PROPORTIONAL BAND ZERO ENERGY BAND DEFINITION S1 S2

Similar documents
T8078C LOW VOLTAGE MODULATING CONTROLLER FEATURES APPLICATIONS PRODUCT SPECIFICATION SHEET

Application Engineering

Quick Setup Guide for IntelliAg Model 3PYP 12 Row Single Row Air Pro

ZIP Economizer Fault Detection and Diagnostics (FDD) Table

Cooling mode. Temperature adjustment button. Override button. 24 VAC COM AN1 COM OPEN CLOSED T2/AN2 T2/COM T3 T3 COM SENSOR COM C-Over COM NSB

MC200CAB/4 Integral Version

Application Engineering

HP21 SERVICE SUPPLEMENT UNIT INFORMATION. TSC6 Two-Speed Control

Model No. DFC-X Support DIRECT FIRED DIGITAL TEMPERATURE CONTROL INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

Flight Systems. Replacement for KASSEC DESCRIPTION



Starting System DS-102 Series 200. Elmatik AS P.O.Box 309 NO-3471, Slemmestad T F

SECTION 2 - PROCEDURES. Features. 2.6 MOTOR CONTROLLER. Modes of Operation JLG Lift 2-5

DFC-1 STANDARD TEMPERATURE CONTROL. DFC-2 TEMPERATURE CONTROL w/ INTEGRAL 40 F-90 F SELECTOR DFTD TEMPERATURE SELECTION DIAL DFTS TEMPERATURE SENSOR

RDG160TU Commercial Thermostat

Digital Room Thermostats with Touch Screen LCD

Temperature Controllers

ENGEN -100/ENGEN -200 ENGINE GENERATOR CONTROLLER

Factory Packaged Controls. OE (AAON Part No. V12090) MODGAS-X Controller Field Technical Guide

LINEAR ACTUATORS INDEX

CM707 (UK Version) PROGRAMMABLE THERMOSTAT FEATURES PRODUCT SPECIFICATION SHEET

Quick Setup Guide for IntelliAg Model YP Air Pro

STRA-24 for chilled beams

Quick Setup Guide for IntelliAg Model YP40 20 Air Pro

ENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE. GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA , USA MEMBER

PRODUCT / TEST MANUAL 2L9K2 BATTERY EARTH FAULT RELAY

LF Series At A Glance

ST48-WHUV.102. Wiring diagram. Product description. PID controller. Order number

DTC B0228, B0413, B0423, Or B3779

HWP Protection Board

Digital Fan Coil Thermostats with 0(2)-10 VDC Fan Output

EUROTHERM ONTROLS. Two phase thyristor power switches. Product data

ARM V FDBK ENSURE MOTOR IS NOT ROTATING DURING POWER UP STILL FAULTS? YES ENSURE ARMATURE WIRING IS ISOLATED FROM ANY OTHER POWER LEADS STILL FAULTS?

NFB24, NFB24-S, NFX24, NFX24-S On/Off, Spring Return, 24 V

C.E. Niehoff & Co. C840D Alternator Troubleshooting Guide CAUTION. Testing Guidelines. Hazard Definitions WARNING.

Temperature Controllers

Versatile and Powerful

C.E. Niehoff & Co. C505, C527, C531, and C534 Alternators Troubleshooting Guide CAUTION. Testing Guidelines. Hazard Definitions WARNING

AA4006 Speed Sensitive Trip Unit. User Manual

ILLUMINATOR LV. Emergency Lighting Inverter System 175VA through 750VA. Illuminator Series LV Single Phase

ELECTRONIC THERMOSTAT: T901

1 Safety instructions. 2 Device components. Dimmer push-button/2-way low voltage. Order No. : Operating instructions

Special voltages: Voltage >500 V AC are only permissible with external control box. 3-phase AC Voltages/frequencies. 1-phase AC Voltages/frequencies

