ProTrip Conversion Kits. For GE Types AK-15, AK-25, and AKU- 25 Low-Voltage Power Circuit Breakers INTRODUCTION. DEH Installation Instructions

Similar documents
MicroVersaTrip Plus and MicroVersaTrip PM Conversion Kits For GE Types AK-25 and AKU-25 Low Voltage Power Circuit Breakers

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

www. ElectricalPartManuals. com Digitrip Retrofit System for BBC LKD 8 Breakers IL 33-LK8-2

Digitrip Retrofit System for the ITE LG-3000 (Frameless) Circuit Breaker

www. ElectricalPartManuals. com Digitrip Retrofit System for the Westinghouse DA-50 IL 33-DAC-2 WARNING

Digitrip Retrofit System for the Federal Pioneer 25-H(L)-2, 30-H(L)-2, 30-H(L)-3, and 30-3 Breakers

Digitrip Retrofit System for General Electric AKR/AKRU-6D/7D-30S Series Breakers

www. ElectricalPartManuals. com Digitrip Retrofit System for Allis-Chalmers LA-4000 F Fused Breakers IL 33-A1K-1 WARNING

Operation and Maintenance Manual

WESTINGHOUSE / CUTLER HAMMER DS POWER BREAKERS

Power Break Circuit Breakers

Digitrip Retrofit System for Allis-Chalmers LA-600 F Electrically Operated Fused Breakers

Test Cabinet (Inspection Box) Instructions. for Testing Accessories on Manually and Electrically Operated EntelliGuard G Low Voltage Circuit Breakers

Zone Selective Interlock Module. For GE Circuit Breakers

Digitrip Retrofit System for Siemens-Allis RLX-1600 Breakers

GE Industrial Solutions. User/Installation Manual for 4.76kV -15kV SecoBloc

www. ElectricalPartManuals. com

Power Break II Circuit Breaker Accessories Motor Operator Mechanism

Digitrip Retrofit System for BBC LKD 8 Breakers

EntelliGuard Power Circuit Breaker Accessories. Network Interlock for Ampere Circuit Breakers. Introduction. Operation

Digitrip Retrofit System for Allis-Chalmers G-25 Breakers

Factory Authorized Mechanism Enhancement (FAME)

Digitrip Retrofit System for the General Electric AKR 6D/7D-30/50 and AKRT 6D/7D-50 Series Breakers

Spectra Series Power Panelboards. General. Installation. Bolt-On Circuit Breaker Kits. DEH059 Installation Instructions

L. Photo. Figure 2: Types CA-16 Relay (rear view) Photo. Figure 1: Types CA-16 Relay (front view)

Type 2 Arc Resistant WL Low Voltage Metal-Enclosed Switchgear

Q and M-Frame Circuit Breakers Instruciton Leaflet for Alarm Switch and Auxiliary Switch Combinaiton

C. Figure 1. CA-16 Front View Figure 2. CA-16 Rear View

GE CONSUMER & INDUSTRIAL

SM-1700 Secondary Shunt Trip Coil Assembly. Powered by Safety

E.S.P. Embedded Sensing Probes for Motor Brushes

ichards MANUFACTURING COMPANY, SALES, INC. 517 LYONS AVENUE, IRVINGTON, NJ Phone Fax

IL 33-DRC-1 Retrofit System for Westinghouse and Cutler-Hammer DS Power Circuit Breakers. Table of Contents

A-Series II Panelboards AD/AE/AQ Type P & N Panel THQB Three-Phase Circuit Breaker Kits

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

IB PowlVac ITE-HK Remote Racking Device

CR193 Vacuum Limitamp* Contactors

www. ElectricalPartManuals. com Instructions for Field Testing of Ground Fault Systems Utilizing Cutler-Hammer Magnum DS Circuit Breakers

Finger Cluster Replacement Parts Primary Disconnects for EntelliGuard* Retrofill Circuit Breakers

GE Industrial Solutions. DEH Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT

ABB. Type CRQ Directional Negative Sequence Relay for Ground Protection B 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION CAUTION

CONTENTS. This Product is Certified by CANADIAN STANDARDS ASSOCIATION and Bears the Mark:

