Vacuum Circuit Breakers (Vehicle)

Similar documents
Vacuum Circuit Breakers (Vehicle)

Vacuum Circuit Breaker (Vehicle)

Vacuum Circuit Breakers (Vehicle) Type HKR 7.5kV to 15kV. Instructions Installation Operation Maintenance SGIM-9928C

Vacuum Circuit Breakers (Vehicle)

Vacuum Circuit Breakers (Vehicle)

Vacuum Circuit Breakers (Vehicle) Type MSV 5kV. Instructions Installation Operation Maintenance SGIM-9988

Vacuum Circuit Breakers (Vehicle)

Vacuum Circuit Breakers (Vehicle)

Vacuum Circuit Breakers (Vehicle) Type FSV 5kV to 15kV. Instructions Installation Operation Maintenance SGIM-9968

Type 2 Arc Resistant WL Low Voltage Metal-Enclosed Switchgear

Installation Instructions For Motor Control Center (MCC) Units

Type 38-3AH3 38 kv vacuum circuit breaker instruction manual. Installation operation maintenance E50001-F710-A238-V1-4A00. Answers for energy.

Instruction manual. Types GMSG and GMSG-GCB 5 kv to 15 kv vacuum circuit breakers.

SecoVac * Ground & Test Device

SIEMENS. XJ-L Busway Systems. Storage, Installation and Maintenance Instructions for... Piece No. 32-J Rev 3

Instruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module.

Instruction and Installation Guide

IB PowlVac ITE-HK Remote Racking Device

Instruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module.

GE CONSUMER & INDUSTRIAL

RGZESDI Inverter Duty AC Induction Motors

SM-1700 Secondary Shunt Trip Coil Assembly. Powered by Safety

SIGNAL WORDS QUALIFIED PERSON

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod

Hubbell has a policy of continuous product improvement. Please visit hubbellpowersystems.com to confirm current design specifications.

Test Cabinet (Inspection Box) Instructions. for Testing Accessories on Manually and Electrically Operated EntelliGuard G Low Voltage Circuit Breakers

Type 3AH kv to 38 kv vacuum circuit breaker operator module instruction manual

COOPER POWER SERIES. 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions. Loadbreak/Deadbreak Connectors MN650016EN

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing

COOPER POWER. SERIES CMU Medium voltage power fuse installation instructions. Fusing Equipment MN132032EN

GE Industrial Solutions. User/Installation Manual for 4.76kV -15kV SecoBloc

5/15/27 kv, 25/31.5/50/63 ka Manual Ground & Test Devices Installation, Operations and Maintenance Manual

COOPER POWER SERIES. Types 4H single-phase and 6H three-phase vacuum interrupter conversion kits. Reclosers MN280014EN

Power Break Circuit Breakers

Cradle Mounted Key Interlock Guide Frame Accessory

CR193 Vacuum Limitamp* Contactors

COOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN

COOPER POWER SERIES. Dielectric grease application to recloser cable instructions. Reclosers MN280070EN

February 28 th, 2018 UPDATE: Important Product Safety Bulletin Immediate Action Required INSTRUCTIONS FOR FIELD RISK MITIGATION

COOPER POWER SERIES. 200 A Fused Loadbreak Elbow Connector Replacement Fuse Installation Instructions. Fusing Equipment MN132021EN

GE Industrial Solutions. DEH Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System

COOPER POWER SERIES. 200 A loadbreak junction 15 and 25 kv class installation instructions. Loadbreak Connectors MN650015EN

COOPER POWER SERIES. Pad-mounted Switchgear MN285019EN. Effective March 2017 Supersedes February 2007 (S )

COOPER POWER SERIES. QD5 Quik-Drive tap-changer reversing neutral stationary contact asssembly kit A26 installation instructions

Instructions for VCP-W Simple Electrical Ground & Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version

