Development of Uninterruptible Power Supply SANUPS A11J Three-phase, Four-wire Model

Similar documents
Development of the Small-Capacity UPS SANUPS A11K Series

Development of the SANUPS P73K Power Conditioner with Peak Power Cut Function

Development of the Single Phase PV Inverter SANUPS P61A

Development of Small-capacity OFF-LINE UPS

Development of the 3-phase PV Inverter SANUPS P83D

Technology that Evolves in Line with Market Changes

High Air Flow Fan San Ace 60 G Type

.3 Section Waste Management and Disposal.

Technology from the New Product SANUPS K for a Smart Grid Society

Development of Power Conditioner with a Lithium Ion Battery

TECHNICAL DATA SHEET KVA UPS Systemss

POWER kva

POWER kva

gimagination at work Technical data sheet Uninterruptible Power Supply LP Series 6 & 10 kva GE Digital Energy

Green Power 2.0 MASTERYS GP

Development of the Regenerative Power Compensation Device SANUPS K23A (R Type)

Hybrid UPS Saves Energy and Achieves High Reliability. Output capacity. 3 kva. 2 kva. Output capacity. 2.1kW. 1.4kW

POWER kva Nominal output power (Cos φ0,8) kva Nominal output power (Cos φ1,0) kw >88 Efficiency (AC AC)

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS

MASTERYS IP+ 10 to 80 kva

TECHNICAL DATA SHEET INFINITY kva 3Ph(in) 3Ph(out)

KEOR HP. THREE-PHASE UPS from 100 to 800 kva GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

SANUPS. Non Toxic Lead-Acid Batteries Online UPS. Maintenance-free for 10 Years. Compact and Lightweight. Constant, Stable-Quality Power Supply

KEOR HP. THREE-PHASE UPS from 100 to 800 kva GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

MEGALINE UPS MODULAR SINGLE-PHASE from 1250 to VA

Technical data sheets

HAIRF UPS. X5 Series KVA

UPS Sentry HPS. power supply sources - isolation transformers and generators over less sophisticated power systems.

Achieves a high-efficiency conversion of 94% despite being isolated type through digital control

TECHNICAL DATA SHEET B8033FXS kva 3Ph(In) 3Ph(Out)

S2000 PRODUCT RANGE. Ultra compact

TECHNICAL DATA SHEET B8031 FXS kva 3Ph(In) 1Ph(Out)

MKN-DSP SERIES - THREE PHASE

DELPHYS GP. Green Power 2.0 range 160 to 1000 kva/kw

UPS5000-E (25-75 kva) Series

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

UPS UNINTERRUPTIBLE POWER SUPPLY GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

Liebert NXC. 10kVA - 60kVA. Compact, Efficient, and Reliable Power Solution

D Series: UPS UPTO - 300KVA - Three / Three Phase

PowerValue 11/31 T kva

Expanding Application of FRENIC-Lift Series for Elevators

Development of Utility Interactive Inverter for Photovoltaic Power System "PMB"

Technical Data Sheets

Master Plus kva

Novel High Efficiency UPS System

MGE TM Galaxy TM 7000

Technical data sheet VH UL. Digital Energy Uninterruptible Power Supply. GE Digital Energy Power Quality

E-15 Uninterruptible Power Systems (UPS)

E-15 Uninterruptible Power Systems (UPS)

kVA. Liebert NX. Enterprise-Scale UPS Protection For Medium And Large Data Centers

Symmetra PX 96/160. Scalable from 16 kw to 160 kw Modular, scalable, high-efficiency power protection for data centers

APC Smart-UPS. GUIDE SPECIFICATIONS FOR 1000VA & 2000VA Smart-UPS 230VAC Uninterruptible Power Supply

ConceptpowerTM Modular kVA

Master DIALOG INDUSTRY RANGE

Technical Data Sheets

MGE TM Galaxy TM 7000 GFC

Control System for a Diesel Generator and UPS

Counter Rotating Fan San Ace 92 9CRA type

POWER+ PREMIUM CBS. BS-EN Emergency electrical installations Electric power systems Emergency lighting Escape lighting