Cutler-Hammer. Instructions for Installation, Operation, and Maintenance of the AMPGARD Reduced Voltage Soft Starter

Vacuum Circuit Breakers (Vehicle) Type HKR 7.5kV to 15kV. Instructions Installation Operation Maintenance SGIM-9928C

Power/Vac Vacuum Replacement Breakers for GE Magne-Blast Type AM & AMH Breakers

Installation Instructions For Motor Control Center (MCC) Units

Cutler-Hammer. Installation Instructions for the Digitrip OPTIM Pole Trip Unit Installation and Operation with L-Frame Series C Circuit Breakers

EXTREME R MOTOR OWNER'S MANUAL

Instruction Bulletin. DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Class 6035

DEH Installation

Page 2 DS LOW VOLTAGE POWER CIRCUIT BREAKERS Digitrip Trip Unit Inside Wiring Guide Outside Wiring Guide Shutter Drawout Unit Position Indicator Escut

Power Break II Switchboard

Record Plus. Molded Case Circuit Breaker Accessories. Plug In Base. DEH40915 Installation Instructions

INSTALLATION GUIDE. Universal System for Zero Turn Mowers

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards

7. SERVICES OVER 600 VOLTS

SecoVac * Ground & Test Device

Instruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module.

Position Switch Kits Accessory Kits for EntelliGuard* Retrofill Circuit Breakers

SERVICE AND REPAIR PARTS NEMA SIZE 5, SINGLE POLE, NORMALLY OPEN, P/N SERIES NEMA SIZE 5A, SINGLE POLE, NORMALLY OPEN, P/N SERIES

Installation Instructions

Control System. Part B, Section 1. This section covers the following unit configurations. Model Voltage 1, 2 Pump Piston (E, F, or G)

DANGER. Instruction Bulletin WARNING. Shunt Trip Kit for Manual DS/DSL Circuit Breakers POWER ZONE III Low Voltage Switchgear Class 6035 INTRODUCTION

Programmer Disconnect Accessory Manual for Retrofil CB

I.L. 29C184A File WARNING

This Kit Is for Use with Types RE, RVE, WE, WVE, VWE, VWVE27, and VWVE38 Reclosers.

Vacuum Circuit Breakers (Vehicle)

Design Guide for Integration of Fixed-Mount Circuit Breakers

COOKSON OWNER'S MANUAL

GEF Renewal Pans. low Vohage Power Circuit Breakers. Type AKR-30S and AKRU-30S. www. ElectricalPartManuals. com

Installation Instructions for R-Frame G-Series (RG) 310+ Trip Unit

COOPER POWER SERIES. Quick Connect Assembly (QCA) Retrofit Kit, General Electric Installation Instructions. Voltage Regulators MN225075EN

Universal Retrofit System Installation Instructions Revised:

ELECTRICAL. Contents - Wiring Diagrams

Utility Distribution System

Cutler-Hammer. Instructions for Potential Transformer and Auxiliary Control Power Disconnecting Means for Use in Ampgard Lineups, 7.2 kv I.B.

a WARNING Allen-Bradley Parts K-Frame Circuit Breaker Instruction Leaflet for Alarm Switch and Alarm /Auxiliary Switch Combination Bul.

Installation and removal instructions for Series NRX RF fixed breaker three-way Type 32 cable interlock kit

Cutler-Hammer. Installation Instructions for Undervoltage Release Mechanism (Handle Reset) with LED for E 2 L and E 2 LM Mining Circuit Breakers

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

3-way multi-family drawout cable interlock kit - type 32 - RF

Service Manual. Extractor Model XR28QP. For The. For: Troubleshooting Adjustments

ANDCO Eagle Actuator Instruction Manual

Operator s Manual Series ATB Automatic Transfer & Bypass Isolation Switches 150, 260, and 400 amp sizes A. Rating Label.

