ESTIMATE SUPPLYING, INSTALLATION, TESTING AND COMMISSIONING OF INDOOR TYPE 33 / KV SUB STATION AT RMRCT, JABALPUR M.P. ABSTRACT OF ESTIMATE

Similar documents
SCHEDULE OF QUANTITIES ITEM DESCRIPTION

AN ISO 9001 & COMPANY TENDER DOCUMENT. TENDER No: DLI/CON/696/411 FOR

TENDER DOCUMENT. (TENDER No: NRO/CON/696/660) FOR

TENDER DOCUMENT TENDER No.: NRO / CON / 592 / 537 FOR SUPPLY & INSTALLATION. DG Sets & Sychronising Panel

TENDER FOR FOR 2 X 1010 KVA, 1500 RPM, 415 V DG SETS FOR CONSTRUCTION OF NEW CDRI CAMPUS AT SITAPUR ROAD, LUCKNOW (U.P.) SUMMARY OF PRICE BID

Tender Schedule for Electrical Works at Varagani Branch. Sl. No. Particulars Quantity Unit Rate Amount

SCHEDULE OF QUANTITY

MAIN INCOMER -1 (500 KVA TRF.)

Bills of Quantities and Schedule for the Electrical Works at M/s.Bank of India, Madurai CPC Branch, East Aavani Moola Street, Tamil Nadu.

INDIAN INSTITUTE OF TECHNOLOGY KANPUR

BILL OF QUANTITY (BOQ) FOR ELECTRICAL WORKS BOGAPURAM BRANCH

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT

Tender Schedule. Sl. No. Particulars Quantity Unit Rate `

DATA SHEET FOR 1 TYPE COMPARTMENTALISED / NON - COMPARTMENTALISED. ( a ) CIRCUIT BREAKER FEEDERS FULLY DRAWOUT / NON DRAWOUT

INDIAN INSTITUTE OF TECHNOLOGY KANPUR

TECHNICAL SPECIFICATIONS OF PCC PANEL

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT

MOTHER DAIRY A UNIT OF GUJARAT CO-OPERATIVE MILK MARKETING FEDERATION LIMITED PURCHASE ENQUIRY

Estimate of Under Ground Electrification Work

BHARAT HEAVY ELECTRICALS LIMITED, JHANSI

: Material Description Quantity UOM

33KV INDOOR SWITCHGEAR

MOTHER DAIRY A UNIT OF GUJARAT CO-OPERATIVE MILK MARKETING FEDERATION LIMITED PURCHASE ENQUIRY

Estimate For The Electrical Works At Pittakayagulla Branch Sl.N Particulars Quantity Unit Rate Amount

Name of work : Electrification of PG Block Second Floor in V.P.S.V Ayurveda college Kottakkal.

Key features. DESIGNS: - Conservator type - Hermetically sealed

Total Cost Abstract. Project Name : - RDPL, Jaipur. Grand Total

Metal Clad VCBs ~ Mk1

QUOTING SHEET BIDDER'S PRICE % QUOTE ABOVE / AT PAR / BELOW In figures

(High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA MATERIALS MANAGEMENT / CAPITAL EQUIPMENT. Enquiry Date:

TECHNICAL SPECIFICATIONS FOR 380/410 KVA, 6 CYLINDER DIESEL GENERATOR SET PACKAGED BY SCOPE OF SUPPLY FOR DIESEL GENERATING SET PACKAGE

ESTIMATE PROPOSED ELECTRICAL & ALLIED WORKS FO INDIA ONE AVIGHNA PARK, CURREY ROAD BRANCH AT C MUMBAI

TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment)

B.O.Q ELECTRICAL WORK OF CANARA BANK, BUDHARAJA BRANCH

BOQ FOR ELECTRICAL WORK OF CANARA BANK RENGALI BRANCH

NPS/003/010 - Technical Specification for 400V Assemblies (LVAC Boards) utilised in Major Substations

B.O.Q's FOR ELECTRICAL WORKS FOR BANK OF INDIA, COLLEGE ROAD, DHAKA BRANCH

56-SDMS-07 REV. 01 SPECIFICATIONS FOR

CONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS

GE Consumer & Industrial Power Protection. New. SecoGear kV Metal-clad Switchgear. GE imagination at work

West Bengal State Electricity Distribution Co. Ltd.

B.O.Q FOR ELECTRICAL WORK (Including Fitting & Fixtures) OF STAFF QUARTERS AT BUUBANESWAR FOR UNITED INDIA INSURANCE CO. LTD

ESTIMATE FOR ELECTRICAL WORKS AT CHINCHOLI BRANCH

Estimate For Electrical Works PROPOSED RUDSET INSTITUTE AT BERHAMPUR

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

KENYA POWER-MOMBASA BRANCH REPLACEMENT OF AIR-CONDITIONING AND ASSOCIATED WORKS BILLS OF QUANTITIES FOR ELECTRICAL INSTALLATIONS BILL NO

PART A: FINANCIAL BID

NEPAL ELECTRICITY AUTHORITY (A Government of Nepal Undertaking)

Extensible Unit - VCE2a

PIX-H Metal-clad switchgear up to 17.5kV

SPECIFICATION FOR BATTERY & BATTERY CHARGER (D.C. SYSTEM)