Polygyr -Compact Exhaust Air Temperature Controller

ASYN205B Central Synchronizing Controller

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

SE8300 Series Installation Guide 24 Vac Low Voltage

ST Wiring diagram. Product description. Temperature controller. Order number

Section 55 Chapter 6

Softstarters. Softstarters Power electronic brakes Type PEB

2.1 Warnings & Agency Approvals Electrical Connections - Specifications Standard Wiring Configurations...2 4

RVD110 RVD G2381en. Installation. Commissioning

System 2000 DRA automatic stairway lighting, Impulse insert. 1 Safety instructions. 2 Device components

BGH2UNCNTRLHT-01 Universal Hot Surface Ignition Control

Explanation 1 Input External Switch 2 Input Hipot Safety Switch

LF Series Spring Return Direct Coupled Actuator

Remote Temperature Controllers. Quick Selection Guide

General Information... 2

Test. What type of cylinder would you use? A. Single-acting cylinder B. Double-acting cylinder Answer:

Reproduction or other use of this Manual, without the express written consent of Vulcan, is prohibited.

Constant Voltage/Constant Current Test System

Electronic Ballast EVG 2000-T

For installation instructions refer to the mounting and dimensions details and the terminal layout drawings on page 5 of this manual.

Versatile and Powerful

ELECTRIC SCHEMATICS LS1 LS2. "1532ES / 1932ES" Service & Parts Manual - ANSI Specifications March 2008 Page 5-9 ART_2236 ART_2243

ECONOMISER SERIES E2T USER MANUAL

Differential Temperature Controller

Installation and Operations Manual

Service Bulletin Power Sliding Door Operation and Troubleshooting (Replaces , Power Sliding Door Problems, dated April 20, 1999)

Components for EEx e Panels

Mount directly to 1.05 jackshafts. AF230 US (p. 02) AF230-S US (p. 20) AF24-S US (p. 18)

Hoffman Controls. Installation & Operating Instructions. General. Installation. Determining Damper Shaft Rotation. Stop Pin Installation

Start-Up, Operation and Service Instructions

Technical Instructions. SQV Series Electromotive Valve Actuators. Document No

Installation Instructions

RVS-DN Digital Reduced Voltage Motor Starter

Visit for more technical information & downloads

PRODUCT INFORMATION BULLETIN

G2515. Installation. Place of installation. Electrical installation. Permissible cable lengths. Securing the controller to the base

DRC Travel Drive Control Application Software

Crompton Controls. This is. Installation and Maintenance Instructions. S10 & Smooth-BRAKE DC Injection Brake Modules. Tel: +44 (0)

FSAF24(-S) US, FSAF120(-S) US

Engineering Bulletin. IntelliPak RTM (Rooftop Module, 1U48) Subject: Generic Building Automation System (GBAS, UCM Module, 1U51)

TRIPS AND FAULT FINDING

J1 Plug Pin Identification

System 350 P352AB Electronic Pressure Control Series

1 potential-free change-over contact (max. 24 V DC/1 A) for SIL collective failure signal SIL functions - safety functions Standard: Safe ESD

Instruction Manual. Duo-battery Solar Panel Controller EPIP20-DB series For Both 10 and 20 amp. Controllers (for use with solar panels only) + -

Available with actuator function: POWER OPEN - POWER CLOSE FAILSAFE MODULATING FAILSAFE MODULATING. Overview. 11 or 14mm drive output (Option)

SAX Electronic Valve Actuator

Injector Solenoid - Test

OUTDOOR UNIT CONTROLLER (OUC)

Metasys Zoning Package Installation

C.E. Niehoff & Co. C703/C703A and C706 Alternators Troubleshooting Guide CAUTION. Testing Guidelines. Hazard Definitions WARNING.

