COOPER POWER SERIES. Type VSA12, VSA16 and VSA20/800 maintenance instructions. Reclosers MN280064EN

Similar documents
Effective May 2017 Supersedes January 2003 (S )

This Kit Is for Use with Types RE, RVE, WE, WVE, VWE, VWVE27, and VWVE38 Reclosers.

COOPER POWER SERIES. Types 4H single-phase and 6H three-phase vacuum interrupter conversion kits. Reclosers MN280014EN

COOPER POWER SERIES. KA662R tank-lifting windlass assembly and installation instructions. Recloser Mountings MN280071EN

Effective June 2016 New Issue

COOPER POWER SERIES. QD5 Quik-Drive tap-changer reversing neutral stationary contact asssembly kit A26 installation instructions

COOPER POWER SERIES. UltraSIL polymer-insulated D-73P disconnect switches installation instructions. Switches MN008004EN

COOPER POWER SERIES. Edison Modular Fuse (EMF) Installation Instructions. Fusing Equipment MN132031EN

Effective March 2015 Supersedes S August 2012

Effective November 2016 Supersedes September 1998 (S )

COOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing

COOPER POWER SERIES. Current-Limiting Type NXC (C-Rated) Fuse Installation Instructions. Fusing Equipment MN132014EN

COOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN

COOPER POWER SERIES. ELSG Full-Range Current-Limiting Fuse Re-Fusing Instructions. Fusing Equipment MN132017EN

COOPER POWER SERIES. Expulsion fuse installation instructions. Capacitors MN230005EN. Effective November 2016 Supersedes November 2001 (S )

COOPER POWER SERIES. High-voltage primary bushings installation instructions. OEM Equipment MN800008EN

COOPER POWER SERIES. Testing a motor capacitor on a voltage regulator procedure instructions. Voltage Regulators MN225064EN

COOPER POWER SERIES. Mercury switch to microswitch retrofit kit KA349WE installation instructions. Reclosers MN280022EN

Type NR oil switch installation and operation instructions

Effective May 2017 Supersedes December 2004 (S )

COOPER POWER SERIES. Electronic control battery testing, charging, and replacement instructions. Reclosers MN280074EN

COOPER POWER SERIES. Type VSO maintenance instructions. Reclosers MN280066EN. Effective October 2017 Supersedes August 1986 (S )

COOPER POWER SERIES. S.T.A.R. Hot line voltage indicator installation instructions. Fault Indicators MN320011EN. Indicator boot.

COOPER POWER SERIES. HX-CB loadbreak fuse cutout installation instructions. Fusing Equipment MN132011EN

COOPER POWER. SERIES CMU Medium voltage power fuse installation instructions. Fusing Equipment MN132032EN

COOPER POWER SERIES. KA716L7001 adjustable control valve kit for Types L, E, 4E, V4E, and V4L reclosers installation and adjustment instructions

COOPER POWER SERIES. KA1169R Closing Coil Transfer-Switch Accessory Operation. Reclosers MN280069EN

COOPER POWER SERIES. Pad-mounted Switchgear MN285019EN. Effective March 2017 Supersedes February 2007 (S )

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. 200 A Fused Loadbreak Elbow Connector Replacement Fuse Installation Instructions. Fusing Equipment MN132021EN

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. 200 A loadbreak junction 15 and 25 kv class installation instructions. Loadbreak Connectors MN650015EN

COOPER POWER SERIES. RTE EL-BAY-O-NET FUSE Re-Fusing Instructions. Fusing Equipment MN132024EN

COOPER POWER SERIES. Dielectric grease application to recloser cable instructions. Reclosers MN280070EN

High-voltage primary bushings installation instructions

COOPER POWER SERIES. S.T.A.R. type LVR faulted circuit indicator installation instructions. Fault Indicators MN320005EN

COOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN

COOPER POWER SERIES. 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions. Loadbreak/Deadbreak Connectors MN650016EN

S Oil-and Vacuum-Break Switches. Type F; Three-Phase; Vacuum Load Break Switch Maintenance Instructions WARNING CONTENTS.

COOPER POWER SERIES. Surge arrester interchangeable fuse cutout combination installation instructions. Surge Arresters MN235004EN

COOPER POWER SERIES. KA146W5 single pole-mounting hanger; KA146W2 tank lifting windlass assembly and installation instructions. Reclosers MN280039EN

Effective November 2016 Supersedes February 2012 (S )

Effective May 2017 Supersedes October 2002 (S )

COOPER POWER SERIES. Quick Connect Assembly (QCA) Retrofit Kit, General Electric Installation Instructions. Voltage Regulators MN225075EN

COOPER POWER SERIES. Type VSA12, VSA12B, VSA16, VSA20, and VSA20A operation and installation instructions. Reclosers MN280063EN

S Fault Indicators. S.T.A.R. Type TPR Faulted Circuit Indicator Installation Instructions. Contents INSTALLATION PROCEDURES

S Reclosers. Contents. Types VXE15 and VXE27 Electronically Controlled, Single-Phase Recloser Maintenance Instructions

COOPER POWER SERIES. Types D and DV recloser installation instructions. Reclosers MN280030EN

S Voltage Regulators GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage. Standards

S Voltage Regulators GENERAL. PRODUCT INFORMATION Introduction. Contents. Acceptance and Initial Inspection. Handling and Storage.

Types VSA12, VSA12B, VSA16, VSA20, and VSA20A; three-phase; air-insulated; electronically controlled recloser

S Voltage Regulators PRODUCT INFORMATION GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage

S Voltage Regulators PRODUCT INFORMATION GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage.

Figure 1. Kearney Type HX cutout.

Figure 1 Type GH single-phase sectionalizer. INTRODUCTION

Installation Instructions for Interlocking Trip Indicator with Remote Reset for Magnum Low Voltage Circuit Breakers

TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS

Instructions for VCP-W Simple Electrical Ground & Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version

COOPER POWER SERIES. 600 A 15/25 kv class BOL-T and separable splice connector assembly installation instructions

COOPER POWER SERIES. 600 A 15 kv and 25 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650004EN

S Fault Interrupters. Type CI; Three-Phase Maintenance Instructions. Service Information

COOPER POWER SERIES. Types VWE, VWVE27, VWVE38X, WE, WVE27, and WVE38X; threephase electronically controlled; installation and operation instructions

Eaton s Cooper Power Systems catalog Medium-voltage vacuum circuit breakers

Factory Authorized Mechanism Enhancement (FAME)

S Sectionalizers. Contents. Types GN3E and GN3VE Maintenance Instructions. Service Information

COOPER POWER CA280012EN

S Reclosers. Types RX, and W Maintenance Instructions CONTENTS

COOPER POWER SERIES. Type 6H and V6H maintenance instructions. Reclosers MN280050EN. Effective May 2017 Supersedes February 2005 (S )

COOPER POWER SERIES. 600 A 35 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650003EN

COOPER POWER SERIES. Metal-enclosed capacitor banks installation instructions. Power Capacitors MN230010EN

KFE10010-E. Reclosers. Contents. Type KFVE and KFVME (27kV) Bus Bar Kit KRK710-1 Installation Instructions. Cooper Power Systems

Two-way cable interlock kit for Magnum drawout circuit breakers

CR193 Vacuum Limitamp* Contactors

COOPER POWER SERIES. Metal-enclosed, pad-mounted capacitor banks installation instructions. Power Capacitors MN230009EN

COOPER POWER SERIES. Manually-Operated M-Force Switch Installation and Operation Instructions. Switches and Disconnects MN008003EN

COOPER POWER SERIES. Fused loadbreak elbow connector installation instructions. Loadbreak Apparatus Connectors MN650014EN

Installation Instructions for KPS and KPH Circuit Breakers and Molded Case Switches

COOPER POWER SERIES. VFI tester operating instructions. Underground Distribution Switchgear MN285001EN

Digitrip Retrofit System for the ITE LG-3000 (Frameless) Circuit Breaker

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

Two-way cable interlock kit for Magnum fixed circuit breakers

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod

S&C Type FVR Substation Circuit Breaker

Florham Park, NJ USA Call (ASCO) for sales or service

Instruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module.