Technical Specifications

FLOAT CHARGER (40A) & BOOST CHARGER (35A) FOR NO BREAK POWER SUPPLY SYSTEM WITH REQUIREMENT FOR SCADA

TENDER DOCUMENT PART-II

UniPack compact secondary substations (CSS) upto 36 kv For safe, reliable and space saving power distribution solutions

२१७१ २-१ ४४ २०१८ २-१ २१०९-४ २०१८ २९ ०६ २०१८ २ २ १२४९ २-१ ४४ २०१८ २१ ०७ २०१८ ३ २ १७०५ २ / -१ ४४ २०१८ १० १० २०१८ १ २ ३ २ ३ १३ २०१८-१९

TECHNICAL SPECIFICATION FOR D G SET KVA

NS Feeder pillar up to 3200A

WEST BENGAL STATE ELECTRICITY DIST. COM. LTD. ( A

FLOAT CHARGER & BOOST CHARGER F O R NO BREAK POWER SUPPLY SYSTEM (Float 100A & Boost 60 A with SCADA application)

FORMAT-III B - ANNEXURE-III

Supply of 63 kva DIESEL GENERATOR SET WITH AMF

3 - Protection components Motor circuit-breakers

DPX moulded case circuit breakers

S H A D E S ELECTRICAL DB MANUFATURING

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

ELECTRICAL ITEMS Cables : Specification: XLPE Insulated Power Cable All Cables Cables PVC Insulated Cables Fire Resistant Cables Aluminium Cables

to UPS outgoing DB. c With 2 nos. 6 Sq.mm + 1 no. 2.5 Sq.mm. PVC insulated copper wire from UPS outgoing DB to CDB / Main panel to LDB /

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

Annex A TECHNICAL SPECIFICATION FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF 400V (750KVA) DIESEL

BHARAT HEAVY ELECTRICAL LIMITED Boiler auxiliaries Plant Ranipet Vellore ,TamilNadu, India

Set /

INDIAN INSTITUTE OF TECHNOLOGY KANPUR

Package Price for Grid Connected 6.0 MW Synchronized Electricity: Please Call For Details Price

Item Code Description Unit Qty Total

(Under Two Part Bid System) Tender No: NFV/ PUR/ BEC K for VCB

Euroload Changeover Switch

FORMAT B (Annexure-III)

NXPLUS C Single busbar. Maintenance-free for lifetime

Bill of Quantity for Electrical & Computer wiring works for Shifting of SMECC Jamshedpur to Jamshedpur Branch Premises

STANDARD SPECIFICATION FOR. LIGHTING AND DC DISTRIBUTION PANELS WITH MCBs DOCUMENT NO: 44LK-5100/E.02/011

FINANCIAL BID NAME OF WORK : ELECTRIFICATION WORK AT THE NEW OFFICE PREMISES OF SBI EXCLUSIF KOZHIKODE BRANCH

TGK Prefabricated Substation Technical Data

Design Standard. Purpose: Design Standard:

Amount (Rs) 1.5 sq. mm ISI marked, FR

SNO DESCRIPTION QTY UNIT RATE AMOUNT MAIN PUMP 1

0.3 This standard is generally based on the following standards:

Package Price for Grid Connected 3.3 MW Synchronized Electricity: Please Call For Details Price

MINIATURE CIRCUIT BREAKER

GMR - 67P 67P 09/05/2016 GMR - 067P

MEDIUM VOLTAGE AIR INSULATED ARC-RESISTANT LOAD BREAK AND DISCONNECT SWITCHES

Standby Amper VOLTAGE

List of materials for 1Km. Of L.T line 1-Ph., 2-Wire AB cable (1 X 25+1X16) sq.mm using 8M X 200 KG. PSC Pole

Standby Amper VOLTAGE

LIST OF EDD DESCRIPTION/ SPECIFICATION AS 19 TH OCTOBER 2016

P 602. Voltage kva kw kva kw Amp 400/230 93,00 74,40 85,00 68,00 123,00 OTHER ACCESSORIES

Distribution transformers Efficiency over life-cycle

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position

sl. No Description Unit Qty Rate (Rs) Amount (Rs)

Transcription:

ESTIMATE SUPPLYING, INSTALLATION, TESTING AND COMMISSIONING OF INDOOR TYPE 33 / 0.415 KV SUB STATION AT RMRCT, JABALPUR M.P. ABSTRACT OF ESTIMATE DESCRIPTION Amount SH: 1 : INDOOR TYPE 33 KV VCB PANELS : 9861450.00 SH: 2 : TRANSFORMERS : 1810400.00 SH: 3 : M.V.PANELS : 5110000.00 SH: 4 : APFC PANEL : 1330000.00 SH: 5 : CABLES : 6098310.00 SH: 6 : EARTHING : 687250.00 SH: 7 D.G. SET 6702590.00 TOTAL 31600000.00

