ALD. Sound attenuating exterior wall grille QUICK FACTS. Excellent noise attenuation A robust grille that withstands severe climatic conditions

Similar documents
CADENZA. Sound attenuator with tapered acoustic baffles for rectangular ducts QUICK FACTS

SERENO

Wall air diffusers with discs for supply air and flush mounting. Quick guide COLIBRI WALL

EAGLE Wall. Wall air diffusers with discs for supply air and flush mounting QUICK FACTS

COLIBRI Ceiling QUICK FACTS. Square ceiling diffuser with discs for supply air

PELICANTM. Wall. Rectangular perforated wall air diffusers for supply air. Quick guide

CAV controllers. Type VFL. Volume flow limiter for insertion into ducting PD VFL 1

SRY. Ceiling mounted linear disc diffuser for supply air QUICK FACTS

CAV controllers. Type VFL. Volume flow limiter for insertion into ducting K

FALCON Ceiling. Circular ceiling air diffuser for supply air QUICK FACTS

PELICAN Ceiling. Square ceiling air diffuser for supply air and extract air QUICK FACTS

Pressure control damper ERPA

External grilles USAV, USVN, USSV and SVN TECHNICAL DATA

PELICAN Ceiling HF. Square extract air diffuser QUICK FACTS

series Silencers

Circular Silencer. Rigid and flexible construction Type CA CB CF CS. TROX GmbH Telephone +49/28 45/ Telefax +49/28 45/

CONSTANTFLOW Volume Flow Controllers

VAV controller. TROX Auranor Norge AS. Telephone Fax

EXCa. Exhaust register

CAV controllers. Type EN. For the precise control of normal and high constant volume flows. 01/2017 DE/en PD EN 1

For installation into ductwork

Homepage > Products > External louvres - louvre blades > Mechanically self-powered dampers > Non-return dampers > Type KUL.

MULTIDIRECTIONAL DIFFUSERS WITH EXTRACTABLE CONES

CAV controllers. Type EN-Ex. For the precise control of normal and high constant volume flows in potentially explosive atmospheres (ATEX)

VAV terminal units. Type TVM. For dual duct systems PD TVM 1

BRC

CA V0 E RANGE In-line centrifugal fans in self-extinguishing plastic

ADRIATIC VF. Active climate beam with cooling, heating and ventilation QUICK FACTS

Adriatic for individually suspended installation Exposed active climate beam with cooling, heating and ventilation

CRP. Commissioning damper, Ductwork Leakage Class 0 QUICK FACTS. Perforated damper blade for better damper characteristic

DCV-CF DCV-CF. DCV-CF Pressure control with airflow measuring CFL Version B03. Pressure controlwith airflow measuring. Product description

IN-LINE MIXED FLOW DUCT FANS MIXVENT-TD Fan Systems

Type MSA. Splitter thickness 200 mm FOR INCREASED INSERTION LOSS AND BROADBAND ATTENUATION EVEN IN THE LOW FREQUENCY RANGE

Type WG. External weather louvre made of galvanised steel sections FOR THE MOST DIVERSE APPLICATIONS, AVAILABLE ALSO IN LARGE SIZES

Rectangular inlet air diffuser

Cell Ventilation Security Grille

JVR CONTENTS. Page Introduction 2 Models and dimensions 3 Technical data. Selection tables 4 Technical data. Selection charts 5 Product codes 6

Sound attenuators. Sound attenuators, Sound attenuating louvres. Sound attenuators. Rectangular sound attenuators DZ-2, DZ-3

Volume Flow Limiters Type VFL

DVAX-ARS. Roof-mounted unit for mechanical smoke extract

CAV controllers. Type RN-Ex. For the precise control of constant volume flows in potentially explosive atmospheres (ATEX) PD RN-Ex 1

CAV controllers. Type RN. For the precise control of constant volume flow rates PD RN 1

for suspended installation. Active climate beam with cooling, heating and ventilation

C O L M A N. Air Distribution JET DIFFUSERS DCJ SERIES DCJ SERIES

Ventilation grilles for installation into walls, sills or rectangular

Adjustable Curved Vane Diffusers. Vanes are parallel to the width dimension Vanes are parallel to the height dimension

ROOFMASTER STEF-HT ROOF FAN

Exhaust air diffuser EYMA-2 and air intake device DYMA-1

CRP. Commissioning damper, Ductwork Leakage Class 0

DIR. VARIZON Displacement unit with adjustable spread pattern. Quick guide

Fresh air and exhaust air systems

BLBd

Ceiling swirl diffusers

Model METRIC SHAFT WT (LBS) mm mm mm mm mm mm mm 572

Aircell Polymer Range

Type VDL FOR HIGH ROOMS, WITH ADJUSTABLE AIR CONTROL BLADES. Homepage > Products > Air Diffusers > Swirl diffusers > Type VDL

