FIRE DOOR OPERATOR LOGIC BOARD REPLACEMENT KIT K A-600

Similar documents
MODEL K B-360/-500

FIRE DOOR OPERATOR WARNING INSTALLATION LOGIC BOARD REPLACEMENT KIT K , K A-400 & K B-400 APPLICATION REMOVE AC AND DC POWER

FUNCTION: Allows existing Logic Control Version 2.0 or 2.0 Rev. B board in field to be replaced with new Logic Control Version 2.0 Rev. B.

LMPLC EES SERIES COMMERCIAL/INDUSTRIAL DUTY EGRESS DOOR OPERATOR. B2/C2 Wiring 2 YEAR WARRANTY LMPLC CONTROL NOT FOR RESIDENTIAL USE.

FDO AU & BU LMPLC ADVANCED LOGIC COMMERCIAL/INDUSTRIAL DUTY DOOR OPERATOR. B2/C2 Wiring

FDO AU AND BU LMPLC ADVANCED LOGIC COMMERCIAL/INDUSTRIAL DUTY DOOR OPERATOR. B2/C2 Wiring

LMPLC COOKSON OWNER'S MANUAL FDO A & B SOLID STATE INDUSTRIAL DUTY FIRE DOOR OPERATOR. B2/C2 Wiring 2 YEAR WARRANTY FDO 1/2 HP FDO A & B

INDUSTRIAL DUTY COMMERCIAL DOOR OPERATOR

GH INDUSTRIAL DUTY COMMERCIAL DOOR OPERATOR

K001A6039. Control Board Replacement Kit WARNING INSTALLATION INSTRUCTIONS APPLICATION REQUIREMENTS: FUNCTION: REMOVE EXISTING BOARD

OWNER'S MANUAL MODEL GH

OWNER'S MANUAL MODEL GT

ADDENDUM MODEL S3 OPERATORS Models: SL/540/570/580/590 & SW420/470/490

OWNER'S MANUAL MODEL GH CHOHS Solid State Logic

SAVE THESE INSTRUCTIONS

OWNER'S MANUAL J H HJ. C2 Wiring MODELS: LOGIC CONTROL (VER. 2.0) INDUSTRIAL DUTY DOOR OPERATOR 2 YEAR WARRANTY LOGIC CONTROL NOT FOR RESIDENTIAL USE

COOKSON OWNER'S MANUAL

OWNER'S MANUAL MODEL GT INDUSTRIAL DUTY DOOR OPERATOR 2 YEAR WARRANTY NOT FOR RESIDENTIAL USE. Serial # (located on electrical box cover)

OWNER'S MANUAL. MODELS: J & H CHSJS CHSHS Solid State Logic LOGIC CONTROL (VER. 2.0) INDUSTRIAL DUTY DOOR OPERATOR. C2 Wiring 2 YEAR WARRANTY

Repair harness. Repair Harnesses

INTERFACE PART NUMBER NOTES

OWNER S MANUAL MODEL T INDUSTRIAL DUTY DOOR OPERATOR

Figure 3-9. Right-Hand Port Connector Configuration. 1. Remove electrical power to the Hydraulic Control Unit.

OWNER'S MANUAL. C2 Wiring SOLID STATE INDUSTRIAL DUTY DOOR OPERATOR 2 YEAR WARRANTY LOGIC CONTROL NOT FOR RESIDENTIAL USE

Advanced Instructions

Shaved-B. Installation Manual & Operation Instructions

Installation/Owner s Manual 1603

L2 FWD REV L1 L2 L1 L2 L3 FWD REV (L.H. UNIT) (R.H. UNIT) HIGH LOW HIGH LOW

Photoelectric. Sensors Invisible Light Beam Protection Area

Installation/Owner s Manual 1601 / 1602

INSTALLATION INSTRUCTIONS FOR PART TRIGGER TRIGGER

OWNER'S MANUAL MODEL GT

MEDIUM DUTY DOOR OPERATOR MODELS MT5011U & BMT5011U

Multiplexing system installation M

SCM-Power Distribution PLUS system Installation and User Instructions:

MEDIUM DUTY DOOR OPERATOR MODELS MJ5011U, MH5011U, MHS5011U, & MGJ5011U

HM SERIES. (Outdated connector) Features P-01

A WORD ABOUT PROPER GROUNDING

Fincor Series 2230 MKII/2240

Contactors & Starters Index

2004 Scion xa. PARKING LIGHTS (+) GREEN At Harness On Top Of Fuse Box DOOR TRIGGER (-) RED/WHITE In 9-Pin On Top Of Fuse Box

