Galaxy Installation 08/

Similar documents
Galaxy VM. Battery Breaker Box Installation 09/

Galaxy VM. Classic Battery Cabinet Installation GVMCBCWUE, GVMCBC2WUE, GVMCBC2WUF, GVMCBC3WUF 07/2017.

Galaxy VM. Modular Battery Cabinets Installation GVMMODBCW, GVMMODBCN 09/

Galaxy 300 Battery Breaker Kit G3HTBKIT1

Symmetra PX kw 208 V. Installation 01/

Galaxy Receiving and Unpacking 09/

Smart-UPS VT kva 208/220 V Single and Parallel Installation. With Batteries 11/2016.

Symmetra PX with Maintenance Bypass

Symmetra PX 20 kw. InfrastruXure 208 V. Installation 01/

Galaxy VX. 380 V, 400 V, 415, and 440 V UPS System Technical Specifications 12/

Symmetra PX. 48 kw 400 V, 96 kw 400 V, 100 kw 208 V, 160 kw 400 V. Receiving and Unpacking 01/2016.

Galaxy kva 3:3 and 3:1. Receiving and Unpacking. 380/400/415 and 208/220 V 04/2016.

Symmetra PX. 250/500 kw 400/480 V Single and Parallel Installation 07/

Easy UPS 3S with Internal Batteries

Galaxy VX. 480 V UPS System Technical Specifications 07/

Galaxy VX Battery Breaker Trip Board (GVXBBTB) and Battery Breaker Capacitor Board (GVXBBCB)

EPS Technical Specifications 06/2015.

Easy UPS 3M. Operation 01/

Galaxy : kva 380/400/415 V 3: kva 220/230/240 V. Technical Specifications 04/

Galaxy Technical Specifications 05/

Electrical Installation

Galaxy kva 380/400/415 V UPS Technical Specifications 08/2017.

Symmetra PX. Technical Specifications 07/

Symmetra PX 96 and 160 kw

Smart-UPS VT Rack Mounted

PowerLogic High Density Metering System 4-Meter Enclosure Installation Guide

Single and Parallel Installation

Safety and General Information

Symmetra PX. 20 kw 208 V. Technical Specifications 01/2016.

AIS and 40 kva 400 V. Site Preparation and Installation Manual

Electrical network protection VIP30, VIP35. User s manual 12/2008

Start UP Guide. Symmetra LX Tower Rack-Mount. UPS Models 200 V, 4-8 kva 208/240 V, 4-8 kva 220/230/240 V, 4-8 kva

M Series External Battery Frame. User Guide

RT Series Step Down Transformer for RT Series UPS 6-10kVA UL Input Vac Output Vac User Guide

Powerware Vdc Extended Battery Cabinet User s Guide.

Single and Parallel Installation. MGE Galaxy kva 208/220 V

ibusway for Data Center

SOS SERIES SOS1 SOS2. Spares On Site Battery Cabinet Installation Guide rEV3

Symmetra PX. 48, 96, and 160 kw 400 V 100 kw 208 V. Operation 09/

Symmetra PX. 48, 96, and 160 kw 400 V 100 kw 208 V Operation 07/2017.

Single and Parallel Installation

Galaxy 300. Technical Specifications 06/

EVlink Parking EVF1 - EVW1

Installation Guide Smart-UPS On-Line SRT1000/1500 UXI-NCLI, SRT1000/1500 UXI-LI, Tower/Rack-Mount

User Manual Easy UPS BV Series 500VA, 650VA, 800VA, 1000VA Safety and General Information

Galaxy 300 and Galaxy 300i

Easy UPS 3S. Operation 07/

Installation Guide Smart-UPS On-Line SRT1000/SRT1500 XLA Tower/Rack-Mount

AIS 5000 UPS kva 480 V. Installation Manual

Dual-Lite Trident TRF 40 Wide Battery Cabinet 20-40kVA Systems USER MANUAL

Altivar 61/71 Adjustable Speed Drives Plastic Kits and Power Terminal Kit

Extended Battery Cabinet for Nfinity

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

RT Series Battery Pack UL for RT 6 and 10 kva UPS UL. Extended Battery Pack. User Guide

1. INTRODUCTION SYSTEM DESCRIPTION Front Panel CONNECTION AND OPERATION TROUBLESHOOTING...8

Galaxy kva Installation manual FR/AA - Page 1

Freedom egen System End-of- Line Functional Checklist

Installation Power Management Unit Battery Cables and Battery Harness

SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL

Delta UPS - Ultron Family. HPH Series, Three Phase 20/30/40/60 kva 208V. User Manual. The power behind competitiveness

model ps600 Address all communications and shipments to: FEDERAL SIGNAL CORPORATION

Product Overview. Product Identification. Amps One CT Two CTs Three CTs

Quick Start Guide TS 910 & TS 920

SINAMICS G130. Motor reactors. Operating Instructions 05/2010 SINAMICS

XPC-EBP64 External Battery Pack User & Installation Manual Xtreme Power Conversion Corporation. All rights reserved.