ROOF FAN ROOFMASTER STEC NON-INSULATED VERSION TECHNICAL CATALOGUE

Circular silencers. Type CA. For the reduction of noise in circular ducts, galvanised sheet steel construction. 02/2017 DE/en PD CA 1

PRODUCT BROCHURE. Rectangular Displacement Diffuser RDW-FD RDW-FD : smartemp.com

Radial roof fans - SMART-UL. Application. Stylistics. Structure. Efficiency adjustment. Acoustics

Ventilation grilles for installation into walls, sills or rectangular

ACOUSTIC CABINET FANS Centribox CVB-CVT Series, Forward Curved Centrifugal Fans

LINEAR BAR GRILLES T SERIES. Quality and e!ciency without compromise

KAT. DOUBLE INLET CENTRIFUGAL FAN with Forward Wheels

BOX BLB Centrifugal Box Fan

ADAPTTM. Extract. Extract air diffuser for the WISE system. Quick Selection

DIRECT-AIR ILB / ILT Series Rectangular duct fans

SDV Vane Swirl Diffusers

Acoustic Twin Fans (ATQ)

IN-LINE DUCT FANS MIXVENT-TD Fan Systems

VAV Terminal Units SDS

Novenco axial flow fans. ZerAx - Standard January 2010

Swegon PACIFIC. Integrated climate beam

Ventilation grilles for installation into walls, sills or rectangular

VARYCONTROL VAV Dual Duct Terminal Boxes

Air distribution product

Fire Block and Pressed Steel Grilles

TD-MIXVENT Series IN-LINE MIXED FLOW DUCT FANS TD-MIXVENT. In-Line duct fans

Mixed Flow Roof Fans (RMH)

CENTRIFUGAL IN-LINE FANS VENT Series

CNA-CNB CNA-CNB CENTRIFUGAL FANS STANDARD TEMPERATURES AND EX

VAV TERMINAL UNIT KYODO-ALLIED TECHNOLOGY PTE LTD

ITEC High Efficiency EC Twin Fan for convenient fitting and full control. Casing constructed from 1.6mm Galvanised sheet steel

Sound attenuators, Sound attenuating louvres

INDUSTRIAL PROCESS AND COMMERCIAL VENTILATION SYSTEMS. Twin City Fan GRAVITY VENTILATORS MGI & MGR GRV TEL & TIL LUG CATALOG 4720 MAY 2014

Ceiling swirl diffusers with perforated face plate

Circular silencers. Type CS. For the reduction of noise in circular ducts, aluminium construction PD CS 1. 02/2017 DE/en

Mixed Flow Roof Fans (RMH)

BSB. SINGLE INLET CENTRIFUGAL FAN with Backward Wheels

Accessories. Front vane panel Coupling sleeve with gasket Galvanised steel Gasket of rubber compound

VENT Series CENTRIFUGAL IN-LINE FANS VENT. In-Line duct fans. Mounting foot

SUPPLY AND RETURN AIR GRILLES TYPE: AS/GS120 AS/GS130

Ceiling diffusers. Type VDR. For large temperature differences in heating mode, high penetration of air, with adjustable air control blades

Catalogue. FlowBar. High Capacity Slot Diffuser.

[Y] Acoustic Splitters with spigot ends/aerodynamically shapped for energy saving (Pressure drop reduction 25% to 30%)

The Straight Way. Rectangular Cabinet Fan. Fans Air Handling Units Air Distribution Products Fire Safety Air Curtains and heating Products Tunnel Fans

ACTIVENT System. Specifications. Product code example ACTA

Ceiling swirl diffusers with perforated face plate

ACOUSTIC CABINET FANS CVB / CVT Series

Extract-air grille with ATK plenum box

Transcription:

Sound attenuating exterior wall grille QUICK FACTS Excellent noise attenuation A robust grille that withstands severe climatic conditions Available in a number of different materials

Technical description General The ALD grille effectively reduces sound emitted from fan rooms and machine rooms, etc. to the surroundings. The sound is attenuated as the air passes through the attenuator between the sound absorbing vanes. Function Exterior wall grilles normally do not have a sound attenuating function. The unique feature of the ALD is that it is a sound attenuating exterior wall grille. Its main application involves use as an air intake/or exhaust air grille in ventilation systems. Other fields of application can include e.g. use as an airing grille in compressor rooms. The integral attenuation has been determined by applying the following method: An ALD grille was installed in the exterior wall of a normally hard room. A diffused field of sound was generated in the room. The sound level was measured on the other side of the wall, with and without sound attenuating grille. The difference was equal to the attenuation in the grille. See Figure 2. For normal fan rooms and machine rooms, the reduction in sound emitted to the surroundings is for ALD 1 approx. 12 db(a), and for ALD 2 approx. 17 db(a) compared with a conventional exterior wall grille. Design The ALD is available in two models, single (type 1) and double (type 2) See Figure 3. Materials and finish The ALD is made of galvanized sheet steel or aluminium. The aerodynamically designed acoustic baffle vanes are filled with ISOVER Cleantec PLUS sound attenuating material. If required, the grille can be surface-treated to prevent corrosion. Installation The grille is supplied as standard without installation accessories. The grille can be installed among others in the following way: 1. with screws through the end walls of the grille. 2. with external flange. 3. With internal flange. (See Figure 1) The ALD in the double model is supplied as two single grilles for assembly at the site. Figure 1. Installation method Maintenance The ALD is under normal operating conditions a maintenance-free external wall grille. After a period of use, it will require conventional cleaning. Figure 2. Environment The declaration of construction materials is available for downloading from our website or can be ordered from one of our sales offices. Accessories - Wire mesh with size 10 x 10 mm mesh: ALDT 1 - Mounting flange: ALDT 2 2 Swegon reserves the right to alter specifications. 20171108

