Circuit Breaker and Transducer: Where do I connect? Robert Foster Application Engineer Megger Paradise, CA 95969

Similar documents
Cost Benefit Analysis of Faster Transmission System Protection Systems

Safe, fast HV circuit breaker testing with DualGround technology

A Cost Benefit Analysis of Faster Transmission System Protection Schemes and Ground Grid Design

Selective Coordination

BCM application note Travel measurement in circuit breaker monitoring

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 6

Good Winding Starts the First 5 Seconds Part 2 Drives Clarence Klassen, P.Eng.

DESIGN AND ANALYSIS OF PRE- INSERTION RESISTOR MECHANISM

Close-Open (Short-Circuit) Time Results Interpretation

Application Note. First trip test. A circuit breaker spends most of its lifetime conducting current without any

ZENSOL AUTOMATION INC.

iracing.com Williams-Toyota FW31 Quick Car Setup Guide

Miniature circuit breaker Application guide

Mechanical Considerations for Servo Motor and Gearhead Sizing

Extracting Valuable Information from HV Circuit Breaker Testing. Charles Sweetser - OMICRON MIPSYCON 2014

White paper: Pneumatics or electrics important criteria when choosing technology

Cam Motion Case Studies #1 and # 2

Utilization of Electric Power Laboratory 3 rd Year G2: Testing & Characteristic of MCCB Used in Commercial and Industrial Applications

White Paper. Phone: Fax: Advance Lifts, Inc. All rights reserved.

PVP Field Calibration and Accuracy of Torque Wrenches. Proceedings of ASME PVP ASME Pressure Vessel and Piping Conference PVP2011-

Circuit breaker interlocking and operation requirements SIEMENS

ETAP Implementation of Mersen s Medium Voltage Controllable Fuse to Mitigate Arc Flash Incident Energy

IMPACT REGISTER, INC. PRECISION BUILT RECORDERS SINCE 1914

Selective Coordination Enforcement:

Analysis of minimum train headway on a moving block system by genetic algorithm Hideo Nakamura. Nihon University, Narashinodai , Funabashi city,

Application of Primary Fuses

A COMPARISON OF THE PERFORMANCE OF LINEAR ACTUATOR VERSUS WALKING BEAM PUMPING SYSTEMS Thomas Beck Ronald Peterson Unico, Inc.

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements

www. ElectricalPartManuals. com Section 13 Switchgear Low Voltage

Study of Fault Clearing by A Circuit Breaker In Presence of A Shunt Capacitor Bank

Components of Hydronic Systems

Chapter 7: DC Motors and Transmissions. 7.1: Basic Definitions and Concepts

Power systems Protection course

Module 6 Assignment Part A

20th. SOLUTIONS for FLUID MOVEMENT, MEASUREMENT & CONTAINMENT. Do You Need a Booster Pump? Is Repeatability or Accuracy More Important?

A Practical Guide to Free Energy Devices

Not all Low Voltage Switchgear is created equal

A comparison of metal-enclosed load interrupter (ME) switchgear and metal-clad (MC) switchgear

Moments. It doesn t fall because of the presence of a counter balance weight on the right-hand side. The boom is therefore balanced.

Arc flash hazard mitigation

A Theoretical, Computational, and Experimental Analysis of an Interdigital Armature in a High Velocity Railgun

Is Your Factory Power Source Corrupting Your Product Testing? September 2015 Author: Steve Boegle Engineering Group Leader, Behlman Electronics

Dynamic Resistance Measurement for Circuit Breakers Applying high DC current

MECHANICAL EQUIPMENT. Engineering. Theory & Practice. Vibration & Rubber Engineering Solutions

EE064D: Circuit Breakers & Switchgears: Design, Testing, Commissioning, Maintenance, Repair & Troubleshooting

Grounding Of Standby & Emergency Power Systems

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14

LEAD SCREWS 101 A BASIC GUIDE TO IMPLEMENTING A LEAD SCREW ASSEMBLY FOR ANY DESIGN

3.2. Current Limiting Fuses. Contents

6/4/2017. Advances in technology to address safety. Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton

Battery Maintenance Solutions for Critical Facilities

WEEK 4 Dynamics of Machinery

Special edition paper

Design Considerations to Enhance Safety and Reliability for Service Entrance Switchboards

TRANSLATION (OR LINEAR)

Input, Control and Processing elements

Autonomously Controlled Front Loader Senior Project Proposal

Inverter control of low speed Linear Induction Motors

Dual Power. Protection. Protection

Chapter 2. Background

837. Dynamics of hybrid PM/EM electromagnetic valve in SI engines

Non-Contact Sensor Performance Report

Types of Motor Starters There are several types of motor starters. However, the two most basic types of these electrical devices are:

Analysis of Switch Gear and Validation

Transmission Switching

Bistable Rotary Solenoid

Step Motor. Mechatronics Device Report Yisheng Zhang 04/02/03. What Is A Step Motor?