Technical Data Sheets

G V Series UNINTERRUPTIBLE POWER SYSTEMS. Phone: Fax: Web:

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

Low Power Consumption Fan 60 mm Sq. 10 mm Thick San Ace 60 9GA Type

SmartOnline SVTX Series 3-Phase 380/400/415V 20kVA 18kW On-Line Double-Conversion UPS, Tower, Extended Run, SNMP Option

Technical Data Sheets

PARALLEL PROCESSING UPS E33A

High-voltage Direct Inverter Applied to Induced Draft Fan Motor at Takehara Thermal Power Station No. 3 of Electric Power Development Co., Ltd.

Series. On-line, Single-phase Parallel Redundant UPS System. 6 and 10 kva Rack Mount. Your Tailored Power Solutions Provider TM

TELECOM- MUNICATIONS DEVICES INDUSTRIAL EMERGENCY DEVICES. (Servers Farms, ISP/ASP/POP)

EFFEKTA Power Supplies

Three Phase UPS Systems Range: 10 to 500kVA

Technical Data Sheets

Static frequency converter couples US paper mill s 25-Hz and 60-Hz electricity grids

Model ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase

Liebert APM UPS. For a 30 to 150 kva / kw (50 or 60Hz) Modular Digital Uninterruptible Power Supply (UPS) System. V nd February 2010

INDUSTRIAL PROCESSES TELECOM- MUNICATIONS DEVICES EMERGENCY DEVICES INDUSTRIAL

Est FlexiPower Mini UPS FPX Mini kVA

Master MPS. Highlights kva kva. Three-phase/Three-phase. Three-phase/Single-phase

TELECOM- MUNICATIONS DEVICES INDUSTRIAL EMERGENCY DEVICES. (Servers Farms, ISP/ASP/POP)

Smart-UPS VT APC Smart-UPS VT 30kVA 208V w/4 Batt. Modules, Start-Up 5X8, Internal Maintenance Bypass

3ph UPS NS3000 series kVA

Powerware Master Modbus

Symmetra PX 250/500. Scalable from 100 kva kw to 500 kw, parallel capable up to 2,000 kw

Regenerative Utility Simulator for Grid-Tied Inverters

Eaton 93PS 8-40kW UPS Technical Specification Manufacturer s declaration in accordance with IEC

Three-phase UPS system. DPA UPScale ST kw Best-in-class modular UPS for maximum availability

Development of Higher-voltage Direct Current Power Feeding System for ICT Equipment

Uninterruptible Power System

Features and Benefits

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

The Master of IEEE Projects. LeMenizInfotech. 36, 100 Feet Road, Natesan Nagar, Near Indira Gandhi Statue, Pondicherry

» Sophisticated» Reliable» Intelligent

Technical Data Sheet. Uninterruptible Power Supply. Digital Energy. imagination at work

Series. Full Three Year Warranty. On-line, Single-phase Parallel Redundant UPS System. 6 and 10 kva Tower. Your Tailored Power Solutions Provider TM

TECHNICAL SPECIFICATIONS

User Manual 1KVA-5KVA INVERTER / CHARGER

1.1 GENERAL CHARACTERISTICS

SUPREME kva three-phase/single-phase 10-80kVA three-phase/three-phase

Liebert. FP 50Z kva

Transcription:

