changed in a continuous way, since these banks are typically based on several capacitor steps with predefined reactive powers that are connected or disconnected according to the Q necessities. This provokes that IL is compensated in steps, depending on the capacitor steps connected in each moment. Instead of using capacitor banks, there is a different alternative to compensate the reactive power that is based on the use of synchronous compensators. These are synchronous machines that, operating with null active power, can behave either as variable capacitors or coils, by simply changing their excitation current [1]. However, their use in the industry is very uncommon, being restricted to large electric power grids. 4.2 Reactive power compensation: modalities There are two main types of reactive power compensation: a) individual and b) centralized. These two modalities are schematized in Fig. 5 (a) and (b), respectively. There is a third modality that can be considered an intermediate case: c) the compensation in group. These three modalities can coexist in the same installation. 5

M M (a) Figure 5. (a) Individual and (b) centralized reactive power compensation The individual reactive power compensation relies on installing capacitor banks in an individual way, in parallel with each single load. This modality is represented in Fig. 5(a) that shows the individual reactive power compensation for a motor. This modality is usually suitable for large machines (e.g. motors) operating under continuous duty cycles. In that situation, is the user knows the Q demanded by the load, he can easily calculate the capacity of the capacitor needed and install it in parallel with the load. Moreover, this reactive power compensation modality is carried out in manual way, i.e., the user connects or disconnects the capacitor manually by using normal switches or, more commonly, contactors. The main advantage of this individual modality is the fact that the conductors located upstream in the installation must only carry the active component of the current (Ia), hence, decreasing the Joule losses and limiting the voltage drops [1, 3]. This is illustrated in Fig. 6, where, once again, we suppose that the magnitudes of IL and IC are equal. (b) M Figure 6. Currents in the installation in the case of individual Q compensation 6

The centralized reactive power compensation modality is based on installing capacitor banks but for the whole industrial installation (Fig. 5 (b)). Usually, these banks are installed in the Transformer Substation (T.S.) containing the transformer through which the whole industrial electric installation is supplied. This modality is usually suitable when there are many loads in the installation that have diverse sizes and operate under different duty cycles. Moreover, this compensation modality is carried out in an automatic way; the system measures the reactive power demanded by the installation and automatically connects or disconnects capacitors accordingly. A typical automatic reactive power compensation system is based on the following elements (Fig. 7) [3]: 1) a measurement device that measures the power factor of the installation (i.e. the Q that the installation is demanding from the grid), 2) a regulator that compares the power factor of the installation with the reference power factor (the one that the user wishes to obtain), 3) a group of switching devices (usually contactors), through which the regulator connects or disconnects the: 4) capacitor steps. 1) Measurement device 4) Capacitor bank 2) Regulator 3) Switching devices Figure 7. Elements of an automatic Q compensation system Some advantages of this compensation modality are: its easier maintenance, its higher flexibility for installation extensions, it is a better option when there is no space beside the loads, it takes more advantage of the capacitor capacities at each moment However, this modality does not avoid the circulation of the reactive component (IL) through the installation conductors. Finally, the third modality, the compensation in group is based, as its name indicates, on compensating the Q of a group of loads by installing, for instance, capacitor banks in the secondary or tertiary panelboards that supply this group of loads. This modality is common is certain parts of the installation with specific loads of the same nature or involved in the same part of the process. 7

4.3 Reactive power compensation: basic design 4.3.1 Determining the Q of the capacitor bank for centralized compensation Let us suppose that a certain industrial premise demands certain amounts of active power (P) and reactive power (Q1) from the grid (the installation has an initial power factor, cos 1). Imagine that the owner of the installation considers that the amount of demanded reactive power is too high; he wants to reduce it, demanding a lower reactive power (let us call it Q2). In other words, he wants to have a higher power factor, cos 2. The question is: which is the value of the reactive power of the necessary capacitor bank to be installed (Qc)? This question can be answered considering the power diagram in Fig. 8. This diagram enables to easily determine the expression to calculate Qc (Equation 3). Q c Q1 1 2 Q2 P Figure 8. Power diagram that enables to obtain Qc Equation 3. Calculation of Qc Once the reactive power capacity of the necessary capacitor bank, Qc, has been calculated, we can determine the capacity of each capacitor of the bank, C. The expression that relates Qc and C depends on the type of capacitor bank (single phase, three-phase with the capacitors connected in delta configuration or three-phase with the capacitors connected in star configuration). Table 1 shows the expression relating Qc and C for each type of bank. These expressions are deduced from well-known circuit theory expressions [1-3]. 8

Type of capacitor bank Expression Single-phase Three-phase (star) Three-phase (delta) Table 1. Expressions relating Qc and C for each type of capacitor bank 4.3.2 Individual Q compensation for a three-phase motor Let us imagine that we want to calculate the necessary capacity of the capacitor to be installed in order to carry out the individual reactive power compensation of a certain three-phase motor. Let us suppose that the rated characteristics of the motor, included in its characteristics plate are: rated power Pn (mechanical), rated current In, rated voltage Un and rated power factor cos n. With these data, we can calculate the reactive power demanded by the motor under rated operation, as indicated in Equation 6 ( is the efficiency of the motor). This Equation is easily deduced considering the usual expressions for calculating the active and reactive power of a three-phase load (Equations 4 and 5): Equation 4. Reactive power of a three-phase load Equation 5. Active power of a three-phase load Equation 6. Reactive power of the motor under rated conditions 9

Taking into account this expression, we can determine the reactive power of the necessary capacitor (Qc). Typically, in practice, it is recommended to take Qc=0,9 Qn. This is done to avoid the possibility of auto-excitation during overrun and the eventual appearance of overvoltages [1]. 5 Conclusions In this work, a basic introduction to the reactive power compensation has been presented. First, the most important problems caused by the generation, transmission and distribution of reactive power are explained. Then, the measures adopted by the electrical utility to discourage the consumption of Q are briefly commented. The reactive power compensation mechanism is analyzed both under intuitive and under physical perspectives. Then, the different modalities for reactive power compensation (individual and centralized) are described and their respective elements, application scopes, advantages and drawbacks analyzed. Finally, the last section is devoted to the basic design of the elements of a reactive power compensation system, both individual and centralized. 6 References 6.1 Textbooks: [1] Roger, J.; Riera, M.; Roldán, C.: Tecnología Eléctrica, Ed. Síntesis, 2010, Cap. 8. [2] Roger, J.; Riera, M; Roldán, C.; Antonino, J.A.: Exercises and questions. Editorial UPV. 2010. [3] Roger, J.; Riera, M.; Pineda, M.; Pérez, J.: "Prácticas de Laboratorio de Tecnología Eléctrica" Editorial UPV. 2011. [4] Reglamento Electrotécnico de B.T. (R.B.T.2002) (MIE-BT). 10