Seals Stretch Running Friction Friction Break-Out Friction. Build With The Best!

Arc flash solutions catalogue Australia. Safety solutions - Protecting employees and the enterprise

Field Experiences with HV Circuit Breaker Condition Monitoring

Determination of Spring Modulus for Several Types of Elastomeric Materials (O-rings) and Establishment of an Open Database For Seals*

2000 Cooper Bussmann, Inc. Page 1 of 9 10/04/00

Roehrig Engineering, Inc.

OKLAHOMA CORPORATION COMMISSION REGULATED ELECTRIC UTILITIES 2017 RELIABILITY SCORECARD

NEW CAR TIPS. Teaching Guidelines

Ensuring the Safety Of Medical Electronics

SHAFT ALIGNMENT FORWARD

Recommended Procedures

Cane Creek Double Barrel Instructions

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

Chapter 6 Generator-Voltage System

FEASIBILITY STYDY OF CHAIN DRIVE IN WATER HYDRAULIC ROTARY JOINT

Application Notes. Calculating Mechanical Power Requirements. P rot = T x W

Research in hydraulic brake components and operational factors influencing the hysteresis losses

Selecting the Optimum Motion Control Solution for the Application By Festo Corporation

SOME FACTORS THAT INFLUENCE THE PERFORMANCE OF

LOCOMOTIVE CIRCUIT BREAKER MAINTENANCE TEST SETUP

High Voltage Surge Arresters Buyer s Guide Section Transmission Line Arrester PEXLINK

Evaluating Selective Coordination Between Current-Limiting Fuses And Non Current-Limiting Circuit Breakers

A Fundamental Study Concerning the Proper Performance of Lift Buffers in Revised JIS A 4306

White Paper. Ground Fault Application Guide. WL Low Voltage Power Circuit Breakers

Motor Type Selection. maxon s EC 4-pole brushless motors

Electrical network protection VIP30, VIP35. User s manual 12/2008

Driven Damped Harmonic Oscillations

OKLAHOMA CORPORATION COMMISSION REGULATED ELECTRIC UTILITIES 2018 RELIABILITY SCORECARD

Experimental Question 1: Levitation of Conductors in an Oscillating Magnetic Field

A Revolution in Circuit Breaker Operating Mechanism Technology

CHAPTER 4: EXPERIMENTAL WORK 4-1

Transmission Error in Screw Compressor Rotors

Balancing of aeroderivative turbine

Transcription:

APPLICATION NOTE Circuit Breaker and Transducer: Where do I connect? Robert Foster Application Engineer Megger Paradise, CA 95969 Abstract Time and travel analysis is the most important test used to determine the correct operation of a circuit breaker. Although the majority of technicians perform timing measurements; travel analysis, or motion measurements, are often ignored. The motion measurement of the contacts and mechanism in circuit breakers provide a variety of important information when performing routine testing and maintenance; however it is a practice that is marginalized due to its apparent difficulty and complexity. Bypassing this measurement and its results can lead to a catastrophic failure in the circuit breaker. This paper will illustrate common best practices that simplify the installation of the transducers and will explain the minimum amount of information required for a test plan to obtain meaningful results. Speed calculation points, conversion constants and conversion tables for different manufactures will also be examined. In addition, there will be graphical example results of different transducer attachment points on the same breaker to show and analyze the effects of transducer mountings on travel results. This paper will enable the reader to have a better understanding of where to install the transducer, how to properly set up the test plan, and it shall give guidance for instances where the manufacturer provides a minimal amount of data on travel analysis setup. Introduction There are numerous types of equipment in the electrical transmission and distribution network that all perform a specific and necessary operation, the circuit breaker is no exception as it serves to protect the valuable assets in the substation. The circuit breaker is unique in the fact that at one time it must function as a nearly perfect conductor while at another time it must function as a nearly perfect insulator, transitioning from one state to the other in a matter of milliseconds, occasionally dispersing enormous amounts of energy during the transition. A circuit breaker is defined as A mechanical switching device and the way to determine if the mechanical switching function is working correctly is to hook up a time and travel analyzer to evaluate the operating characteristics of the circuit breaker. When bulk oil circuit breakers were Pg1