COOPER POWER SERIES. Expulsion fuse installation instructions. Capacitors MN230005EN. Effective November 2016 Supersedes November 2001 (S )

COOPER POWER SERIES. Edison Modular Fuse (EMF) Installation Instructions. Fusing Equipment MN132031EN

COOPER POWER SERIES. KA716L7001 adjustable control valve kit for Types L, E, 4E, V4E, and V4L reclosers installation and adjustment instructions

TYPE AST. Grounding Switch. ALL Ratings INSTALLATION & INSTRUCTION MANUAL

TIASTAR Motor Control Center Installation And Maintenance Instructions For Units Only

Effective November 2016 Supersedes February 2012 (S )

Effective June 2016 New Issue

COOPER POWER SERIES. HX-CB loadbreak fuse cutout installation instructions. Fusing Equipment MN132011EN

Factory Authorized Mechanism Enhancement (FAME)

COOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN

Instruction Manual 15kV KVAN-1125M 1200/2000A Maxi-Vac Medium-Voltage Vacuum Circuit Breaker

ibusway for Data Center

GWI Rev. 1 October 2007 Supersedes Rev. 0 Dated February 2004

ProTrip Conversion Kits. For GE Types AK-15, AK-25, and AKU- 25 Low-Voltage Power Circuit Breakers INTRODUCTION. DEH Installation Instructions

COOPER POWER SERIES. High-voltage primary bushings installation instructions. OEM Equipment MN800008EN

NorthStar. brand. Instruction Manual. SLIM Tach SL Thru-Shaft Diameter. Magnetoresistive Encoder Designed for GE Wind Energy

Vacuum Circuit Breaker Type VAD-3

O & M Manual for the EATON Generator Ready Loadcenter

ADVAC Medium Voltage Vacuum Circuit Breaker Installation and Operation Manual

High-voltage primary bushings installation instructions

User manual W-VACi. W-VACi 12 / 17.5 / 24 kv IEC Vacuum Circuit Breakers

Effective March 2015 Supersedes S August 2012

S Voltage Regulators PRODUCT INFORMATION GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage.

SIEMENS. Combination Starter Enclosure Kit Classes 49EC17 & 49EC18 Instruction Guide E87010-A0151-T003-A1-49EC. August, 2012

Vacuum Circuit-Breakers, Type HVX kv, of cassette design, cassette with motor drive

Simple Electrically Operated Ground & Test Device For use in Type VCP-W Switchgear rated up to 15kV, 25 and 40kA UPPER TERMINAL SET VERSION

Magnum breaker remote racking device (MRR1000)

S Fault Indicators. S.T.A.R. Type TPR Faulted Circuit Indicator Installation Instructions. Contents INSTALLATION PROCEDURES

S Voltage Regulators GENERAL. PRODUCT INFORMATION Introduction. Contents. Acceptance and Initial Inspection. Handling and Storage.

INSTRUCTION MANUAL. HCV-5HA 7.2kV, 400A-7.0kA HCV-5HAL 7.2kV, 400A-7.0kA INSTALLATION - OPERATION - MAINTENANCE

COOPER POWER SERIES. S.T.A.R. type LVR faulted circuit indicator installation instructions. Fault Indicators MN320005EN

Effective May 2017 Supersedes December 2004 (S )

1. Safety practices General Introduction Standards...3

ABB ADVAC TM. INSTALLATION/MAINTENANCE INSTRUCTIONS Medium Voltage Vacuum Power Circuit Breakers and Auxiliary Devices

Introduction CAUTION. S&C Power Operated Metal-Enclosed Switchgear Outdoor Distribution (4.16 kv, through 34.5 kv)

Specification Guide. for RMVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

Quik-Spec Coordination Panelboard

COOPER POWER SERIES. RTE EL-BAY-O-NET FUSE Re-Fusing Instructions. Fusing Equipment MN132024EN

50 / 75 / 150 DHP [Cable or Hard Bus Application] Ground and Test Device

Type GM38 38 kv metal-clad switchgear instruction manual. Installation operation maintenance E50001-F710-A236-V1-4A00. Answers for energy.