MEDIUM DUTY DOOR OPERATOR MODELS MJ5011U, MH5011U, MHS5011U, & MGJ5011U

OnCommand Troubleshooting Guide Hayward Industries

LMPLC OWNER S MANUAL MODEL FDCL. B2 Wiring ADVANCED LOGIC INDUSTRIAL DUTY FIRE DOOR OPERATOR 2 YEAR WARRANTY LMPLC CONTROL NOT FOR RESIDENTIAL USE

LMPLC OWNER S MANUAL MODEL FDCL ADVANCED LOGIC INDUSTRIAL DUTY FIRE DOOR OPERATOR 2 YEAR WARRANTY LMPLC CONTROL NOT FOR RESIDENTIAL USE

INSTALLATION INSTRUCTIONS & MANUAL BOOK FOR ARCHITECTS, GENERAL CONTRACTORS & DEALERS REV-2

Ebling Back Blade Snow Plow Wireless Controller Kit Only sold by SnowplowsPlus.com and ControlAllWireless.com

115 VAC Control Boxes for

INSTRUCTIONS FOR REMOVAL OF GROUND FAULT PROTECTION DEVICE FROM HOBART GENERATOR SETS SPECIFICATION NUMBER

TROUBLESHOOTING GUIDE FOR HEAT PUMP BOOSTERS MODELS: HPB11, HPB15, & HPB22

Owner s Manual. Series 6050 and Vehicular Swing Gate Operator. Copyright 2010 DoorKing, Inc. All rights reserved. WARNING

Installation/Owner s Manual 1601 / 1602

Installation/Owner s Manual

High Level Alarm Panel

AIRSTREAM - BATTERY CONTROL CENTER - Diesel

APOLLO Gate Operators, Inc.

The Power Systems Industry Experts. Installation Instructions. PT100 Stationary Generator Monitoring System

Installation/Owner s Manual Series 6500

Logic 5.0 Commercial Door Operator INSTALLATION MANUAL

CTC 400 Cab Trailer Communication Power Line Carrier Technology Communications for Trucks and Trailers

Installation and Wiring Instructions for the TL- Prefix SARGuide Illuminated Touchpad for 80 Series Exit Devices to ElectroLynx Connector System

DZ11TA Commercial. 7 ½ & 10-Ton, Three-Phase Split System Heat Pump 11 EER/ IEER /3.3 COP/R-410A

Wiring Diagrams DIAGRAM INDEX

Installation/Owner s Manual Series 6500

SED2 Variable Frequency Drives Conventional Bypass (C-Bypass) Options

HYPPOETL HYPPO DUALETL 12 VOLT DC Swing Gate Operator

OWNER S MANUAL MODEL SW470 MEDIUM DUTY SWING GATE OPERATOR MODEL SW490 HEAVY DUTY SWING GATE OPERATOR

FM SECURITY AND REMOTE START SYSTEM

MODEL 422 Submersible Pump Controller

Control Replacement # Page 1 REPLACEMENT OF OBSOLETE SEMI- AUTO CONTROLS WITH KIT #

BOOK 4 ELECTRICAL RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 4:

ELECTRICAL SYSTEM RP-7

* * M400 Series Double Locks. Double Electromagnetic Locks: M422, M452, M492. Installation Instructions. Mounting Bracket (2)

FROG-D 3P. FREQUENCY READOUT OF GENERATOR THREE PHASE GENERATOR DISPLAY MODELS: FDA700 for Delta Winding FDA710 for Star Winding

TECHNICAL SERVICE BULLETIN GO-BASTA TROUBLESHOOTING A DEAD BATTERY

SINGLE-PHASE PUMP START AND PROTECTION BOX Type V1M, V1N, V1E, V1F

INSTALLATION INSTRUCTIONS FOR EGA AND EGH SERIES ELECTRIC HEATERS IN V OR H SERIES UNITS

SAVE THESE INSTRUCTIONS

Installation/Owner s Manual

Installation/Owner s Manual

Model Parts Guide. CAUTION: Read the instructions before using the appliance!