the prevalent technology in substations, travel measurements were performed without question. Over the years, because of various reasons such as lack of outage time, lack of maintenance personnel, and the complexity of hooking up a transducer to the circuit breaker, travel measurements are being performed less and less. Time and travel measurements have been replaced with just contact timing or reduced to solely first trip testing. A recent study by CIGRE working group A3.06 released in 2012 found that 50% of the major failures in a circuit were due to the operating mechanism and 30% were due to the electrical control and auxiliary circuits. While contact timing and first trip are important tests and should be performed, they will not fully test the operating characteristics of the mechanism; therefore neglecting travel measurements should not be standard practice if the true health of the circuit breaker is to be determined. Basic measurements made with the transducer Although the transducer can be attached to the circuit breaker to determine the travel of different parts of its components such as the dashpot, the primary application of a motion transducer is to measure the motion of the main/arcing contacts in the circuit breaker. For the context of this paper, the transducer representing the motion of the main/arcing contacts shall be the focus. The transducer can be hooked to many different parts of the circuit breaker, directly to the pull rod of the main contacts, directly to the mechanism, somewhere on the linkage in between or even to an auxiliary switch. Many parameters are determined from the transducer but the most important measurement is the stroke of the circuit breaker, in fact all other parameters are derived from the stroke of the circuit breaker. The stroke is defined as the total travel distance of the contacts from resting position in one state, e.g. Closed, to the resting position in the other state i.e. Open or vice versa. It is imperative that one is diligent in connecting the transducer to the manufacturer s recommended attachment point on the circuit breaker and correcting for any multiplication factors if a direct connection to the contacts cannot be made. At the very least the technician must be consistent in measuring the stroke through periodic maintenance in order to trend the results. If the circuit breaker is gang operated i.e. it has one mechanism operating all 3 three phases then only one transducer is needed, if the circuit breaker has separate operating mechanisms for each phase, then an individual transducer should be used for each mechanism. Once the stroke of the circuit breaker is determined you can derive the velocity of the contacts in different regions of the travel. The most Pg2

common region to measure velocity is during the arcing zone of the circuit breaker where it is actually interrupting or clearing the fault. Occasionally damping is also measured on the travel curve by calculating the velocity in the damping zone or the time between two predefined points on the travel curve in the damping zone. By observing the closing time along with the travel measurement the penetration or contact wipe can be determined, this is how far the contacts are engaged. Penetration is the length measured from initial contact touch to the final resting position after the operation. Overtravel is measured directly from the travel curve and is the maximum displacement past the resting position that the contacts reach during the operation. Similarly, Rebound is measured from minimum displacement, after the maximum displacement (Overtravel), to the final resting position of the contacts. See Figure 1 for examples of the different parameters that can be measured with a travel transducer. Other parameters can be determined as well but they are all derivatives of the actual stroke measurement of the contacts so it is important to connect the transducer correctly and to accurately measure the stroke of the circuit breaker. Pg3