SAVE THESE INSTRUCTIONS

This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.

MGE Galaxy kva. Installation manual. Single UPS. Integrated Parallel UPS. Parallel UPS with SSC. Frequency converters

Installation Instructions for Load Management Kit A051C329

GHA. Gas-Insulated Switchgear. Gas-Insulated Switchgear. Switchgear extension and replacement of a panel

Installing Power Components

Sheet No. Component /Detail

Solar module user manual Conergy PM 225P-250P

Operating Manual (Edition 04/2004) sinamics. Braking Module / Braking Resistor SINAMICS G130

Owner's/Installation Manual

ACC Series Power Conditioner OPERATION & INSTALLATION MANUAL

BRAVER UPS. (Uninterruptible Power System) User s Manual

www. ElectricalPartManuals. com TOSHIBA 1600EP SERIES MANUFACTURED IN THE U.S.A. OPERATION MANUAL BATTERY CABINET SYSTEM SINGLE PHASE- 8/10/14/18 kva

SM-1700 Secondary Shunt Trip Coil Assembly. Powered by Safety

Altivar Installation Manual. English 07/2013 ST /2013.

Installation. Symmetra MW II kw 480 V. UPS Summary Normal Normal

Enclosure for AMP1 Series Energy Meters with Swing Panel Kit

Safety Working with LV Drives

www. ElectricalPartManuals. com

Quick Start Guide TS 910

BR62 Battery Rack Installation, Operation, & Maintenance Manual

Installation manual. Modbus Interface DIII EKMBDXA7V1. Installation manual Modbus Interface DIII. English

PIX. Operation - Replacement of Fuses Replacement of Voltage Transformers Technical manual. Medium Voltage Distribution

2016 Photovoltaic Solar System Plan Review List

Conext Core XC Series Grid Tie Photovoltaic Inverter, 0G-XC-BB

Conext Core XC-NA Series Grid Tie Photovoltaic Inverter

USER MANUAL ONLINE UPS 6000L(XL)/10000L(XL) Uninterruptible Power Supply

Thank you for choosing EATON products. Safety information and operating instructions are included in this manual. Do not attempt to operate the UPS

TOD-BCU-PNUS2. Installation Manual. Connection Box for EIBS16GU2 or EIBS16GU2+ (Storage Battery System) For Installation Company Use

User Manual Back-UPS BC500-RS, BC650-RS 650 VA 230 V

Transformer Installation, Operation, and Maintenance Manual

Installation Instructions and User Manual For. 100 Watt Inverter Power System

Installation And Operation Instructions

USER MANUAL. Uninterruptible power supply MODEL: 53965,

SITE PLANNING DATA LIEBERT EXM 3-PHASE UPS: KVA/KW, 60HZ, VAC, SINGLE INPUT

Transcription:

Galaxy 5000 40 130 kva 480 V Installation 08/2017 www.schneider-electric.com

Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries SAS referred to in this guide are the sole property of Schneider Electric SA and its subsidiaries. They may not be used for any purpose without the owner's permission, given in writing. This guide and its content are protected, within the meaning of the French intellectual property code (Code de la propriété intellectuelle français, referred to hereafter as "the Code"), under the laws of copyright covering texts, drawings and models, as well as by trademark law. You agree not to reproduce, other than for your own personal, noncommercial use as defined in the Code, all or part of this guide on any medium whatsoever without Schneider Electric's permission, given in writing. You also agree not to establish any hypertext links to this guide or its content. Schneider Electric does not grant any right or license for the personal and noncommercial use of the guide or its content, except for a non-exclusive license to consult it on an "as is" basis, at your own risk. All other rights are reserved. Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. As standards, specifications, and designs change from time to time, please ask for confirmation of the information given in this publication.

40 130 kva 480 V Table of Contents Important Safety Instructions SAVE THESE INSTRUCTIONS...5 Safety Precautions...6 Electrical Safety...8 Battery Safety...9 Specifications... 11 Input... 11 Bypass... 11 Output... 11 Battery...12 Recommended Overcurrent Protection...12 Recommended Cable Sizes...13 Install Seismic Anchoring...14 Connect Power Cables in Single Systems...20 Connect the Power Cables in Single Utility/Mains Systems...20 Connect the Power Cables in Dual Utility/Mains Systems...20 Connect Power Cables in Parallel Systems...22 Connect the Power Cables in Single Utility/Mains Systems...22 Connect the Power Cables in Dual Utility/Mains Systems...22 Connect the Communication Cables...24 Overview of Communication Cables in Single Systems...24 Overview of Communication Cables in Parallel Systems...25 Connect the Relay Communication Card...26 Connect General Shutdown or Remote Emergency Power Off...28 Connect Parallel Communication Cables in Redundant Parallel Systems...28 Connect Parallel Communication Cables in Parallel Capacity Systems...29 Install an External Battery Cabinet...33 Install the ATIZ Board and the Ground Busbar...33 Install the Battery Circuit Breaker...34 Connect the Power and Control Cables...36 Install the Batteries...43 990 5217C-001 3