Installation Instructions for R-Frame G-Series (RG) 310+ Trip Unit

CCP2-FLR1-21_ flange-rod operating mechanism

Vacuum Circuit Breaker Type VAD-3

3-way multi-family drawout cable interlock kit - type 32 - RF

COOPER POWER SERIES. Instructions for oil-filled, single-phase overhead distribution transformers. Distribution Transformers MN201003EN

MODEL ELC-12/40-CVM-D BATTERY CHARGER

CM52 Network Protector with Arc Flash Reduction Module

Installation and removal instructions for Series NRX RF fixed breaker three-way Type 32 cable interlock kit

Digitrip Retrofit System for General Electric AKR/AKRU-6D/7D-30S Series Breakers

Horizontal Circuit Switchers

O & M Manual for the EATON Generator Ready Loadcenter

Florham Park, NJ USA Call (ASCO) for sales or service

Digitrip Retrofit System for the Federal Pioneer 25-H(L)-2, 30-H(L)-2, 30-H(L)-3, and 30-3 Breakers

Installation Instructions For Motor Control Center (MCC) Units

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

Transcription:

Reclosers MN8006EN Effective October 07 Supersedes June 99 (S80--) COOPER POWER Type VSA, VSA6 and VSA0/800 maintenance instructions SERIES

DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information, recommendations, descriptions and safety notations in this document are based on Eaton Corporation s ( Eaton ) experience and judgment and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser. THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or other-wise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and descriptions contained herein. The information contained in this manual is subject to change without notice. MAINTENANCE INSTRUCTIONS MN8006EN October 07 i

Contents DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY... i Safety for life... iii Safety information... iii Safety instructions... iii Introduction.... Description and operation... Specifications and ratings.... Maintenance.... Frequency of maintenance... Periodic maintenance inspection... Manual operation.... To close recloser... To open recloser... Insulation level withstand tests... Shop maintenance instructions... 6 Bushings...6 Vacuum interrupters...6 Operating mechanism...7 Motor...9 Gear reduction unit...0 Electrical components... 0 Sensing current transformer tests...0 Control cable check... Control circuit components... Service parts list... 6 Bushings and interrupter (Figure )...8 Interrupter cabinet (Figure )...0 Operating linkage assembly (Figure )... Operator cabinet (Figure )... Terminal panel (Figure 6)... Decals and labels (Figure 7)...6 Operating mechanism electrical parts (Figure 8)...7 Operating mechanism electrical parts (Figure 9)...9 ii MAINTENANCE INSTRUCTIONS MN8006EN October 07

! SAFETY FOR LIFE Safety for life Eaton meets or exceeds all applicable industry standards relating to product safety in its Cooper Power series products. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Eaton employees involved in product design, manufacture, marketing, and service. We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around high voltage lines and equipment, and support our Safety For Life mission.! SAFETY FOR LIFE Safety information The instructions in this manual are not intended as a substitute for proper training or adequate experience in the safe operation of the equipment described. Only competent technicians who are familiar with this equipment should install, operate, and service it. A competent technician has these qualifications: Is thoroughly familiar with these instructions. Is trained in industry-accepted high and low-voltage safe operating practices and procedures. Is trained and authorized to energize, de-energize, clear, and ground power distribution equipment. Is trained in the care and use of protective equipment such as arc flash clothing, safety glasses, face shield, hard hat, rubber gloves, clampstick, hotstick, etc. Following is important safety information. For safe installation and operation of this equipment, be sure to read and understand all cautions and warnings. Hazard Statement Definitions This manual may contain four types of hazard statements: DANGER Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in equipment damage only. Safety instructions Following are general caution and warning statements that apply to this equipment. Additional statements, related to specific tasks and procedures, are located throughout the manual. DANGER Hazardous voltage. Contact with hazardous voltage will cause death or severe personal injury. Follow all locally approved safety procedures when working around high- and low-voltage lines and equipment. G0. WARNING Before installing, operating, maintaining, or testing this equipment, carefully read and understand the contents of this manual. Improper operation, handling or maintenance can result in death, severe personal injury, and equipment damage. G0.0 WARNING This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply can result in death, severe personal injury and equipment damage. G0. WARNING Power distribution and transmission equipment must be properly selected for the intended application. It must be installed and serviced by competent personnel who have been trained and understand proper safety procedures. These instructions are written for such personnel and are not a substitute for adequate training and experience in safety procedures. Failure to properly select, install or maintain power distribution and transmission equipment can result in death, severe personal injury, and equipment damage. G. MAINTENANCE INSTRUCTIONS MN8006EN October 07 iii

Introduction Service Information MN8006EN covers the maintenance instructions for the type VSA electronically controlled, threephase, vacuum recloser. The manual includes a general description of the recloser and its operation and instructions for periodic inspection, testing and shop repairs. Keyed service parts exploded-view drawings of the unit, along with ordering information are included at the back of the manual. Description and operation The VSA, VSA6 and VSA0/800 three-phase reclosers feature vacuum interruption and air insulation. Current interruption takes place in the rugged vacuum interrupter assemblies which are suspended from the recloser cover by insulating supports, as shown in Figure. The moving contacts, located in each interrupter assembly, driven by the recloser operating mechanism, close or open the circuit. Interruption takes place within two and one-half cycles, while utilizing a contact stroke of one-half inch. Recloser tripping and closing are initiated by signals from the recloser control unit. When current in excess of the programmed minimum trip level is detected, on any phase or phases, the recloser control initiates a trip signal which energizes a solenoid in the operating mechanism of the recloser. When actuated, this solenoid trips the opening springs, which opens the interrupter contacts. Closing springs provide the force required to close the vacuum interrupters, as well as the force required to charge the opening springs. A 0 Vac motor charges the closing springs through a multi-stage gear drive. When 0 Vac is present, the motor is automatically operated to keep the closing springs in a charged state. To close the recloser the control initiates a signal which energizes a solenoid in the recloser operating mechanism. Once actuated the solenoid releases the closing springs, which close the vacuum interrupters and charge the opening springs. Therefore a sequence of Open-Close-Open is available after loss of 0 Vdc power. An external 0 Vac source is required to operate the drive motor. A battery, in the electronic control, supplies the Vdc tripping and closing power. Recloser tripping employs stored spring energy. The stored spring energy is released, to open the recloser, when the trip solenoid is actuated by the Vdc trip signal. The Vdc trip signal is originated at the recloser control. The 0 Vac supply is not required to trip the recloser. A totally manual closing operation can be accomplished even during loss of motor power and with the closing springs discharged. A hand crank can be applied to the motor to charge the closing springs. Once charged, the closing springs can be released either from inside or from below the operator mechanism cabinet. As with electrical operations, the opening springs are charged by release of the closing springs, so even a manually closed unit has energy stored for a trip operation. Major parts and assemblies of the VSA recloser are shown in Figures and. Being aware of the location of these components and their part in the operation of the recloser will give a quicker and clearer understanding of the recloser maintenance and repair procedures that follow. Figure. Type VSA recloser with side panels removed MAINTENANCE INSTRUCTIONS MN8006EN October 07