LF24-ECON-R03(-R10) US Operation, Installation and Wiring

V200 V200. Control on water, proportional integral. Simplified Master / Slave operation GENERAL DESCRIPTION

P445 Series Electronic Lube Oil Control

1 Safety instructions. 2 Device components. Light Management Rotary dimmer. Operating instructions

Installation Instructions

Transcription:

Honeywell T0C INDIVIDUAL ROOM TEMPERATURE CONTROLLER INSTALLATION GUIDE Cover removal Mounting T0C 00-00 R Wiring T0C.mm (max) Remote Temperature Sensor Screen wire 0 Connect screen wire to terminal or 0 ON System Switches SYSTEM & PARAMETER SELECTION SWITCHES ON OFF ON CONTROL SYSTEM PROPORTIONAL BAND ZERO ENERGY BAND DEFINITION S S DEFINITION S S Xp (system dependent) S S S ZEB S Thermo-Electric OFF ON Actuator (TPM) On / Off ON OFF Modulating ON ON Heat / Cool Changeover OFF OFF -Stage Heating + OFF ON -Stage On/Off Cooling -Stage Cooling + ON OFF -Stage On/Off Heating K ON ON ON K ON ON OFF K OFF OFF ON OFF ON ON ON OFF ON K K ON OFF Heat + Cool Sequence ON ON K OFF OFF OFF OFF ON OFF ON OFF OFF

MODULATING CONTROL Up to x M0C actuators (0.VA each) can be connected to each output. Maximum rating of On/off output is 00mA. A V~ contactor or relay must be used to switch higher current or voltage loads.

ON/OFF CONTROL Maximum rating of On/off output is 00mA. A V~ contactor or relay must be used to switch higher current or voltage loads.

TPM CONTROL (THERMO-ELECTRIC ACTUATORS) Maximum rating of On/off output is 00mA. A V~ contactor or relay must be used to switch higher current or voltage loads.

LAYOUT & TERMINAL CONNECTIONS Terminals Potentiometer System Switches Sensor Diagnostic LED. volt supply. volt supply (0v). Valve open. Valve close. Valve common. Valve open / stage on/off control (applications,,,0,,). Valve close / stage on/off control (applications,,,0,,). Heat / Cool changeover input. Heat / Cool changeover input 0. Energy savings input. Energy savings input. Remote sensor input. Remote common (for remote sensor & remote setpoint inputs). Remote setpoint input All terminals are suitable for connection of up to.mm stranded cable. STARTUP & COMMISSIONING SEQUENCE On power up, T0C will undergo a test and synchronisation sequence to enable Installers and Commissioning Engineers to test the system is wired correctly. Test Sequence For all control modes, the test sequence will last 0 seconds, and will consist of switching the control outputs on and off in the sequence illustrated below. The outputs are connected to terminals,,, and. Valve Synchronisation For modulating systems, the test sequence will be followed by a valve synchronisation (taking approximately minutes), where the valves will be driven to the closed position to establish a baseline control reference. For On/off and TPM control systems, the valve closure sequence will last 0 seconds. The synchronisation sequence will be repeated hours after power up, and thereafter every hours. The Diagnostic LED will illuminate in the sequence illustrated for Terminal below, if no faults are detected (see Section entitled Diagnostics & Fault Indication for a complete description). On/off & TPM Systems Terminal Close Valves Terminal Terminal Terminal (secs) Normal Control Only applies for On/off Heat + Cool Sequence system 0 Modulating Systems Terminal Terminal Terminal Close Valves (min approx.) Normal Control Terminal (secs)

