CENTER BREAK GROUP OPERATED AIR BREAK SWITCHES RATED 15.5kV THROUGH 170kV EFFECTIVE DATE: 10/25/16 REV B

Similar documents
Product Specifications for Aluminum Vertical Break Switches

Product Specifications for Phase Over Phase GOABS(r)

Publication No.: PSG

Aluminum Vertical Break Switch 345 kv, 1300 kv BIL 2000 A A.

Product Specification Guide. Title: Southern States 72 kv RLSwitcher Vertical Interrupter Style Reactor Switcher

Product Specification Guide. Title: Southern States 362 kv RLSwitcher Vertical Interrupter Style Reactor Switcher

TYPE V CENTER BREAK SWITCH

Operators/Accessories. Type V2-CA Aluminum. Vertical Break Switch. Ordering Information Furnish: Available Accessories. Standard Operator Features

TYPE EE and EEB CENTER- SIDE-BREAK SWITCH TYPE VEE and CBV CENTER BREAK V SWITCH 1200, 1600, 2000 & 3000 Amperes 7.

34-SDMS-01 SPECIFICATIONS FOR

Aluminum Vertical Break Switch kv A.

Transmission Switching

Copper Vertical Break Switch kv A.

SERIES G100 / G110 SPECIFICATION 15KV & 25KV SUBMERSIBLE & VAULT MOUNTED SF 6 -INSULATED VACUUM LOAD INTERRUPTING SWITCHES

35-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

Catalog 14A January 2013

25 kv Apparatus Bushings

Copper Double Break Switch

Type M3 Hookstick Disconnect Switches Up to 38kV 600 or 900 Amp 40kA Momentary

35-kV Thru-Bushings F Series (bolt-in) for Air-Insulated to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

35-kV 200-kV BIL Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

M-Force three-phase switch

15 kv and 25 kv Thru-Bushings

CLEAVELAND / PRICE INC. Type RL-C Side Break Switch kv A. Bulletin DB-104E12

SERIES 802 / 812 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTERS AND FUSE ASSEMBLIES

100 / 110 DRYWELL FUSE SPECIFICATION

A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system.

Specifications. S&C Omni-Rupter Switches Outdoor Distribution (14.4 kv and 25 kv) Conditions of Sale

M-Force three-phase switch

15-kV Wall-Mount Switchgear Three-Phase Indoor/Outdoor 600 Amp S&C Mini-Rupter Switch

3.0OVERHEAD TRANSMISSION SWITCHES

43-SDMS-01 SPECIFICATIONS FOR

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

Solid Dielectric Load Break Switch SPECIFICATION. 25kV, 630A, 4 WAYS, 4 WAYS SWITCHED PADMOUNTED VACUUM LOAD INTERRUPTER

Three-Phase Pole Mounted Recloser

25-kV Apparatus Bushings A Series (clamp-in) for Elbow to Air-Insulated Service 200 Amp and 600 Amp

Transmission Switching

AIRBREAK SWITCHES East Ginter Rd. Tucson, Arizona USA (520) Fax (520)

PRECISE HIGH VOLTAGE DISTRIBUTION FUSE CUTOUT

TYPE BLT DISCONNECT SWITCHES

Type EB, EBB, EBF and VEB DOUBLE SIDE BREAK SWITCHES 38 kv through 362 kv 600 to 3000 Ampere

CITY OF MARYVILLE ELECRIC DEPARTMENT Maryville, Tennessee SPECIFICATIONS FOR 15KV POWER CIRCUIT BREAKERS. September 2018

Horizontal Circuit Switchers

Horizontal Circuit Switchers

FIXED POWER FACTOR CORRECTION EQUIPMENT 5KV CLASS MEDIUM VOLTAGE SECTION Z

35-kV Safefront SuperWell Mini-Switch Source Isolated Pad-Mounted Switchgear 50 Amp (Max) Clip-Mounted Current Limiting Fuses

Horizontal center break disconnector Type SDF, up to 550 kv Maximum reliability and minimal maintenance

شركة كهرباء محافظة القدس المساهمة المحدودة

Descriptive bulletin. Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS

Typical Specification

Disconnect & ByPass Switches

Technical Specification For Outdoor Substation Harmonic Filter Banks

Underground Distribution Switchgear

WESTERN ELECTRICITY SUPPLY COMPANY OF ORISSA, WESCO. GUARANTEED TECHNICAL PARTICULARS 1 of 2

MATERIAL SPECIFICATION ELECTRIC OPERATIONS ORGANIZATION. M3902 ****Supercedes BECo Standard E and ComElectric Spec ****

AVX. Operation and Maintenance Manual AVX 1200A A 15kV to 362kV. ALUMINIUM VERTICAL BREAK DISCONNECT SWITCH 15kV to 362kV 1200A A

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008

IB-FAS3 Mar Type FAS THRU 115Kv Amp 61 KA Momentary. Vertical-Break, Gang-Operated Outdoor Air Disconnect Switch.