Important Safety Instructions SAVE THESE INSTRUCTIONS Important Safety Instructions SAVE THESE INSTRUCTIONS 40 130 kva 480 V Read these instructions carefully and look at the equipment to become familiar with it before trying to install, operate, service or maintain it. The following safety messages may appear throughout this manual or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure. The addition of this symbol to a Danger or Warning safety message indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed. This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages with this symbol to avoid possible injury or death. DANGER DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury. Failure to follow these instructions will result in death or serious injury. WARNING WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury. Failure to follow these instructions can result in death, serious injury, or equipment damage. CAUTION CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. Failure to follow these instructions can result in injury or equipment damage. NOTICE NOTICE is used to address practices not related to physical injury. The safety alert symbol shall not be used with this type of safety message. Failure to follow these instructions can result in equipment damage. 990 5217C-001 5

40 130 kva 480 V Please Note Important Safety Instructions SAVE THESE INSTRUCTIONS Electrical equipment should only be installed, operated, serviced, and maintained by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. A qualified person is one who has skills and knowledge related to the construction, installation, and operation of electrical equipment and has received safety training to recognize and avoid the hazards involved. Safety Precautions DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH All safety instructions in this document must be read, understood and followed. Failure to follow these instructions will result in death or serious injury. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Read all instructions in the Installation Manual before installing or working on this UPS system. Failure to follow these instructions will result in death or serious injury. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Do not install the UPS system until all construction work has been completed and the installation room has been cleaned. Failure to follow these instructions will result in death or serious injury. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH The product must be installed according to the specifications and requirements as defined by Schneider Electric. It concerns in particular the external and internal protections (upstream breakers, battery breakers, cabling, etc.) and environmental requirements. No responsibility is assumed by Schneider Electric if these requirements are not respected. After the UPS system has been electrically wired, do not start up the system. Start-up must only be performed by Schneider Electric. Failure to follow these instructions will result in death or serious injury. 6 990 5217C-001

Important Safety Instructions SAVE THESE INSTRUCTIONS 40 130 kva 480 V DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH The UPS system must be installed according to local and national regulations. Install the UPS according to: IEC 60364 (including 60364 4 41- protection against electric shock, 60364 4 42 - protection against thermal effect, and 60364 4 43 - protection against overcurrent), or NEC NFPA 70, or Canadian Electrical Code (C22.1, Part 1) depending on which one of the standards apply in your local area. Failure to follow these instructions will result in death or serious injury. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Install the UPS system in a temperature controlled indoor environment free of conductive contaminants and humidity. Install the UPS system on a non-flammable, level and solid surface (e.g. concrete) that can support the weight of the system. Failure to follow these instructions will result in death or serious injury. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH The UPS is not designed for and must therefore not be installed in the following unusual operating environments: Damaging fumes Explosive mixtures of dust or gases, corrosive gases, or conductive or radiant heat from other sources Moisture, abrasive dust, steam or in an excessively damp environment Fungus, insects, vermin Salt-laden air or contaminated cooling refrigerant Pollution degree higher than 2 according to IEC 60664-1 Exposure to abnormal vibrations, shocks, and tilting Exposure to direct sunlight, heat sources, or strong electromagnetic fields Failure to follow these instructions will result in death or serious injury. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Do not drill or cut holes for cables or conduits with the gland plates installed and do not drill or cut holes in close proximity to the UPS. Failure to follow these instructions will result in death or serious injury. HAZARD OF ARC FLASH WARNING Do not make mechanical changes to the product (including removal of cabinet parts or drilling/cutting of holes) that are not described in the Installation Manual. Failure to follow these instructions can result in death, serious injury, or equipment damage. 990 5217C-001 7