ABB ! CAUTION. Type KRV Directional Overcurrent Relay E 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION. Instruction Leaflet

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod

Fisher 657 Diaphragm Actuator Sizes and 87

Installation Instructions

Instructions for Installation, Operation and Maintenance of Low Voltage Power Circuit Breakers Types DSII and DSLII

RENEWAL PARTS AK-2-15 AK-2-25 AK-3-25 AKF-2-25 AK-2A-15 AK-2A-25 AK-3A-25 AKF-2A-25 AKU-2-25 AKU-3-25 AKU-2A-25 AKU-3A-25

Vacuum Circuit Breakers (Vehicle)

Florham Park, NJ USA Call (ASCO) for sales or service

Vacuum Circuit Breakers (Vehicle)

DEH g Installation Instruction for Cable Operator Mechanisms for SE150, SF250, SG600 & SK1200 Spectra RMS Circuit Breakers

MODEL JH JACKSHAFT INDUSTRIAL DOOR OPERATOR INSTALLATION MANUAL. OPERATOR SPECIALTY COMPANY, INC. P.O. Box 128 Casnovia, MI 49318

A. Submit manufacturer's literature and technical data before starting work.

Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) E

Cutler-Hammer. Installation Instructions for the ND OPTIM 550 PowerNet and/or Zone Interlock Accessories (ICK 550N, ZGK550N, ZGPK550N) I.L.

USE AND CARE GUIDE DUALCHECK CIRCUIT TESTER

Transcription:

DEH 40026 Installation Instructions g ProTrip Conversion Kits For GE Types AK-15, AK-25, and AKU- 25 Low-Voltage Power Circuit Breakers INTRODUCTION GE Conversion Kits are designed for upgrading existing GE low-voltage power circuit breakers, rather than replacing the entire breaker. The Conversion Kits include ProTrip Trip Units, the latest technological advance in GE trip systems. ProTrip Conversion Kits are designed and tested to conform to ANSI Standard C37.59, allowing the retrofitter to properly install the kit and acceptance test the breaker. This publication covers installation of ProTrip Conversion Kits on GE types AK-15, AK-25, and AKU-25 low-voltage power circuit breakers. Each Conversion Kit contains all the components needed to convert from an existing GE trip system.

TABLE OF CONTENTS SECTION 1. GENERAL INFORMATION...4 SECTION 2. BEFORE INSTALLATION...4 SECTION 3. FRONT-FRAME CONVERSION Separation of the Front and Back Frames...5 Removal of the Existing Trip Device...6 Remounting the X and Y Relays...7 Installing the Flux Shifter...8 Installing the Trip Unit Bracket and Trip Unit...10 SECTION 4. BACK-FRAME CONVERSION Current Sensor Installation...13 Stud Shield Modification...15 Remounting Primary Disconnects...15 SECTION 5. CONFIGURING THE TRIP UNIT...16 SECTION 6. FOUR-WIRE GROUND FAULT OPTION...16 SECTION 7. TESTING AND TROUBLE-SHOOTING Testing...17 Trouble-Shooting...17 Nuisance Tripping on Ground Fault-Equipped Breakers...17 2

LIST OF FIGURES 1. Arc chute retainer and arc chutes.... 5 2. Screw to be removed from connecting links.... 5 3. Breaker bottom bracket connected to the escutcheon and the back frame... 6 4. Type EC-2A trip device, with adjacent device removed... 6 5. Front view of the front frame, showing relocation of the X and Y relays... 7 6. Right side view of the front frame, showing relocation of the Y relay.... 8 7. Y relay installed on the arc chute retainer... 8 8. Unassembled flux shifter and mounting hardware... 8 9. New flux shifter installed on the right side of the breaker mechanism (shown in the reassembled breaker).... 9 10. Mounting and adjusting the flux shifter shown from the right side of the mechanism.... 9 11. Flux shifter as isntalled on the breaker.... 9 12. Trip unit, mounting plate, support bracket, and harness... 10 13. Trip unit support bracket mounted to the breaker frame on a manually operated stationary breaker.... 10 14. Trip unit support bracket mounted to the breaker frame on an electrically operated draw-out breaker.... 10 15. Bottom view of the trip unit support bracket installed on an electrically operated breaker, showing the X relay and insulator.... 11 16. Trip unit attached to the mounting plate... 11 17. Trip unit and mounting plate attached to the breaker.... 12 18. Flux shifter wiring harness in place... 12 19. Components for the current sensor assembly for one pole... 13 20. Current sensor assembly, right-side view.... 13 21. CT terminal board bracket and insulator installed... 13 22. Completed CT installation..... 13 23. Right-side view of the back frame, showing installation of the flux shifter actuator bushing.... 14 24. Modification of the lower stud shields.... 15 25. Primary disconnect modification for AK-15 breakers... 15 26. Neutral sensor outline... 16 27. Cabling diagram for PtoTrip trip units with ground fault on four-wire loads.... 19 3