HUBBELL Type M3 Hookstick Disconnect Switches Up to 38kV 600 or 900 Amp 40kA Momentary

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)

35-kV Safefront 200 Amp SuperWell Primary Metering Station Pad-Mounted Outdoor

MATERIAL STANDARD ELECTRIC OPERATIONS ORGANIZATION. ****Supercedes BECo Standard E and ComElectric Spec ****

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS

Section 2 - Substation Switchgear

DAQO Technical Differences of Isolated Phase Bus Standards. Study of Design Standard Variances, Insulator Design and Shipping Section Design

Specifications. S&C Alduti-Rupter Switches with Power Fuses Outdoor Distribution (14.4 kv through 46 kv)

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

Detail Bill of Material Page 1 of 1 Project Name: Amphi School - MVS Replacement Negotiation No: TU700213X7K2 General Order

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

34-SDMS-02 SPECIFICATIONS FOR

43-SDMS-04 REV. 00 SPECIFICATIONS FOR

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS

Technical Specification for 33 KV 200 AMPs,H.G,Fuse set.

Semi-pantograph disconnector type DSSP, up to 300 kv Maximum reliability and minimal maintenance

MGVCL//11KV D.O.FUSE/SPECIFICATIONS -:11KV DROP OUT FUSE CUTOUTS:-

Specification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers

OVERHEAD DISTRIBUTION SWITCHES

Pantograph disconnector type GW54, up to 550 kv Maximum reliability and minimal maintenance

SPECIFICATION BULLETIN

045 : 2000 CEB STANDARD

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

GE Industrial Solutions. User/Installation Manual for 4.76kV -15kV SecoBloc

Transformer bushings, type GOH. Technical guide

15-kV Live Terminal 600 Amp Group Operated Pad-Mounted Metal-Enclosed Outdoor Switchgear 140 Amp (Max) Clip Mount Current-Limiting Fuses

Single-Phase Step Voltage Regulator

TABLE OF CONTENTS FOREWORD... 2 INTRODUCTION SCOPE NORMATIVE REFERENCES DEFINITIONS AND ABBREVIATIONS... 3

Type SDV6 distribution circuit breaker. Top performance - proven reliability. Answers for energy.

35-kV Safefront Mini-Switch Source Isolated Pad-Mounted Switchgear 50 Amp (Max) Clip-Mounted Current-Limiting Fuses

S&C Loadbuster Disconnect Switches. Outdoor Distribution (14.4 kv through 34.5 kv)

56-SDMS-07 REV. 01 SPECIFICATIONS FOR

Guide Specification. Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break

Technical Specification for Pole Mounted Capacitor Rack

1ZSE EN, REV. 4. Wall bushings type GSA-AA Technical guide

A. Submit manufacturer's literature and technical data before starting work.

SECTION WIRING DEVICES

Bus bar Bushings up to 1.1kV and from 1.6kA to 4kA for Liquid Filled Transformers:

Specifications. S&C Power Fuses Types SM- 4, SM-5, SMD-20, and SMD-40 Outdoor Distribution (4.16 kv through 34.5 kv)

Transcription:

CENTER BREAK GROUP OPERATED AIR BREAK SWITCHES RATED 15.5kV THROUGH 170kV EFFECTIVE DATE: 10/25/16 REV B TCV2 Hubbell has a policy of continuous product improvement. Please visit hubbellpowersystems.com to confirm current design specifications.