Types of transducers and the parameters needed for proper measurements There are two types of transducers used to measure the contacts of the circuit breaker, linear or rotary. A linear transducer will measure a value of length typically in either inches or millimeters whereas a rotary transducer will measure a value of angle, typically degrees, which then must be converted to inches or millimeters. There are various designs of transducers such as resistive, optical, magnetic etc. but they generally give an analog or digital output. Linear transducers are available in a wide variety of lengths ranging from 25 mm or less, commonly used for vacuum circuit breakers, all the way up to 1000 mm or more, typical lengths are from 225-300 mm for SF6 dead tank circuit breakers and 500-600 mm for bulk oil circuit breakers. When first setting up for motion measurements, the type of transducer to be used, rotary or linear, must be selected. Although a lot of breakers allow you to use either type of transducer, the manufacturer generally will specify a preference and it is always recommended to use the manufacturer s specified attachment point, transducer type, and conversion factor (if needed). Caution: Before connecting the transducer, always ensure that the circuit breaker is in the open position, make sure no energy is stored in the mechanism, or if it is impractical to discharge all the energy in case of some pneumatic or hydraulic mechanisms, make sure the maintenance pin that blocks operation is set, finally de-energize the power going to the control circuitry. No matter where the transducer is placed, no part of the transducer, mounting bracket, or travel rod if used, must be in the direct path of any moving parts of the circuit breaker that will cause damage to the transducer or its accessories. If a linear transducer is used it must be of suitable length to cover the total travel distance the transducer will encounter, including overtravel, on both close and open operations. If unsure of whether the transducer is of suitable length, a common practice is to attach the transducer in one position e.g. closed, then detach the transducer and operate the circuit breaker so it changes state. Now that the circuit breaker is in the opposite position i.e. open, re-attach the circuit breaker to see if it is of suitable length. Once a transducer of adequate length is selected, the next consideration in size is to make sure the transducer will fit in the space provided. There are two types of measurements made with a linear transducer, the first is a direct measurement as in Figure 2, where the transducer or linkage rod is connected directly to the moving contacts; direct measurements are common in bulk oil circuit breakers, minimum oil breakers, most vacuum CBs and some dead tank SF6 circuit breakers. Although finding a suitable mounting bracket and correctly mounting the transducer can be difficult at times, this method is beneficial because the actual stroke of the transducer is equal to the Pg4

actual stroke of the contacts, therefore no conversion factor is needed and all parameters measured with the transducer are direct representatives of the motion of the contacts in the circuit breaker; the motion isn t distorted by any gears, linkages or mechanical play of the interconnections. The second type of measurement with a linear transducer is an indirect measurement as in Figure 3, where the transducer is not connected directly to the moving contacts but to a part of the circuit breaker that is connected to the moving contacts such as the mechanism or interconnecting linkage. When this type of connection is used, the travel of the transducer may or may not be equal to the travel of the main contacts. If the travel of the transducer is different, a conversion factor or ratio should be used in order to obtain the correct stroke length and travel parameters of the circuit breaker. For example, 80 mm of transducer stroke can be equivalent to 120 mm of contact stroke so a multiplication factor of 1.5 shall be used. Pg5

When a rotary transducer is used, the measured quantity is in degrees, or occasionally radians, and is then converted to a unit of length. There are two types of conversions, the first is a constant conversion where one degree is equal to a certain value of length throughout the entire travel of the contacts. This is common where the mechanical linkage is simple with few interconnecting parts. When the linkage is more complicated, the ratio of the angle to length may not be constant throughout the total travel of the contacts i.e. one degree might equal one and a half millimeters for the first ten degrees then for the next ten degrees of travel, one degree might equal two and a half millimeters. In these cases a conversion table must be used to account for the varying values. Rotary transducers have the advantage of being relatively small and with a few accessories one kit can hook up to many different styles or types of circuit breakers. The disadvantage of the rotary transducer is that you need to know the conversion factor or table in order to calculate the correct parameters of your circuit breaker. If the conversion factor or table is not provided in the manual, the breaker manufacturer should be contacted. Rotary transducers are most common on live tank SF6 circuit breakers but are also used on certain types of dead tank SF6 breakers, bulk oil circuit breakers and generator circuit breakers. See Figure 4 and Figure 5 for examples of rotary transducer connections. Pg6

Circuit Breaker and Transducer: Where do I connect? Pg7

Once the proper transducer, and conversion factor if needed, is selected, most of the parameters such as stroke, overtravel, rebound, penetration etc. will come out of the measurements automatically. One of the exceptions to this is the velocity measurement. In order to calculate the velocity the analyzer must be told where on the curve velocity should be measured. Two different points on the travel curve are selected and the average velocity between these two points is calculated. These points can reference many different points on the curve such as distance below close, distance above open, percentage of stroke, distance below upper point etc. Another common reference point is an event during the timing e.g. contact touch or contact separation. The two most important factors that influence the selection of the speed calculation points are that the velocity is measured on a linear portion of the travel curve and that it is measured during the arcing zone, therefore the calculation points are generally near contact touch on the close and contact separation on the open. A common misconception for calculating velocity is to take the total travel distance (stroke) and divide it by the total time it takes for the contacts to reach the fully closed position, this will not determine the velocity during the arcing zone but the average velocity for the total travel. In this case the acceleration at the beginning of the travel and deceleration at the end will mask the instantaneous velocity around the arcing zone. The speed calculation points can vary by manufacturer, type of circuit breaker, type of mechanism etc. so the manufacturer should be consulted to select the proper speed calculation points; this information is generally available in the manual or in the original test report provided with the circuit breaker. If no information is given, it is recommended to use contact touch and 10 ms before for the close calculation points and contact separation and 10 ms after for the open calculation points. See Table 1 for a list of common transducer types and speed calculation points used by different manufacturers. Note: the manufacturer or manual should always be consulted for proper transducer and speed calculation points. Pg8

