Wiring Diagrams DIAGRAM INDEX

Similar documents
Wiring Diagrams DIAGRAM INDEX. POWER SCHEMATICS Figure Number. Label Diagram No. 30HX ALL ALL

Wiring Diagrams (Including Accessories) (50/60 Hz)

30GX AIR-COOLED LIQUID CHILLER

30GX AIR-COOLED LIQUID CHILLER

wiring diagrams SINGLE PACKAGE ROOFTOP GAS HEATING/ELECTRIC COOLING UNITS

Installation Instructions Electric Heaters 5 20 kw

Installation Instructions Electric Heaters 5 20 kw

Installation Instructions

PRODUCT DRAWING WIRING DIAGRAM FIELD CONNECTIONS MILLENNIUM MODEL YT CHILLERS (STYLE J) WITH ELECTRO-MECHANICAL STARTER JOB DATA:

Installation Instructions

Installation Instructions

CHILLER MODEL NO. YS SOLID STATE STARTER, MODEL NO. SSS, L B OPTIONAL FACTORY INSTALLED DISCONNECT SWITCH AMPS OR

Installation Instructions

WIRING DIAGRAM MODEL YK (STYLE G) LIQUID CHILLERS OPTIVIEW CONTROL CENTER WITH ELECTRO-MECHANICAL STARTER

INSTALLATION, START-UP AND SERVICE INSTRUCTIONS

MODELS YCRL0064, 0074, 0084, 0096, 0118, 0126, 0156, 0177, 0198, 0200, 0230, 0260, 0300, 0345, 0385, 0445, 0530 and YCRL0610 STYLE "A"

Installation Instructions

Installation Instructions

YCAL0014E_ - YCAL0124E_ R-22 & HFC-407C STYLE C (60 Hz)


Temperature Control Panel Wiring Diagram Model: ISPA-120-1P-15A

ELEMENTARY DIAGRAM CONNECTION DIAGRAM CONTROL PANEL AND CONNECTION DIAGRAM SYSTEM WIRING FOR MODELS:

WIRING DIAGRAMS FB4C FE4A/FE5A FH4C FV4C FX4D FY5B PF4MA PF4MB LABEL

Installation Instructions

Application Engineering

Installation Instructions

McQuay. Evaporative Condenser Cooled Chiller. EGR Vintage A. Last Manufactured: Replacement Parts List No Revision B 07/2010

MODEL 422 Submersible Pump Controller

FIELD CONNECTIONS MODEL YK CHILLERS (STYLE F AND G) WITH VARIABLE SPEED DRIVE

R-410A 50Hz & 60Hz. Renewal parts /3/ MODELS ONLY. Issue Date: September 07, 2011

FIELD CONNECTIONS FOR YK CHILLER (STYLE G) OPTIVIEW CONTROL CENTER WITH REMOTE MEDIUM VOLTAGE SSS

PERFORMANCE DATA TYPICAL FIELD WIRING CERTIFIED DIMENSION PRINT CERTIFIED ROOF CURB DIMENSION PRINTS

WIRING DIAGRAMS MODEL YK (STYLE G) LIQUID CHILLERS OPTIVIEW CONTROL CENTER WITH SSS, LV VSD W/ MODBUS, & MV VSD

SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS DESCRIPTION FEATURES H2CA300, 360, 480 & THRU 50 NOMINAL TONS

12 CB30M SERIES UNITS INCLUDING ECB29 ELECTRIC HEAT

Application Engineering

Installation Instructions

Wiring Diagrams DIAGRAM INDEX POWER SCHEMATICS

Installation Instructions

WIRING DIAGRAMS FA4C FY4A FC4D FX4C FH4C

Installation Instructions

Installation Instructions Central Battery Units

Water to Water Geothermal Heat Pump 3-Phase Models Both 208 & 480

Application Data CONTENTS. COMPRESSOR PHYSICAL DATA (Table 1) Table 1 Open-Drive Compressors

SIGNAL WORDS QUALIFIED PERSON

Installation Instructions

ARUF Series Multi-Position

Centrifugal Chiller PE046, PE047, PE048, PE050 PEH PF083, PF096, PF105, PF116 PH PHH PL

Air-Cooled Scroll Compressor Chillers Models AGZ 010A to AGZ 034A Models AGZ 026B to AGZ 130B. Revised Electrical Data Tables.