Table of Contents Scope Scope... 3 Insulators Insulators... 9 General Requirements Applicable Standards... 3 Switch / Type... 3 Switch Ratings... 3 Drawings Approval Drawings...10 Final Drawings...10 Field Drawings...10 Current Carrying Parts Contacts...7 Blades...7 Terminal Pads...7 Operation Operation... 8 Operating Mechanisms Operating Mechanisms... 8 Bases / Mounting Hardware Bases / Mounting Hardware... 9 Shipping Requirements Shipping Requirements...10 Shipment...10 Tables Rated Withstand Voltage (Table 4)... 4 Rated Momentary (Table 14)... 5 Phase Spacing (Table 6)... 6 Insulators (kv, BIL, TR)... 9 Attachments Request for Proposal Nameplates Nameplates... 9 2

Scope This specification covers the technical requirements for 15.5kV through 170kV outdoor, three-pole, groupoperated air switches, and, also load break air switches for line and bus switching, loop sectionalizing, transformer-bank switching, and load-current switching. The switch shall include grounding blades, arcing horns, insulators, motor operators, and other accessories, as specified. Quantities and ratings of the switches shall be listed in the Request for Proposal (RFP). General Requirements Applicable Standards The switches shall comply with the latest revisions of the following standards as of Effective Date 10/25/16 Rev B, as listed. The specific job technical requirements and this specification shall take final precedence in the event of conflict: ANSI standards C37.30.1, C37.100 NEMA standard SG-6, the latest revision ASTM standards A36-84, A123-84, A153-82, B98-83, and B221-83 Switch / Type This specification covers switch types as listed in Table 1, ANSI C37.30.1 in ratings of 15.5kV through 170kV, 600 through 2000 Amperes. The switch type shall be center side break TCV2 and TCB2, or equal. Switch Ratings Temperature Rise: The maximum allowable temperature rise as determined by ANSI C37.30.1 rated current shall be per the following: 30 C X 53 C The manufacturer shall provide, upon request, certified test data on each type of switch to be furnished. For installations below 3300-ft. altitude, the rated withstand and radio influence voltages shall be as shown in Table 4. Per ANSI C37.100, altitude correction factors will apply for altitudes above 3300 ft. 3

ANSI C37.30.1 TABLE 4 PREFERRED VOLTAGE RATINGS FOR STATION CLASS OUTDOOR AIR SWITCHES Line Number Rated Maximum Voltage (rms kv) Lightning Impulse (kv peak) Rated Withstand Voltage Power Frequency (rms kv) Dry 1 min Wet 10 s Corona Voltage & RIV Test Voltage (rms kv) Limit of RIV (µv @ 1 MHz) (1) (2) (3) (4) (5) (6) 1 8.3 95 38 30 -- -- 2 15.5 110 50 45 -- -- 3 25.8 150 70 60 -- -- 4 38 200 95 80 -- -- 5 48.3 250 120 100 -- -- 6 72.5 250 120 100 -- -- 7 350* 175 145 -- -- 8 123 350 175 145 78 500 9 450 235 190 78 500 10 550* 280 230 78 500 11 145 350 335 145 92 500 12 450 235 190 92 500 13 550 280 230 92 500 14 650* 335 275 92 500 15 170 450 235 190 108 500 16 550 280 230 108 500 17 650 335 275 108 500 18 750* 385 315 108 500 19 245 550 280 230 156 500 20 650 335 275 156 500 21 750 385 315 156 500 22 900* 465 385 156 500 23 1050 545 455 156 500 24 362 1050 545 455 230 500 25 1300* 610 525 230 500 26 550 1550 710 620 349 500 27 1800* 810 710 349 500 28 800 2050 940 830 508 750 4