SECTION 1. GENERAL INFORMATION GE Conversion Kit installation is straightforward, but does require careful workmanship and attention to these instructions. Familiarity with the breaker is highly desirable. Then general approach is to first remove the existing trip devices from the breaker, then install the ProTrip components. Following this procedure, the converted breaker is performance tested before it is returned to service. The majority of trip unit kit installations do not require any customized assembly work. However, some installations may involve unusual mounting conditions or accessory combinations that require minor modifications and/or relocation of components. In most instances, this supplementary work can be done on site. In preparation for the conversion, the installer should verify that the appropriate current sensors and trip unit have been furnished. Whenever a ProTrip kit is installed on a breaker with a four-wire system, an associated neutral sensor (CT) is required for separate mounting in the equipment. Ensure that retrofitted breakers are applied within their short-circuit ratings. Note that all ProTrip trip units supplied with conversion kits are equipped with long-time, short-time, instantaneous, and defeatable ground fault (LSIGX) trip functions. The installer should be aware of how these functions will affect his application before installing the conversion kit. As a service-related consideration, the installation of a ProTrip kit provides an excellent opportunity to perform normal maintenance on the breaker, particularly when the front and back frames are separated. Such procedures are described in the installation and maintenance manuals supplied with the breaker and equipment. SECTION 2. BEFORE INSTALLATION Before starting any work, turn off and lock out all power sources leading to the breaker, both primary and secondary. Remove the breaker to a clean, well-lighted work area. WARNING: Low-voltage power circuit breakers use high-speed, stored-energy spring operating mechanisms. The breakers and their enclosures contain interlocks and safety features intended to provide safe, proper operating sequences. For maximum personnel protection during installation, operation, and maintenance of these breakers, the following procedures must be followed. Failure to follow these procedures may result in personal injury or property damage. Only qualified persons, as defined in the National Electrical Code, who are familiar with the installation and maintenance of low-voltage power circuit breakers and switchgear assemblies, should perform any work on these breakers. Completely read and understand all instructions before attempting any breaker installation, operation, maintenance, or modification. Turn off and lock out the power source feeding the breaker before attempting any installation, maintenance, or modification. Follow all lock-out and tag-out rules of the National Electrical Code and all other applicable codes. Do not work on a closed breaker or a breaker with the closing springs charged. Trip an OPEN breaker and be sure the stored-energy springs are discharged, thus removing the possibility that the breaker may trip OPEN or the closing springs discharge and cause injury. Trip the breaker OPEN, then remove the breaker to a well-lighted work area before beginning work. Do not perform any maintenance that includes breaker charging, closing, tripping, or any other function that could cause significant movement of a draw-out breaker while it is on the draw-out extension rails. Do not leave the breaker in an intermediate position in the switchgear compartment. Always leave it in the CONNECTED, TEST, or DISCONNECTED position. Failure to do so could lead to improper positioning of the breaker and flashback. 4

SECTION 3. FRONT-FRAME CONVERSION Front-frame conversion consists of the following steps: 1. Separation of the front and back breaker frames. 2. Removal of the existing trip devices. 3. On electrically operated breakers with EC trip devices, relocating and remounting the X and Y relays. 3. Installation of the flux shifter and trip paddle. 4. Installation of the trip unit mounting bracket. 5. Installation of the trip unit wire harness. Separation of the Front and Back Frames Use the following procedure to separate the front and back frames of the breaker. 1. Remove the breaker from its enclosure and place it on a suitable work surface. 2. Verify that closing springs are discharged and that the breaker is OPEN. 3. Loosen the two captive nuts and lift off the arc chute retainer, shown in Figure 1. 4. Lift the three arc chutes straight up and out of the breaker. 5. Remove the long screw and nut through the two connecting links on each side of the breaker, as shown in Figure 2. 6. Carefully place the breaker on its back surface, resting on the primary disconnects. Figure 1. Arc chute retainer and arc chutes. Figure 2. Screw to be removed from connecting links. 5