New Products Introduction Development of Uninterruptible Power Supply SANUPS A11J Three-phase, Four-wire Model Hideaki Matsuo Narumi Yanagisawa Hiroyuki Hanaoka Masahiko Nagai Yoshinori Kaneko Makoto Kitazawa Hirofumi Kimura 1. Introduction Economic globalization is prevalent across the globe, however the economic development of Southeast Asia in particular is attracting much attention. This region was formerly a world production base, but population growth and industrial development has given way to an increase in middle-class, resulting in the region maturing into a major market. Many Japanese companies have established themselves in this region and industrial infrastructure, in particular power infrastructure as the foundation of corporate activities, is a key topic. As such there are high expectations of the demand for uninter r uptible power supply (hereinafter UPS ) will be grown. Up until now, Sanyo Denki has sold the single-phase, two-wire 5 kva to 20 kva small capacity UPS SANUPS A11J series to overseas buyers, however foreseeing an expansion in demand for the mid-capacity range in the Southeast Asian region, we have added a three-phase, fourwire 15 kva to 45 kva model to this series. This document introduces the newly developed SANUPS A11J series, three-phase, four-wire 15 kva to 45 kva model. 2. Background of the Development In general, AC power of 15 kva or more adopts the three-phase method of power supply. In Japan, most three-phase AC systems use the three-phase, three-wire system to supply power along three power wires. This is an economical method and has a large power supply capacity per wire. However, most indoor three-phase AC systems used in overseas adopt the three-phase, four-wire method. Powerreceiving equipment of buildings, etc., receive high voltage three-phase, three-wire power, then connect a secondary winding of a transformer in a Y connection and draw a neutral wire from a neutral point to become a three-phase, four-wire method. The three-phase, four-wire line voltage becomes magnified by 3, and has the advantage of being able to use both the interline (three-phase) and interphase (singlephase) voltages. In Southeast Asia, voltages such as 380 V / 220 V (three-phase/single-phase) are used for power distribution of both three-phase power and single-phase lights. Due to the differences in three-phase AC systems, the three-phase, three-wire UPS for the Japanese domestic market must support not only different voltages, but also different power feeding systems, hence cannot be used overseas with the current specifications. As such, Sanyo Denki has reapplied our single-phase technology from the current SANUPS A11J series, and developed a new product in a short timeframe in order to apply a three-phase, four-wire UPS product on the market at an early stage. The three-phase, four-wire model of the SANUPS A11J series supports the differences in power feeding methods by making a Y connection for 3 single-phase UPS units using a common neutral wire, as described above. 3. Product Overview The three-phase, four-wire model of the SANUPS A11J series was developed for server and network equipment application. This model comprises of an inverter unit, current collector and battery unit and is designed for installation on an EIA standard 19 inch rack (hereinafter referred to as rack). The current SANUPS A11J series uses the singlephase 5 kva inverter as the base unit, and stacks four units in parallel to enable construction of a single-phase UPS with a maximum of 20 kva. For the newly developed three-phase, four-wire model, a single-phase, 5 kva to 15 kva inverter is arranged on 29 SANYO DENKI Technical Report No.38 Nov. 2014

each of the three-phases (R, S, T) to enable construction of a three-phase, four-wire UPS with a maximum of 45 kva. Fig. 1 shows a schematic for the inverter. R Unit 19-inch rack Load equipment R S Unit R Unit 5 k-15 kva Server and network equipment T Unit Neutral point (N) S Unit 5 k-15 kva T Unit 5 k-15 kva T S N Collector unit Fig. 1: Schematic for the inverter The circuit configuration adopts the double-conversion method that puts the power supply quality first, and it achieves high efficiency while using the CVCF (Constant Voltage Constant Frequency) method that is not affected by input voltage or input frequency. By selecting I/O voltage from phase voltages of 220 V, 230 V and 240 V, it is possible to set line voltage at 380 V, 398 V or 415 V, thus supporting the power source environments of Asia and Europe. Also, the operation panel uses an LCD display, providing the device with an easy-to-use user interface. Fig. 2 shows a front view when the new model is installed on a rack and Fig. 3 shows its back view. Fig. 4 shows an external view of the inverter unit with an operation panel, and Fig. 5 shows an external view of the inverter unit without an operation panel. Fig. 2: Front view when installed on a rack (15 kva to 45 kva) R Unit S Unit T Unit 19-inch rack Collector unit Fig. 3: Back view when installed on rack (15 kva to 45 kva) SANYO DENKI Technical Report No.38 Nov. 2014 30