Case study of Siemens SPS2-38-40-2 Circuit Breaker In order to investigate how transducer placement affects travel measurements, several transducers, both rotary and linear, were attached to a Siemens SPS2-38-40-2 SF6 dead tank circuit breaker fitted with an FA2.20 mechanism. The breaker is rated at 38kV and capable of interrupting 40kA, it has one break per phase and is gang operated, see Figure 6 and Figure 7. Siemens recommends measuring motion with a linear transducer that is attached to an actuating arm on the mechanism (Figure 8). They state that 80 mm of travel at the mechanism is equal to 120 mm of travel at the contacts i.e. there is a 1.5 multiplication factor used to determine the true contact motion. They also state that the speed calculations points of Contact Touch and 10 ms before for the close operation and Contact Separation and 10 ms afterwards for the open operation shall be used. In addition to the standard transducer connection, four more transducer connections were made; one linear transducer was connected to the end linkage arm on the third phase and three rotary transducers were attached to the rotating splines that drive the interrupter (Figure 9). The same speed calculation points were used for all connections. Pg9

Circuit Breaker and Transducer: Where do I connect? Pg10

Circuit Breaker and Transducer: Where do I connect? In order to compare the different transducer measurements, at first no conversion factors were used on the two linear transducer connections and a factor of 1 degree equals 1 millimeter was used for the rotary transducer. In Figure 10 below you can see the motion traces from the three different connections for a close operation, all three are scaled at 10 mm per division. M A on the graph in red is the linear transducer connected directly to the mechanism per Siemens recommendations, this will be referred to as Linear A. M B in black is the rotary transducer and is connected to the rotating spline on B Phase, this will be called Rotary B. Lastly M C in blue is the linear transducer connected to the end of the interconnect linkage near the rotating spline on C phase and shall be referred to as Linear C. For all graphs, the bottom of the curve is the fully open position and the top of the curve is the fully closed position. The timing for each phase is also included where a thin line is open and a thick line is closed. From the timing results, all three phases are relatively in sync with 0.3 ms difference between the slowest and the fastest phase with a close time of about 48 ms. As expected, the travel measurements vary widely due to the different connection points. The stroke for Linear A is 78.9 mm, Rotary B is 59.0 mm (degrees) and Linear C is 106.5 mm. From these stroke measurements the travel dependent parameters i.e. velocity, overtravel, penetration, rebound etc. will all vary by transducer placement as well. Pg11

An examination of the open operation will show similar variance in stroke values for the different connections as seen in Figure 11. As mentioned above, the circuit breaker manual states that 80 mm of motion at the mechanism is equivalent to 120 mm of contact movement, therefore with a transducer stroke of 78.9 mm the contact stroke is determined to be 118.35 mm. Since the other transducers were measuring motion on the same operation, the ratios of the alternate linear transducer and rotary transducer can be calculated. Using simple algebra the ratios of 59.0 = 118.35 mm (Rotary B) and 106.5 mm = 118.35 mm (Linear C) are used to determine the conversion factors of 2.003 mm/ and 1.1099 mm/mm respectively. With this information the circuit breaker was measured again with the appropriate conversion Pg12

factor applied to each transducer. The results are shown in Figure 12, Figure 13, Figure 14, and Figure 15. Pg13

From the results above it can be seen that even with three different transducer attachment points and two different types of transducers, that all three produce very similar results as long as the correct conversion factor is applied. The maximum difference between stroke values is 0.2 mm on the close operation and 0.5 mm upon opening. Penetration, overtravel, and rebound are very close for the three different measurements too. One interesting observation is that the travel trace of Linear A, the linear transducer connected directly to the mechanism, has an oscillation throughout the entire movement, and Linear C, the linear transducer connected to the end of the linkage, has a slight oscillatory movement at the beginning and the end of travel. Most likely the flex in the travel rod and the connection of the rod to the transducer is causing some of this movement. Additionally since Linear A is connected directly to the mechanism, the vibrations of the mechanism are affecting the motion throughout the entire travel. Pg14