Contact position indicator Auxiliary switch (accessory) Trip-reset knob Drive motor Operation counter Spring charge indicator Operator cabinet heater Manual close lever Multi-ratio current transformer terminal board (accessory) Manual close lever Manual trip lever Figure. Operating mechanism Specifications and ratings The recloser will interrupt fault currents only when applied within its specified ratings. Consult the following ratings and compare to system characteristics at point ofapplication prior to installation. Table. Voltage ratings VSA- VSA-6 VSA-0 Maximum design voltage (kv)... Nominal operating voltage (kv).-..-..-. Basic insulation level (BIL) (kv) 0 0 0 60 Hertz withstand voltage (kv) Dry, one minute 0 0 0 Wet, ten seconds Max RIV at.0 MHz/9. kv (mv) 00 00 00 Table. Duty cycle Percent of maximum circuit interrupting rating Maximum X/R ratio -0 88-8 90-00 Total Number of unit operations Table. Mechanical life Open-close, no load, operations 00 Table. Electrical specifications Trip solenoid: Operating voltage (Vdc) Peak current (A). Actuation time (cycles (ms)). () Close solenoid: Operating voltage (Vdc) Peak current (A). Actuation time (cycles (ms)). () Spring charging motor: Standard Accessory Operating voltage (Vac) 0 0 Voltage range (Vac) 90-7 90-7 Maximum current, rms (A) 8 Steady state current (A). 9 Running time (cycles (S)) 0 (0.67) 0 (0.67) Dc resistance, nominal: Bushings, terminal-to-terminal (mw) 0 Interrupter, terminal-to-terminal (mw) 9 MAINTENANCE INSTRUCTIONS MN8006EN October 07

Table. Current ratings VSA- VSA-6 VSA-0 Continuous current rating (A) 800 800 800 Symmetric interrupting current (A),000 6,000 0,000 Cable charging current (A) Magnetizing current (A) 8 8 8 Second current, symmetric (A),000 6,000 0,000 Momentary current, asymmetric (A) 0,000,600,000 Table 6. Mechanical specifications Operating temperature ( C) Minimum -0 Maximum +0 Closing mechanism Spring operated Opening mechanism Spring operated Contact gap (inches (mm)) 0. (,7) Close contact travel time (cycles (ms)) 0. (8) Open contact travel time (cycles (ms)) 0. (8) Maximum arcing time (cycles (ms)).0 (7) Interrupting time (cycles (ms)). () Allowable contact erosion (inches (mm)) 0. (,) Opening time ( vdc solenoid, signal to 9- contact part) (ms) Closing time ( vdc solenoid, signal to contact make) (ms) Maintenance Frequency of maintenance Because reclosers are applied under widely varying operating and climactic conditions, maintenance intervals are best determined by the user, based on actual operating experience. To assure proper and trouble-free operation, reclosers must be maintained when they have operated the equivalent of a rated duty cycle (see Table ). In the absence of specific operating experience the following procedures are recommended: When the type VSA recloser is operated under usual service conditions as defined in ANSI (American National Standards Institute) C7.60, Standard Requirements for Overhead, Pad Mounted, Dry Vault and Submersible Automatic Circuit Reclosers and Fault Interrupters for AC Systems, it is recommended that the following maintenance procedures be performed at the completion of an equivalent duty cycle. NNote: ANSI C7.6, Guide for the Application, Operation and Maintenance of Automatic Circuit Reclosers, gives a procedure for converting the rated standard duty cycle into an equivalent duty cycle based on the actual operating duty of the recloser. Periodic maintenance inspection Each maintenance inspection at the completion of an equivalent duty cycle should include at least the following:. Bypass and remove the recloser from service: a. Disconnect the control cable from the recloser. b. Remove the fused pullout switch to de-energize the 0 Vac power source to the operator mechanism.. Visually inspect external components: a. Check for broken or cracked bushings; replace as necessary. (See Shop Maintenance Instructions Bushings for procedure.) b. Check for paint scratches and other mechanical damage; touch up to inhibit corrosion.. Visually inspect the operator mechanism: a. Check interior of the operator mechanism cabinet for accumulation of dust and dirt; clean as necessary. b. Check door gasket for effectiveness of seal, repair or replace as required. c. Visually inspect all components for worn or broken parts and corrosion; replace as necessary. d. Check for broken or loose wiring terminals at the various components and terminal boards. CAUTION Do not use excessive force when replacing brush holder caps; excessive tightening may crack the caps. e. Check the motor brushes for excessive wear and burning; replace as needed. f. Record counter reading in the record log.. Close and trip the recloser manually several times to check mechanical operation. (See Manual Operation To Close the Recloser for manual operating instructions.). Perform a dielectric withstand test to check the insulation level of the recloser and the vacuum integrity of the interrupters. (See Insulation Level Withstand Tests for procedure.) 6. Remove cabinet side panels to expose the internal components. 7. Check the contact erosion of the vacuum interrupters: a. Locate the scribe mark on the moving contact rod at the top of the interrupter. (See Figure.) However, if the recloser has not completed an equivalent duty cycle within THREE YEARS, it is recommended that an inspection be made at that time. (See Steps one through ten of Periodic Maintenance Inspection. ) MAINTENANCE INSTRUCTIONS MN8006EN October 07