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

COOPER POWER SERIES. KA1169R Closing Coil Transfer-Switch Accessory Operation. Reclosers MN280069EN

S Voltage Regulators PRODUCT INFORMATION GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage

PAD-MOUNTED SWITCHGEAR INSPECTION & MAINTENANCE RECOMMENDATIONS TYPE PSI/II. 15kV 25kV. Qualified Persons

S Voltage Regulators GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage. Standards

Transformer Installation, Operation, and Maintenance Manual

Magnum Breaker Remote Racking Device (MRR1000)

Installation and Operation

EISHO TEK. Vacuum Circuit Breaker

Effective November 2016 Supersedes September 1998 (S )

Transcription:

Vacuum Circuit Breakers (Vehicle) Type DTR 7.5kV to 15kV Instructions Installation Operation Maintenance SGIM-9938B

Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment damage. De-energize and ground the equipment before maintenance. Maintenance should be performed only by qualified personnel. The use of unauthorized parts should not be used in the repair of the equipment. Follow all safety instructions contained herein. IMPORTANT The information contained herein is general in nature and not intended for specific application purposes. It does not relieve the user of responsibility to use sound practices in application, installation, operation, and maintenance of the equipment purchased. Siemens reserves the right to make changes in the specifications shown herein or to make improvements at any time without notice or obligations. Should a conflict arise between the general information contained in this publication and the contents of drawings or supplementary material or both, the latter shall take precedence. QUALIFIED PERSON For the purpose of this manual a qualified person is one who is familiar with the installation, construction or operation of the equipment and the hazards involved. In addition, this person has the following qualifications: (a) is trained and authorized to de-energize, clear, ground, and tag circuits and equipment in accordance with established safety practices. (b) is trained in the proper care and use of protective equipment such as rubber gloves, hard hat, safety glasses or face shields, flash clothing, etc., in accordance with established safety practices. (c) is trained in rendering first aid. SUMMARY These instructions do not purport to cover all details or variations in equipment, nor to provide for every possible contingency to be met in connection with installation, operation, or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser s purposes, the matter should be referred to the local sales office. The contents of this instruction manual shall not become part of or modify any prior or existing agreement, commitment or relationship. The sales contract contains the entire obligation of Siemens Energy, Inc. The warranty contained in the contract between the parties is the sole warranty of Siemens Energy, Inc. Any statements contained herein do not create new warranties or modify the existing warranty.

Vacuum Circuit Breakers (Vehicle) Table of Contents Introduction and Safety... 2 Introduction... 2 Qualified Person... 2 Signal Words... 2 Dangerous Procedures... 2 Field Service Operation... 2 Receiving, Handling and Storage... 3 Introduction... 3 Receiving Procedure... 3 Shipping Damage Claims (when applicable)... 3 Handling Procedure... 3 Storage Procedure... 3 Space Heating... 3 Vehicle Description... 4 Vehicle Function and Operational Interlocks... 4 Alignment... 4 Recommended Tools... 4 Installing Circuit Breaker Module Into Compartment... 4 Racking Operations... 4 Maintenance... 6 Introduction and Maintenance Intervals... 6 Recommended Maintenance and Lubrication... 6 Removal from Switchgear... 6 Checks of the Primary Power Path... 7 Inspection of Primary Disconnects and Cleanliness Check... 7 Fastener Check... 8 Racking Mechanism... 8 Electrical Control Checks... 8 Check of the Wiring and Terminals... 8 Electrical Close and Trip Check (Control Power Required)... 8 Checks of the Spring Charging Motors... 8 1