INSTRUCTIONS FOR REMOVAL OF GROUND FAULT PROTECTION DEVICE FROM HOBART GENERATOR SETS SPECIFICATION NUMBERS

CHEMICAL MIXING SYSTEM OPERATING AND INSTALLATION INSTRUCTIONS

SFGH-100SC SIREN & LIGHT SYSTEM Installation & Operation

OWNER S MANUAL MODEL SL580 HEAVY DUTY SLIDE GATE OPERATOR MODEL SL590 HEAVY DUTY, HARSH ENVIRONMENT SLIDE GATE OPERATOR

Installation Instructions

DZ11S Commercial & 10-Ton, Three-Phase

INSTALLATION INSTRUCTIONS

MANUAL. MiniMax V / VK

Transporter Current Flow Diagram No. 671 / 1 Edition

Pantera Electronics Rocker Switch Installation Manual

Plug and Play Kit Installation and Wiring (Non-Combo and Combo)

MODELS BG770 & BG790 VEHICULAR BARRIER GATE OPERATOR

SC30 powered through NN3D (6 meter antenna cable)

GLM SERIES CONTROL Users Manual Rev:

jegs.com


GTEC Transfer switch Open transition

DMC-500 TM. DC Motor Drive Control. Operation / Installation Manual Manual Part Number: S8M5003 Date: August 11, Computer Weld Technology, Inc.

Power Supply. & Door Controllers 238 SECURITY DOOR CONTROLS

Transcription:

FIRE DOOR OPERATOR LOGI BOARD REPLAEMENT KIT K79-13493A-600 APPLIATI Replacement of logic board for model FDO-AU operator with fi rmware version 600. INSTALLATI REMOVE A AND D POWER 1. Disconnect A power to the operator. 2. Open operator cover. 3. Remove D power by disconnecting the battery connection. To prevent possible SERIOUS INJURY or DEATH from electrocution, disconnect electric power to operator BEFORE installing. ALL electrical connections MUST be made by a qualified individual. REMOVE EXISTING BOARD 1. Match replacement logic board dip switch settings to the current logic board. Refer to page 5, if needed. 2. Remove all the ends of the wires connected to the existing board and neatly lay them over the side of the electrical box. Leave jumper wires located on the board connected until new logic board wiring. 3. Remove the nylon nuts (7) holding the logic board to the electrical box and hold for reassembly of new board. 4. Remove the screw holding the heat sink to the electrical box and hold for reassembly of new board. 5. Remove logic board from the box, leaving the existing standoffs in place. INSTALL NEW BOARD 1. Install the new logic board in the electrical box using the old standoffs. Be sure to install in the same confi guration as it was removed. 2. Secure logic board in place with the nylon nuts (7) removed in step 3. 3. Secure the heat sink to the electrical box with the screw removed in step 4. LOGI BOARD WIRING Single Phase A Operators Follow wiring directions on page 2. For additional help refer to the wiring diagram on page 3. Three Phase A Operators Follow wiring directions on page 4. For additional help refer to the wiring diagram on page 5. PROGRAM SETTINGS Follow instructions on page 6 for FDO optional control settings. TROL NETIS Follow instructions on the back page for FDO. 1

LOGI BOARD REPLAEMENT ASSEMBLY Existing Nylon Nuts Existing Screws New Logic Board Existing Standoff 2

SINGLE PHASE A WIRING NOTE: For additional help with wiring refer to the wiring diagram on next page. EXISTING WIRES Jumper Wires NOTE: Remove jumpers from original board and install them on new logic board as follows. 1. onnect the black wire from pin J17 to #23 on the terminal block. 2. onnect the yellow wire from pin 3 to pin 2. 3. onnect the blue wire from pin 1 to pin 0. 4. onnect the orange wire from pin 4 to pin 5. 5. onnect the brown wire that runs from #16 to #20 on the 6. onnect the original blue wire from pin J12 to #18 on the 7. onnect the black wire from pin J30 to #24 on the Transformer 1. onnect the black wire that runs from the primary on the transformer to pin 0. 2. onnect the white wire that runs from the primary on the transformer to pin 7. 3. onnect one of the brown wire that runs from the secondary on the transformer to pin J9. 4. onnect one of the brown wire that runs from the secondary on the transformer to pin J8. BRAKE 1. onnect the black wire from the brake to pin J17. 2. onnect the red wire from the brake to pin J16. Limit Switches onnect the original limit harness to the 4 pin terminal on the board marked J3 limit switch. Motor 1. onnect the original grey wire from the motor to pin J6. 2. onnect the blue wire from the motor to pin 8. 3. onnect the purple wire from the motor to pin J7. 4. onnect the yellow wire from the motor to pin J5. Overload 1. onnect one of the black wires from the overload to pin 7. 2. onnect one of the black wires from the overload to pin 6. NOTE: For pushbuttons, sensing devices, power wiring and other additional options refer to wiring diagram on next page. 3