Since the close operation requires more energy, closing the breaker and charging the opening spring, this effect is more apparent on the close operation. One interesting note is that the velocity is different for each connection, this is in part due to the calculation points being based on contact touch and separation so the variance in the timing will affect where on the curve the velocity is calculated. On Linear A the vibrations will also affect the velocity calculations, if one of the speed calculation points rests on the crest of an oscillation and the other speed calculation point rests on the trough of an oscillation, the speed can vary dramatically compared to points taken on a neutral part of the oscillation. This effect can be seen by examining several operations in a row and observing that the velocity of Linear A can vary by 0.16 m/s or 3%, whereas the other two connections vary by a magnitude less. Play in the linkages will have some effect on the velocity calculations. One last thing to consider is that a linear conversion factor was assumed, i.e. a conversion constant was used. Comparing Rotary B to Linear C, they align better at the beginning and a the end of travel, in the middle of the movement they diverge slightly, since this is the portion of the curve that velocity is calculated, it follows that the speeds would diverge slightly as well. If the geometries were analyzed and a conversion table was built for both connections, they would most likely overlap throughout most of the travel and the velocities would align more closely. The motion traces of the three different rotary transducers can be examined to see how the same connection can be placed at different distances from the mechanism, i.e. at different parts along the interconnecting linkages, and yield similar results. Figures 16 and Figure 17 show the results from a close operation. M A on the graph in red is the rotary transducer connected directly to the rotating spline that drives the interrupter in A phase, this will be referred to as A phase. Similarly M B in black is the rotary transducer connected to Phase B and will be referred to as B phase. Lastly M C in blue is the rotary transducer connected to Phase C and shall be referred to as C phase. Pg15

Once again all three traces are very similar with a variance in stroke of only 1.2 mm between the shortest and the longest phase. A few things to note are that A phase begins to move approximately 0.5 ms before phases B and C which can be expected since it is the closest connection to the mechanism. Both A and C phase produce very smooth traces throughout the motion but B phase has some oscillations in the first 20 ms of travel. These oscillations are most likely due to a mechanical delay, B phase is pushed by the linkage from A phase and then it has to push the linkage to phase C. Any mechanical play within the connections between B and the other two phases will result in small perturbations. The velocities of A and C are fairly close but B phase is 0.2 m/s slower. This is most likely caused by two different factors, first the oscillations in the trace can cause different speed points to be taken as mentioned above, secondly the timing of the three phases is slightly different and Pg16

the speed calculation point is based on contact touch, careful observation of the speed calculation points reveals that they do not line up in time. Observing the open operation in Figure 18 and Figure 19 shows even more consistency between the different phases. All three traces practically lay on top of each other with no deviation until the contacts reach the closed position. The stroke of the different phases is closer with only a 0.5 mm difference between the shortest and the longest phase. Once again the velocities of the three phases are different but observing the contact times and speed calculation points shows that the velocity is calculated at slightly different points on each curve thus Pg17

changing the values slightly. If the speed calculation points are changed to reference below closed and a differential, then B and C travel at the same velocity while A phase travels slightly slower due to it having to push the other two phases. What to do if very little or no information is provided by the manufacturer Occasionally the manufacturer may not provide the appropriate information for travel measurements and it is left to the technician to decide what type of transducer to use and where to connect, what conversion factor/table to use (if any) and the proper speed calculation points for determining the velocity of the contacts. Careful consideration should be taken before attaching a transducer and once a method is determined, the same attachment and measurement parameters should be used in the future for trending purposes. Although these travel recordings will provide valuable data and can be used for future reference, it should be noted that the values obtained may not necessarily be comparable to the factory test reports or parameter limits. Once again, no matter where the transducer is placed, no part of the transducer, mounting bracket, or travel rod if used, must be in the direct path of any moving parts of the circuit breaker in order to avoid damage to the transducer and its accessories. The first thing to look for in deciding where to connect the transducer is if connection directly to the contacts or actuating arm of the contacts is possible. Then a linear transducer can be connected and the correct stroke, velocities and other parameters will be measured without the need of a conversion table. If direct connection to the contacts is not possible, which is often the case, then a spot that is very close to the contacts with the minimal amount of linkages between the connection point and the contacts should be selected; either a linear or rotary transducer can be used. Per IEC 62271-100, the mechanical characteristics can be recorded with a travel transducer at convenient locations on the drive to the contact system where there is a direct connection, and a representative image of the contact stroke can be achieved. Connecting directly to the mechanism can cause unwanted vibrations and influence the results, if possible this should be avoided. If an indirect connection is used then there are two options, create a conversion table/factor, or measure the absolute value of the motion, in either length or angle, and trend the results with the transducer connected in the same spot during future testing. If a conversion factor or table is to be used, the connection points and linkages can be examined and measured to develop a trigonometric function that relates the transducer movement to the contact motion. The function can also be determined from the mechanical drawings of the circuit breaker. Pg18