Installation Instructions

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 20 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

Pressure Makeup Jockey Pump Controller

WIRING DIAGRAM, MILLENNIUM TM MODEL YT (STYLE J) LIQUID CHILLERS GRAPHIC CONTROL CENTER WITH ELECTRO-MECHANICAL STARTER PRODUCT DRAWING JOB DATA:

331-SV. User Manual THREE PHASE DUPLEX LIFT STATION CONTROL PANEL WITH STATIONVIEW CONTROLLER. Ashland, OH

Installation Instructions

PACKAGED LIQUID CHILLER 6. HUMIDIFIER SECTIONS. C Member. Liquid Chiller. nowlc And noalc Series

ELECTRIC SCHEMATICS LS1 LS2. "1532ES / 1932ES" Service & Parts Manual - ANSI Specifications March 2008 Page 5-9 ART_2236 ART_2243

ACCESSORY KIT INSTALLATION INSTRUCTIONS

Coil Data Nominal Current MA Nominal VA Sealed Single Pole Normally Open (SPNO) White Rodgers Q

User s Manual. ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual

A I R H A N D L E R S CB26UH-R. MERIT Series R-22 - Upflow / Horizontal P R O D U C T S P E C I F I C AT I O N S

XCITE Owner s Manual. Reso-not TM Damping System XCITE 1502C HYDRAULIC POWER SUPPLY

SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 15 Troubleshooting Basic Controls

MEDIUM SILHOUETTE UNIT COOLERS AIR AND ELECTRIC DEFROST MODELS

Liebert CSU3000 DISCONTINUED PRODUCT. CSI Mainframe Cooling Systems. CT(Three Module) Model 20, 30 & 37 ton Mainframe Chiller

YCAS AIR-COOLED LIQUID CHILLERS YCAS0373 THROUGH YCAS0653 STYLE G (R22) (50 Hz)

MAGNETIC MOTOR STARTERS

Controls, Start-Up, Operation, Service, and Troubleshooting

Coil Data Nominal Current MA Nominal VA Sealed. Coil Data Nominal Current MA Nominal VA Sealed. Single Pole Double Throw (SPDT)

Application Engineering Europe

Installation Manual. Mixing Box Control Systems Installation, Operation, and Maintenance Manual. 605 Shiloh Road Plano, Texas

Installation Instructions

ELITE SERIES R-410A Ready - Multi-Position

SE-125 MANUAL GROUND-FAULT GROUND-CHECK MONITOR

FM200 FLOW/NO-FLOW MONITOR INSTALLATION AND TECHNICAL MANUAL 120 VAC MODEL 6/1/2017

SineWave Guardian TM 380V 600V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 17 ❷ Startup/Troubleshooting Pages WARNING

Installation Instructions

Installation Instructions

Table of Contents. 1. Model Designation And Unit Models Guide Specifications Technical Data Performance Data 10

CRECOMZR054B00 CRECOMZR055B00. VERTICAL AND HORIZONTAL ECONOMI$ER2 ACCESSORY MEDIUM ROOFTOP UNITS 15 to 27 1/2 TONS WARNING TABLE OF CONTENTS

User s Manual. ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual

Bussmann series Quik-Spec Power Module Switch elevator disconnect

300% Motor full load amps at 80 seconds, 400% Motor full load amps at 35 seconds

McQuay. Air-Cooled Global Reciprocating Condensing Unit. ACR Vintage A. Last Manufactured: 2003

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

Blank-off. HVAC unit screws. Spacer for 1" filter ILL. 3. Screw

Screw. (Note 4) Spacer for 1" filter ILL. 3. Screw

SAVE THESE INSTRUCTIONS

Product Catalog TSE Series Scroll Central Chillers

Matrix AP 400V 690V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 20 ❷ Startup/Troubleshooting Pages WARNING