IMPORTANT Form A electronic control must be equipped with the KA7ME fuse accessory. This accessory supplies a MDQ-. closing coil control fuse which is required to operate the closing solenoid. Controls must not be programmed with reclose delay intervals that are shorter than 0. second. The instantaneous reclose delay plug must not be used. The KA77ME- reclose delay plug provides a fixed 0. second delay. A maximum of one 0. second delay can be used, successive reclosing operations must be a minimum of two () seconds. Scribe mark 0. Refer to the applicable sections of the Type VSA, VSA6 and VSA0/800 Installation Instructions, S80- -, for procedures to return the recloser to service. Manual operation Figure. Interrupter contact wear inspection b. If the scribe mark falls below the top of the upper support plate, when the interrupter is closed, the interrupter has reached the end of its useful life and must be replaced. (See Vacuum Interrupters for replacement procedure.) 8. Check the electrical operation of the recloser: a. Reinstall the fused pullout switch to energize the motor circuit. If this recloser has been manually tripped while the motor circuit was de-energized (SPRINGS DISCHARGED), the motor will run to charge the closing springs (SPRINGS CHARGED). b. Momentarily apply Vdc to terminals A (+) and E (-) of the control terminal board, mounted vertically along the left edge of the panel board. The recloser will close, and the motor will run to recharge the closing springs for the next closing operation. The recloser can be manually closed and tripped with a set of operating levers on the operator mechanism inside the cabinet (Figure ) or a set of pullrings located externally on the underside of the cabinet (Figure ). To close recloser Proceed as follows:. Apply rated voltage to the input terminal block on the side of the operator cabinet. NNote: If closing springs are discharged, the motor will operate immediately to charge the springs. Manual trip lever c. Momentarily apply -Vdc to terminals A (+) and C (-) of the control terminal board. The recloser will trip open. d. Electrically open and close the recloser several times to check its operation; leave in the open iposition. 9. Check operation of recloser with its control. Checkout procedures for a recloser with a FA control, and for the control only, are described in the applicable control installation manual: Form A electronic recloser controls refer to S80-7-, Form C microprocessorbased controls refer to S80-77-. Figure. Manual operation control levers Manual close lever MAINTENANCE INSTRUCTIONS MN8006EN October 07

. When closing spring status indicator reads SPRINGS CHARGED, lift up the MANUAL CLOSE lever on the operating mechanism, or pull the external MANUAL CLOSE pullring to release the charged springs an close the recloser. NNote: Immediately upon closing, the motor will operate to again charge the closing springs. If motor operating power is not available the closing springs may be charged by manually cranking the mechanism until the closing springs status indicator reads SPRINGS CHARGED:. Remove bolt and seal assembly from hole in right side of cabinet.. Insert manual crank shaft through the cabinet wall and onto the shaft protruding from the mechanism (Figure 6). Manual close Manual trip Figure. Manual operation pullrings. Crank the motor in a COUNTERCLOCKWISE direction until the spring status indicator reads SPRINGS CHARGED. Approximately 0 revolutions are required. To open recloser To release the opening spring either pull down the TRlP RESET knob on the front of the operator mechanism or the PULL TO OPEN pullring under the cabinet. Return knob or pullring to the RESET position after the unit has tripped, to enable the electronic closing circuit. Insulation level withstand tests High potential withstand tests provide information on the dielectric condition of the recloser and the vacuum integrity of the interrupters. Testing is performed at 7. kv rms (7% of the rated low frequency withstand voltage of the VSA recloser). Test e: Proceed as follows:. Manually close main contacts of recloser.. Ground recloser housing.. Connect all three bushings on one side of the recloser together.. Apply proper test voltage to the connected bushings.. The recloser should withstand the test voltage for 60 seconds. Test e: Proceed as follows:. Manually close main contacts of the recloser.. Ground housing.. Ground outer two phase bushings (- and -6).. Apply proper test voltage to center phase bushings (-).. The recloser should withstand the test voltage for 60 seconds. Test e: Proceed as follows:. Open main contacts of recloser.. Ground recloser housing.. Connect and ground all three bushings on one side of the recloser.. Connect the other three bushings together.. Apply proper test voltage to the ungrounded bushings. 6. The recloser should withstand the test voltage for 60 seconds. 7. Reverse the ground and test connections and apply test voltage to the ungrounded bushings for 60 seconds. 8. The recloser should withstand the test voltage for 60 seconds. Figure 6. Manually charging closing springs Test resultse: These high potential withstand tests provide information on the dielectric condition of the recloser and the vacuum integrity of the interrupters. MAINTENANCE INSTRUCTIONS MN8006EN October 07

. If the recloser passes the closed contacts tests (Tests and ) but fails the open-contacts test (Test ) a deteriorated vacuum in one or more of the interrupters is most likely the cause. Retest each vacuum interrupter individually to determine the failed phase or phases, and replace the interrupter(s). Retest to confirm the repair.. If the recloser fails the closed-contacts tests (Tests and ) the cause is likely to be a diminished electrical clearance or a failed insulation. After correcting the problem, retest to confirm the repair. Shop maintenance instructions The operations described in this section should be performed under the cleanest conditions possible. No special tools are required for any of the repair procedures. Bushings Bushing maintenance generally consists of a thorough cleaning and a careful examination for chips, cracks or other physical damage during the periodic maintenance inspection. Bushing porcelain must be replaced whenever damage is discovered. The porcelain can be replaced without removing the bushing assembly from the recloser. To replace bushing porcelain proceed as follows, refer to Figure 7:. Unscrew the bushing terminal, discard the terminal gasket. Bushing terminal Terminal gasket Bushing porcelain Roll pin Bushing rod Figure 7. Bushing porcelain replacement Hex nuts Bushing clamps Lower gasket Split ring. Remove the three hexnuts and bushing clamps that secure the bushing to the recloser housing.. Remove and discard the lower bushing gasket.. Twist off the split aluminum ring from the old bushing and install on the new bushing porcelain, if it is still in good condition; replace if damaged. CAUTION Bushing damage. The split aluminum ring must be replaced if damaged. The clamping ring cushions and distributes the pressure between the bushing flange and the bushing. If bushing clamps are assembled without a new clamping ring, the bushing may be damaged when clamp hardware is tightened. T.. Install a new lower bushing gasket and slide the new bushing porcelain, into the recloser housing, over the bushing rod. Make sure that the roll pin is seated in the locking groove in the top of the bushing. 6. Position the clamping ring with the split centered between two clamp bolts. 7. Install bushing clamp hardware and tighten nuts evenly, a little at a time, to 6-0 ft-lbs. torque. CAUTION Dielectric failure, bushing damage. To prevent gasket leaks or bushing damage, clamping force must be applied gradually and equally in rotation to each bolt. If the clamping force is not evenly applied, seal leakage can result, compromising the dielectric capabilities of the recloser and can cause possible personal injury. Unequal clamping force can cause bushing breakage. T. 8. Apply a very small amount of petroleum jelly to the knurled inside surface of the bushing terminal. 9. Install a new terminal gasket and the bushing terminal, tighten to ft-lbs. torque. Vacuum interrupters Vacuum interrupters must be replaced when: They lose their vacuum as evidenced by a failure during the low-frequency dielectric withstand test across the open contacts; or The interrupter contacts have eroded beyond their useful life as evidenced by the position of the scribe mark on the moving contact rod. To replace an interrupter refer to Figure 8, and proceed as follows:. Remove fused pullout switch to de-energize AC power source to operator mechanism.. Make sure recloser contacts are open; manually operate mechanism until contact position indicator reads OPEN and closing spring status indicator reads SPRINGS DISCHARGED.. Remove nylon hardware, or wire tie, securing insulating barrier to stringers, remove insulating barrier.. Remove hardware and clamp that secure long bushing rod to lower interrupter support bracket. MAINTENANCE INSTRUCTIONS MN8006EN October 07 6