1 : INDOOR TYPE 33 KV VCB PANELS : Sl. DESCRIPTION OF ITEMS QTY UNIT RATES AMOUNT 1 33 KV INDOOR TYPE H.T. PANEL : Nominal System Voltage - 33 KV, 50 Hz. Highest System Voltage - 36 KV, 50 Hz. Supply, installation, testing and commissioning of Extendable Indoor type 3 Pole,33 KV Vaccum Circuit Breaker ( VCB ) with H.T. panel board,effectively earthed,ip-4x protection, compartmentalized cubical segregated and modular in costruction M.V. panel board, floor mounted, fabricated with minimum 2.5 mm thick ( Load bearing members ) and 2.0 mm thick (doors & covers) made of CRCA M.S.sheet, powder coated, bus-bar chamber, outgoing switchgears etc, colour coded PVC sleeved vertical / horizontal busbar of required size & length, insulators, hardware, gasket, hinged door, fine control wiring of suitable size of wire etc two earthing terminal busbar of size 25 x 5 mm with nut & bolts at out side of the panel, rating and name plates for all switchgears, wiremesh jali for ventilation etc comprising with the followings- INCOMER : A. 1 No 33 KV, 25 KA, 1250 A vertical isolation, horizontal drawout type VCB with integral earthing facility, copper busbars of adequate capacity etc with the following - i Rear Cable box suitable for 240 sq mm XLPE cable. ii Shunt Trip coil & Closing Coil - 24 V DC. iii Manually and motor operated, spring charged trip free type VCB, incorporating mechanical as well as electrical ON/OFF indication.spring charge / discharge mechanical indication "OFF" push buttons (shrouded) test/ service position limit switches with 6 NO / 6NC breaker aux. contacts in service position. iv 3 Nos C.T.,s with double wound,resin cast dual ratio C.T.'s 200/100/5+5 (seperate core for metering and separate core for

Sl. DESCRIPTION OF ITEMS QTY UNIT RATES AMOUNT protection). a. 15 VA burden for protection ( Purpose- Relaying ) Class of accuracy- 5 P Accuracy limit factor - 10 b. 15 VA burden for instrumentation ( Purpose- Metering ). Class of accuracy- 0.5 STR ( Short time thermal rating ) -25 KA (rms) for 1 sec. IL ( Impulse withstand voltage ) -36/70/170 KVp. v. 3 nos VT,drawout type,1 phase,3 limbs,with H.T.Fuses. PTR- 33KV/ 3/110 V/ 3 AC Core-1 : 100 VA, class-1. Core-2 : 50 VA, class-3p. IL-36/70/170 KVp. vi Protection arrangement for the incoming breaker shall comprise of the following: a Microprocessor based Numerical relay non directional with Three O/C and One E/F relay with communication facility with standard modbus / SCADA compactibility. O/C setting range shall be of 50-200% ( in step of 1 % ) and E/F setting range shall be of 20-80% ( in step of 1 % ) The relay should be capable of storing minimum last 5 fault record with following features- 1 Self diagonisis. 2 Minimum last 5 abnormal fault recording. 3 On line display of current. 4 Communicable with Open Protocal having RS-485 port. 5 Instantaneous Over-current protection with adjustable timer. 6 Breaker failure detection vii. 1 No Master trip relay hand reset type. ( MTR ) viii. 1 No.Trip Circuit supervision relay.( TSR ) ix. 1 No Energy meter 3 Phase-4 wire, having import and Export facility. x. 1 no Multi function meter with communication facility. B OUT GOINGS : 4 No 33 KV, 25 KA, 1250 A vertical isolation, horizontal drawout type VCB with integral earthing facility, copper busbars of adequate capacity etc with the following with each Breaker -

Sl. DESCRIPTION OF ITEMS QTY UNIT RATES AMOUNT i Rear Cable box suitable for 185 sq mm XLPE cable. ii Shunt Trip coil & Closing Coil - 24 V DC. iii Manually and motor operated, spring charged trip free type VCB breaker, incorporating mechanical as well as electrical ON/OFF indication.spring charge / discharge mechanical indication "OFF" push buttons (shrouded) test/ service position limit switches with 6 NO / 6NC breaker aux. contacts in service position. iv 3 Nos C.T.,s with double wound, dual ratio C.T.'s 150/5+5 (seperate core for metering and separate core for protection). a. 15 VA burden for protection ( Purpose- Relaying ) Class of accuracy- 5 P Accuracy limit factor - 10 b. 15 VA burden for instrumentation ( Purpose- Metering ). Class of accuracy- 0.5 STR ( Short time thermal rating ) -25 KA (rms) for 1 sec. IL ( Impulse withstand voltage ) -36/70/170 KVp. v. 3 nos VT,drawout type,1 phase,3 limbs,with H.T.Fuses. PTR- 33KV/ 3/110 V/ 3 AC Core-1 : 100 VA, class-1. Core-2 : 50 VA, class-3p. IL-36/70/170 KVp. vi. Protection arrangement for the incoming breaker shall comprise of the following: a Microprocessor based Numerical relay non directional with Three O/C and One E/F relay with communication facility with standard modbus / SCADA compactibility. O/C setting range shall be of 50-200% ( in step of 1 % ) and E/F setting range shall be of 20-80% ( in step of 1 % ) The relay should be capable of storing minimum last 5 fault record with following features- 1 Self diagonisis. 2 Minimum last 5 abnormal fault recording. 3 On line display of current. 4 Communicable with Open Protocal having RS-485 port. 5 Instantaneous Over-current protection with adjustable timer.