40 130 kva 480 V Important Safety Instructions SAVE THESE INSTRUCTIONS RISK OF OVERHEATING NOTICE Respect the space requirements around the UPS system and do not cover the product s ventilation openings when the UPS system is in operation. Failure to follow these instructions can result in equipment damage. RISK OF EQUIPMENT DAMAGE NOTICE Do not connect the UPS output to regenerative load systems including photovoltaic systems and speed drives. Failure to follow these instructions can result in equipment damage. Electrical Safety DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH Electrical equipment must be installed, operated, serviced, and maintained only by qualified personnel. The UPS system must be installed in a room with restricted access (qualified personnel only). Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. Turn off all power supplying the UPS system before working on or inside the equipment. Before working on the UPS system, check for hazardous voltage between all terminals including the protective earth. The UPS contains an internal energy source. Hazardous voltage can be present even when disconnected from the utility/mains supply. Before installing or servicing the UPS system, ensure that the units are OFF and that utility/mains and batteries are disconnected. Wait five minutes before opening the UPS to allow the capacitors to discharge. A disconnection device (e.g. disconnection circuit breaker or switch) must be installed to enable isolation of the system from upstream power sources in accordance with local regulations. This disconnection device must be easily accessible and visible. The UPS must be properly earthed/grounded and due to a high leakage current, the earthing/grounding conductor must be connected first. Failure to follow these instructions will result in death or serious injury. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH In systems where backfeed protection is not part of the standard design, an automatic isolation device (backfeed protection option or other device meeting the requirements of IEC/EN 62040 1 or UL1778 5th Edition depending on which of the two standards apply to your local area) must be installed to prevent hazardous voltage or energy at the input terminals of the isolation device. The device must open within 15 seconds after the upstream power supply fails and must be rated according to the specifications. Failure to follow these instructions will result in death or serious injury. When the UPS input is connected through external isolators that, when opened, isolate the neutral or when the automatic backfeed isolation is provided external to 8 990 5217C-001

Important Safety Instructions SAVE THESE INSTRUCTIONS 40 130 kva 480 V the equipment or is connected to an IT power distribution system, a label must be fitted at the UPS input terminals, and on all primary power isolators installed remote from the UPS area and on external access points between such isolators and the UPS, by the user, displaying the following text (or equivalent in a language which is acceptable in the country in which the UPS system is installed): DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Risk of Voltage Backfeed. Before working on this circuit: Isolate the UPS and check for hazardous voltage between all terminals including the protective earth. Failure to follow these instructions will result in death or serious injury. Battery Safety DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Battery circuit breakers must be installed according to the specifications and requirements as defined by Schneider Electric. Servicing of batteries must only be performed or supervised by qualified personnel knowledgeable of batteries and the required precautions. Keep unqualified personnel away from batteries. Disconnect charging source prior to connecting or disconnecting battery terminals. Do not dispose of batteries in a fire as they can explode. Do not open, alter, or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic. Failure to follow these instructions will result in death or serious injury. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Batteries can present a risk of electric shock and high short-circuit current. The following precautions must be observed when working on batteries Remove watches, rings, or other metal objects. Use tools with insulated handles. Wear protective glasses, gloves and boots. Do not lay tools or metal parts on top of batteries. Disconnect the charging source prior to connecting or disconnecting battery terminals. Determine if the battery is inadvertently grounded. If inadvertently grounded, remove source from ground. Contact with any part of a grounded battery can result in electric shock. The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance (applicable to equipment and remote battery supplies not having a grounded supply circuit). Failure to follow these instructions will result in death or serious injury. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH When replacing batteries, always replace with the same type and number of batteries or battery packs. Failure to follow these instructions will result in death or serious injury. 990 5217C-001 9

40 130 kva 480 V Important Safety Instructions SAVE THESE INSTRUCTIONS NOTICE RISK OF EQUIPMENT DAMAGE Wait until the system is ready to be powered up before installing batteries in the system. The time duration from battery installation until the UPS system is powered up must not exceed 72 hours or 3 days. Batteries must not be stored more than six months due to the requirement of recharging. If the UPS system remains de-energized for a long period, Schneider Electric recommends that you energize the UPS system for a period of 24 hours at least once every month. This charges the batteries, thus avoiding irreversible damage. Failure to follow these instructions can result in equipment damage. 10 990 5217C-001

Specifications Specifications 40 130 kva 480 V Input 40 kva 50 kva 60 kva 80 kva 100 kva 130 kva Nominal input voltage (V) 480 Frequency (Hz) 60 Nominal input 48 59 71 94 117 151 current (A) 1 Maximum input 59 70 88 111 150 182 current (A) 2 Input current 71 84 97 111 164 182 limitation (A) 3 Input phase rotation Input power factor A, B, C clockwise > 0.98 THDI 5% 3% Maximum short circuit withstand (ka) 20 30 Bypass Frequency (Hz) 60 40 kva 50 kva 60 kva 80 kva 100 kva 130 kva Nominal bypass current (A) 48 59 71 94 117 151 Output 40 kva 50 kva 60 kva 80 kva 100 kva 130 kva Overload capacity Nominal output current (A) 125% for 10 minutes 150% for 1 minute 220% for 1 second 48 59 71 94 117 151 Frequency (Hz) 60 THDU 0.5% phase to phase for linear loads 2 % phase to phase for non-linear loads 1. Input current based on rated load and batteries fully charged. 2. Input current based on full battery recharge, nominal voltage, and rated load. 3. Nominal voltage -10% voltage with partial recharge. 990 5217C-001 11