32XR. 3 Phase Duplex Pump Control Panel (Level Transmitter Based) Quick Start Guide

Product Catalog TSE Series Scroll Central Chillers

Installation Instructions

McQuay Air-Cooled Reciprocating Chiller ALR

TA Ta VA CTRL-XFRMR

Screw. (Note 4) Spacer for 1" filter ILL. 3. Screw

J1 Plug Pin Identification

List price 2012 USD A Service manual, CA-UK B Service manual, CIM5-UK C Service manual, CIM6-UK 29.

Starcool Reefer Parts Service Manual, CIM6, Spare part catalog Short Form manual, CIM6, ES. Back plate, evaporator

INSTALLATION INSTRUCTIONS FOR Owner's Copy FILTERED AND REGULATED POWER SUPPLY VOLTS DC INPUT: Hz.

Transcription:

30HK040-060;30HL050,060;30HW018-040 Reciprocating Liquid Chillers with ComfortLink Controls 50/60 Hz Wiring Diagrams DIAGRAM INDEX UNIT 30 VOLTAGE DIAGRAM TYPE FIGURE LABEL DIAGRAM All Component Arrangement 1 30HK510176 All Low Voltage (24-V) Control Schematic 2 30HK510176 HK,HL040-060 All 115-V Control Schematic 3 30HK510177 All Power Schematic 4 30HK510177 All Field Wiring Diagram 5 30HK510228 All Component Arrangement 6 30HW500417 All Low Voltage (24-V) Control Schematic 7 30HW500417 30HWA/B,C/S018-040 All Power Schematic 8 30HW500418 All 115-V Control Schematic 9 30HW500418 All Field Wiring Diagram 10 30HW500768 SAFETY CONSIDERATIONS Installing, starting up, and servicing this equipment can be hazardous due to system pressures, electrical components, and equipment location. Only trained, qualified installers and service mechanics should install, start up, and service this equipment. Untrained personnel can perform basic maintenance functions such as cleaning coils. All other operations should be performed by trained service personnel. When working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached to the equipment. Follow all safety codes. Wear safety glasses and work gloves. Use care in handling, rigging, and setting bulky equipment. ELECTRIC SHOCK HAZARD. Open all remote disconnects before servicing this equipment. Use only designated overload protection. SEQUENCE OF OPERATION Start-Up When the unit Enable/Off/Remote switch is set to the ENABLE position, the 24-v control circuit will be energized. When there is a call for cooling and all safety devices are satisfied, the compressor will start unloaded after a delay of 1 to 3 minutes. The low pressure and oil pressure safety switches (if so equipped) will be bypassed for a 2-minute period after the compressor has been started. Capacity Control The 30HW018 and 028-040 units have 3 standard stages of capacity control, the 30HW025 units have 2 standard stages of capacity control, and the 30HK,HL units have 4 standard stages of capacity control. The standard capacity staging is provided by electrically actuated suction cut-off unloaders. One additional stage of capacity control can be provided by the optional hot gas bypass. When the leaving fluid temperature rises above the set point, the control will begin to add stages of capacity by starting a compressor. The control uses a leaving-water temperature control with entering water compensation routine and will add additional stages of capacity as required to meet the required load. If the unit is equipped with hot gas bypass, the hot gas bypass solenoid and compressor unloader for the circuit will be energized as the first stage of capacity. When the leaving-fluid temperature starts falling below the set point, the control will remove stages of capacity to match the decrease in building load. Automatic Lead/Lag Control (30HK,HL) This standard feature will automatically balance the wear factors (combination of compressor starts and run hours) of each compressor. Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 2 PC 903 Catalog No. 563-060 Printed in U.S.A. Form 30H-3W Pg 1 11-99 Replaces: New Tab 5c