Sl. DESCRIPTION OF ITEMS QTY UNIT RATES AMOUNT 6 Breaker failure detection vii. 1 No Master trip relay hand reset type. viii. 1 No.Trip Circuit supervision relay. ix. 2 No Aux. Relay for Transformer protection x. 1 no Multi function meter with communication facility. xi. 1 No Energy meter 3 Phase-4 wire, having import and Export facility. C. INDICATING LAMPS FOR ALL CIRCUIT BREAKERS : i. Red Colour : For Breaker ON indication. ii. Green Colour : For Breaker OFF indication. iii. Amber Colour : For Breaker trip indication. iv. Blue Colour : For Spring charged indication. v. White colour : For Trip ckt.healthy indication. vi. Red Colour : For 'R' Phase indication. vii. Yellow Colour : For 'Y' Phase indication. viii. Blue Colour : For 'B' Phase indication. D. ACCESSORIES FOR ALL CIRCUIT BREAKERS : i. 1 No TNC switch without bell alarm contact. ii. 1 No local - remote selector switch. 2 position, 4 ways, stayput locable in both position lever type handle, angular movement 90 deg, 2 contact close in each position. iii. 1 No space heater with thermostat range 30-90 deg celsius. iv. Antipumping circuit v. Push Button for trip ckt healthy. 1 Set 9679000.00 9679000.00 2 BATTERY AND BATTERY CHARGER : Supplying,erection,testing and commissioning of 24 Volts DC 180 AH supply system comprising of one set of Lead acid sealed maint. free batteries, and battery charger with Boost charger and float charger complete suitable for operating the control devices of HT panel. 1 No. 169000.00 169000.00

Sl. DESCRIPTION OF ITEMS QTY UNIT RATES AMOUNT 3 D.C. MCB PANEL : A. DISTRIBUTION BOARD : Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volt, on surface/ recess, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 2 + 12 way, Double door 1 No. 4900.00 4900.00 B. DC MCB : Supplying and fixing following size 5 A to 32 A rating, DC MCB 6 A SP DC MCB 12 No. 525.00 6300.00 25 A SPN DC MCB 1 No. 2250.00 2250.00 TOTAL 9861450.00

2 : TRANSFORMERS : Sl. DESCRIPTION OF ITEMS QTY UNIT RATES AMOUNT 1 TRANSFORMERS (INDOOR TYPE) : ( Copper wound ) Supply, receiving, storing, inspection, handling, assembling, installing in correct aligned position,effecting proper connections, testing and commissioning of continous rating following outdoor type oil filled off circuit tap changer transformer with the following specifications confirming to IS : 2026. No load voltage Ratio : 33 / 0.415 KV No. of Phases / Freq.: 3 Phase / 50 Hz. Type : Core type, double copper wound Cooling : ONAN Vector Group : DYN 11 Temperature rise (Oil winding) : 50 / 55 Deg. Taps on HV for HV variation : -10% to + 5% in step Termination ( HV ) : Air filled cable box. Termination (LV) : Air filled cable box suitable for 1.1 KV, Al. Cond. cable, XLPE insulated.3rx3.5cx 240 sqmm. Transformer shall be supplied with following fittings: a. Conservator with drain valve. b. oil level indicator. c. Silicagel breather with oil seal. d. First filling of filtered oil as per IS 335 i/c make up fill during installation of transformer plus 10% extra oil. e. Off circuit switch f. Lifting lugs g Earthing terminals - 2 nos. h. Thermometer pocket. i. Air release plug. j. Inspection cover. k. Top filter valve 1 No. l. Bucholtz relay with shut off valve.

Sl. DESCRIPTION OF ITEMS QTY UNIT RATES AMOUNT m. 150 mm dial winding and oil temperature indicator and 2 sets of contacts for alarm & trip n. Radiator with top and bottom shut off valves. o. 100 mm dial oil level gauge with max pointer Rating and Diagram plate. p. Bi-directional Plain/Flanged Rollers. q. 150 mm dial winding temperature indicator with max pointer. A. 500 KVA Transformer - 33 / 0.415 KV 1 Each 1810400.00 1810400.00 TOTAL 1810400.00

3 : ELECTRICAL PANELS : Sl. DESCRIPTION OF ITEMS QTY UNIT RATE AMOUNT No. In Figures In Words 1 MAIN L.T.PANEL : Supplying, installation, testing and commissioning of indoor type, sectionalised, compartmentalized, MV Panel board of suitable size fabricated from CRCA sheet of 2 mm thick for frame work, enclosure and doors, 3 mm thick for gland plates with stiffers where required, having vibration free structure chemically treated with seven tank process before painting for surface treatment and powder coated,with aluminum busbar with DMC / SMC busbar supports suitable for 3 Phase 415 V 50 Hz AC supply i/c providing and fixing the following switchgear mounted thereon complete with gaskets and interconnections, connection as per specification complete as required. ( The board shall be dust & vermin proof with suitable degree of IP protection ) ( The depth of Panel should not be less than 0.90 Mtr.) A. INCOMING SWITCHGEARS : a. 2 Nos Four Pole 1000 A,415 V, MDO type Air Circuit Breaker,50 KA Breaking Capacity, with inbuilt Microprocessor based release with suitable CT's. having Overload, Short circuit,earth fault, instantaneous protection, over voltage & undervoltage release,castle lock etc complete as per specification and requirement with the followingsb. 2 No. Digital Ammeter c. 2 No. Digital Volt meter d. 3 Nos. 1000 / 500 / 5 Amps. C.T. for metering. e. 3 Nos. 250V Phase Indicating lamp with MCBs. f. 2.5 Sq.mm. Lugged copper Control wires L.S. g. Lugged Copper connecting leads. Rating: As required,