40 130 kva 480 V Specifications Battery 40 kva 50 kva 60 kva 80 kva 100 kva 130 kva Nominal voltage (VDC) End voltage (VDC) Maximum floating voltage (VDC) I Nom discharge 4 (A) I Max discharge 5 (A) 432 356 490 90 113 135 180 225 293 109 137 164 219 273 355 Recommended Overcurrent Protection NOTE: Main circuit breaker rating to the system should be calculated according to the site configuration and recommended value is at least 150% of the rated current of the type of transformer used in the system with maximum trip setting. The recommended circuit breakers in the table are based on UPS power rating. Transformer rating is not considered. Ratings of cables and overcurrent devices supplied for information only. Consult Schneider Electric before adopting. 40 kva 50 kva 208 V: 208 V 480 V: 208 V 480 V: 480 V 600 V: 208 V 600 V: 600 V 208 V: 208 V 480 V: 208 V 480 V: 480 V 600 V: 208 V 600 V: 600 V Input (A) 175 80 80 60 60 225 90 90 70 70 Output (A) 150 150 60 150 50 175 175 80 175 60 60 kva 80 kva 208 V: 208 V 480 V: 208 V 480 V: 480 V 600 V: 208 V 600 V: 600 V 208 V: 208 V 480 V: 208 V 480 V: 480 V 600 V: 208 V 600 V: 600 V Input (A) 300 110 110 90 90 350 150 150 125 125 Output (A) 225 225 90 225 80 300 300 125 300 100 100 kva 130 kva 208 V: 208 V 480 V: 208 V 480 V: 480 V 600 V: 208 V 600 V: 600 V 208 V: 208 V 480 V: 208 V 480 V: 480 V 600 V: 208 V 600 V: 600 V Input (A) 450 200 200 150 150 600 250 250 200 200 Output (A) 350 350 150 350 125 450 450 200 200 175 4. Nominal battery discharge current based on rated load and nominal battery voltage. 5. Maximum battery discharge current based on rated load at the end of the discharge. 12 990 5217C-001

Specifications 40 130 kva 480 V Recommended Cable Sizes NOTE: Upstream protective devices and downstream distribution circuits and protective devices as appropriate to the installation and distribution requirements must be installed. NOTE: All wiring must comply with all applicable national and/or electrical codes. Cable sizes in this manual are based on table 310-16 of the National Electrical Code (NEC) with the following assertions: 90 C conductors (THHN) for 75 C termination Use of copper conductors Recommended 75 C cables sizes below are for 480 V input/output UPS, depending upon recommended overcurrent protection stated in this manual. Ground cables are sized in accordance with NEC Article 250-122 and Table 250-122. Power and control/communication cables must be routed in separate conduits. Upstream and downstream bypass cables must have the same type and lengths for all UPSs installed in each integrated parallel system. Any deviation will create an unequal sharing of the load currents in bypass mode. 40 kva 50 kva 60 kva 80 kva 100 kva 130 kva Input Bypass Output 80% rated breakers 100% rated breakers 80% rated breakers 100% rated breakers 80% rated breakers 100% rated breakers 1/0 AWG 2/0 AWG 3/0 AWG 2 x 1 AWG 2 x 2/0 AWG 2 x 4/0 AWG 4 AWG 3 AWG 2 AWG 1/0 AWG 3/0 AWG 250 kcmil 1/0 AWG 2/0 AWG 3/0 AWG 2 x 1 AWG 2 x 2/0 AWG 2 x 4/0 AWG 4 AWG 3 AWG 2 AWG 1/0 AWG 3/0 AWG 250 kcmil 1/0 AWG 2/0 AWG 3/0 AWG 2 x 1 AWG 2 x 2/0 AWG 2 x 4/0 AWG 4 AWG 3 AWG 2 AWG 1/0 AWG 3/0 AWG 250 kcmil NOTE: For 80% rated breakers, cable sizes are based on combined 125% continuous load and 100% non-continuous load scenario. Recommended Battery Cable Sizes Battery circuit breaker rating (A) Cable size 175 2/0 AWG 250 250 kcmil 400 600 kcmil 990 5217C-001 13