Sizing Dimensions General The velocity of the air flowing through the grille should be checked to prevent inherent sound and high pressure drop problems from arising. To obtain the velocity, divide the volume flow through the grille by its net area. The velocity in the net area should not exceed 10 m/s. The net area can be obtained by multiplying the gross area of the grille by the factor obtained from Diagram 1. Diagram 1. The selected grille s net area can be obtained by multiplying the factor read in the diagram below by the gross area of the grille. Figure 3. ALD Dimension print Nominal width, supplied on request. Nominal height, supplied from 450 mm and in steps on request. E = nominal width - 15 mm. F = nominal height - 15 mm. Size of opening = nominal width x nom. height. For grilles larger than 2400 x 2400 mm report the size of opening from case to case. weights ALD, single model, galvanized sheet steel, approx. 50 kg/m 2 grille surface. ALD, double model, galvanized sheet steel, approx. 100 kg/m 2 grille surface. ALD, single model, aluminium, approx. 20 kg/m 2 grille surface. ALD, double model, aluminium, approx. 40 kg/m 2 grille surface. 20171108 Swegon reserves the right to alter specifications. 3

Sizing / Pressure drop Calculate the gross face area, B x H (m 2 ). Find the relevant airflow in Diagram 2 or 3 (depending on type of grille). Plot vertically upward to the required size of grille (gross). Read the pressure drop that refers to plenum/duct installation. Use Diagram 1 to check that the velocity in the net area does not exceed 10 m/s. If there is no risk of rain water being sucked in, then the velocity must not exceed 2 m/s in the net area. Acoustic data For most ventilation systems, Swegon s acoustic external wall grilles meet the requirements on low sound level emitted to the surroundings. Air volume - Pressure drop Diagram 2 and Diagram 3 show the pressure drop of the ALD with a width of B=1000 mm and various heights. If pressure drop is required for other widths, the air volume must be recalculated. You are welcome to use our ProAc acoustic calculation software which in addition to required sound attenuation also presents inherent sound generation and pressure drop figures for individual products. ProAc is available for downloading from our home page on the Internet. Static integrated attenuation, db Type Static integral attenuation, db to ISO 7235 63 125 250 500 1K 2K 4K 8K ALD-1 2 5 7 12 18 21 16 16 ALD-2 3 9 12 21 32 34 32 32 Diagram 2. ALD type 1. Airflow pressure drop, (gross area) 4 Swegon reserves the right to alter specifications. 20171108

Exemple ALD type 2: The distance between the external wall and the ventilation unit is too short to provide space for a traditional sound attenuator. A sound attenuating ALD, type 2 is installed as an air intake grille. The airflow is 0.3 m 3 /s and the grille is mounted in a duct having a width of 1000 mm and a height of 500 mm. From Diagram 3 we find that the ALD-1000-500, type 1 has a pressure drop of 24 Pa. The gross face area will be 0.5 m 2. Diagram 1 indicates a net factor of 0.13, which gives us a net area of 0.065 m 2. The net velocity will be 4.6 m/s which is too high if there is risk of rain water being sucked into the grille. Select instead the ALD-1000x800, type 1 that has 3 Pa in pressure drop and 1.9 m/s in net velocity. If there is no risk of rain water being sucked in, then 4,6 m/s in net area is acceptable. Figure 4. Models, ALD 1 and ALD 2. Diagram 3. ALD type 2. Airflow pressure drop, (gross area) 20171108 Swegon reserves the right to alter specifications. 5

Ordering key Specification text Product Sound attenuating ALD a aaaa- bbbb- c- d Version Width Height Model 1 = Single 2 = Double Material 1 = galvanized sheet steel 2 = aluminium Example of specification text to VVS AMA. Swegon s rectangular sound attenuating external wall grille, type ALD, with the following functions: Aerodynamically shaped acoustic baffle vanes for the lowest pressure drop/best sound attenuation. Designed for severe climate conditions. Type-approved, sound-insulating material, ISOVER Cleantec PLUS. Size ALDa aaaa - bbbb - c - d xx items ALDa aaaa - bbbb - c - d xx items e tc. Accessories Wire mesh ALDT 1 Mounting frame ALDT 2 6 Swegon reserves the right to alter specifications. 20171108