DIAGNOSTICS & FAULT INDICATION T0C provides simple user diagnostics and fault indication using an LED, positioned at the bottom right side of the printed wiring board. The T0C cover can be removed to view the LED correctly. By pulsing the LED on and off in predefined sequences, T0C is able to indicate valve position, heating or cooling demand, or whether a fault has been detected. The tables and graphs opposite illustrate how to interpret the LED outputs. Fault Indication If a fault is detected, this will be indicated as a higher priority than valve position or cooling / heating demand. Faults are indicated by,, or LED pulses, followed by a second delay, then a repeat of the pulse sequence. Most detectable faults are associated with errors in reading sensor or setpoint values. In the unlikely event of an internal sensor or unit setpoint fault, the only option is to replace the complete controller. However, if a remote sensor fault is indicated, the most likely reason is a bad connection, so all wiring connections should be checked and re-made if necessary. Internal Sensor Remote Sensor Unit Fault Indication 0 0 Fault Internal Sensor out of range Remote Sensor out of range Faulty setpoint measurement Suggested Action Replace controller Check sensor connections Replace controller (secs) Diagnostics Valve Position / Cooling or Heating Demand Valve position or cooling/heating demands are indicated by an initial code sequence of pulses, followed by the position or demand data, and this is repeated on a fixed cycle rate. The duration of the data pulse provides the important information, for example : Valve position : LED on for a duration proportional to the valve position, where 0s on = valve fully open On/off or TPM demand : LED on for an amount proportional to the on period of the cycle, where 0s on = 0 demand T0C will only provide demand or position data on the current operating output, and this will be indicated by the initial pulse sequence of,, or pulses. By reference to the table, the current operating mode and demand can be determined for each of the possible control options. Valve position / Demand Valve position / Demand Valve position / Demand 0 0 0 Output Type 0 0 (secs) Output Type 0 0 (secs) Output Type 0 0 (secs) Modulating Control On/off Control TPM Control 0 Valve closed Valve closed Valve Position Modulating Cooling Valve closed Valve closed Valve Position Modulating Heating nd Stage On/off Heating demand st Stage On/off Heating demand Valve Position Modulating Cooling+ On/off Heating nd Stage On/off Cooling demand st Stage On/off Cooling demand Valve Position Modulating Heating+ On/off Cooling Valve closed Valve Position (Cooling Operation) Valve Position (Heating Operation) Modulating Heat / Cool Changeover Valves closed Position of Cooling Valve Position of Heating Valve Modulating Cool + Heat Sequence Valve closed Valve closed Valve Demand On/off Cooling Valve closed Valve closed Valve Demand On/off Heating nd Stage On/off Heating demand st Stage On/off Heating demand Valve Demand On/off Cooling+ -Stage On/off Heating nd Stage On/off Cooling demand st Stage On/off Cooling demand Valve Demand On/off Heating+ -Stage On/off Cooling Valve closed Valve Demand (Cooling Operation) Valve Demand (Heating Operation) On/off Heat / Cool Changeover Valves closed Cooling Valve Demand Heating Valve Demand On/off Cool +Heat Sequence Valve closed Valve closed Valve Demand TPM Cooling Valve closed Valve closed Valve Demand TPM Heating nd Stage On/off Heating demand st Stage On/off Heating demand Valve Demand TPM Cooling+ -Stage On/off Heating nd Stage On/off Cooling demand st Stage On/off Cooling demand Valve Demand TPM Heating+ -Stage On/off Cooling Valve closed Valve Demand (Cooling Operation) Valve Demand (Heating Operation) TPM Heat / Cool Changeover Valves closed Cooling Valve Demand Heating Valve Demand TPM Cool +Heat Sequence

