ASSA ABLOY. 7100SZ Series SafeZone External Sensor. Installation and Instruction Manual ASSA ABLOY. Patent Pending

Similar documents
7100SZ Series SafeZone Installation and Instruction Manual

Power drill Center punch Wire stripper

ASSA ABLOY Series Power Operator Installation and Instruction ASSA Manual ABLOY ASSA ABLOY

QUADSCAN User s Guide Door Mounted Presence sensor

USERS GUIDE LO-21U LOCKOUT RELAY

5600 Series Power Operator Installation and Instruction Manual

ASSA ABLOY Series Power Operator Installation and Instruction ASSA Manual ABLOY ASSA ABLOY

ASSA ABLOY Series Multi-Point Hold Open Installation and Instruction Manual

USERS GUIDE BODYGUARD III SMR PRESENCE SENSOR

BODYGUARD III-C USER S GUIDE

5700 Series Power Operator Stop (Push) Side Mount Installation and Instruction

Overview. Chassis Packaging

ASSA ABLOY MPI (Infinite Hold Open Range) Support Unit Models. Multi-Point Electromechanical Overhead Concealed Closer Holder Releasing Device

5700 Series Power Operator Hinge (Pull) Side Mount Installation and Instruction ASSA Manual ABLOY

Requirements LEO Power Operator Installation Instructions Patents: 5,881,497; 7,316,096; 7,484,333 CAUTION CAUTION WARNING

Alliance Towel Dispensing System. Operation Manual

Installation Instructions Series 78-B/FHA Hold Open

Series 2003T. Belt Drive Telescoping Slide Door INSTALLATION INSTRUCTIONS. To be used with H210 C2150 Ver.10 Control Setup Instructions

Multi-point closer/holder with motion sensor 7100SZ DOOR CLOSER CATALOG

Requirements LEO Power Operator Installation Instructions Patents: 5,881,497; 7,316,096; 7,484,333 CAUTION CAUTION WARNING

INSTALLATION INSTRUCTIONS

7100SZ SERIES. Multi-Point Closer/Holder with Motion Sensor

A-dec O Clock Delivery System

Reproduction or other use of this Manual, without the express written consent of Vulcan, is prohibited.

DOOR SAFETY KIT INSTALLATION MANUAL

A-dec 541 Delivery System and 545 Assistant s Instrumentation

MA-5200 Series MA-5300 Series

LED Downlight Ceiling Fixtures

SIGNETMARINE. Livewell Bait Pump Alarm. No Dead Bait.

X20020 INFRESCO P 4kW Issue 4 User manual Date 16/02/16. Page 1 of 9 KEY FEATURES

SKD U Electronic Valve Actuator

LED Reference for Circuit Board

7100SZ Series SafeZone. Multi-Point Closer/Holder with Motion Sensor

7100SZ Series SafeZone. Multi-Point Closer/Holder with Motion Sensor

ENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE. GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA , USA MEMBER

MP-5400 Series. Application. Features. Applicable Literature. Electronic Positive Positioning Hydraulic Actuator General Instructions

Plasma Display Electric Pop-Up Lift (PUL)

ANTI-LOCK BRAKE SYSTEM

Automotive: Lightbars

TRAC-Station BT Installation Instructions

Removable Applied Panel Mounting System

SKD U Electronic Valve Actuator

Package Contents. Mounting Hardware

Page 1 of 4 Model: BTL4E-004 V2.0 Pulsar Electronic LED Turn Signal Flasher Unit Installation & Operation Instructions:

4600 Heavy Duty Designer Deadlatch Handles With 4300, 4500, and 4900 Series Deadlatches

56- Electric Latch Retraction Exit Devices Installation and Wiring Instructions

Installation Instructions

C50254A PH3 AIR INTAKE SHUT-OFF VALVE DODGE 6.7L CUMMINS WITH POWERGUARD SMART OVERSPEED LIMITER

M670/M680BD MAGNALOCK SERIES Installation Instructions

2904 Power Supply Installation Instructions I-EA00041

Dodge Engineering & Controls, Inc. Toll Free (877) Fax: (978) EN44 and EN88 Non-Spring Return Electronic Actuators

VLP-UL-KIT INSTALLATION INSTRUCTIONS. The VLP-UL-KIT for 36 or 48 is a field installable solenoid latch pullback for the Von Duprin 33/35 &

ACSI MODEL 1406BB-04-AO POWER SUPPLY INSTALLATION INSTRUCTIONS

U00X ULTRASONIC LEVEL SWITCH. Ultrasonic Liquid Level Switches INSTALLATION AND OPERATIONS MANUAL. For Models: U002, U003 & U004

Product Manual (Revision C) Original Instructions. Air/Fuel Ratio Control. Installation and Operation Manual

Not Included. Rear Half Harness

SLIDING DOOR OPERATOR INSTRUCTION MANUAL

Installing the Switch Chassis

Dycon D2430 EN54-4 Fire Alarm Power Supply Series

Installation and Operating Manual

Full-featured operator with slim profile for moderate to high traffic applications LOW ENERGY OPERATOR CATALOG