7. Remove the two mounting screws and lock washers attaching the bottom bracket to the escutcheon, as shown in Figure 3. 8. Loosen the recessed Allen screw in the side of the charging handle base and lift off the handle. 9. Remove the snap ring and flat washer on the charging handle mounting shaft. 10. Remove the four Philips-head screws and lock washers on the front of the escutcheon and lift off the escutcheon. 11. Lift the bottom bracket from its back frame attachment. 12. Remove the nuts and washers securing the front frame to the two long studs from the back frame. 13. Remove the nuts and washers on the studs connecting the front frame bracket to the back frame (one on each side). 14. Lift the front frame off the back frame. Removal of the Existing Trip Device Figure 4 shows an existing Type EC-2A trip device with the adjacent trip device already removed, to illustrate this procedure. 1. Remove the existing overcurrent trip devices and trip paddles. 2. On draw-out breakers, remove the primary disconnects from the bottom (load) copper studs. 3. Remove the three bottom (load) copper stud assemblies. On Power Sensor-equipped breakers, these will have been removed with the trip devices. 4. On breakers equipped with Type EC trip devices, remove and discard the mounting brackets on the lower front of the back frame. Figure 3. Breaker bottom bracket connected to the escutcheon and the back frame. Figure 4. Type EC-2A trip device, with adjacent device removed. 6

Remounting the X and Y Relays On electrically operated breakers equipped with Type EC trip devices, the Y relay is mounted on the front frame at the right side of the operating mechanism. 1. To provide mounting space for the new flux shifter, remove the Y relay and remount it on the left end of the arc chute retainer, as illustrated in Figures 5, 6, and 7. 2. Modify the breaker s wiring harness to suit. The X relay should be remounted after the trip unit mount and bracket are installed, as described in Installing the Trip Unit Bracket. Figure 5. Front view of the front frame, showing relocation of the X and Y relays. 7

Installing the Flux Shifter Figure 8 shows the unassembled flux shifter and its mounting hardware. The flux shifter is mounted to the right of the operating mechanism, as shown in Figure 9. 1. Remove the existing flux shifter device. 2. Mount the flux shifter trip paddle on the breaker s trip shaft as shown in Figures 9 and 10. Push the drawout locking lever in to allow the trip bar to rotate to an accessible point. 3. Save the new actuating bushing for installation in the right operating link in the back frame, as described in Section 4. 4. Mount the flux shifter assembly to the right side of the front frame, as shown in Figures 9 and 10. On Power Sensor breakers equipped with a shunt trip, mount the flux shifter on top of the shunt trip bracket. If no shunt trip is installed, use the 1 /8-inch spacer provided, as indicated in Figures 10 and 11. On ECequipped breakers, the mounting hole must be drilled and tapped for a #10-32 screw. Figure 6. Right side view of the front frame, showing relocation of the Y relay. Figure 8. Unassembled flux shifter and mounting hardware. Figure 7. Y relay installed on the arc chute retainer. 8

5. When the flux shifter and its trip paddle are installed and the front and back frames are reassembled, the flux shifter must be adjusted as follows: a. Make sure that the breaker mechanism is OPEN, then charge the closing springs with the charging handle. b. Set the gap between the trip paddle and the end of the flux shifter trip rod, as shown in Figure 10. Use a 0.10-inch rod as a gage. To make the adjustment, loosen the jam nut, then turn the adjusting nut as necessary. Be sure to relock the adjustment with the jam nut. 6. Optional test The flux shifter may be tested by closing the breaker and applying a 9 Vdc power source to the flux shifter leads (the red wire is positive). The breaker should trip. Figure 9. New flux shifter installed on the right side of the breaker mechanism (shown in the reassembled breaker). Figure 11. Flux shifter as installed on the breaker. Figure 10. Mounting and adjusting the flux shifter shown from the right side of the mechanism. 9