Fig. 4: ith an operation panel (single-phase 5 kva to 15 kva) output capacity in regards to load capacity for at least 1 unit (5 kva), even in the unlikely event of an error occurring on the unit, the remaining error-free units would continue inverter power feeding, thus providing high reliability. This function was also adhered in the new model and if the inverter units connected to each phases have enough leeway to cover the inverters installed on each phase (5 kva) against the load capacity, it would be possible to continue inverter power feeding with the remaining errorfree units even in the case of an error or maintenance on one unit. Moreover, the inverter of this unit has eliminated the common wire in order to acquire synchronization of the voltage phases during parallel operation and secures a high reliability which is not dependent on the reliability of the common portion. Fig. 5: ithout an operation panel (single-phase 5 kva to 15 kva) 4.4 management function In order to reliably provide backup power from a battery during a power outage, the self-diagnosis function is included to automatically test the battery. Furthermore, a variety of battery management functions, including battery life warning, estimated battery operation time, battery charging rate, and estimated backup time, are included in order to improve reliability. 4. Features 4.1 High efficiency By adopting a three-level inverter in the DC/AC conversion circuit, it is possible to achieve an efficiency of 93% or higher with a single-phase 5 kva inverter. This efficiency enables the device to reduce running costs and contribute to energy saving. 4.2 Output power factor 0.9 In recent years, many types of control power supplies built into servers have gained functions to compensate for the power factor of the input current. This tends to raise the load power factor. In order to handle this situation, the new model has achieved an output power factor of 0.9. This makes it possible to feed power with leeway in the load device with an increasingly higher input power factor. 4.3 High reliability by parallel redundant operation In the case of the current SANUPS A11J series, 5 kva base units can be stacked in parallel up until four units. Because of this, for example if there was leeway in the 4.5 Weight reduction In this development, a three-phase, mid-capacity UPS was separated into an inverter unit, current collector and battery unit, forming a structure able to be installed on generalized racks. Moreover, the inverter unit is equipped an inverter module, while the battery unit is equipped with a battery module, therefore they can both be divided into blocks and have successfully achieved weight reduction as individual devices. Reducing weight on the new model has lowered costs associated with transporting the unit to the installation location compared with general mid-capacity UPS. Also, when the unit is delivered, a mixed delivery service can be used, consolidated cargo instead of charter service. 4.6 Improved maintainability By modularizing the inverter and battery portions to modules, the maintainability of the device including replacement and so forth has significantly improved. Fig. 6 shows an external view of the inverter module, Fig. 7 shows an example of inverter module installation and Fig. 8 shows an example of battery module installation. Each module is a plug-in system and during parallel 31 SANYO DENKI Technical Report No.38 Nov. 2014

redundant operation, even in the unlikely event of an error occurring, inverter power feeding will continue as per normal, allowing speedy replacement and high availability. Moreover, there is a built-in maintenance by-pass circuit, making it possible to perform maintenance and replace modules while continuing power feeding from utility power. The mass of both the inverter module and battery module are kept under 18 kg, reducing the risk of maintenance engineers injuring themselves during their tasks. 4.7 Operation panel The operation panel has also been modularized and can be removed. Fig. 9 shows an external view of the operation panel. This panel can be connected to any inverter unit. The display is a 16 digit x 2 line LCD, displaying information on equipment status, measurements etc. clearly. Fig. 9: Operation panel Fig. 6: Inverter module (single-phase 5 kva) Inverter module Fig. 7: Example of inverter module installation 4.8 Network compatibility The UPS management software, SANUPS SOFTWARE and the LAN interface card have been prepared as optional products enabling control of UPS in a network environment. By using these options, a flexible and powerful network environment can be constructed. 4.9 Wide range input There is a wide input voltage allowable range of -20% to +15% if the load factor exceeds 70%, and -40% to +15% if the load factor is 70% or less. Moreover, in regards to the input frequency also, if the frequency is fixed (I/O asynchronous mode) power feeding at an output frequency of 50/60 Hz is possible within an input frequency range of 40 Hz to 120 Hz. With corresponding to wide range of input, the frequency of switching to battery power feeding decreases and it is possible to arrest the battery deterioration. module Fig. 8: Example of battery module installation SANYO DENKI Technical Report No.38 Nov. 2014 32