Capacity-Control Steps Refer to the Capacity- Control Steps Tables 1 and 2 below for capacity control steps for standard units. NOTE: If the optional factory-installed hot gas bypass is used, there will be one more stage of unloading added and the units will be able to operate down to 10% of full load capacity. Table 1 Capacity-Control Steps 30HW UNIT 30HW CONTROL STEPS % CAPACITY OPERATING CYCLES 1 33 2 018 2 67 4 3 100 6 025 1 50 2 2 100 4 028 1 33 2 2 67 4 3 100 6 035 1 33 2 2 67 4 3 100 6 040 1 33 2 2 67 4 3 100 6 UNIT 30 HK040 HK,HL050 HK,HL060 LEGEND Disp. Displacement Table 2 Capacity-Control Steps 30HK,HL SEQUENCE A SEQUENCE B CONTROL Operating Cylinders Operating Cylinders STEPS % Disp. % Disp. Total Ckt 1 Ckt 2 Total Ckt 1 Ckt 2 1 25 2 2 25 2 2 2 50 4 2 2 50 4 2 2 3 75 6 4 2 75 6 2 4 4 100 8 4 4 100 8 4 4 1 40 4 4 20 2 2 2 60 6 4 2 60 6 4 2 3 80 8 6 2 80 8 4 4 4 100 10 6 4 100 10 6 4 1 33 4 4 33 4 4 2 66 8 4 4 66 8 4 4 3 88 10 6 4 88 10 4 6 4 100 12 6 6 100 12 6 6 NOTES: 1. All compressors are designated from left to right when viewed from front of unit. Circuits are also designated form left to right. 2. If accessory hot gas bypass is installed, the hot gas bypass valve will be opened (energized) only on control step no. 1. 2

NOTES: 1. Factory wiring is in accordance with the National Electrical Codes. Any field modifications or additions must be in compliance with all applicable codes. 2. Use 75 C min wire for field power supply. 3. All circuit breakers Must Trip Amps are equal to or less than 156% FLA. 4. Oil pressure safety switches are standard on 30HL units only. 5. All field interlock contacts must have a minimum rating of 2 amps at 24 vac sealed. See field interlock wiring. 6. Compressors thermally protected three phase motors protected against primary single phase conditions. 7. Terminals 9 and 10 of TB5 are for field connection of remote On-Off. The contacts must be rated for dry circuit application capable of handling a 5 vdc 1 ma to 20 ma load. LEGEND A Alarm C Contactor, Compressor CB Circuit Breaker CH Crankcase Heater CR Control Relay CWFS Chilled Water Flow Switch CWP Chilled Water Pump Interlock DLS Demand Limit Switch EMM Energy Management FU Control Transformer Fuse GCS Ground Current Sensing GND Ground HGS Hot Gas Solenoid HPS High-Pressure Switch LPS Low-Pressure Switch MBB Main Base Board OPS Oil Pressure Switch PL Plug POT Potentiometer R Relay (Condenser) SW Switch T Thermistor TB Terminal Block TRAN Transformer UL Unloader Terminal Block Factory Wiring Field Wiring Accessory or Option Wiring Fig. 1 Component Arrangement; 30HK,HL040-060 3

LEGEND FOR FIG. 2-4 A ALM C CB CFR CH CNP COMP CR CWFS CWP CWPI EMM FU GCS GND HPS LLSV LPS OAT OPS PL POT R SPT SW T TB TDR TRAN UL LEGEND Alarm Alarm Contactor, Compressor Circuit Breaker Condenser Fan Relay Crankcase Heater Condenser Pump Compressor Control Relay Chilled Water Flow Switch Chilled Water Pump Chilled Water Pump Interlock Energy Management Control Transformer Fuse Ground Current Sensing Ground High-Pressure Switch Liquid Line Solenoid Valve Low-Pressure Switch Outdoor-Air Temperature Oil Pressure Switch Plug Potentiometer Relay (Condenser) Space Temperature Switch Thermistor Terminal Block Time-Delay Relay Transformer Unloader Terminal Block Terminal (Unmarked) Terminal (Marked) Splice Factory Wiring Field Wiring Accessory or Option Wiring To indicate common potential only. Not to represent wiring. 4