Installing the Trip Unit Bracket and Trip Unit The ProTrip Trip Unit mounts on the lower right side of the breaker. The trip unit, mounting plate, support bracket, and wiring harness are shown in Figure 12. Figure 13. Trip unit support bracket mounted to the breaker frame on a manually operated stationary breaker. Figure 12. Trip unit, mounting plate, support bracket, and harness. 1. For an electrically operated breaker, attach the X Relay to the inside of the trip unit support bracket with the three #10 screws and lock washers provided, as illustrated in Figures 14 and 15. Be sure to install the insulating shield between the relay and the support bracket, as shown. 2. Modify the X Relay harness by adding 16-gauge extension wire, splices, and ring terminals, as provided. Work one wire at a time. Route the wires as shown in Figure 5, ensuring that the wires do not interfere with the closing solenoid plunger or the trip unit. 3. Mount the support bracket to the two tapped holes on the right side of the breaker with the screws and lock washers provided, as in Figure 13 for a manually operated breaker and in Figure 14 for an electrically operated breaker. Figure 14. Trip unit support bracket mounted to the breaker frame on an electrically operated draw-out breaker. 10

4. Insert the 50-pin connector on the wiring harness through the rear of the rectangular hole in the mounting plate and secure with the two small screws provided to the mounting plate, as shown in Figure 16. 5. Remove the large screw from the rear of the trip unit. Line up the connector on the rear of the trip unit with the connector on the mounting plate and join them. Insert the large screw just removed through the rear of the mounting plate to secure the trip unit, as shown in Figure 16. Figure 15. Bottom view of the trip unit support bracket installed on an electrically operated breaker, showing the X relay and insulator. Figure 16. Trip unit attached to the mounting plate.. 11

6. Attach the mounting plate with the three screws and lock washers provided to the tapped holes in the support bracket, as shown in Figure 17. 7. Run the wiring harness from the flux shifter through the wiring trough on the front of the frame, as shown in Figure 18. Attach the 4-pin connector to the corresponding connector on the trip unit wiring harness. 8. The additional three pairs of terminals on the trip unit wiring harness will be connected to the current sensors after the breaker has been reassembled. Figure 17. Trip unit and mounting plate attached to the breaker. Figure 18. Flux shifter wiring harness in place. 12

SECTION 4. BACK-FRAME CONVERSION The components used in the installation of the current sensor for each pole are shown in Figure 19. Figure 20. Current sensor assembly, right-side view. Figure 19. Components for the current sensor assembly for one pole. Current Sensor Installation The three current sensors (CTs) are mounted to the back frame in the locations from which the existing trip devices were removed. The following installation process is illustrated in Figure 20. 1. Insert the lower copper stud through the rectangular slot in the back frame and attach it with the existing mounting screw. 2. Place the right-angle bus strap in position in the back frame and loosely attach it with the existing bolt. 3. Insert the copper sleeve into the center of the CT, then place the CT in position between the bus strap and lower stud. Loosely secure it with the long bolt through the bus strap and CT into the tapped hole in the stud. 4. Align the assembly, then tighten the two 3/8-inch bolts in the bus strap to 250 in-lb to assure proper contact integrity. 5. Install the CT terminal board-mounting bracket below the CTs with the two #8-32 1/2-inch screws provided, as shown in Figure 21. Bring the screws in from the rear through the existing holes in the back frame. 6. Install the insulator and bracket to the right side of the back frame below the CTs with the screws and nuts provided, as shown in Figure 21. 7. Mount the terminal boards from each CT to the bracket with the six #6-32 1/2-inch screws and washers provided, as shown in Figure 22. Figure 21. CT terminal board bracket and insulator installed.. Figure 22. Completed CT installation.. 13