5. Circuit Architecture Fig. 10 shows a circuit block diagram of this device. (R_UNIT) Bypass circuit Back feed protection switch Rectifier Inverter Input/ bypass MCCB switch connector Charger Control circuit Inverter module No.1 Inverter module No.2 Inverter module No.3 S_UNIT Output select switch there is sufficient charging ability even if specifications call for prolonged periods of backup and it is possible to flexibly respond to charging currents which differ depending on battery configuration (capacity), therefore eliminating the need to install more chargers or change specifications. 5.2 Control circuit configuration By using surface mounting for the control circuit board, the mounting area was reduced for the new model. Furthermore, communication between the units and operation panel adopts CAN bus (Controller Area Network: A highly reliable communication method developed as a LAN for use in automobiles) therefore realizing high-speed and high reliability communication. T_UNIT R Fuse Fuse module 5.3 Electrical characteristics Table 1 shows the general specifications of this device. S 6. Benefits for Our Customers AC input Three-phase, four-wire 380/398/415 V Ground T Fuse Collector unit Arrester Maintenance bypass circuit Maintenance bypass breaker External interface circuit Output breaker Fig. 10: Circuit block diagram (45 kva) AC input Three-phase, four-wire 380/398/415 V PC interface Contact signal interface Remote ON/OFF, EPO Card interface (optional) 5.1 Main circuit configuration The inverter module of the new model is comprised of a rectifier, inverter, and charger, and it includes the following improvements. (1) By using high input power factor chopper in the rectifier, the UPS input power factor can be improved and it can support a wide range. In the case of the chopper method, it is possible to jointly use as a booster circuit of the battery voltage, thereby the number of components can be reduced. (2) Conversion efficiency of the inverter has been improved by adopting a three-level method. The threelevel method has the following features. a) The switching frequency is halved compared to the half-bridge method. b) A low-voltage switching device can be used. c) The ripple current through the AC filter is halved compared to the half-bridge method. (3) It is now possible to control and change the charging current of the charger with the CPU. This means that In the past, when customers performing system integration (SI) ordered UPS, it was restricted due to the UPS output capacity of each individual order. Due to this, if changes in output capacity (increases/decreases) occurred immediately before shipment there were problems such as wasted time and expense related to specification changes and impact on lead time, which all resulted in increased costs. With this unit, by adjusting the number of inverter modules installed on the inverter unit, it is possible to construct 15 k / 30 k and 45 kva UPS systems. This means there is no need for orders to be constrained by UPS output capacity, making low-risk procurement possible. 33 SANYO DENKI Technical Report No.38 Nov. 2014