SINGLE PHASE WIRING DIAGRAM (FDO5011AU & FDO5021AU) NOTES: 1. See AUTI owner s manual for dip switch functions and programming procedures. 2. To REVERSE motor direction; REVERSE purple and gray motor wires at J6 & J7. 3. Unit comes standard in 2 wiring mode. B2 wiring mode requires a LiftMaster Monitored Entrapment Protection device. For B2 mode, remove one end of jumper from -3 and connect to -16. Dip switch #4 (S1-4) must be in the position. To protect against fi re and electrocution: Replace LY with fuse of same type and rating. SINGLE PHASE WIRING DIAGRAM 47-35901 ATTENTI SAFETY LIMIT SW. LOSE LIMIT SW. N NO N NO N OPEN LIMIT SW. NO MOTOR 115V MOTOR NETI D BRAKE SOLENOID + J30 J17 J16 230V MOTOR NETI J14 J15 J3 J4 S1 J18 J19 J5 4 STROBE LIGHT 24V + AUXILIARY TERMINAL BLOK _ ADVERTENIA 250 MA 10 MAX 9 8 PREAUIÓN 7 6 5 4 VOIE BOARD 3 2 1 OPTIAL USER INTERFAE SPEAKER NOTE: 1) See owner s manual for DIP Switch Functions and programming procedures. 2) TO REVERSE MOTOR DIRETI: REVERSE PURPLE AND GRAY MOTOR WIRES. 3) For B2 wiring remove one end of jumper from -3 and connect to -16. (OR) J8 J13 J12 5 6 7 8 9 10 11 12 LIFTMASTER MITORED ENTRAPMENT PROTETI (LMEP) SEE NOTE 3 FUSE 2AMP 2-WIRE N- MITORED REVERSE EDGE KEY-TEST OPEN LOSE STOP NO SEDARY ADVERTENIA 5 J9 8 13 14 15 16 17 18 19 20 21 22 23 24 ADVERTENIA 0 TRANSFORMER 7 PRIMARY 2 6 BREAKER 1 L1 (OR) J1 L2 115/230V POWER IN ALARM INPUT (DRY TAT LY. DO NOT INDUE VOLTAGE) 3 L3 J6 J7 9 HASSIS GROUND 115V LY 4

THREE PHASE A WIRING NOTE: For additional help with wiring refer to the wiring diagram on next page. EXISTING WIRES Jumper Wires NOTE: Remove jumpers from original board and install them on new logic board as follows. 1. onnect the black wire from pin J17 to #23 on the 2. onnect the blue wire from pin 7 to pin 6. 3. onnect the brown wire that runs from #16 to #20 on the 4. onnect the brown wire that runs from J12 to #18 on the 5. onnect the black wire that runs from J30 to #24 on the Transformer 1. onnect the black wire that runs from the primary on the transformer to T2 on the overload. 2. onnect the white wire that runs from the primary on the transformer to T1 on the overload. 3. onnect one of the brown wires that runs from the secondary on the transformer to 96 on the overload. 4. onnect one of the brown wires that runs from the secondary on the transformer to pin J8. Limit Switches onnect the limit harness to the 4 pin terminal on the board marked J3 limit switch. Motor 1. onnect the grey wire from the motor to pin J7. 2. onnect the purple wire from the motor to pin J6. 3. onnect the yellow wire from the motor to pin J5. Overload 1. onnect the brown wire from 95 on the overload to pin J9. 2. onnect the black wire from T3 on the overload to pin 4. 3. onnect the black wire from T2 on the overload to pin 5. 4. onnect the black wire from T1 on the overload to pin 1. 5. onnect the black wire from L1 on the overload to pin 7. 6. onnect the black wire from L2 on the overload to pin 0. 7. onnect the black wire from L3 on the overload to pin 9. NOTE: For pushbuttons, sensing devices, power wiring and other additional options refer to wiring diagram on next page. Brake 1. onnect the black wire from the brake to pin J17. 2. onnect the red wire from the brake to pin J16. 5