TC26-B Vehicle Sensor

GCU-10. Automatic Engine Control Unit Operators Manual

Installation Instructions 1812 Folder Disk Clutch Retrofit Kit Martin Yale #WRA

Plasma Display Electric Ceiling Lifts

MODEL 422 Submersible Pump Controller

ELECRAFT KX3 Application Note

Installation Instructions

Techcon Systems TS500R-PC Controller For Positive Displacement PC Pump

USE AND CARE GUIDE DUALCHECK CIRCUIT TESTER

Dycon D1532SM. EN50131/PD6662 Grade 3, 12V 2A Power Supply. Technical Description Installation and Operating Manual DYCON POWER SOLUTIONS LTD

ANTI-LOCK BRAKE SYSTEM - REAR WHEEL

ATP-2040 Electric Damper Actuator/Transmitter

Model 550 Series Vibration Switches

Type 2000 Transducer Product Instructions

Validator and Control Board Update Instructions for BC1

INSTALLATION INSTRUCTIONS

Sure-Lites. Installation Instructions for the Sure-Lites UX Self Powered Exit Sign with Self Diagnostics. IB505037EN Important Safeguards

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS

Installation Instructions

INSTALLATION INSTRUCTIONS

INSTRUCTION SHEET FOR SIGNALMASTER MODELS SM518A AND SM428A

A-dec 570L Dental Light on a Non-DCS System INSTALLATION GUIDE

Installation Manual. Mixing Box Control Systems Installation, Operation, and Maintenance Manual. 605 Shiloh Road Plano, Texas

RoadComfort TM. Installation Manual Vibration Massage & Heat

MP-5200 Series. Application. Features. Applicable Literature. Electronic Hydraulic Actuator General Instructions

INSTALLATION INSTRUCTIONS

Installation Instructions

PIRANHA 5 INSTALLATION GUIDE

INSTALLATION INSTRUCTIONS

SCCP PWM Charge Controller/Load Manager Owner s Manual

BE SURE POWER IS DISCONNECTED PRIOR TO INSALLATION! FOLLOW NATIONAL, STATE, AND LOCAL CODES! READ THESE INSTRUCTIONS ENTIRELY BEFORE INSTALLATION!

Automotive: Lightheads

AutoSteer Installation Guide

HANDLING MECHANICAL INSTALLATION

B21 Series BASOTROL Gas Valve

ASSA ABLOY. Installation Instructions. MP9800 Series Multi-Point Lock with MELR Option (Electric Latch Retraction)

Slope Detector IV Installation Instructions

Installation, Operation and Maintenance Manual

Transcription:

700SZ Series SafeZone External Sensor Installation and Instruction Manual Patent Pending.76 (0). (79.8) Tools required:.0 (0.8) Allen wrench set (inch) Flat blade screwdriver (potentiometer & terminal size) Screwdriver (Phillips size ) Tape rule Power drill Center punch Wire stripper Table of Contents: Mechanical Installation Wiring Diagrams Sensor Settings Sensing Field Settings Trouble Shooting Specifications 6 Safety Precautions 6 Copyright 00, 0 Yale Security Inc., an Group company. All rights reserved.

Opening the sensor Mechanical Installation. Apply adhesive backed template, supplied with sensor, to appropriate surface and aligned with centerline of door on side of opening opposite from SafeZone Mount.. Drill two /8" holes for mounting.. Drill one /" hole for cable access.. Insert mounting screws into mount surface, but do not screw them fully in.. Route wiring through backplate. MOUNTING TEMPLATE / HOLE THEN INSERT CABLE PLACE TEMPLATE AT LEASE ABOVE BOTTOM OF HEADER 6. Mount sensor backplate and tighten screws. 7. Complete wiring connections and sensor setup and testing. 8. Secure sensor cover to backplate. *.0" Frame Face MOUNTING TEMPLATE PLACE TEMPLATE AT LEASE ABOVE / HOLE BOTTOM OF HEADER THEN INSERT CABLE *.0" Min. Above Frame Face 0'-0" Max height Above floor surface Electrical Cable * Note: If frame face is.0" or greater, Sensor can be mounted on frame face. C L Of Door See page for Wiring Diagrams See page for Sensor Adjustments For optional cable routing, notch cover in one of the areas shown. Copyright 00, 0 Yale Security Inc., an Group company. All rights reserved.

Wiring Diagram (Wiring external sensor to SafeZone Unit) 0VAC External Sensor Terminal Connection (Red) VDC (+) (Black) VDC (-) (White) Relay Common (Green) Relay N.O. Relay N.C. Note: Input power tolerance is +/- 0% for AC, and -0% to +0% for DC power. Wiring Diagram (Wiring external sensor to SafeZone Unit) VDC External Sensor Red Jumper Wire Black Green L N G SafeZone Unit 0VAC Closer Solenoid Red Jumper Wire Black Green VDC (-) VDC (+) SafeZone Unit VDC Closer Solenoid Copyright 00, 0 Yale Security Inc., an Group company. All rights reserved.