40 130 kva 480 V Install Seismic Anchoring Install Seismic Anchoring NOTE: The structural engineer or design engineer of record is responsible for detailing the equipment anchorage requirements for the given installation. The installer and manufacturer of the anchorage system are responsible for assuring that the mounting requirements are met. Schneider Electric is not responsible for the specification and performance of anchorage systems. NOTE: Schneider Electric does not provide any seismic kit for the battery cabinet. Contact the battery cabinet vendor for seismic installation for the battery cabinet. NOTE: The anchor bolts are not provided. Use anchor bolts that suit the floor material. The minimum requirement is 1/2 inch grade 5 hardware. Hole Positions for UPS Cabinet Top View 14 990 5217C-001

Install Seismic Anchoring 40 130 kva 480 V Hole Positions for Top Entry Cabinet Hole Positions for PDU Cabinet 990 5217C-001 15

40 130 kva 480 V Install Seismic Anchoring Hole Positions for Maintenance Bypass Cabinet/Transformer Cabinet NOTE: Example shown is UPS and top entry cabinets, but installation procedure is similar for the other cabinet types. 1. Drill anchoring holes in the floor according to the hole positions given for each cabinet to be seismically anchored (anchoring bolts not provided). 2. Install the anchor bolts in the right and left side of the UPS cabinet. 3. Install the anchor bolts in the rear and front of the UPS cabinet. 16 990 5217C-001

Install Seismic Anchoring 40 130 kva 480 V 4. Install the kickplates on front, right and rear sides of the UPS cabinet. 5. Install the seismic straps on the floor to the left of the UPS cabinet. 990 5217C-001 17

40 130 kva 480 V Install Seismic Anchoring 6. Slide the top entry cabinet brackets under the seismic straps. 7. Install the anchor bolts in the left bracket of the top entry cabinet. 8. Install the front kickplate on the top entry cabinet. 18 990 5217C-001

Install Seismic Anchoring 40 130 kva 480 V 9. If OSHPD review is required: Position all OSHPD certification labels on the UPS cabinet. NOTE: For Galaxy 5000 range, OSHPD Application # : OSP-0261-10, Special Seismic certification valid up to 1.41 g. 990 5217C-001 19

40 130 kva 480 V Connect Power Cables in Single Systems Connect Power Cables in Single Systems Connect the Power Cables in Single Utility/Mains Systems 1. Remove the protection cover in the bottom of the UPS cabinet. 2. Connect the input cables to the input terminals and to the UPS grounding plate. 3. Connect the output cables to the output terminals and to the UPS grounding plate. 4. Connect the battery cables to the battery terminals. 5. Fasten the cables to the UPS cabinet. 6. Reinstall the protection cover. Connect the Power Cables in Dual Utility/Mains Systems 1. Remove the protection cover in the bottom of the UPS cabinet. 2. Connect the input cables to the input terminals and to the UPS grounding plate. 3. Connect the bypass cables to the bypass terminals and to the UPS grounding plate. 4. Connect the output cables to the output terminals and to the UPS grounding plate. 5. Connect the battery cables to the battery terminals. 6. Fasten the cables to the UPS cabinet. 20 990 5217C-001

Connect Power Cables in Single Systems 40 130 kva 480 V 7. Reinstall the protection cover. 990 5217C-001 21

40 130 kva 480 V Connect Power Cables in Parallel Systems Connect Power Cables in Parallel Systems Connect the Power Cables in Single Utility/Mains Systems NOTE: A maximum of two UPS units can be installed in parallel for rated power. 1. Remove the protection covers in the bottom of the UPS cabinets. 2. Connect the input cables to the input terminals and to the UPS grounding plate in UPS 1. Repeat in UPS 2. 3. Connect the output cables to the output terminals and to the UPS grounding plate in UPS 1. 4. Connect the parallel cables from the output terminals in UPS 1 to the output terminals in UPS 2. 5. Connect the battery cables to the battery terminals in UPS 1 and UPS 2. 6. Fasten the cables to the UPS cabinets. 7. Reinstall the protection covers. Connect the Power Cables in Dual Utility/Mains Systems NOTE: If the two UPS units are placed side by side, connect cables as indicated below. In other configurations, always make sure that the cables between the UPS units and the bypass source are the same type and the same length. The cables between the UPS units and the load must also be the same type and length. NOTE: The drawings below show configurations without an external system bypass cabinet. 22 990 5217C-001

Connect Power Cables in Parallel Systems 40 130 kva 480 V 1. Remove the protection covers in the bottom of the UPS cabinets. 2. Connect the input cables to the input terminals and to the UPS grounding plate in UPS 1. Repeat in UPS 2. 3. Connect the bypass cables to the bypass terminals and to the UPS grounding plate in UPS 1. Repeat in UPS 2. 4. Connect the output cables to the output terminals and to the UPS grounding plate in UPS 1. 5. Connect the parallel cables from the output terminals in UPS 1 to the output terminals in UPS 2. 6. Connect the battery cables to the battery terminals in UPS 1 and UPS 2. 7. Fasten the cables to the UPS cabinets. 8. Reinstall the protection covers. 990 5217C-001 23