THREE PHASE WIRING DIAGRAM (FDO1023AU & FDO1043AU) AUTI To protect against fire and electrocution: Replace LY with fuse of same type and rating. THREE PHASE WIRING DIAGRAM 47-35900 230V - 3 PH MOTOR NETI 460V - 3 PH MOTOR NETI INTERNAL MOTOR NETIS ATTENTI SAFETY N LIMIT SW. NO LOSE N LIMIT SW. NO NOTE: 1) See owner s manual for DIP Switch Functions and programming procedures. 2) TO REVERSE MOTOR DIRETI: REVERSE PURPLE AND GRAY MOTOR WIRES. 3) For B2 wiring remove one end of jumper from -3 and connect to -16. 4) Internal motor overload on models up to and including 3/4 HP. External overload located in electrical enclosure for 1 HP models. N OPEN NO LIMIT SW. D BRAKE SOLENOID MOTOR O/L SEE NOTE 4 _ + J30 J17 J14 J15 J3 J4 S1 J18 J16 J19 J5 4 STROBE LIGHT 24V + _ J13 FUSE 1 3 J6 J7 T3 T2 MOTOR T1 2 AMP OPTIAL USER INTERFAE 250 MA MAX SPEAKER 10 9 8 7 6 5 4 3 2 1 ADVERTENIA PREAUIÓN VOIE BOARD AUXILIARY TERMINAL BLOK (OR) J8 J12 J9 13 LIFTMASTER MITORED ENTRAPMENT PROTETI (LMEP) SEE NOTE 3 14 15 16 17 18 19 20 21 22 23 24 5 6 7 8 9 10 11 12 2 6 J1 9 ADVERTENIA L1 L2 L3 7 2-WIRE N- MITORED REVERSE EDGE NO KEY-TEST OPEN LOSE STOP HASSIS GROUND 0 230/460V 3PH POWER IN ALARM INPUT (DRY TAT LY. DO NOT INDUE VOLTAGE) 8 5 ADVERTENIA L3 L2 L1 95 96 T3 T2 T1 TRANSFORMER SEDARY PRIMARY 6

OPTIAL TROL SETTINGS - FDO ALARM DELAY TO LOSE S1-1 and S1-2 set the Alarm Delay to lose time of the operator. Alarm Delay to lose is the time between when the operator first receives an active alarm signal and the door starts to close. Refer to illustrations below for various settings. 10 SED DELAY 30 SED DELAY 45 SED DELAY 60 SED DELAY FIRE ALARM SYSTEM Select the alarm system being used. If the alarm is a normally open system then S1-3 must be off. If the alarm is a normally close system then S1-3 must be on. N.O. ALARM N.. ALARM LiftMaster Monitored Entrapment Protection (LMEP) S1-4 must be on if LiftMaster Monitored Entrapment Protection (LMEP) is connected. S1-4 must be off if LiftMaster Monitored Entrapment Protection (LMEP) is not connected. LIFTMASTER MITORED ENTRAPMENT PROTETI NETED LIFTMASTER MITORED ENTRAPMENT PROTETI NOT NETED 7

IMPORTANT NOTE: The 3-Button ontrol Station provided must be connected for operation. 3-BUTT STATI OR 3 POSITI KEYSWITH WITH SPRING RETURN TO ENTER AND STOP BUTT STANDARD 2 OR MORE KEY-TEST 6 7 8 9 10 6 7 8 9 10 11 12 6 7 8 9 10 Open Open Open Open lose lose lose lose Stop Stop Stop Stop Keyswitch LIFTMASTER MITORED ENTRAPMENT PROTETI SENSING DEVIE TO REVERSE OR STOP ALARM SYSTEM NO OR N TATS 1 2 5 6 11 12 11 12 LMEP Must set DIP switch #4 (S1-4) to. 2-wire non-monitored reversing edge N ontacts Must set DIP switch #3 (S1-3) to. NO ontacts Must set DIP switch #3 (S1-3) to. STROBE LIGHT/SPEAKER WIRING 15 17 TB1 1 2 - + Strobe Light Speaker IMPORTANT: All inputs must be contact only! This includes: Alarm Inputs, ontrol Inputs, Sensing Edges and Sensing Devices. For any other devices not mentioned please consult the factory. 2010, The hamberlain Group, Inc. 01-35774 All Rights 8Reserved