8. Remove the bushing from the right operating link and replace it with the new flux shifter actuating bushing, as illustrated in Figure 23. On pre-1969 breakers, the hole in the link must be enlarged to 7/16-inch diameter. 9. Reassemble the front and back frames, using the reverse of the procedure described in Section 3, Separation of the Front and Back Frames. Be sure to engage the flux shifter actuator bushing on the right operating link with the flux shifter operating lever, as illustrated in Figure 10. 10. Bring the three CT wires back from the trip unit to the back frame and connect to the CT terminal boards, as shown in Figure 22. The lengths of the wires as supplied assure connection to the proper terminal board. Note that the black wire (tap) connects to the left terminal and the white wire (common) to the right terminal. Figure 23. Right-side view of the back frame, showing installation of the flux shifter actuator bushing. 14

Stud Shield Modification Modify the left- and right-pole lower stud insulator shields as illustrated in Figure 24. Remount on the back plate using the original screws and special nuts supplied with the kit. Remounting Primary Disconnects On draw-out breakers, remount the primary disconnect fingers to the new lower studs. On AK-15 breakers only, use the following procedure to modify the primary disconnects, as illustrated in Figure 25. 1. Place the spacer with the off-center hole in the hole in the stud, while sliding the new retainer completely over the stud. 2. Place the new retaining ring on the stud. Insert the tip of the upper fingers under the retaining ring and place the bow-tie spacers in the fingers. 3. Place the retainer over the upper fingers and insert the bolt. 4. Inset the tip of the lower fingers under the retaining ring and place the bow-tie spacers in the fingers. Locate the lower retainer to hold the bow-tie spacers in place. 5. Place the cylindrical spacer and spring on the bolt and secure it with a washer and nut. 6. Tighten the nut to obtain 60 70 pounds of pressure per set of four fingers when the fingers are spread 1 /2 inch apart. If a pressure gauge is not available, compress the spring to 13/16 inch to obtain proper pressure. Figure 24 Modification of the lower stud shields. CAUTION: Adequate primary contact force is essential. Tighten the nuts on the 1/4 20 mounting bolts to obtain a spring dimension of 13/16 to 27/32 inch. The proper distance between the contact fingers is 7/16 inch. Proper contact force is 60 70 pounds, with the contacts spread to 1/2 inch. Figure 25. Primary disconnect modification for AK-15 breakers. 15

SECTION 5. CONFIGURING THE TRIP UNIT See DEH-40034 for detailed instructions for setting up ProTrip trip units. SECTION 6. FOUR-WIRE GROUND FAULT OPTION The ground fault option for four-wire installations requires the installation of an additional current sensor on the neutral bus in the equipment. The sensor is connected to the trip unit through the connector provided in the wiring harness. 1. Mount the neutral sensor on the outgoing neutral lead, normally in the bus or cable compartment in the equipment. Figure 26 shows the outline of the neutral sensor. 2. Connect the neutral sensor wire harness to the correct taps on the sensor. To maintain the same polarity as the phase sensors, connect the white wire to the common terminal, black to the tap. 3. Route the wires through the equipment and connect to the two-pin connector on the trip unit wiring harness. The wires should be tied to the breaker frame in an easily accessible location. It may be located with the communication harness. Figure 26. Neutral sensor outline. 16