. Loosen bolts that secure upper interrupter clamp. As clamp is loosened atmospheric pressure, acting on the bellows, will cause the contact rod to move down into interrupter. This action can be verified by observing the scribe mark on the contact rod. It should move down, toward contact rod support plate, when clamp is loosened. Short bushing lead Upper interrupter clamp Insulating barrier Stringer Nylon hardware Long bushing lead 0. Carefully place interrupter and lower current exchange assembly into position; situate moving contact rod within upper clamp as assembly is installed. Install washers and locknuts to secure lower current exchange plate to stringers.. Loosen tension bolt to relieve opening spring tension, Figure 9.. Manually close recloser.. Tighten top and bottom contact rod clamp hardware to 0- ft-lbs torque.. Tighten tension bolt to re-apply tension to opening spring, Figure 9. Tension bolt Nyliner bushing Vacuum interrupter Insulating barrier Wire tie Lower nterrupter clamp Clamp hardware Stringer hardware Figure 8. Vacuum interrupter replacement NNote: Bushing lead clamp assembly Clamp hardware If contact rod does not move, interrupter may have lost vacuum, or the contact rod may be sticking within the clamp. Use a screwdriver to gently spread clamp to free rod. 6. Remove hardware attaching lower current exchange plate to stringers. Carefully lower plate and vacuum interrupter assembly from between stringers. 7. Loosen lower current exchange clamp and remove interrupter. If stationary contact rod sticks within clamp use a screwdriver to gently spread clamp to free rod. 8. Remove insulating barrier from top of old interrupter and install on new interrupter. 9. Install stationary contact rod into lower current exchange plate, do not tighten clamp hardware. CAUTION Interrupter damage. When installing the moving contact rod into the upper clamp avoid twisting or cocking the rod. Excessive force can damage the bellows, causing loss of vacuum and irreparable damage to the interrupter and/or premature interrupter failure. Opening springs Figure 9. Opening spring tension bolt. Install clamp and hardware to secure long bushing lead to lower current exchange assembly and tighten. 6. Manually trip and close recloser several times to check operation. 7. Install insulating barrier and secure with nylon hardware, or wire ties, as applicable 8. Perform Insulation Level Withstand Test (see page 8). 9. Install fused pullout switch to energize AC power source to operator mechanism. Operating mechanism The spring operated mechanism uses solenoids to release charged opening and closing springs. The closing springs are charged by a motor-gear reduction drive. The closing operation charges the opening springs. The upper portion of the operating mechanism in the operator cabinet incorporates the tripping mechanism which includes the trip solenoid, mechanical linkages and associated switches. The lower portion of the mechanism incorporates the closing mechanism which includes the close solenoid, motor, gear reduction drive, clutch, closing springs, mechanical linkages and associated switches. The opening springs and the linkages to operate the interrupters are located under the head of the recloser. 7 MAINTENANCE INSTRUCTIONS MN8006EN October 07

The major components of the operating mechanism are easily accessible without need to remove the mechanism. However, if necessary, the complete operating mechanism can be removed from the operating cabinet as a unit. Mechanism removal. Remove fused pullout switch to de-energize AC power source to operator mechanism.. Make sure recloser contacts are open; manually operate mechanism, if necessary, until contact position indicator reads OPEN and closing spring status indicator reads SPRINGS DISCHARGED.. Remove screws attaching auxiliary switch to mechanism frame. Remove auxiliary switch.. Loosen operating bar turnbuckle assembly, inside interrupter housing, see Figure 0. Operating bar assembly 6. Turn operating bar clockwise 90 degrees to isengage roll pin from anti-bounce latch. 7. Unplug wiring harness from panel board on the back of the cabinet. 8. Remove trip reset knob and front plate, remove cotterpin to disconnect external trip pullring from threaded pin on trip link, Figure. Cotter pin Trip pullring Roll pin Turnbuckle assembly Figure 0. Turnbuckle assembly. Remove link pin that attaches operating mechanism to operating bar assembly, Figure. Figure. Removal of external trip pullring 9. Disconnect external quick-close pull hook by removing attaching stop nut, Figure. Operating bar assembly Link pin Spacer Stop nut Manual close lever External quick close pullring Figure. Attachment of external quick-close pullring Figure. Location of link pin MAINTENANCE INSTRUCTIONS MN8006EN October 07 8

0. Remove two 8 inch hex nuts and lockwashers from top of mechanism channel.. Remove inch hex nut lockwasher attaching bottom of channel to cabinet.. Remove inch hex head bolt and lockwasher attaching top of mechanism channel.. Maneuver complete mechanism assembly out of operator cabinet. Mechanism installation Installation of the operating mechanism is essentially the reverse of disassembly; however, two adjustments must be made after the mechanism is installed. External Quick-Close pullring adjustment. The stop nut that secures the external quick-close pullring must be adjusted to prevent over travel of the manual close lever assembly, refer to Figure.. From under the mechanism housing, pull quick-close lever down until linkage comes to its mechanical stop.. Adjust stop nut until the top edge of the manual close lever just contacts the spacer. Anti-bounce latch adjustment. The anti-bounce latch assembly must be properly adjusted to operate properly, refer to Figure.. Loosen operating bar turn-buckle.. Adjust turnbuckle to provide a inch gap between operating bar roll pin and the anti-bounce latch.. Secure turnbuckle. Anti-bounce latch assembly switch. The motor has permanently lubricated, sealed ballbearings that require no service. Periodically check motor brushes for wear or burning, replace as required. NNote: Brush replacement kits are available for both the 0- Vac and 0-Vac motors. The kit consists of two brushes and two brush caps. Motor replacement The universal drive motor must be replaced, as an assembly, if it become damaged or worn. To replace the motor proceed as follows, refer to Figure : CAUTION Do not attempt to replace the drive motor while recloser contacts are closed, or while operator springs are charged. If the operator assembly were to trip while hands are within operating linkage personal injury could result.. Remove fused pullout switch to de-energize AC power source to operator mechanism.. Make sure recloser contacts are open; manually operate mechanism until contact position indicator reads OPEN and closing spring status indicator reads SPRINGS DISCHARGED.. Cut motor leads, close to old motor.. Remove hardware securing motor and carefully remove from operator assembly.. Position replacement motor into operator assembly, engage motor shaft into coupling, secure with hardware removed. Apply Loctite # (blue) to screw threads prior to assembly. 6. Trim motor leads, leave sufficient length to splice new motor leads to old motor leads. 7. Slide shrink tube over motor leads, splice and solder leads. Shrink tubes over joints. 8. Install fused pullout switch to energize AC power source. gap Roll pin Operating bar turnbuckle assembly Drive motor hardware Figure. Anti-bounce latch adjustment Motor CAUTION This type of motor should NEVER be energized while disconnected from gear reduction unit. Uncontrolled motor speed will result when operated without load, excessive speed will damage motor. A universal series-type motor is used to charge the closing springs. The motor is energized from either a 0- or 0-Vac auxiliary power source, through a fused pullout Universal drive motor Motor leads Figure. Motor replacement 9 MAINTENANCE INSTRUCTIONS MN8006EN October 07