Introduction and Safety Introduction The DTR family of vacuum circuit breakers is designed to meet all the applicable ANSI, NEMA and IEEE standards. Successful application and operation of this equipment depends as much upon proper installation and maintenance by the user as it does upon the careful design and fabrication by Siemens. The purpose of this Instruction Manual is to assist the user in developing safe and efficient procedures for the installation, maintenance and use of the equipment. Contact the nearest Siemens representative if any additional information is desired. Signal Words The signal words Danger, Warning and Caution used in this manual indicate the degree of hazard that may be encountered by the user. These words are defined as: Danger - Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. Warning - Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. Caution - indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. Hazardous voltages and high-speed moving parts. Will cause death, serious injury or property damage. Only qualified persons thoroughly familiar with the equipment, instruction manuals and drawings should install, operate and/or maintain this equipment. Qualified Person For the purpose of this manual a Qualified Person is one who is familiar with the installation, construction or operation of the equipment and the hazards involved. In addition, this person has the following qualifications: Training and authorization to energize, de-energize, clear, ground and tag circuits and equipment in accordance with established safety practices. Training in the proper care and use of protective equipment such as rubber gloves, hard hat, safety glasses, face shields, flash clothing, etc., in accordance with established safety procedures. Dangerous Procedures In addition to other procedures described in this manual as dangerous, user personnel must adhere to the following: 1. Always work on de-energized equipment. Always deenergize a breaker, and remove it from the switchgear before performing any tests, maintenance or repair. 2. Always perform maintenance on the breaker after the spring-charged mechanisms are discharged. 3. Always let an interlock device or safety mechanism perform its function without forcing or defeating the device. Field Service Operation Siemens can provide competent, well-trained Field Service Representatives to provide technical guidance and advisory assistance for the installation, overhaul, repair and maintenance of Siemens equipment, processes and systems. Contact regional service centers, sales offices or the factory for details, or telephone Siemens Field Service at 1-800-241-4453. Training in rendering first aid. 2

Receiving, Handling and Storage Introduction This manual covers the Receiving, Handling and Storage instructions for vacuum circuit breakers shipped separately from the switchgear. This section of the manual is intended to help the user identify, inspect and protect the circuit breaker prior to its installation. Receiving Procedure Make a physical inspection of the shipping container before removing or unpacking the circuit breaker. Check for shipment damage or indications of rough handling by the carrier. Check each item against the manifest to identify any shortages. Accessories such as the manual charging crank, the racking crank and the split plug jumper are shipped separately. Shipping Damage Claims (when applicable) - Follow normal shipment damage procedures, which should include: 1. Check for visible damage upon arrival. 2. Visible damage must be noted on delivery receipt, and acknowledged with driver s signature. Notation, Possible internal damage, subject to inspection must be on delivery receipt. 3. Notify the Siemens Sales office immediately of any shipment damage. 4. Arrange for carrier s inspection. Do not move the unit from its unloading point. Handling Procedure Heavy weight. Can cause death, serious injury, or property damage. Use of a qualified rigger to hoist the circuit breaker. 4. The palleted circuit breaker can also be moved using a properly rated fork-lift vehicle. The pallets are designed for movement by a standard fork-lift vehicle. Storage Procedure 1. When the breaker will be placed on its pallet for storage, be sure the unit is securely bolted to the pallet and covered with polyethylene film at least 10 mils thick. Indoor Storage - Whenever possible, store the circuit breaker indoors. The storage environment must be clean, dry and free of such items as construction dust, corrosive atmosphere, mechanical abuse and rapid temperature variations. Outdoor Storage - Outdoor storage is not recommended. When no other option is available, the circuit breaker must be completely covered and protected from rain, snow, dirt and all other contaminants. Space Heating - Space heating must be used for both indoor and outdoor storage to prevent condensation and corrosion. When stored outdoors, 250 watts per breaker of space heating is recommended. 1. Carefully remove the shipping carton from the circuit breaker. Keep the shipping pallet for later use if the breaker is to be stored prior to its installation. 2. Inspect for concealed damage. Notification to carrier must take place within 15 days to assure prompt resolution of claims. 3. Each circuit breaker should be appropriately lifted, using lifting sling rated for at least 2,000 lbs. Breaker shall be lifted by Upper B phase post insulator. 3