Sl. DESCRIPTION OF ITEMS QTY UNIT RATE AMOUNT No. In Figures In Words B. BUS - BAR : 4 Nos. 1200 Amp.Electrolytic grade Aluminum Bus Bars insulated with colored Heat Shrinkable PVC Sleeves & duly supported on SMC/DMC molded supports. C. BUS-COUPLER : a. 1 Nos Four Pole 1000 A,415 V, Manually operated and drawout type Air Circuit Breaker,50 KA Breaking Capacity, with under Voltage and castle lock arrangement. D. OUTGOING SWITCHGEARS : a. 2 Nos Four Pole 1000 A,415 V, M.D.O.type Air Circuit Breaker,50 KA Breaking Capacity, with inbuilt Microprocessor based release with suitable CT's. having Overload, Short circuit,earth fault, and undervoltage release complete as per specification and requirement. (i) 1 No. Digital Multi-function Panel Mounted Meter. (ii) 3 Nos. 1000 / 500 / 5 Amps. C.T. for metering. (iii) 3 Nos. 250V phase Indicating lamp with MCBs. (iv) 2.5 Sq.mm. Lugged copper Control wires L.S. (v) Lugged Copper connecting leads. Rating: As required, b. 2 No.- 400 Amp.36 KA, TP MCCB with Cu. N- link.with Microprocessor based release with integral overload, short circuit and earth fault protection and A digital Ammeter with suitable CT's c. 2 No. - 250 Amp. 36 KA, TP MCCB with Cu. N- link. with Thermal magnetic trip unit.with A digital Ammeter with suitable CT's. Note :- All MCCB's shall be provided with rotary operated mechanism and padlocking arrangement. 1 No 2760000.00 2760000.00

Sl. DESCRIPTION OF ITEMS QTY UNIT RATE AMOUNT No. In Figures In Words 2 SUB L.T.PANEL Supplying, installation, testing and commissioning of indoor type, sectionalised, compartmentalized, MV Panel board of suitable size fabricated from CRCA sheet of 2 mm thick for frame work, enclosure and doors, 3 mm thick for gland plates with stiffers where required, having vibration free structure chemically treated with seven tank process before painting for surface treatment and powder coated,with aluminum busbar with DMC / SMC busbar supports suitable for 3 Phase 415 V 50 Hz AC supply i/c providing and fixing the following switchgear mounted thereon complete with gaskets and interconnections, connection as per specification complete as required. ( The board shall be dust & vermin proof with suitable degree of IP protection ) ( The depth of Panel should not be less than 0.90 Mtr.) A. INCOMING SWITCHGEARS : a. 2 Nos Four Pole 1000 A,415 V, Manually operated and drawout type Air Circuit Breaker,50 KA Breaking Capacity, with inbuilt Microprocessor based release with suitable CT's. having Overload, Short circuit,earth fault, and undervoltage release complete as per specification and requirement. b. 1 No. Digital Multi-function Panel Mounted Meter. c. 3 Nos. 1000 / 500 / 5 Amps. C.T. for metering. d. 3 Nos. 250V phase Indicating lamp with MCBs. e. 2.5 Sq.mm. Lugged copper Control wires L.S. f. Lugged Copper connecting leads. Rating: As required, B. BUS - BAR : 4 Nos. 1200 Amp.Electrolytic grade Aluminum Bus Bars insulated with colored Heat Shrinkable PVC Sleeves & duly supported on SMC/DMC molded supports.

Sl. DESCRIPTION OF ITEMS QTY UNIT RATE AMOUNT No. In Figures In Words C. BUS-COUPLER : a. 1 Nos Four Pole 1000 A,415 V, Manually operated and drawout type Air Circuit Breaker,50 KA Breaking Capacity, with under Voltage and castle lock arrangement. D. OUTGOING SWITCHGEARS : a. 2 No. - 630 Amp. 36 KA, TP MCCB with Cu. N- link. with Microprocessor based release with integral overload, short circuit and earth fault protection and A digital Ammeter with suitable CT's b. 2 No. - 400 Amp. 35 KA, TP MCCB with Cu. N- link. with Thermal magnetic trip unit.with A digital Ammeter with suitable CT's. c. 2 No. - 250 Amp. 35 KA, TP MCCB with Cu. N- link. with Thermal magnetic trip unit.with A digital Ammeter with suitable CT's. d. 2 No. - 100 Amp. 25 KA, TP MCCB with Cu. N- link. with Thermal magnetic trip unit.with A digital Ammeter with suitable CT's. 1 No. 2350000.00 2350000.00 TOTAL 5110000.00

4 : AUTOMATIC P.F.CORRECTION PANEL : Sl. DESCRIPTION OF ITEMS QTY UNIT RATES AMOUNT 1 AUTOMATIC P.F.CORRECTION PANEL : ( 175 KVAr ) Supply, installation, testing and commissioning of totally enclosed cubical Power Factor Correction Panel board fabricated with 14/16 swg M.S.sheet powder coated, hardware, all interconnections of suitable size of pvc insulated cu.leads with lugs, two earthing terminal on both end of panel, control wiring etc complete as required, comprising with the followings- NOTE:- Sheet 14 swg : panel sides,upper,lower,and Ft.doors Sheet 16 swg : back side and compartments. Glande plates : 3 mm thick. Cable entry : Provision at bottom and upper sides. A. 1 No. - 400 A, T.P. MCCB 35 KA ( As Incomer ) B. following capacities Mix Di-electric Three phase Power Capacitora. 1 Set - 25 KVAr with 60 A TP MCB.( Fixed ) b. 2 Set - 05 KVAr with AC3-20 A Power Contactor & 20 A TP MCB c. 4 Set - 10 KVAr with AC3-60 A Power Contactor & 63 A TP MCB d. 5 Set - 20 KVAr with AC3-60 A Power Contactor & 63 A TP MCB C. 1 No. - 12 stage Automatic power factor Correction Controller with suitable size C.T. for operation. D. 1 Set - VAF meter with suitable size of 3 nos C.T.'s. E. 4 Nos - Al. Bus Bar of 500 A F. 1 Set - 3 Nos. LED type RYB Indicating Lamps through SP MCB. 2 Set 665000.00 1330000.00 TOTAL 1330000.00