40 130 kva 480 V Connect the Communication Cables Connect the Communication Cables Overview of Communication Cables in Single Systems NOTE: Run control and communication cables separately from the power cables to ensure sufficient isolation. Reinforce the insulation of the control and communication cables if any risk of contact with the power cables exists. A. Network management card (SELV) B. Optional communication cards (SELV or LV) C. Relay communication card (SELV) D. External battery circuit breaker cables (SELV) E. General shutdown cable (SELV) 24 990 5217C-001

Connect the Communication Cables 40 130 kva 480 V Overview of Communication Cables in Parallel Systems NOTE: Run control and communication cables separately from the power cables to ensure sufficient isolation. Reinforce the insulation of the control and communication cables if any risk of contact with the power cables exists. A. Network management card (SELV) B. Optional communication cards (SELV or LV) C. Relay communication card (SELV) D. External battery circuit breaker cables (SELV) E. General shutdown cable (SELV) F. INTN board for connection of external bypass cabinet cable (ELV), CAN cables (SELV), and exchange-current cables (SELV). 990 5217C-001 25

40 130 kva 480 V Connect the Communication Cables Connect the Relay Communication Card DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Isolate and lockout/tagout all power sources for this card (also known as SECI) before making connections. Never connect SELV (safety extra low voltage) and non-selv circuits to the different outputs of the same card. Failure to follow these instructions will result in death or serious injury. NOTE: Only one relay communication card can be installed in a UPS. Output contacts: Permissible voltage: 250 V, 30 VDC Permissible current: 2 A Cable: 4 x 0.93 mm², Ø 6.6 mm +/- 0.3 mm Pin Description 6 Low battery warning 5 Load on battery power 4 Load on automatic bypass 3 Load on UPS 2 Battery inoperable 1 General alarm Input contacts: Switched voltage: 5 VDC Consumption: 10 ma Cable: 4 x 0.34 mm², Ø 5 mm +/- 0.5 mm Pin A B Description UPS OFF UPS ON 1. Remove the screws and remove the cover from the relay communication card. 2. Run the communication cables through the cable entry holes. 3. Connect the conductors to the input terminals on the relay communication card. 26 990 5217C-001

Connect the Communication Cables 40 130 kva 480 V 4. Connect the conductors to the output terminals on the relay communication card. 5. Reinstall the cover and secure it with the screws. 6. Tighten the screws to lock the cables. 7. Indicate the location of the power sources on the labels. 8. Insert the card in the slot in the UPS cabinet. 9. Secure the card with two screws. 990 5217C-001 27

40 130 kva 480 V Connect the Communication Cables Connect General Shutdown or Remote Emergency Power Off The general shutdown button causes UPS shutdown and opening of the battery circuit breaker (opening of the bypass static switch depends on customisation settings). The REPO (remote emergency power off ) option is applicable to installations where pressing the button also causes the upstream utility/mains source and bypass source circuit breakers to open. In parallel systems, there must be a single general shutdown button with a separate contact for each UPS unit. 1. Remove the wire jumper from the terminal block. 2. Connect the general shutdown normally closed contact to terminals 1 and 2 (SELV). 3. Secure the cable. Connect Parallel Communication Cables in Redundant Parallel Systems NOTE: The 10 m (33 ft) supplied cables limit the distance between two UPS units to approximately 6 m (20 ft). 1. Connect a communication cable from XMS02 in UPS 1 to XMS02 in UPS 2. 2. Connect a communication cable from XMS03 in UPS 1 to XMS03 in UPS 2. 3. Install a blue plug in connector XMS06 in UPS 1. 4. Connect a communication cable from XMS07 in UPS 1 to XMS06 in UPS 2. 5. Install a red plug in connector XMS07 in UPS 2. 28 990 5217C-001

Connect the Communication Cables 40 130 kva 480 V 6. Install the protection cover supplied with the parallel system over the communication cables. Connect Parallel Communication Cables in Parallel Capacity Systems NOTE: The 10 m (33 ft) supplied cables limit the distance between two UPS units to approximately 6 m (20 ft). 990 5217C-001 29

40 130 kva 480 V Connect the Communication Cables 1. Use the XMS02 and XMS03 terminals to create a loop between all UPS units as shown on the illustration (all the XMS02 and XMS03 terminals must be used). 30 990 5217C-001

Connect the Communication Cables 40 130 kva 480 V 2. Daisy-chain the UPS units using the XMS06 and XMS07 terminals. Fit a blue plug in the connector on the first UPS units and a red plug in the connector on the last UPS unit (all the XMS06 and XMS07 connectors must be used). 3. Connect terminals 7, 8, 9, and 10 on the auxiliary terminal block TB2 in the system bypass cabinet to UPS terminal blocks XMS04/XMS05 pins 1, 2, 3, and 4 and create a loop connection between the system bypass cabinet and the UPS units as shown. 990 5217C-001 31