Line Number ANSI C37.30.1 TABLE 14 PHASE SPACING AND GROUND CLEARANCE FOR STATION CLASS OUTDOOR AIR SWITCHES Rated Maximum Voltage (rms kv) Rating Lightning Impulse Withstand Voltage (kv peak) Minimum Phase-to-Phase Metal-to-Metal Distance Disconnecting Switches Ground Clearance Recommended Minimum Veritical Break Disconnecting Switches and Bus Supports Centerline-to-centerline phase spacing Side Break (Horizontal Break) Disconnecting Switches All Horn-Gap Switches (Vertical and Side Break) (mm) (in) (mm) (in) (mm) (in) (mm) (in) (mm) (in) (mm) (in) (1) (2) (3) (4) (5) (6) (7) (8) 1 8.3 95 178 7 191 7.5 152 6 457 18 762 30 914 36 2 15.5 110 305 12 254 10 178 7 610 24 762 30 914 36 3 27 150 381 15 305 12 254 10 762 30 914 36 1220 48 4 38 200 457 18 381 15 330 13 914 36 1220 48 1520 60 5 48.3 250 533 21 457 18 432 17 1220 48 1520 60 1830 72 6 72.5 250 533 21 457 18 432 17 1220 48 1520 60 1830 72 7 350* 787 31 737 29 635 25 1520 60 1830 72 2130 84 8 123 350 787 31 737 29 635 25 1520 60 1830 72 2130 84 9 450 1120 44 991 39 846 34 1830 72 2310 91 2620 103 10 550* 1350 53 1190 47 1070 42 2130 84 2740 108 3050 120 11 145 350 787 31 737 29 635 25 2440 60 3350 72 2130 84 12 450 1120 44 991 39 846 34 1830 72 2310 91 2620 103 13 550 1350 53 1190 47 1070 42 2130 84 2740 108 3050 120 14 650* 1600 63 1330 52.5 1270 50 2440 96 3350 132 3660 144 15 170 450 1120 44 991 39 846 34 1830 72 2310 91 2620 103 16 550 1350 53 1190 47 1070 42 2130 84 2740 108 3050 120 17 650 1600 63 1330 52.5 1270 50 2440 96 3350 132 3660 144 18 750* 1830 72 1560 61.5 1470 58 2740 108 3960 156 4270 168 19 245 550 1350 53 1190 47 1070 42 2130 84 2740 108 3050 120 20 650 1600 63 1330 52.5 1270 50 2440 96 3350 132 3660 144 21 750 1830 72 1560 61.5 1470 58 2740 108 3960 156 4270 168 22 900* 2260 89 1930 76 1800 71 3350 132 4870 192 4870 192 23 1050 2670 105 2300 90.5 2110 83 3960 156 5500 216 5500 216 24 362 1050 2670 105 2300 90.5 2130 84 3960 156 5500 216 5500 216 25 1300* 3020 119 2690 106 2640 104 4430 174 6100 240 26 550 1550 3150 124 7620 300 27 1800* 3660 144 7620 300 8230 324 28 800 2050 4220 166 15240 600 5

ANSI C37.30.1 TABLE 6 PREFERRED CONTINUOUS AND WITHSTAND CURRENTS FOR STATION CLASS OUTDOOR AIR SWITCHES Withstand currents Line Number Rated continuous current (A) Short-time withstand (ka) Peak withstand (ka) 60 Hz 50Hz (1) (2) (3) (4) 1 600 25 65 63 2 1200 38 99 95 3 1600 44 114 110 4 2000 44 114 110 5 2000 63 164 158 6 3000 63 164 158 7 3000 75 195 188 8 4000 75 195 188 Note: Please check IEEE 37.30.1 specification for most up-to-date information. 6

Current Carrying Parts Contacts Current carrying parts shall be of copper or aluminum alloy construction with silver-to-silver or silver-tocopper alloy current transfer contacts. Contacts shall be of the reverse loop, self-wiping type. The current carrying path shall not be springs, pins, or bearings. Exposed contacts shall be self-wiping silver-to-copper and silver-to-silver. All other current carrying contacts, including hinged-end contacts, shall be silver-to-silver, unless sealed and insulated from contamination and corrosion. Internal sealed contacts may be either silver-to-silver or silver-to-copper. External silver-to-silver contact surfaces that are applied to copper shall be plated application. Minimum thickness of either type surface shall be.0005 inches. Silver applied to aluminum is NOT acceptable. Blades The switch blades shall be tubular and 6063-T6 aluminum. The switch blades and other live parts shall be designed to prevent the accumulation of water. Terminal Pads All terminal pads shall be machined and copper, aluminum, or bronze. The pads shall be equipped with tinplated copper shields in a NEMA configuration, or plated to a minimum thickness of.0005. Switches with ampere ratings between 600 and 2000 shall have terminal pads with four holes on a NEMA spacing of 1 ¾-inch. Bolt holes shall be 9/16-inch. 7