NOTES: 1. Factory wiring is in accordance with the National Electrical Codes. Any field modifications or additions must be in compliance with all applicable codes. 2. Use 75 C min wire for field power supply. 3. All circuit breakers Must Trip Amps are equal to or less than 156% FLA. 4. Oil pressure safety switches are standard on 30HL units only. 5. All field interlock contacts must have a minimum rating of 2 amps at 24 vac sealed. See field interlock wiring. 6. Compressors thermally protected three phase motors protected against primary single phase conditions. 7. Terminals 9 and 10 of TB5 are for field connection of remote On-Off. The contacts must be rated for dry circuit application capable of handling a 5 vdc 1 ma to 20 ma load. Fig. 2 Low-Voltage Control Schematic; 30HK,HL040-060 5

Fig. 3 115-V Control Schematic; 30HK,HL040-060 6

7 Fig. 4 Power Schematic; 30HK,HL040-060

NOTES: 1. Factory wiring is in accordance with the National Electrical Code (NEC). Field modifications or additions must be in compliance with all applicable codes. 2. Wiring for main field power supply must be rated 75 C minimum. Use copper, copper clad aluminum or aluminum conductors for all units. 3. Control power is factory supplied. TRAN3 primary voltage is 230 v for 208/230-3-60 and 380/415-3-50 units. TRAN3 primary voltage is 460 v for 460-3-60 and 575 v for 575-3-60. TRAN3 secondary voltage is 115 v for all units. 4. Terminals 9 and 10 of TB5 are for field connection for remote on-off control. The contacts must be rated for dry circuit application capable of reliably switching a 5 vdc,.5ma load. 5. The maximum load allowed for the remote alarm relay circuit is 15 va sealed, 30 va inrush at 24 volt. 6. The maximum load allowed for the condenser fan, condenser pump or cooler pump relays is 15 va sealed, 30 va inrush each at 115 volt. 7. For GCS accessory, remove jumper wire from TB2, terminals 5/8 for compressor A1 and from terminals 6/10 for compressor B1. LEGEND A Alarm CFR Condenser Fan Relay CNFS Condenser Flow Switch CNP Condenser Pump CNPI Condenser Pump Interlock CWFS Chilled Water Flow Switch CWP Chilled Water Pump CWPI Chilled Water Pump Interlock GCS Ground Current Sensing HGBP Hot Gas Bypass LWT Leaving Water Temperature TB Terminal Block TRAN Transformer Field Power Wiring Field Control Wiring Factory-Installed Wiring Field-Installed Device Fig. 5 Field Wiring Diagram; 30HK,HL040-060 8

NOTES: 1. Factory wiring is in accordance with the National Electrical Codes. Any field modifications or additions must be in compliance with all applicable codes. 2. Use 75 C min wire for field power supply. 3. All circuit breakers Must Trip Amps are equal to or less than 156% FLA. 4. Oil pressure safety switches are standard on 30HWA units only. 5. All field interlock contacts must have a minimum rating of 2 amps at 24 vac sealed. See field interlock wiring. 6. Compressors thermally protected three phase motors protected against primary single phase conditions. 7. Terminals 9 and 10 of TB5 are for field connection of remote On-Off. The contacts must be rated for dry circuit application capable of handling a 5 vdc 1 ma to 20 ma load. LEGEND A Alarm C Contactor, Compressor CB Circuit Breaker CH Crankcase Heater CR Control Relay CWFS Chilled Water Flow Switch CWP Cooler Water Pump DLS Demand Limit Switch EMM Energy Management FU Fuse GCS Ground Current Sensing GND Ground HGBP Hot Gas Bypass HPS High-Pressure Switch LPS Low-Pressure Switch MBB Main Base Board OPS Oil Pressure Switch PL Plug POT Potentiometer SW Switch T Thermistor TB Terminal Block TDR Time Delay Relay TRAN Transformer UL Unloader Terminal Block Factory Wiring Field Wiring Accessory or Option Wiring Fig. 6 Component Arrangement; 30HWA/B,C/S018-040 9