5 : CABLES : Sl. DESCRIPTION OF ITEMS QTY UNIT RATES AMOUNT 1 L.T. CABLING : Supply & Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade including excavation of cable trench & back filling after laying of cable with sand & brick protection as required. a. 2 Core, 2.5 sq. mm Armoured Copper Control Cable 200 RM 398.00 79600.00 b. 3 Core, 2.5 sq. mm Armoured Copper Control Cable 100 RM 450.00 45000.00 c. 12 Core, 2.5 sq. mm Armoured Copper Control Cable 100 RM 990.00 99000.00 d. 4 Core, 10 sq. mm XLPE Aluminium. Cable. 300 RM 450.00 135000.00 e 3.5 Core, 35 sq. mm XLPE Aluminium. Cable. 60 RM 620.00 37200.00 f 3.5 Core, 185 sq. mm XLPE Aluminium. Cable. 400 RM 2170.00 868000.00 g 3.5 Core, 240 sq. mm XLPE Aluminium. Cable. 500 RM 2750.00 1375000.00 h 3.5 Core, 300 sq. mm XLPE Aluminium. Cable. 350 RM 3180.00 1113000.00 2 CABLE END TERMINATION : ( 1100 V Gr.Cable ) Supplying and making indoor end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade a. 2.0 Core, 2.5 sq. mm to 12 core 2.5 sqmm Ar. cable (19 mm) 24 Nos 240.00 5760.00 b. 4 Core, 10 sq. mm ( 22 mm) 24 Nos 250.00 6000.00 c. 3.5 Core, 35 sq. mm (28 mm) 10 Nos 350.00 3500.00 d. 3.5 Core, 185 sq. mm (50 mm) 10 Nos 700.00 7000.00 e 3.5 Core, 240 sq. mm (62 mm) 18 Nos 900.00 16200.00 f 3.5 Core, 300 sq. mm (70 mm) 20 Nos 1450.00 29000.00

Sl. DESCRIPTION OF ITEMS QTY UNIT RATES AMOUNT 3 33 H.T. CABLES : Supply of one number XLPE power cable of 33 KV grade of following size in existing masonary open duct as required. a. 3 C X 240 sq mm. ( 33 KV ) Armoured Aluminium Earthed Cable 200 Mtrs 4950.00 990000.00 4 33 KV Heat shinkable Indoor XLPE cable jointing Kit : Supplying & making indoor cable end termination with heat shrinable jointing kit compolete with all accessories including lugs suitable for the following size of 3 core XLPE aluminium conductor cable of 33 KV grade as required. a. 240 sq mm 8 Nos 43600.00 348800.00 5 33 KV Heat shinkable out door XLPE cable jointing Kit : Supplying & making outdoor cable end termination with heat shrinable jointing kit compolete with all accessories including lugs suitable for the following size of 3 core XLPE aluminium conductor cable of 33 KV grade as required. a. 240 sq mm 2 Nos 49000.00 98000.00 6 33 KV H.T.BOOTS : Supply, installataion of heat shrinkable L type 33 KV HT boots complete with valcanizing insulation tape and cleaning solvent suitable for the following size of cable - ( and as per approved material.) a. 3 Nos X 240 sq mm 8 Sets 42000.00 336000.00

Sl. DESCRIPTION OF ITEMS QTY UNIT RATES AMOUNT 7 Cable Trench a Earth work in excavation of cable trench by machenical means (hydrolic excavated ) including disposal of excavated earth lead up to 50 mtr. 90 m3 300.00 PP b providing & laying of cement concrette1:3:6 8 m3 4500.00 36000.00 c providing & laying of cement concrette.1:1.5:3 30 m3 6250.00 187500.00 d providing of cement plaster 20 mm thick 1: 6 mortor 400 m2 190.00 76000.00 e providing, cutting & fixing of TMTsteel Bar 500 kg 65.50 32750.00 f Providing & fixing of Chukker plate on covering Trench 30 m2 4900.00 147000.00 Total 6071310.00