Brush replacement. Remove brush caps and carefully pull old brushes from motor.. Install new brushes, with cove positioned to cup over the commutator. CAUTION Do not use excessive force when replacing brush holder caps; excessive tightening may crack the caps.. Install brush caps to secure. Gear reduction unit The pinion gear at the opposite end of the motor shaft coupling engages a gear reduction train consisting of a first and second intermediate gear and the main gear. All gears are permanently lubricated to provide maintenance- free operation and prevent corrosion. Oil impregnated bronze bearings provide long wear life. Inspect all gear teeth and bearings carefully; disassemble the unit only when part replacement is necessary. Electrical components Electrical circuit components of the operating mechanism require no maintenance and should provide troublefree operation. If control circuit malfunction is indicated, check out the circuitry in the following order: WARNING Hazardous voltage. When checking the CT output of one phase, the output from the other two phases must be shorted. If the test circuit is energized while there is no load connected to the CT secondaries, dangerous voltages will be generated. Contact with high voltage can cause severe personal injury or death. T06.. Substitute another electronic control - known to be in working order. Follow the procedures in the electronic control service manual to test and repair the control.. Check the control cable for breaks or shorts.. Check the circuit components in the operating mechanism. Sensing current transformer tests The sensing transformers can be tested using the circuits shown in Figure 6. Connect all three phases of the recloser in series across a 00 ampere ac test supply and close the recloser with the manual closing crank. Ratio test for sensing-current transformers Refer to Figure 6, Ratio Test Circuit (A).. Energize 00 ampere test source.. Check current through control cable receptacle sockets K-G (Phase A), K-H (Phase B) and K-J (Phase C). For each sensing bushing CT checked, the milliammeter should indicate 00 milliamperes (ma) (0 ma when testing 000: ratio CTs) plus or minus ten percent.. A 00 ma reading verifies the 000: ratio (a 0 ma reading verifies the 000: ratio) of each current transformer. Be sure to allow for tolerances of metering equipment. De-energize test source and proceed with polarity test. Polarity test Refer to Figure 6, Polarity Test Circuit (B).. Connect sockets G, H and J of the control cable receptacle in series with jumper leads as indicated in Figure 7. The jumper leads connect the secondaries of the current transformers in parallel so that total output current, measured at points K and J, should be 00 ma, 0mA when testing 000: ratio CTs.. Energize the 00 ampere test source. A 00 ma reading (0mA when testing 000: ratio CTs) indicates correct polarity for all three sensing transformers. If the meter across K and J reads only 00 ma (0 ma when testing 000: ratio CTs), the polarity of one of the transformers is reversed. Check for uniform location of the polarity marks on all three transformers; reposition as necessary.. De-energize ac test current and remove jumper wires from receptacle sockets. MAINTENANCE INSTRUCTIONS MN8006EN October 07 0

Recloser contacts in closed position 00 AMP AC test circuit Test leads connecting phases in series Control cable receptacle sockets K K A MA A MA Sensing CT S G G MA B H C MA J Ratio test circuit (A) B H C J Polarity test circuit (B) Test leads connect bushing CT secondaries in parallels Figure 6. Test circuit for checking bushing current transformers Sensing-current transformer replacement To replace a damaged current sensing transformer proceed as follows, refer to Figure 7. Spacer Coil retainer plate Threaded spacer Washer Lockwasher Capscrew Sensing CT Figure 7. Current sensing transformer replacement. Remove bushing that passes through the current transformer that is to be replaced.. Label sensing current transformer leads. Use labeling in accordance with connection diagram. The X leads are white and the X leads are black.. Cut leads, on transformer side of the original splice, to disconnect current transformer.. Remove capscrews that secure current transformers Remove and discard damaged sensing CT; retain coil retainer plate. NNote: Sensing CTs are marked with a black spot to indicate polarity, when installing the replacement CT orient the black dot to match the dot on the other CTs that are already installed.. Install replacement CT, secure with hardware removed. 6. Trim CT leads as required. Slide shrink tube over each lead, splice connection and solder. Slide shrink tube over splice and apply heat to shrink. When splicing connections, refer to previous labeling to assure proper leads are connected before soldering. 7. Install bushing assembly. 8. Perform the ratio and polarity tests after replacement of any sensing CT to make sure they are properly installed. Control cable check With the cable removed at the control, use an ohm meter to check the continuity of each circuit through the connection at the operator cabinet up to the control terminal block. The connector pin sockets and the control terminal block are lettered correspondingly. Remove and replace each conductor at the control terminal block while checking. A zero reading will indicate continuity, an infinite reading indicates an open circuit. Continuity between terminals and unlike pin socket indicates a shorted circuit. Replace if cable is damaged. Control circuit components The operating sequence of the various circuit components is diagrammed in Figure 8. See Figures 9 and 0 for connection diagrams and wiring tables. A schematic MAINTENANCE INSTRUCTIONS MN8006EN October 07

diagram of recloser circuits is shown in Figure. MANUAL CLOSE SWITCH /MCS SPRING POSITION SWITCH (0 Vac) /SP CAM OPERATED SWITCH OPEN MOTOR CIRCUIT /aa MOTOR M OPEN CLOSED OPEN CLOSED OPEN CLOSED ENERGIZED 6 7 8 9 0 CLOSING SPRINGS DE-ENERGIZED CHARGED DISCHARGED SPRING POSITION OPEN SWITCH ( Vdc) /SP CLOSED b CONTACT TO OPEN CLOSED CLOSING CIRCUIT /bb CLOSED MANUAL TRIP AND OPEN RESET SWITCH /LS CLOSED CLOSING ENERGIZED SOLENOID COIL /CC DE-ENERGIZED MAIN OPEN CONTACTS a CONTACT TO OPEN TRIP COIL /a TRIP SOLENOID COIL /TC CLOSED OPEN CLOSED ENERGIZED DE-ENERGIZED a CONTACT TO OPEN OPEN TRIP SOLENOID COIL /a CLOSED AUXILIARY SWITCH OPEN a CONTACT AUXILIARY SWITCH b CONTACT CLOSED OPEN CLOSED 0 or 0 Vac APPLIED CLOSE SIGNAL OPEN SIGNAL NNote: Unit in OPEN position with closing springs discharged when auxiliary power is initially applied. (MANUAL CLOSE or TRIP pullrings are not operated.) Drawing shows operational sequence only; it does not have a scaled time base. Figure 8. Sequential operation of control circuit components in recloser MAINTENANCE INSTRUCTIONS MN8006EN October 07

a a D A S TB TB TC bb R V LS aa C M SP (0V) CC CH FU 0 SP (V) TB MCS TB R R AS D C CH FU 0 M R R R AUXILIARY SWITCH DIODES N09 SURGE CAPACITOR MECHANISM CABINET HEATER FUSE BOX MOTOR CONTROL RECEPTACLE RECLOSER RECEPTACLE AUXILIARY SWITCH RECEPTACLE a CONTACT TO OPEN a TRIP COIL a CONTACT TO OPEN a TRIP CIRCUIT SPRING POSITION SP SWITCH (Vdc) SPRING POSITION SP SWITCH (0 Vac) CLOSE MOTOR CIRCUIT CAM OPERATED SWITCH aa OPEN MOTOR CIRCUIT b CONTACT TO CLOSE bb CLOSING CIRCUIT TRIP COIL (SOLENOID) TC CLOSE COIL (SOLENOID) CC MANUAL CLOSE SWITCH MCS CONTACT FOR MANUAL LS LIMIT SWITCH - TRIP & RESET V VARISTOR Figure 9. Location and connection table of control components on operating mechanism MAINTENANCE INSTRUCTIONS MN8006EN October 07