A ALM C CB CFR CH CNP COMP COTP CR CWFS CWP CWPI EMM FIOP FU GCS GND HGBP HPS LPS MBB OAT OPS PL POT R SPT SW T TB TDR TOR TRAN UL LEGEND FOR FIG. 7-9 LEGEND Alarm Alarm Contactor, Compressor Circuit Breaker Condenser Fan Relay Crankcase Heater Condenser Pump Compressor Compressor Overtemperature Protection Control Relay Chilled Water Flow Switch Cooler Water Pump Chilled Water Pump Interlock Energy Management Factory-Installed Option Fuse Ground Current Sensing Ground Hot Gas Bypass High-Pressure Switch Low-Pressure Switch Main Base Board Outdoor-Air Temperature Oil Pressure Switch Plug Potentiometer Relay Space Temperature Switch Thermistor Terminal Block Time-Delay Relay Toroid Transformer Unloader Terminal Block Terminal (Unmarked) Terminal (Marked) Splice Factory Wiring Field Wiring Accessory or Option Wiring To indicate common potential only. Not to represent wiring. 10

NOTES: 1. Factory wiring is in accordance with the National Electrical Codes. Any field modifications or additions must be in compliance with all applicable codes. 2. Use 75 C min wire for field power supply. 3. All circuit breakers Must Trip Amps are equal to or less than 156% FLA. 4. Oil pressure safety switches are standard on 30HWA units only. 5. All field interlock contacts must have a minimum rating of 2 amps at 24 vac sealed. See field interlock wiring. 6. Compressors thermally protected three phase motors protected against primary single phasing conditions. 7. Terminals 9 and 10 of TB5 are for field connection of remote On-Off. The contact must be rated for dry circuit application capable of handling a 5 vdc 1 ma to 20 ma load. Fig. 7 Low-Voltage Control Schematic; 30HWA,B,C,S018-040 11

Fig. 8 Power Schematic; 30HWA,B,C,S018-040 12

Fig. 9 115-V Control Schematic; 30HWA,B,C,S018-040 13

NOTES: 1. Factory wiring is in accordance with the National Electrical Code (NEC). Field modifications or additions must be in compliance with all applicable codes. 2. Wiring for main field power supply must be rated 75 C minimum. Use copper, copper clad aluminum or aluminum conductors for all units. 3. Control power is factory supplied. TRAN3 primary voltage is 230 v for 208/230-3-60, 380-3-60 and 380/415-3-50 units. TRAN3 primary voltage is 460 v for 460-3-60 and 575 v for 575-3-60. TRAN3 secondary voltage is 115 v for all units. 4. Terminals 9 and 10 of TB5 are for field connection for remote On-Off control. The contacts must be rated for dry circuit application capable of reliably switching a 5 vdc,.5ma load. 5. The maximum load allowed for the remote alarm relay circuit is 15 va sealed, 30 va inrush at 24 volt. 6. The maximum load allowed for the condenser fan, condenser pump or cooler pump relays is 15 va sealed, 30 va inrush each at 115 volt. 7. For GCS accessory, remove jumper wire from TB2, terminals 5/8 for compressor A1. LEGEND A Alarm CFR Condenser Fan Relay CNFS Condenser Flow Switch CNP Condenser Pump CNPI Condenser Pump Interlock CWFS Chilled Water Flow Switch CWP Chilled Water Pump CWPI Chilled Water Pump Interlock GCS Ground Current Sensing HGBP Hot Gas Bypass LWT Leaving Water Temperature TB Terminal Block TRAN Transformer Field Power Wiring Field Control Wiring Factory-Installed Wiring Field-Installed Device Fig. 10 Field Wiring Diagram; 30HWA,B,C,S018-040 14

Copyright 1999 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 2 PC 903 Catalog No. 563-060 Printed in U.S.A. Form 30H-3W Pg 16 11-99 Replaces: New Tab 5c