Operation Switch blades shall be under positive control at all times, and the travel from the fully closed position to the fully open position shall be accomplished with one smooth continuous motion. Operating Mechanisms Each gang-operated switch unit shall be furnished with an operating mechanism as specified on the Switch Requirement sheet. Operating mechanisms shall be complete with galvanized steel vertical operating pipe, group operating pipe, and interphase pipe; galvanized steel or malleable iron bell cranks, outboard bearings, pipe guides, operating levers or cranks, universal joints, as needed; and galvanized steel mounting channels, angles, or plates. Details of structural members necessary to support the switches and operating mechanisms on the supporting structures will be provided as required. Galvanized steel shims, bolts, nuts, flat washers, palnuts, or lock washers and beveled washers shall be provided for all operator support brackets, bases, etc., required for attachment to the supporting structure. Operating mechanisms shall be suitable for operating the switches from grade elevation. The design of the operating mechanism shall provide smooth, completely controlled, synchronized movement of the switch blades throughout the entire cycle of operation of closing or opening. Optional stops on the switch bases shall be incorporated in the design for open position to prevent misalignment of the switch blades. Galvanized steel control and interphase pipes shall be of sufficient size and design to eliminate twist in the torsional operating pipes and significant sag in push-pull interphase pipes. All switches shall include provisions for interphase adjustment of each individual switch pole. These provisions shall be of a continuously adjustable type for correction of any misalignment in the switch insulators, bases, and operating pipes. It shall be mechanically impossible, after final adjustment has been made, for any switch to remain in a partially open or partially closed position at the completion of any operator cycle. The rotation insulator stack on each switch pole and the outboard bearing shall have maintenance-free sealed bearings to provide smooth and trouble-free operation of the switch. The operating mechanism shall have position indicators and provisions for pad locking in both the open and closed positions. It shall be provided with a 1/0-grounding conductor, and length will be dependent on switch type. The maximum operating effort shall be fifty pounds for a swing handle operator or thirty-five pounds for a manually-operated gear mechanism. 8

Bases / Mounting Hardware All switches shall be provided with bases, clips, shims, galvanized mounting bolts, nuts, split washers, lock washers, beveled washers, and specified fittings to meet dimensions shown on the drawings. The base shall be constructed of ASTM A36 steel or 6061-T6 aluminum, the latest revision, with sufficient rigidity to maintain proper alignment at the tops of the insulators and adjustment of the blades and contact under all climatic and loading conditions. All steel shall be hot-dipped galvanized in accordance with ASTM A123, the latest revision. Mounting dimensions shall conform to those shown on the drawings accompanying the order. Provisions shall be made for the adjustment of all insulator stacks, by use of tipping the screws located under the insulator. The use of shims as a means of adjustment is NOT acceptable. Nameplates All switches shall be equipped with a non-corrosive nameplate, in accordance with ANSI C37.30, permanently attached. In addition to the requirements of ANSI C37.30, the manufacturer s CO, S.O. or JO number shall be marked on the nameplate. Insulators Supplied insulators, if specified on the RFP, shall be in accordance with the latest revisions of ANSI C29.8 and C29.9, and shall conform to the following table. The insulator type and color, other than ANSI 70 (Sky Grey), is to be noted on the RFP. kv BIL POST 15.5 110 TR 205 OR 225 27 150 TR 208 OR 227 38 200 TR 210 OR 231 48.3 250 TR 214 OR 267 72.5 350 TR 216 OR 278 121 550 TR 286 145 650 TR 288 169 750 TR 291 245 900 TR 304 245 1050 TR 312 365 1300 TR 367 Station post insulators shall be supplied with the proper fittings required to develop the impulse level and to support the busses or switch parts, as required. Bolts and other hardware for joining the units or stacks shall be furnished. Galvanized hardware shall be furnished for mounting live parts and bases to insulators. The hardware shall include galvanized lock washers and sized for the insulator specified. 9

Drawings Approval Drawings Within thirty (30) days of receipt of order, three (3) copies of the approval drawings or CAD files, in AutoCAD, DWG, or DXF format, will be submitted for approval. Final Drawings Final drawings, three (3) copies and instruction manuals will be sent within forty-five (45) days after receipt of approved drawings for file in AutoCAD, DWG, and DXF format. Field Drawings One copy of all drawings and installation instructions will be sent with each switch in a sealed waterproof envelope. Shipping Requirements Switches can be shipped with all live parts and bearings assembled and bolted into position on the bases with the blades securely wired closed into the contacts. Each three-pole switch shall be crated in a manner suitable for stacking. Operating pipes and interphase bars shall be shipped unassembled and banded together, one set per switch properly identified and protected against damage. All other loose parts for each switch shall be shipped in a wooden box properly identified. Switches rated 161kV and below can include the insulators assembled, when required. Each bundle, crate, or pallet shall be marked utilizing a weatherproof marking. Shipment For freight and shipping please refer to HPS Terms and Conditions of Sales. All equipment and materials under the same schedule shall be shipped at the same time, if possible. 10

Notes 11

Hubbell Power Systems, Inc. hubbellpowersystems.com Copyright 2017 Hubbell Incorporated. Because Hubbell has a policy of continuous product improvement, we reserve the right to change design and specifications without notice. Printed in the U.S.A. TD_10_134E