Table 1: General specifications of the SANUPS A11J Three-phase, Four-wire model Item Units Rating or characteristic Remarks MODEL - A11J153 A11J303 A11J453 Rated output capacity (N units setting) kva/kw 15/13.5 30/27 45/40.5 Apparent power/effective power Rated output capacity (N+1 unit setting) kva/kw - 15/13.5 30/27 Apparent power/effective power Method AC input AC output Charging method - Utility synchronous continuous inverter power supply Cooling method - Forced air cooling Inverter method - High frequency PWM Number of phases - Three-phase, four-wire Rated voltage V 380/398/415 (phase voltage: 220/230/240) Allowable voltage range: -40% to +15% (Note 1) Rated frequency Hz 50/60 Choice of automatic judgment or fixed (Note 2) Maximum Capacity N units setting kva 16.5 or less 33 or less 49.5 or less Max. capacity when charging the battery N+1 unit setting kva - 18.6 or less 35.1 or less Max. capacity when charging the battery Number of phases - Three-phase, four-wire Rated voltage V 380/398/415 (phase voltage: 220/230/240) Same as input voltage Voltage setting precision % Within 2 Rated frequency Hz 50/60 Same as input frequency Frequency precision % Within 1/ 3/ 5 When asynchronous: 0.5% or less Waveform distortion rate % 3/8 or less Linear load/wave rectifier load during rated operations Sudden variation of load % Within 5 0 100% sudden variation Transient Power outage/return % Within 5 During rated operations voltage fluctuation Sudden variation % Within 5 10% sudden variation of input voltage Response time Cycle 5 or less Except when load is open Load power factor - 0.9 (delay) Fluctuation range: 0.7 (delay) to 1.0 Overcurrent protection % 110 or higher 110 (220) or higher 110 (165) or higher Automatic switching to bypass circuit (Note 3, 4) Overload endurance Operating environment Inverter % 110/118 110/118 (220/236) 110/118 (165/177) 1 minute/instantaneous Bypass % 200/800 200/800 (400/1600) 200/800 (300/1200) 30 seconds/2 cycles Type - Small-sized valve regulated lead-acid battery Backup time Minutes 10 5 3 Ambient temperature 25ºC, initial value, load power factor 0.8 Expected life Years 5 Ambient temperature 25ºC Ambient temperature ºC 0 to 40 Relative humidity % 20 to 90 19 inch rack installation space U 40 EIA standard Mass kg 460 496 532 I/O terminal block position - Front bottom (field wiring type) Suitable wire size: AWG1 (max) External interface position - Bottom of the front side (serial communication, LAN, contact signal and remote ON/OFF, EPO) LAN interface is optional Note 1. The allowable voltage range for AC input varies depending on the load factor. -40% to +15% if the load factor is 70% or less.-20% to +15% if the load factor exceeds 70%. Regarding the voltage error detection -40% if load factor is 70% or less, the power return detection will be -20%. Note 2. When automatic judgment is set, the frequency synchronous range can be set from 1%, 3% and 5% (factory setting: 3%) and the allowable frequency range at this time (asynchronous operation range) will be 8%. The device will switch to battery operation once 8% is exceeded. If set to fixed frequency, the output frequency will be fixed at 50 Hz or 60 Hz regardless of the input frequency and the allowable frequency range at this time will be 40 Hz to 120 Hz. The device will switch to battery operation once the 40 to 120 Hz range is exceeded. In the case of either setting (automatic judgment and fixed frequency) recovery from out of allowable range will occur when the frequency has returned to 8% or less. Moreover, the input frequency must be within the values set in the frequency synchronous follow-up range ( 1%, 3%, 5%) or the inverter will not start. Note 3. The synchronous changeover conditions with the bypass circuit are that the frequency setting mode is set to automatic judgment and that the input frequency is within the frequency synchronous range and the input voltage is within the rated value fluctuation range. Note 4. Values within parentheses are when the N+1 unit setting is enabled. Note 5. When starting up, the output supplies from the inverter. (Inverter start-up type) (Note 4) (Note 4) SANYO DENKI Technical Report No.38 Nov. 2014 34

7. Conclusion Further globalization of the economy moving forward will position the securement of power infrastructure across various regions as an important issue. Therefore, higher reliability, higher efficiency, and lower cost UPS will be in demand. We will continue to quickly develop products to meet these market demands and provide the products that fulfill our customers needs. We sincerely thank the many people involved in the development and realization of this UPS product for their advice and support. Hideaki Matsuo Joined Sanyo Denki in 1997. Narumi Yanagisawa Joined Sanyo Denki in 1995. Hiroyuki Hanaoka Joined Sanyo Denki in 1988. Masahiko Nagai Joined Sanyo Denki in 1993. Yoshinori Kaneko Joined Sanyo Denki in 1992. Worked on the structural design of UPS. Makoto Kitazawa Joined Sanyo Denki in 1999. Hirofumi Kimura Joined Sanyo Denki in 2007. 35 SANYO DENKI Technical Report No.38 Nov. 2014