SECTION 7. TESTING AND TROUBLE- SHOOTING WARNING: Do not change taps on the current sensors or adjust the trip unit settings while the breaker is carrying current. Failure to adhere to these instructions will void all warranties. Testing Before installing a converted breaker back into service, perform the following steps: 1. Verify that the trip unit is securely installed by performing a continuity test on the CT wiring and the trip unit. a. Disconnect the black CT wires at each phase sensor. b. Check for continuity with a continuity tester or VOM from the white lead of the phase A CT to the white lead of the phase B CT. c. Repeat this continuity test for the white leads of the phase A and phase C CTs. d. Measure the resistance across each phase sensor and compare the values measured to the values listed in Table 1. e. Reconnect the black CT leads to all of the phase sensors. Ensure that this is done before continuing with performance testing of the breaker. CAUTION: In addition to the continuity test described in Step 1 and before performance testing of the converted breaker, each phase of the breaker should be primary injected with a current level of about 10%, but no more than 20%, of the CT rating. WARNING: If the converted breaker is energized or tested by primary injection with a sufficiently high test current with a loose or open circuit between the CTs and the trip unit, damage will occur to the trip unit, wire harness, 50-pin trip unit connector, and CTs. Failure to adhere to these instructions will void all warranties. 2. Check the insulation on the primary circuit with a 1,000-volt Meggar. 3. Measure the resistance across the line and load terminals for each phase using a micro-ohmmeter or millivolt tester. If the resistance differs considerably from phase to phase, the electrical connections may not be properly tightened or it could also indicate improper contact wipe. 4. To verify that the breaker has been properly retrofitted, perform a primary injection test on each phase. This test will check the CTs, bus, wiring harness, flux shifter, and trip unit as a complete system. a. A high-current, low-voltage power supply should be connected across each line and load terminal to simulate an overcurrent fault. b. Set the long-time trip at 0.5 to minimize the breaker stress. c. When ground fault is installed, the test can be performed by wiring two adjacent poles in series or by using the GE Digital Test Kit, cat. no. TVRMS2. This will prevent the breaker from tripping because of an unbalanced current flow. CAUTION: Do not attempt to use GE Test Kit cat. no. TVTS1 or TVRMS on this trip unit. Trouble-Shooting When malfunctioning is suspected, first examine the breaker and its power system for abnormal conditions such as the following: The breaker is not tripping in response to overcurrent conditions or incipient ground faults. The breaker is remaining in a trip-free state because of mechanical interference along its trip shaft. The shunt trip (if present) is activating improperly. Nuisance Tripping on Ground Fault-Equipped Breakers When nuisance tripping occurs on breakers equipped with ground fault trip, a probable cause is the existence of a false ground signal. Each phase sensor is connected to summing circuitry in the trip unit. Under no-fault conditions on three-wire load circuits, the currents add to zero and no ground signal is developed. This current sum is zero only if all three sensors have the same electrical characteristics. If one sensor differs from the others (such as by a different rating or wrong tap setting), the circuitry can produce an output sufficient to trip the breaker. Similarly, a discontinuity between any sensor and the trip unit can cause a false trip signal. The sensors and their connections should be closely examined if nuisance tripping is encountered on any breaker whose ProTrip trip unit has previously demonstrated satisfactory performance. After disconnecting the breaker from all power sources, perform the following procedure: 1. Check that all phase sensors are the same type (current range). 2. Verify that the tap settings on all three phase sensors are identical. 3. Verify that the wiring harness connections to the sensors have the proper polarity (white lead to common, black lead to tap), as shown in the cabling diagram in Figure 27. 4. On ground fault breakers serving four-wire loads, check that the neutral sensor is properly connected, 17

as indicated in Figure 27. In particular, check the following: a. Verify that the neutral sensor has the same rating and tap setting as the phase sensors. b. Verify continuity between the neutral sensor and its equipment-mounted secondary disconnect block. Also check for continuity from the breakermounted neutral secondary disconnect block through to the trip unit wiring harness connector. c. If the breaker s lower studs connect to the power source, then the neutral sensor must have its load end connected to the source. d. Verify that the neutral conductor is carrying only the neutral current associated with the breaker s load current (the neutral is not shared with other loads). 5. If the preceding steps fail to identify the problem, then measure the sensor resistances. The appropriate values are listed in Table 1. Since the phase and neutral sensors are electrically identical, their resistances should agree closely. Breaker CT Rating, A Resistance, ohms AK-15 AK-25 AKU-25 150 225 225 600 7 15 12 20 12 20 40 50 Table 1. CT resistance values. 18

Figure 27. Cabling diagram for ProTrip trip units with ground fault on four-wire loads. 19

These instructions do not cover all details or variations in equipment nor do they provide for every possible contingency that may be met in connection with installation, operation, or maintenance. Should further information be desired or should particular problems arise that are not covered sufficiently for the purchaser s purposes, the matter should be referred to the GE Company. g GE Industrial Systems General Electric Company 41 Woodford Ave., Plainville, CT 06062 DEH40026 R03 0899 1999 General Electric Company