40 130 kva 480 V Connect the Communication Cables 4. Install the protection cover supplied with the parallel system over the communication cables. 32 990 5217C-001

Install an External Battery Cabinet Install an External Battery Cabinet 40 130 kva 480 V Install the ATIZ Board and the Ground Busbar 26 Inch and 32 Inch Battery Cabinet 990 5217C-001 33

40 130 kva 480 V Install an External Battery Cabinet 48 Inch Battery Cabinet 1. If the ATIZ board option has been purchased, install the ATIZ board in the first battery cabinet. 2. Install the ground busbar. Install the Battery Circuit Breaker DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Protect the battery circuit with a DC battery circuit breaker equipped with an undervoltage coil (MN 24 VDC).The battery circuit breaker must be rated. The undervoltage coil must be wired to the UPS as shown in the Connection Diagrams below. Failure to follow these instructions will result in death or serious injury. NOTE: In systems with several battery cabinets, only one battery circuit breaker is necessary. 34 990 5217C-001

Install an External Battery Cabinet 40 130 kva 480 V NOTE: The battery circuit breaker is preinstalled in the battery cabinet. 1. Secure the XR1 connector box to the battery cabinet frame. 2. Secure the temperature sensor to the battery cabinet frame. 3. When the batteries have been connected to the circuit breaker, install the front cover in front of the circuit breaker. Battery Circuit Breaker Control Wiring TB5 QF1 wire color 1 Brown 2 Brown 3 Yellow 4 Blue / yellow 5 Jumper 2 to 4 990 5217C-001 35

40 130 kva 480 V Install an External Battery Cabinet Connect the Power and Control Cables 1. Route the power and ATIZ cables between the UPS and battery cabinets as shown below. For multiple adjacent cabinets, cables interconnect through openings in the middle cabinet(s). Power Cable and ATIZ Connections for 26 Inch, 32 Inch, and 48 Inch Battery Cabinets 2. Route the control cables between the UPS and the battery cabinets as shown in the illustration relevant to your configuration. For multiple adjacent cabinets, cables interconnect through openings in the middle cabinet(s). a. For installation of three or four battery cabinets: Move jumper to pins 5 and 6 in battery cabinet 1 and move jumper to pins 2 and 3 in battery cabinet 3. b. For installation of four battery cabinets: Move jumper to pins 5 and 6 in battery cabinet 2 and move jumper to pins 2 and 3 in battery cabinet 4. Control Cable Connections for One 26 Inch and 32 Inch Battery Cabinet 36 990 5217C-001

Install an External Battery Cabinet 40 130 kva 480 V Control Cable Connections for Two 26 Inch and 32 Inch Battery Cabinets 990 5217C-001 37

40 130 kva 480 V Install an External Battery Cabinet Control Cable Connections for Three 26 Inch and 32 Inch Battery Cabinets 38 990 5217C-001

Install an External Battery Cabinet 40 130 kva 480 V Control Cable Connections for Four 26 Inch and 32 Inch Battery Cabinets 990 5217C-001 39

40 130 kva 480 V Install an External Battery Cabinet Control Cable Connections for One 48 Inch Battery Cabinet Control Cable Connections for Two 48 Inch Battery Cabinets 40 990 5217C-001

Install an External Battery Cabinet 40 130 kva 480 V Control Cable Connections for Three 48 Inch Battery Cabinets 990 5217C-001 41

40 130 kva 480 V Install an External Battery Cabinet Control Cable Connections for Four 48 Inch Battery Cabinets 42 990 5217C-001

Install an External Battery Cabinet 40 130 kva 480 V Install the Batteries DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Batteries must only be installed or supervised by qualified personnel knowledgeable of batteries and the required precautions. Keep unqualified personnel away from batteries. Failure to follow these instructions will result in death or serious injury. NOTE: A minimum clearance of 150 mm (5.90 in) is required between the top of the battery cells and the next shelf. 26 Inch Battery Cabinet 990 5217C-001 43

40 130 kva 480 V Install an External Battery Cabinet 48 Inch Battery Cabinet 1. Place the battery cells on each shelf and interconnect the batteries. 2. Interconnect all the battery assemblies from each shelf and connect the complete battery assembly to the battery circuit breaker. 44 990 5217C-001

Printed in. Schneider Electric Schneider Electric 35 rue Joseph Monier 92500 Rueil Malmaison France + 33 (0) 1 41 29 70 00 www.schneider-electric.com As standards, specifications, and design change from time to time, please ask for confirmation of the information given in this publication. 2015 2017 Schneider Electric. All rights reserved. 990 5217C-001