Vehicle Description Vehicle Function and Operational Interlocks Type DTR vacuum circuit breakers are comprised of the interrupter/operator module fitted to a vehicle. This interrupter/operator module is an integral arrangement of operating mechanism, dielectric system, vacuum interrupters, and means of connecting the primary circuit. The vehicle supports the interrupter/operator module, providing mobility and fully coordinated application in Federal Pacific Type DST-2 switchgear. This manual should be used jointly with the Circuit Breaker Operator manual, SGIM-9918. Alignment All aspects of the circuit breaker structure which impact alignment and interchangeability are checked at the factory. Field adjustment will not normally be required, but variations in existing switchgear may require field adjustment. Recommended Tools Hazardous voltages and high-speed moving parts. Will cause death, serious injury, and property damage. De-energize before working on this equipment. Do not by-pass interlocks or otherwise make interlocks inoperative. Racking Crank: Original circuit breaker racking crank may be used. Racking Release Tool (5/8 Hex). Installing Circuit Breaker Module Into Compartment (Figures 1a,1b, 1c) Racking Operations (Figures 1a,1b, 1c) A Racking In Procedure: B. Move the breaker to the test position using the racking lever (Figure 1a). Shift the lever back and forth until hearing a clicking sound of the interlock bar (1) engaging the cell interlock rail. The interlock pedal will come upward and indicate blocked. If operation of the circuit breaker in the test position is desired, the secondary disconnect contacts must be engaged manually by sliding assembly forward until contact is made with the cell secondary assembly and the lockout switch (3) must be manually reset. Note: The lockout switch (3) located below the interlock pedal (2) prevents recharging the motor following any racking operations when the pedal is depressed. C. To continue racking to the connected position, insure that the breaker has been tripped electrically or manually and that the closing springs are discharged. With the racking lever inserted (Figure 1a), depress the interlock pedal (2) and rack breaker until the interlock bar falls securely into the interlock rail slot. Insure the interlock petal position indicator shows blocked. Reset the lockout switch (3) to permit electrical operations and replace power fuses (if removed previously). B Racking Out Procedure: A. Trip the breaker either electrically through a remote control switch or manually through the trip-close knob on the mechanism. B. With the breaker open, place the racking lever as shown in Figure 1b, depress the interlock pedal (2) and proceed racking to test position. Lockout switch (3) opens motor circuit. C. To continue racking to the fully withdrawn position, operate the breaker manually to insure that the breaker is open and discharged. Insert racking lever as shown in Figure 1b, depress interlock pedal (2) and proceed racking until breaker has been fully withdrawn from the cubicle. D. Insert handling dolly and remove breaker. A. With the breaker mechanism in the open and spring discharged position, roll the breaker onto the cell rails using the handling dolly and check that it moves freely. Note: Whenever the breaker is opened either electrically through a remote control switch or manually through the trip-close knob on the mechanism. This will automatically free the inlocklock pedal (2) permitting the release of the interlock bar (1) and removes power to the charging motor. 4

Vehicle Description Figure 1a. Method of Racking Circuit Breaker Figure 1b. Method of Racking Circuit Breaker Figure 1c. Method of Racking Circuit Breaker The closing spring, if charged, will automatically discharge when the circuit breaker is withdrawn from the switchgear. 5