6 : EARTHING : Sl. DESCRIPTION OF ITEMS QTY UNIT RATES AMOUNT 1 EARTH STATION : Preparation of the Plate Earth Station: (as per IS:3043) COPPER PLATE EARTH STATION : Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonary enclosure with cover plate having locking arrangement and watering pipe of 2.7 mtr. Long etc. with charcoal / coke and salt as required. 8 Nos. 13500.00 108000.00 2 G.I.PLATE EARTH STATION : Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonary enclosure with cover plate having locking arrangement and watering pipe of 2.7 mtr. Long etc. with charcoal / coke and salt as required. 20 Nos. 6580.00 131600.00 3 Providing and fixing earth bus of 50 mm x 5 mm copper strip on surface for connection etc. as required 30 Mtr. 1980.00 59400.00 4 Providing & fixing 50 mm x 5 mm G. I. strip on surface or in recess for connection etc. as required 70 Mtr. 350.00 24500.00 5 Providing & fixing 25 mm x 5 mm. Cu. strip on surface or in recess for connection etc. as required with 40 mm g.i. pipe 100 Mtr. 1450.00 145000.00 6 Providing & fixing 25 mm x 5 mm G. I. strip on surface or in recess for connection etc. as required with 40 mm g.i. pipe 350 Mtr. 625.00 218750.00 TOTAL 687250.00

Supply, Installation, Testing nad Commissioning of 500 KVA D.G.SET at RMRC T Jabalpur Sl. DESCRIPTION OF ITEMS QTY UNIT RATES AMOUNT 1 DIESEL GENERATOR SET : ( With Acoustic M.S.Enclosure ) Providing, Installing, Testing and commissioning of 'Silent Type' Diesel Generating set having Standby Power Rating of 500 KVA, 415 volts at 1500 RPM, 0.8 lagging power factor at 415 V suitable for 50 Hz, 3 phase system and consisting of the followings : A. ENGINE: Diesel engine 4 stroke water cooled, electric start, of suitable BHP at 1500 RPM suitable for above output of alternator at 40 Degreee C, 50% RH & at 1000 Metre MSL and conforming to BS 5514, BS 649, IS 10000, capable of taking 10% over loading for one hour after 12 hours of continuos operation. The engine will be fitted complete with all the required accesories. B. Engine mounted Instrument Panel fitted with and having digital display for following : a. Start-stop switch with key b. Water temperature indication c. Lubrication oil pressure indication d. Lubrication oil temperature indication e. Battery charging indication f. RPM indication g. Over spped indication h. Low lub. Oil trip indication i. Engine Hours indication Sl. DESCRIPTION OF ITEMS QTY UNIT RATES AMOUNT

C. ALTERNATOR : Synchonous alternator rated at 500 KVA, 415 volts at 1500 RPM, 3 phase 50 Hz, AC supply with 0.8 lagging power factor at 40 Degree C, 50% RH & at 1000 metre MSL. The alternator shall be having SPDP enclosure, brushless, continuous duty, self excited and self-regulated through AVR conforming to IS : 4722/BS 2613 suitable for tropical conditions and with class - F/H insulation. D. Base Frame & Foundation : Both the engine and alternator shall be mounted on suitable base frame made of MS channel with necessary reinforcement which shall be installed on existing cement concrete foundation with vibration isolation arrangement as per recommendations of manufacturer. E. Fuel Tank : Daily service fuel tank of 990 litres capacity fabricated out of 3 mm thick M.S sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine complete with MS class C pipes of suitable dia. Complete with valves, level indications & accessories as required as per specifications. F. Exhaust system : Dry exhaust manifold with residential exhaust silencer. G. STARTING SYSTEM : 24 V starting system comprising of starter motors, voltage regulator and arrangement for initial excitation complete with suitable nos. of batteries (25 plates, 180Amp. Hour capacity lead acid type) as required as per specifications. H. Accoustic and weather proof enclouser (Outdoor type) with arrangement for fresh air intake for cooling of the engine & alternator, extraction, discharging hot air in to the atmosphere as Sl. DESCRIPTION OF ITEMS QTY UNIT RATES AMOUNT

I. Turbochargers with After Cooler : Turbocharger mounted on the engine to convert pulse energy or exhaust gases for more power, improved fuel economy, altitude compensation & lower exhaust temperature,smoke & noise levels. 1 Nos 4750000.00 4750000.00 2 D.G. CONTROL AND MAIN PANEL ( INDOOR TYPE ) :AMF Panel Supplying, installation, testing and commissioning of wall mounted type sectionalised, compartmentalized panel of suitable size fabricated from CRCA steel sheet of 2 mm thick for frame work, enclosure and doors, 2 mm thick for gland plates with stiffers where required, having vibration free structure chemically treated with seven tank process before painting for surface treatment and powder coated,with suitable size of aluminum busbar with DMC / SMC busbar supports suitable for 3 Phase 415 V 50 HZ AC supply i/c providing and fixing the following switchgear mounted thereon complete with gaskets and interconnections, connection as per specification complete as required. ( The board shall be dust & vermin proof with suitable degree of IP protection ) ( The depth of Panel should not be less than 0.90 Mtr.) NOTE : All switchgears Ics shall be equal to 100% Icu. a. A.M.F. CONTROLS : Logic : The A.M.F.logic shall start the set automatically only in the event of : 1. Mains failure. 2. Phase failure. 3. Voltage, drop to 85 % of 415 volts ( not fault tripping ) and STOP in the event of: Sl. DESCRIPTION OF ITEMS QTY UNIT RATES AMOUNT