Sensor Settings Terminal Block Hold Time Buttons Wire Knockouts (Inside Cover) Cover removal slot Increase (+) Decrease (-) LED Wire Passage Hold Time Lateral and Angular Antenna Adjustments Planner Antenna (Narrow) Hold open time is defined as the amount of time the door will remain open AFTER movement in opening is no longer detected. Front Cover Default Factory Settings: Sensitivity Hold Time 0 seconds Immunity Detection Mode (Bidirectional) Door Control Mode Setting Hold Open Time: Press and release the Increase (+) or decrease (-) buttons until desired setting is achieved. Reset Hold Time to Default: Holding both buttons depressed simultaneously for seconds will set unit at default hold time of 0 seconds. Setting Time (Seconds) 0 0. 6 7 8 (Default) 0 6 7 6 8 8 9 0 Setting - Setting -6 Setting 7-9 Recommended Hold Time Settings Sensitivity Setting Sensitivity is factory set at setting #. The sensitivity range is (0-9). This setting can be adjusted along with other advanced settings when using the optional remote. Optional remote for advanced setting. List number 700REM Copyright 00, 0 Yale Security Inc., an Group company. All rights reserved.

Sensing Field Adjustments The position of the sensing field is determined by the vertical and lateral angle of the antenna. Vertical Angle Adjustments Lateral Angle Adjustments 0º 0º º - + Sensing field as close to the door as possible: Antenna is set at the position of 0 Sensing field close to the door: Antenna is set at the position of 0 Sensing field far from the door: Antenna is set at the position of Nominal Detection Pattern with Sensor Set as follows: Mounting Height: 7'-" Sensitivity: (factory default) Immunity: (factory default) Direction Mode: (Bi-Directional; factory default) Door Control: (factory default) Vertical Tilt: 0 Lateral Tilt: 0 Altering the lateral tilt angle will shift the detection pattern left or right of center. Note: Always walk the opening during senor adjustment to confirm the detection pattern is adequate for the opening and application. Adjusted hole open times as required for application. See page for hold open time settings. " 6" 0 6" " 0 6" " 8" Troubleshooting SYMPTOMS PROBABLE CAUSE CORRECTIVE Red LED does not light up. (No power to sensor) Power switch is off. Loose wire connection. ACTION Turn power switch to ON position. Inspect wiring for loose connections. Door Stops several times in the same cycle without sensing presence in the door way. Door not closing when cover installed. Sensitivity is set too high Eye is sensing the closer cover. Change sensitivity setting using optional remote. Adjust the sensing field away from cover edge. (See Sensing Field Adjustments above. Copyright 00, 0 Yale Security Inc., an Group company. All rights reserved.

SafeZone Sensor Technical Specifications DESCRIPTION SPECIFICATION Frequency:. GHz Suppl y voltage: VDC: -0% / +0%: Mounting height: Normal: 7 ; Maximum: 0-0 Tilt angle: 0 to 90 vertical - to + lateral Detection area: Wide Narrow ft (W) x 6.ft (D) 6.ft (W) x 8.ft (D) (supplied as optional) Minimum detection speed: in/sec. (measured in axis) Power consumption: < W Standard output relay: Max contact voltage Max contact current Max switching power 60 VDC / VAC A (resistive) 0W (DC) / 60VA (AC) Hold time: 0. sec. to 9 sec. (adjustable) Temperature range: - F to F Dimensions:.7in (W) x.in (H) x.0in (D) Weight: 0.lbs Material: ABS Safety Precautions Shut off all power going to the header before attempting any wiring procedures. Maintain a clean & safe environment when working in public areas. Constantly be aware of pedestrian traffic around the door area. Always stop pedestrian traffic through the doorway when performing tests that may result in unexpected reactions by the door. Always check placement of all wiring and components before pow ering up to ensure that moving door parts will not catch an y wires and cause damage to equipment. Ensure compliance with all applicable safet y standards upon completion of installation. ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS Circuit board components are vulnerable to damage by electrostatic discharge (ESD). ESD can cause immediate or subtle damage to sensitive electronic parts. An electrostatic charge can build up on the human body and then discharge when you touch a board. A discharge can be produced when walking across a carpet and touching a board, for example. Before handling any board, make sure you dissipate your body s charge. CAUTION: In the event a unit needs to be opened, observe the following precautions. Ground yourself by touching a conductive surface of the door or other element connected to common earth ground to discharge the static electricity present in your body. Avoid walking around while replacing items inside the case, especially if you are on carpet or during conditions of low temperature and low humidity. Handle the board by the edges only to avoid touching electronic components. Store a loose board in an anti-static bag. 000 Highway 7 East Monroe, NC 8 Tel: (877)- 97- Fax: (800)-8-096 www.nortondoorcontrols.com Copyright 00, 0 Yale Security Inc., an Group company. All rights reserved. 6