If the stroke of the contacts are known, another, less accurate, method of creating a conversion factor is to assume a linear relationship between the connection point and the contacts. The known stroke of the contacts can be divided by the measured stroke of the transducer to create the conversion factor. This value can then be used to measure the travel characteristics for initial fingerprint measurements and future testing. It should be noted that if the relationship between the connection point and the contacts is not linear, the other stroke dependent parameters such as velocity, overtravel, rebound etc. may not be correct. Additionally, if this measurement is made when there are issues with the circuit breaker i.e. the stroke is not correct, the subsequent measurements will also be incorrect. If there are other circuit breakers of the same type available it is beneficial to compare measurements to verify the correction factor. If no speed calculation points are provided by the manufacture then it is recommended to use contact touch and 10 ms before for close and contact separation and 10 ms after for the open. This will assure that the velocity is measured in the critical arcing zone of the interrupter. Once again it should be mentioned that once a method of transducer connection, conversion factor, and speed calculation points are used, they should continuously be employed through the life of the circuit breaker in order to trend the results. Conclusion Circuit breakers are a key element in the electrical transmission and distribution network throughout the world. IEEE C37.09 states that Travel-time curves shall be obtained for all outdoor circuit breakers with an interrupting time of three cycles or less and NETA requires time and travel analysis on medium and high voltage SF6 and Oil circuit breakers. In order to verify that the circuit breaker will operate effectively when called upon to protect various assets in the network, time and travel analysis must be performed. When determining what type of transducer should be used, where it shall be connected, and what conversion factor and speed calculation points are to be applied, the first step to be taken is to consult the manual, if there is no directions contained in the manual or if the directions are unclear, the next step is to contact the manufacturer. If this option is not available either, then the technician performing the testing must decide how to proceed. Preferably a direct connection to the contacts shall be obtained but if this is impractical, a connection point that is near the contacts with a minimal amount of linkage that can accurately represent the travel of the contacts shall be used. If the geometry of the circuit breaker is known, a conversion factor or table can be created to accurately measure the stroke and the parameters that are dependent on the stroke. Pg19

Even if the original measurement points that the manufacturer used are not known, valuable data will still be measured with a transducer as long as it is placed in a sensible location. In fact, even if motion is measured at different points on the circuit breaker, as long as the correct conversion factor is applied, the results will come out very similar. If an accurate conversion factor or table cannot be created or is not known, the absolute value of the transducer stroke and its parameters can be measured upon commissioning or when the circuit breaker is in a known good condition. These values can then be trended over time to track any changes in the movement or operation of the circuit breaker. Lastly, once one type of connection and conversion factor is chosen, all future measurements should be made using the same setup in order to correctly trend the results. Bibliography IEEE Std C37.100-1992 (R 2001) IEEE Standard Definitions for Power Switchgear CIGRE TB 510: Reliability of High Voltage Equipment Part 2: SF6 Circuit Breakers; WG A3.06; 2012 Siemens Type SPS2-38-40-2 Circuit Breaker Manual IEC 62271-100: International Standard High-voltage switchgear and controlgear Part 100: Alternatingcurrent circuit-breakers CBTestingGuide_AG_en_V02: Megger Circuit Breaker testing guide 2012 IEEE Std C37.09-1999 (R2007): IEEE Standard Test Procedure for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis NETA ATS 2013: Standard for Acceptance Testing Specifications Pg20