ENERGY SAVINGS MODE T0C has an Energy Management System, where the detection of an external input signal will cause the cooling and heating setpoints to change to pre-defi ned setup and setback temperatures, enabling maximum energy effi ciency. This input signal must be in the form of a contact closure, connected to terminals 0 and. In Mode the Setup/Setback values can be set between -K by means of an on-board potentiometer. In cooling only systems (,, ) the setpoint will be increased (setup) by the set value fi xed by the potentiometer. In heating only systems (,, ) the setpoint will be decreased (setback). In heat/cool changeover systems (,, ) the heating setpoint will be decreased in heating mode, and the cooling setpoint will be increased in cooling mode. In cooling + heating systems (,,,, 0,,,, ) the cooling setpoint will be increased by the set value and the heating setpoint will be decreased by the same amount. The effect is to widen the Zero Energy Band. Input Wiring Connections T0C 0 Switch should be rated 0 Vdc 0. ma nominal = Normal Operation = Mode ENERGY SAVINGS : EXAMPLES () Modulating Cooling Potentiometer 0 Valve position Setting K Cooling = Normal Cooling + Cooling Setup = Normal Cooling + K Example: Setup value = k Normal Temp ( C) () Modulating Heating Potentiometer 0 Valve position Setting K Heating = Normal Heating - Heating Setback = Normal Heating - K Example: Setback value = k Normal Temp ( C) () Modulating Cooling +Heating Sequence ZEB Potentiometer 0 Valve position Normal Heating Normal ZEB Normal Cooling ZEB = Normal ZEB + Heating Setback + Cooling Setup = K + K + K = K Temp ( C) Example: Setup/setback value = k Heating Cooling

REMOTE SETPOINT ADJUSTMENT T0C allows its setpoint to be adjusted remotely by up to ±K. This is achieved by the connection of a Remote Adjustment module to terminals and, as shown in the wiring schematic. Suitable modules are : QB0 (Remote Adjust), and QC0 (Sensor + Remote Adjust). To ensure measurement stability when wiring these modules, use screened cable, and connect the screen wire to terminal or 0 of the T0C, as shown. QB0 REMOTE SETPOINT ADJUST T0C 0 QB0 Use screened cable Screen wire QC0 SENSOR + REMOTE SETPOINT ADJUST T0C QC0 0 Use screened cable Screen wire REMOTE SENSOR T0C is supplied with an on-board temperature sensor. If remote temperature sensing is required (for example in return air sensing applications), then a suitable Honeywell Remote Sensor can be connected to terminals and as shown in the wiring schematics. T0C auto detects the Remote Sensor on power up, and will use the Remote Sensor measurement in preference to its internal sensor. The power must be switched off then on again for a remote sensor to be detected. Remote Sensors are available as wall-mounted or airfl ow (return air) models : T0C00 Airfl ow Sensor supplied with. m cable QA00 Wall-mounted Sensor QC0 Wall-mounted sensor + Remote Adjust All Remote Sensors require screened cable to be used to ensure stability of temperature measurement. The screen wire must be connected to terminal or 0 of T0C, as shown. If this cable is to be extended then the maximum cable run will be 0m, and the extension must also use screened cable. T0C 0 T0C00 SENSOR T0C00 Use screened cable Screen wire QA00 WALL-MOUNTED SENSOR T0C QA00 0 Use screened cable Screen wire AUTOMATIC HEAT / COOL CHANGEOVER If automatic or central Heat / Cool changeover is required, set both system switches S and S to the off position (see page ). Automatic changeover is initiated by a thermostat positioned on the water fl ow pipe, detecting the presence of heated or chilled water, and sending the appropriate signal to the controller. A suitable product is the S0A00 pipe-thermostat. Central changeover is initiated by a switch, and can be used to centrally switch a group of connected T0C controllers from Heating to cooling operation. See wiring schematics for connection details. Automatic Heat / Cool Changeover T0C 0 S0A00 Central Heat / Cool Changeover T0C T0C T0C Central Switch = Heating = Cooling VALVES, ACTUATORS & OPTIONAL ACCESSORIES Optional Accessories A range of optional accessories are available for use with T0C : F00-00 Range stops F00-00 Wall-plate Q0A0 Fan Speed Switching Subbase QA00 Wall mounted Remote Sensor QB0 Remote Adjust Unit (±K) QC0 Sensor + Remote Adjust Unit (±K) T0C00 Return Air Sensor (.m cable) S0A00 Pipe-mounted Changeover Thermostat Environmental Controls Honeywell Control Systems Ltd. Newhouse Industrial Estate Motherwell, ML SB Scotland honeywell http://europe.hbc.honeywell.com 00-00 R