XK XJ X X X X X MULTI-RATIO CT (ACCESSORY) X X X X X PHASE C 6 A B C D E E F G H J K L M N N P XK XH X X X X 00Ω 00Ω 00Ω X XK XG X X X X X PHASE B PHASE A RECEPTACLE AND PLUG R 6 7 8 9 0.K X X X X X X X X X X 6 7 8 9 0 LS SP "M" MCS 8 7 6 aa TC CC a a SP bb BATTERY CHARGER (ACCESSORY) K AUXILIARY SWITCH (ACCESSORY) "b" "a" "b" "a" "b" "a" "b" "a" 6 9 0 7 8 6 6 0 9 8 7 6 "TB" FU FRN 0 V.A.C. CUST. CONNECTION C V C V HEATERS MECH. CAB. FU FRN- CH CH IEH IEH HEATERS INTERR. ENCL. 6 GR X X X X X GR X X X X X GR X X X X X AUXILIARY SWITCH RECEPTACLE WIRING PIN NO. CONNECTED TO A TB- B TB- C TB- D TB- E TB- F TB-6 G TB-7 H TB-8 J TB-9 K TB-0 L TB- M TB- T GROUND RECLOSER CONTROL RECEPTACLE R GR X X X X X GR X X X X X GR X X X X X AUXILIARY SWITCH RECEPTACLE (ACCESSORY) R Figure 0. Connection diagram for other control components MAINTENANCE INSTRUCTIONS MN8006EN October 07

V.D.C. A TRIP CIRCUIT CLOSING CIRCUIT 6 a 8 7 SP ELECTRONIC CONTROL B C D TC N a F E bb LS CC TB H FU AMP TYPE FRN-R FU AMP TYPE FRN-R NC MCS 0 VAC MOTOR CLOSING CIRCUIT GND CABINET HEATERS CH CH.K.K IEH K FU AMP TYPE FRN-R K IEH ENCLOSURE HEATERS V V C C SP NC NO 6 aa H "M" TB FU AMP TYPE FRN-R Figure. Schematic diagram of recloser circuits MAINTENANCE INSTRUCTIONS MN8006EN October 07

Service parts list The service parts and hardware listed and illustrated include only those parts and assemblies usually furnished for repair or involved in the maintenance procedures described in this manual. Further breakdown of listed assemblies is not recommended. Dimensions of all common hardware parts have been carefully checked so that they may be locally acquired.the suffix letter of the character catalog number for common hardware parts codes the plating of the part: A - No plating; raw material H - Silver M - Black oxide Q - Cadmium + zinc + chromate Y - Zinc + chromate Z - Electro zinc + bronze irridite A hardware kit, Catalog No. KA89R, contains anassortment of roll pins, cotter pins, retaining rings, stopnuts, etc. common hardware parts used in Eaton s Cooper Power series reclosers that may not be readily locally available. To assure correct receipt of any part order, always include recloser type and serial number. Because of Eaton s continuous improvement policy, there may be instances where the parts furnished may not look exactly the same as the parts ordered. However, they will be completely interchangeable without any rework of the recloser. Prices of Replacement Parts, Section S80-0 Part No., lists recommended spare parts and prices for mostparts. Parts not listed in price list may still be available,consult your Eaton representative for price and availability. MAINTENANCE INSTRUCTIONS MN8006EN October 07 6

9 8 6 7 8 9 0 8 7 7 6 6 8 0 0 8 9 8 9 8 6 6 7 7 8 7 6 6 0 9 0 0 9 Figure. Bushings and Interrupters 7 MAINTENANCE INSTRUCTIONS MN8006EN October 07

Bushings and interrupter (Figure ) Item no. Description Catalog number - Bushing assembly,long lead (items thru ) - Bushing assembly, short lead (items,,, ) Bushing terminal assembly KAVSML 6 Upper bushing gasket KP090A7 6 Ceramic bushing KP09VS 6 Bushing rod, long KAVSML Bushing rod, short KAVSML 6 Bushing clamping ring KP066VS 6 7 Lower bushing gasket KP090A9 6 8 Bushing clamp KPVS 8 9 Hex nut, /8-6, stl K8806087A 8 0 Bushing rod clamp KP6VS 6 Cap screw, /8-6 x, bronze K70700A Lockwasher, med, /8, bronze K900807000A Hex nut, /8-6 bronze K880607A Connector current exchange and KA86VS bracket assembly (Includes items thru ) Machine screw, hex hd, /8-6 x -/, bronze K707A 6 Lockwasher, /8, med, stl K9008007000Z 7 Stationary clamping block KA77VS 8 Bottom plate KA00VS 9 Stationary bracket KA78VS 0 Roll pin, /6 x /, stl K97088700A Machine screw, hex hd, /- x, bronze K70000A Lockwasher, / med, bronze K9008000000A Machine screw, hex hd, /-0 x -/, stl K7000Q Washer, / med, stl K90000000Z Elastic stop nut, /-0, stl KP00A 6 Stringer assembly KAVS 6 7 Machine screw, hex hd, /8-6 x /, stl K700707Z 6 8 Lockwasher, /8, stl K9008007000Z 6 9 Elastic stop nut KP00A 6 0 Washer, /8, stl K900007000Z 7 Qty. per assy. Item no. Description Catalog number Qty. per assy. Vacuum interrupter VSA KA77VS VSA6 KA77VS VSA0/800 KA77VS Insulating barrier KP80VS Barrier kit KP0VS Cable clip Wire tie (used in place of cable clip above) K99907000A Machine screw, rd K78006A hd, #0- x /8, nylon 6 Hex nut, #0-, nylon K8000A 7 Machine screw, hex hd, /-0 x, stl K70000Q 6 8 Washer KP97VS 6 9 Belleville washer KP8A 0 Transfer bar KP96VS 6 Spherical disc KP9VS Elastic stop nut KP00A 6 Transfer rod and stop assembly KA70VS Stop KP96VS Washer KP090A09 6 Bushing KP88VS 7 Retaining ring KP0A 8 Bracket KP9VS 9 Spacer KP0A7 0 Lockwasher, / med, K900800000Z Nut, hex, /-0" K880000Q Sensing current transformer VSA, VSA6 000: ratio KA90M- VSA0/800 000: ratio KA90M- Plate KP6M 9 Cap screw, hex hd, /-0 x /, stl K70000Q Lockwasher, med, /, stl K900800000Z 6 Flat washer, /, stl K90000000Z 7 Threaded Spacer KP008A6 8 Spacer KP0A7 9 Nyliner KPA MAINTENANCE INSTRUCTIONS MN8006EN October 07 8

9 0 7 8 6 6 0 7 8 9 Figure. Interrupter cabinet 9 MAINTENANCE INSTRUCTIONS MN8006EN October 07