Maintenance Introduction and Maintenance Intervals Periodic inspections and maintenance are essential to obtain safe and reliable operation of the circuit breaker as well as the switchgear. Hazardous voltages and high-speed moving parts. Will cause death, personal injury, and property damage. De-energize before working on this equipment. Read instruction manuals, observe safety instructions, and limit use to qualified personnel. When circuit breakers and/or the switchgear are operated under Usual Service Conditions, maintenance and lubrication is recommended at five year intervals or at the number of operations indicated in Table 2. Usual and Unusual service conditions for Medium Voltage Metal-Clad Switchgear are defined in ANSI C37.20.2, section 8.1. Generally, usual service conditions are defined as an environment in which the equipment is not exposed to excessive dust, acid fumes, damaging chemicals, salt air, rapid or frequent changes in temperature, vibration, high humidity, and extremes of temperature. The definition of usual service conditions is subject to a variety of interpretations. Because of this, you are best served by adjusting maintenance and lubrication intervals based on your experience with the equipment in the actual service environment. Regardless of the length of the maintenance and lubrication interval, Siemens recommends that circuit breakers and switchgear should be inspected and exercised annually. Recommended Maintenance and Lubrication Periodic maintenance and lubrication should include all the tasks shown in Table 1. Recommended procedures for each of the listed tasks are provided in this section of the manual. Failure to properly maintain the equipment could result in death, serious injury or product failure, and can prevent successful functioning of connected apparatus. Instructions should be carefully reviewed, understood, and followed. The maintenance tasks in Table 1 must be performed regularly. Table 1: Maintenance Tasks Checks of the primary power path Cleanliness check Inspection of primary disconnects Electrical control checks Wiring and terminals check Secondary disconnect check Automatic spring charging check Electrical close and trip check High potential test Insulation test Inspection and cleaning of insulation Functional tests Primary disconnect contact cleanliness and lubrification Racking mechanism cleanliness and lubrification Circuit Breaker Operator tasks as detailed in manual SGIM-9918 The list of tasks in Table 1 does not represent an exhaustive survey of maintenance steps necessary to ensure safe operation of the equipment. Particular applications may require further procedures. Should further information be desired or should particular problems arise which are not covered sufficiently for the Purchaser s purposes, the matter should be referred to the local Siemens sales office. The use of unauthorized parts in the repair of the equipment, or tampering by unqualified personnel will result in dangerous conditions which will cause death, serious injury or equipment damage. Follow all safety instructions contained herein. Removal from Switchgear Prior to performing any inspection or maintenance checks or tests, the circuit breaker must be removed from the switchgear. The Installation and Initial Functional Tests section describes the removal procedure in detail. Principal steps are repeated here for information and guidance, but without the details of the preceding section. 1. The first step is to de-energize the circuit breaker. Depressing the Trip pushbutton opens the breaker prior to removal from the switchgear (Refer to Circuit Breaker Operator / Manual SG-9918). 2. The second step in the removal procedure is to de-energize control power to the circuit breaker. Open the control power disconnect device. 3. Rack the breaker to the DISCONNECT position. 6

Maintenance Figure 2. Racking Mechanism. 4. Perform the spring discharge check. This is done by first depressing the red Trip pushbutton. Second, depress the back Close pushbutton. Third, depress the red Trip pushbutton again, and observe the spring condition indicator. It should read Discharge (Refer to Circuit Breaker Operator / Manual SGIM-9918). The phase barriers are plates of glass polyester insulating material and attached to the circuit breaker to provide suitable electrical insulation between the vacuum interrupter primary circuits and the housing. 5. Remove the breaker from the switchgear. Refer to the preceding installation section of this manual for special instructions and precautions regarding removal of a breaker which is not at floor level. Checks of the Primary Power Path The primary power path consists of the three vacuum interrupters, the three upper and the three lower primary disconnects. These components are checked for cleanliness and condition (Figure 3). The vacuum interrupters are discussed in the Circuit breaker Operator Manual SGIM-9918. Note: Maximum Contact Resistance is read from primary bus stab to primary bus stab. A value of 13 micro-ohms should be added to the maximum contact resistance specified in Circuit Breaker Operator Manual SGIM-9918. Inspection of Primary Disconnects and Cleanliness Check Figure 3 is a side view of the DTR Circuit Breaker with the insulating barriers removed to show the vacuum interrupter, and the upper and lower primary disconnects. All of these components must be clean and free of dirt or any foreign objects. Use a dry lint-free cloth. For stubborn dirt, use a clean cloth saturated with denatured alcohol. Figure 3. Primary Power Path 7