1. Mains ON. 2. Fault conditions. 3. Over Loading etc. The set shall be capable of starting and taking up the load within the time 10 30 secs.and shall be run for 3-5 mts after change over or closing. b. ELECTRICAL DISTRIBUTION : A. 4 Nos. 1200 Amp. Al. busbars with insulators etc. B. INCOMING SWITCHGEARS : a. 2 Nos Four Pole 1000 A,415 V, Electrically operated and drawout type Air Circuit Breaker,50 KA Breaking Capacity, with inbuilt Microprocessor based release with suitable CT's.,Overload, Short circuit,earth fault, instantaneous protection, castle lock etc complete as per specification and requirement each with the followingsb. 1 No. Digital Multi-function Panel Mounted Meter with RS 485 Port. c. 3 Nos. 1000 / 500 / 5 Amps. C.T. for metering. d. 3 Nos. 250V Phase Indicating lamp with MCBs. e. 2.5 Sq.mm. Lugged copper Control wires L.S. f. Lugged Copper connecting leads. Rating: As required, g. 1 Nos. Triping or Trip Free relays.( Master Trip Relay ) h. 1 Nos. Reverse Power relays. i. 1 Nos. Over voltage protection relays j. 1 Nos. Under Voltage protection relays Sl. DESCRIPTION OF ITEMS QTY UNIT RATES AMOUNT C. OUTGOING SWITCHGEARS :

a. 1 Nos Four Pole 1000 A,415 V, Electrically operated and drawout type Air Circuit Breaker,45 KA Breaking Capacity, with inbuilt Microprocessor based release with suitable CT's.,Overload, Short circuit,earth fault, instantaneous protection, castle lock etc complete as per specification and requirement each with the followingsb. 1 No. Digital Multi-function Panel Mounted Meter with RS 485 Port. c. 3 Nos. 1000 / 500 / 5 Amps. C.T. for metering. d. 3 Nos. 250V Phase Indicating lamp with MCBs. e. 2.5 Sq.mm. Lugged copper Control wires L.S. f. Lugged Copper connecting leads. Rating: As required, g. 1 Nos. Triping or Trip Free relays.( Master Trip Relay ) h. 1 Nos. Reverse Power relays. i. 1 Nos. Over voltage protection relays j. 1 Nos. Under Voltage protection relays D. Other Measuring Instruments : ( 1 Sets ) a. Volt meter (D.C. 0-30 ) for battery. b. Frequency meter. c. KW meter. d. Hour meter. e. Ameter D.C. (0-30 amps.) E. Operational switches for controls : ( 1 Sets ) a. Test manual Auto Off. b. Reset,start,stop,acknowledge,test,close,trip, control ON/OFF switch,remote stop etc. c. Load, Line, Alternator Voltage monitor switch. Sl. DESCRIPTION OF ITEMS QTY UNIT RATES AMOUNT F. Audio/Video annunciation for -

a. High Water temp. b. Low Lubricating oil pressure c. Engine over speed d. Engine fails to start. e. Full load / Max. load warning G. Impulse counter with locking and reset facility. H. Indications : ( 1 Sets ) a. D.C.control on b. LLOP ( Low Lubricating Oil Pressure ) c. HCT ( High coolent temp. ) d. LOS ( Load on set. ) e. LOM ( Load on mains.) f. Charging on. g. Mains on. h. D.G.Set running. i. STF. ( Start Failure ) j. Over speed. k. Test l. Earth fault. m. Over load. n. Set of indicating lamp to indicate OPEN, CLOSE, TRIP. 1 set 1275000 1275000.00 Sl. DESCRIPTION OF ITEMS QTY UNIT RATES AMOUNT 3 A BATTERY CHARGER : ( 1 Sets ) Battery charger complete with transformer / rectifier selector switch for trickle, OFF and boost and current adjustment. trickle charging facility

and an isolating switch, Auto cut Off Including control relays,timers,control fuses, control wiring of 2.5 sqmm wire size,etc complete as required, as per A.M.F.design aspects.both the contactor must be electrically interlocked (for mains & D.G.supply.) etc complete as required. B ENERGY METER : ( 1 No ) a. 1000/5 A Three phase Energy meter -- 01 no. b. 1000/5 A C.T. s, - 4 Nos. 1 No. 195000.00 195000.00 4 D.G.SET FOUNDATION : Providing Cement Concrete foundation 1:1.5:3 ( 1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size ) in foundation of DG set including form work etc as required ( excluding reinforcement ) and as per manufacturer's and stack designer's recommendations, 18 m3 6250.00 112500.00 5 Providing, cutting, bending & laying of TMT reinforcement steel 1000 kg 65.5 65500.00 6 Providing & fixing of M.S. tubular/ square pipe for trusses /perlins for shed over d.g. set 1400 kg 109.25 152950.00 7 Providing & fixing of precoated galavnized iron sheet 90 m2 620 55800.00 Sl. DESCRIPTION OF ITEMS QTY UNIT RATES AMOUNT 8 Supply, stacking & filling of murrum 90 m3 850 76500.00 9 EXHAUST PIPING :

Supply and fixing of following B class M.S.pipe for exhaust with thermal insulation and aluminium cladding in over all length of pipe, s.s.flexible pipes, rain cowl etc i/c clamping of pipe, bends, reducer, suitable opening in wall if required etc complete as req. a. 150 mm Dia 5 RM 3868.00 19340.00 TOTAL : 6702590.00

Make Of Material 1 H.T. Panel ( VCB ) Schneider Electric / ABB / L& T / Crompton 2 L.T. Panel switchgear L& T / C& S / ABB / Schneider Electriic 3 Power Capacitor L&T / Neptune / Epcos ( Siemens ) 4 Cables Finolex / Havells / Polycab / Gloster 5 Transformer Krilosker / Areva / Schneider Electric / Crompton All Material Should Be ISI Marked