Interrupter Cabinet (Figure ) Item no. Description Catalog number Qty. per assy. Interrupter cabinet cover KA8VS Enclosure KA77VS Rear cover support KA78VS Cover and operating cabinet support KA79VS Side panel KA80VS900 6 Ventilating screen plug KP0A 7 Speed nut KP00A 8 Screw, self tapping, # x /, st stl K807007A 9 Machine screw, hex hd, /8-6 X, st stl K70700A 6 0 Hex nut, /8-6 K8800607Q 6 Item no. Description Catalog number Qty. per assy. Washer, /8, st stl K90007000A 6 Lock washer, /8 external tooth K90007000Z 6 Heater guard KP7CE Resistor, 000 ohms KP87VR Bracket KPNR 6 Machine screw, rd hd, #8- x 7/6, st stl K7080A 7 Lockwasher, #8 med, st stl K9008008000A 8 Washer, #0, brass K900000A 8 9 Nut, hex, #8-, st stl K880008A 0 Nylo Clip KP006A Washer, /, st stl K9000600A 8 7 6 7 0 9 6 8 9 7 6 8 8 0 Figure. Operating linkage assembly MAINTENANCE INSTRUCTIONS MN8006EN October 07 0

Operating linkage assembly (Figure ) Item no. Description Catalog number Qty. per assy. Connector and rod assembly KAVS Groove pin KP6A 6 Retaining ring, Type C, stl K970907000M 6 Groove pin KP6A 6 Spacer KP0A9 6 Link assembly KA6VS 7 Spacer KP0A0 6 8 Link assembly KAVS 9 Spacer KP0A Item no. Description Catalog number Qty. per assy. 0 Link KP00VS Spacer KP009A9 Groove pin KP6A7 Main operating spring KP09VS Spring retainer KP078VS Retaining ring, Type WA-8 K970907000M 6 Bolt, spring retainer KP0VS 7 Washer, /8, stl K900007000Z 6 7 0 9 8 Section A-A 0 8 6 7 0 9 0 Section A-A HEAT ON OFF 6 AUTOMATIC RECLOSURE RVSO 8 7 JKH JKH GHJGYS ZI GFJ JGHFDYJ H HGVDIUDJH ; JH I]HJF UUT8YGGIO DDJD GJD IFG HGFKGKU VKUY;;KQ JD FHHZ YHSD GJ JXSF JGJ G MGRAW EDISON 9 9 8 0 7 6 Figure. Operator cabinet MAINTENANCE INSTRUCTIONS MN8006EN October 07

Operator cabinet (Figure ) Item no. Description Catalog number Qty. per assy. Cabinet assembly, complete KAVS (includes items thru ) Cabinet only KAVSM Gasket KP08A7 Latch assembly KAVS Machine screw, flat hd, #0- x /, stl K760007Z Spacer KP006A 6 Flat washer K90000000Z 7 Bushing KP0A 8 Handle assembly KPVS 9 Vent plug KP0A 0 Window KP0M Speed nut KP00A 8 Gasket KP08A9 Machine screw, hex K70000A hd,/- x, st stl Washer KP090A0 Nut, hex, /-, st stl K88000A 6 Spacer KP0A 7 Fuse clip KP09ME 8 Fuse KP07A 9 Nut, hex, #8-, st stl K880008A 0 Lockwasher, #8, st stl K9008008000A Heater assembly for Operator cabinet. KVSOVA Resistor, 00 ohm, 0 watt, IRC K99990008A Toggle switch, DPST K99990009A Decal KP07VR Fuse holder KP07A Fuse, Type AGC, A-0V KP07A Item no. Description Catalog number Qty. per assy. Nut, hex, #8-, st stl K880008A Lockwasher, #8, med, st stl K9008008000A Spring KPVSM Elastic stop nut KP00A6 6 Washer KP090A9 7 Machine screw, rd hd, #6- x /8, brass K70607A 8 Flat washer, #6, st stl K900006000A 9 Spacer KP07A 0 Lockwasher, /, med, st stl K900800000A Crank assembly KAVSM Spacer KP0A6 Hex nut, /-0, stl K880000Q Lockwasher, /, med, stl K900800000Z THE FOLLOWING PARTS ARE APPLICABLE TO THE BCT ACCESSORY ONLY Terminal block KP0A 6 Machine screw, rd hd, #8- x /, brass K70800A 7 Machine screw, rd hd, #0- x -/8, stl K70006A 6 8 Lockwasher, ext tooth, #0, stl K90000000Z 6 9 Hex nut, #0-, stl K880000Z 6 0 Panel KP098VSM Machine screw, K7000Z rd hd, /-0 x /, stl Lockwasher, /, split, med, stl K900800000Z Hex nut, /-0, stl K880000Z MAINTENANCE INSTRUCTIONS MN8006EN October 07

8 9 8 6 7 A B C D E F G H J K L M N O P 0 6 6 7 8 9 0 7 0 ON 6 6 0 6 OFF 9 Figure 6. Terminal panel 7 8 9 MAINTENANCE INSTRUCTIONS MN8006EN October 07

Terminal Panel (Figure 6) Item no. Description Catalog number Qty. per assy. Terminal strip KP0A6 Machine screw, rd hd, #6- x /8, stl K70606A Lockwasher, #6, external tooth, stl K90006000A Hex nut, #6-, stl K880006A Marker strip KP076A 6 Marker strip KP0A6 7 Capacitor assembly KA6VS 8 Capacitor KA8CE 9 Silicon diode KP0A9 0 Resistor KP0A Rivet, 0.6 x 9/, stl K9080008Z 6 Flat washer, #6, brass K90000A 6 Bracket and socket assembly KA89VSM Machine screw, K7007A rd hd #0- x /8, stl Lockwasher, #0 external tooth, stl K9000000A 6 Hex nut, #0-, stl K88000A 7 Capacitor assembly KA96M 8 Machine screw, K70807A rd hd, #8- x /8, stl 9 Lockwasher, #8, external tooth, stl K90008000A Item no. Description Catalog number Qty. per assy. 0 Hex nut, #8-, stl K880008A Fuse box KP6A Machine screw, K707Q rd hd, #0- x -/8 Tapping block KP87VS Strap KP86VS Machine screw, K7006A rd hd, #0- x /8 6 Lockwasher, #0, stl K900800000A 7 Fuse, Bussmann Type FRN-R KP07A 8 Panel Board KP077VSM 9 Spacer KP0A 0 Spacer KP00A Hex nut, #0-, brass K88000A Lockwasher, #0, med, brass K9008000000A Flat washer, #0, brass K900000A Control cable assembly KA06VS Terminal block KP0A7 6 Label KPVSM 7 Cable receptacle KP06A 8 Screw, self tapping, K70607A #6- x /8 9 Lock washer, #6, medium, stl K9008006000A MAINTENANCE INSTRUCTIONS MN8006EN October 07

ELECTRONIC CONTROL MUST USE TYPE MDQ-. FUSE ONLY Type VSA, VSA6 and VSA0/800 maintenance instructions RESET 9 0 MANUAL CLOSE TRIP SPRINGS DISCHARGED SPRINGS CHARGED 7 8 6 TYPE"VSA" 6 Figure 7. Decals and Labels MAINTENANCE INSTRUCTIONS MN8006EN October 07