Maintenance Always re-install the phase barriers carefully to the original location prior to inserting the circuit breaker in the housing. When the contacts are mated with the switchgear s primary stud assembly, there is forceful contact distributed over a wide area. This maintains low current flow per individual contact finger. Inspect the contact fingers for any evidence of burning or pitting that would indicate weakness of the contact finger springs. Inspect the primary disconnect arms for physical integrity and absence of mechanical damage. Inspect the flexible connectors that connect the bottom movable contacts of the vacuum interrupters to the lower primary disconnect arms for tightness and absence of mechanical damage, burning, or pitting. Using a clean cloth saturated with denatured alcohol, clean old lubricant from primary disconnects, and apply Siemens contact lubricant (reference 15-172-791-214) in a very thin layer. Fastener Check Inspect all fasteners for tightness. Both lock-nuts and retaining rings are used. Replace any fasteners that appear to have been frequently removed and replaced. Racking Mechanism Racking mechanism is to be wiped clean, and a film of Klueber Isoflex Topas L32 grease (part # 3AX11333H), Anderol 732 aerosol synthetic fluid grease (reference # 15-172-816-058) or Beacon #325 (part # 15-337-131-001) is to be applied on the shaft surfaces, threads and nuts. Electrical Control Checks Check of the Wiring and Terminals 1. Physically check all of the switchgear wiring for evidence of abrasion, cuts, burning or mechanical damage. 2. Check all terminals to be certain they are solidly attached to their respective device. Electrical Close and Trip Check (Control Power Required) A check of the breaker control circuits is performed while the unit is still connected to the switchgear by the plug jumper. This check is made with the breaker energized by control power from the switchgear. 1. Once the breaker springs are charged, move the switchgear Close/Trip switch to the Close position. There should be both the sound of the breaker closing and indication that the breaker contacts are closed by the main contact status indicator. 2. As soon as the breaker has closed, the automatic spring charging process is repeated. 3. After a satisfactory close operation is verified, move the switchgear Close/Trip switch to the Trip position. Verify by both sound and contact position that the contacts are open. Completion of these checks demonstrates satisfactory operation of auxiliary switches, internal relays and solenoids. Checks of the Spring Charging Motors of the spring charging motor are necessary. Table 2. Periodic Maintenance and Lubrication Tasks Sub-Assembly Primary Power Path Item Primary Disconnects Inspect For 1. Burnt or damaged fingers 2. Lubrication of contact surfaces. 3. Tightness of nuts and other locking devices Electrical Controls Wiring 1. Mechanical damage or abrasion High Potential Test Terminals and Connectors Close and Trip Solenoids,Anti- Pump Relay, Auxiliary Switches, Secondary Disconnect Primary Circuit to Groundand between Primary Disconnects Control Circuit to Ground 1. Tightness and absence of mechanical damage 1. Automatic charging 2. Close and trip with control power 1. 60 second withstand, refer to Circuit Breaker Operator Manual SGIM-9928 for ratings. 1. 60 second withstand, refer to Circuit Breaker Operator Manual SGIM-9928 for ratings. Insulation Interrupter Operator Mechanism Racking Mechanism Barriers and all Insulating Components Refer to Circuit Breaker Operator Manual. 1. Cleanliness 2. Cracking, crazing, tracking, or other sign of deterioration 1.Cleanliness 2.Lubrification of shaft surfaces. 8

Siemens Energy, Inc. 7000 Siemens Rd. Wendell, NC 27591 SGIM-9938B (2-2009) Printed in U.S.A. 2001 Siemens Energy, Inc. SIEMENS is a registered trademark of Siemens AG.