Principals of Operation... 1 Rotary Vane Priming Pump VPE and VPES... 2 Rotary Vane Priming Pump VPO and VPOS Priming Valve...

Similar documents
Table of Contents Illustrations

Priming Systems Installation Instructions

S200-P Series Centrifugal Fire Pumps Operation and Maintenance Instructions

HL Series Centrifugal Fire Pumps Operation and Maintenance Instructions

Operation and Maintenance. CG Series Centrifugal Fire Pumps. Illustrations

S200-G Series Centrifugal Fire Pumps Operation and Maintenance Instructions

Operation and Maintenance. S100 Series Centrifugal Fire Pumps. Table of Contents. Visit us at F /22/02 6/21/18

Table 6-1. Problems and solutions with pump operations. No Fluid Delivery

Operation and Maintenance. CS Series Centrifugal Fire Pumps. Table of Contents. Visit us at F /14/95

Eclipse GEN 2.0 CAFSystem, Model 150-ESECL as used with TC20 Series PTO Installation Instructions

Eclipse GEN 2.0 CAFSystem, Model 150-ECL CAFS PTO Kit Installation Instructions

Installation. Installation. 12. System Diagram... 10

M-3025CB-AV Fuel Pump

Vane Pumps. Single Stage Single and Double Vane Pumps. Vickers. Overhaul Manual

TWO-STAGE HYDRAULIC PUMP. RWP55-IBT-Air

MAINTENANCE MANUAL FOR THERMOSTATIC TEMPERATURE REGULATING VALVE TRAC STYLE P

ESCONDIDO FIRE DEPT TRAINING MANUAL Section DRIVER OPERATOR Page 1 of 10 Apparatus Service Tests Revised

Operating Manual for Rotary Gear Pumps CMI, S.A. (Mendaro, Guipuzkoa, Spain)

HL Series Centrifugal Fire Pumps Installation Instructions

FTM-L SERIES SINGLE OR TWIN DIRECT STEAM MIXER KETTLE COMPLETE WITH HYDRAULIC POWER TILT BRIDGE PARTS AND SERVICE MANUAL

Hydraulic Maintenance & Troubleshooting. Content - Norman Kronowitz Presenter Jim Trinkle

CP-1, CP-2, CP-2L & CPD-2 Series Overhaul

Electric Diesel Pump EDP/12, EDP/24

KP-C Series. Close Coupled End Suction Centrifugal Pumps. Installation, Operation and Maintenance

CAB TILT HYDRAULIC SYSTEM

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

INSTRUCTIONS FOR INSTALLATION, START-UP, AND OPERATION

AHFP-im-issue INSTRUCTION MANUAL HIGH FLOW DIESEL PUMP AHFP70LPM (70LPM) AHFP100LPM (100LPM) AHFP150LPM (150LPM) AHFP70LPM AHFP100LPM AHFP150LPM

D/G-10 Maintenance. Daily. Shutdown Procedure During Freezing Temperatures. Periodically

k. Components not properly adjusted. Refer to machine technical manual for proper adjustment of components.

High Rise Fire Pumps CM/CGV Series, CMU/CGV Series. Operation and Maintenance

Water Treatment Plant Maintenance Considerations. Operation and Maintenance. Types of Maintenance 5/1/15

Section 10 Chapter 17

TILLOTSON LTD., CLASH INDUSTRIAL ESTATE, TRALEE, CO. KERRY, IRELAND PHONE: FAX:

SERVICE PARTS LIST SPECIFY CATALOG NO. AND SERIAL NO. WHEN ORDERING PARTS 13 HP DIRECT DRIVE PRESSURE WASHER CATALOG NO

INSTRUCTION MANUAL ELECTRIC DIESEL PUMP KIT

Air-Assist Service Jack Max. Capacity: 10 Tons

CH-4 Series Fire Pumps Overhaul Instructions

D-04/G-04 Maintenance

LAWN SPRINKLER, IRRIGATION PUMP

L-l0 Cumins Turbo charged engine needs five minute cool down at idle speed. Wisconsin engine needs five minute cool down at idle speed

AIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST

CL Series Centrifugal Fire Pumps Installation Instructions

W & Y Series Split Shaft Transmission Operation & Maint.

AIR/HYDRAULIC INJECTION GUN MODEL INSTRUCTIONS

Click Here for Printable PDF File. CHAPTER 3 - BASIC INFORMATION for PERFORMING HYDRAULIC SYSTEM MAINTENANCE

CIRCLE SEAL CONTROLS

Troubleshooting The Transmission Hydraulic System

SERVICING INSTRUCTIONS

RELEASING PRESSURE IN THE HYDRAULIC SYSTEM,

Air Trap TATSU2. Copyright 2013 by TLV CO., LTD. All rights reserved ISO 9001/ ISO M-02 (TATSU2) 7 August 2013.

Free Float Air Trap JA3 JAF3 / JA5 JAF5 JA7 / JA7.2 / JA7.5 / JA8

STERILMATIC DIGITAL ELECTRIC STERILIZER PARTS AND SERVICE MANUAL

AMB100L-im-issue INSTRUCTION MANUAL 240V DIESEL MINI BOWSER AMB100L AMB100L

OWNERS MANUAL INSTALLATION AND OPERATING INSTRUCTIONS REPAIR PARTS LIST. Centrifugal Pump Primer MODEL 6D, HAN-DEE PRIMER

Electric Fuel Pump FPM

Troubleshooting:Passenger Car

Operating instructions Form no safety definitions

LIQUIDYNAMICS Light Viscosity Bulk Transfer Cart

HALLMARK INDUSTRIES INC

Body type location. Model number location. Small Engine Parts

ESCONDIDO FIRE DEPT TRAINING MANUAL Section DRIVER OPERATOR Page 1 of 13 Pumps and Accessory Equipment Revised

Voltmaster Centrifugal Trash Pumps

PROCESS PUMPS (INDIA) PVT LTD

S200-P Passport Series Fire Pump Service Parts List

INSTRUCTION MANUAL. Series PROCUNIER SAFETY CHUCK CO. (Serial Nos. B4870 and higher. (Serial Nos. B9230 and higher

Return to Instruction Sheet index TCI Installation Instructions for Turbo Hydramatic 350C & 250C

IMPORTANT OPERATING CONDITIONS. Failure to comply with any of these conditions invalidates the warranty. STANDARD CONFIGURATIONS

M-150S Series 12-Volt Fuel Pump M-150S-B100-MU Manual Nozzle & M-150S-B100-AU Automatic Nozzle Owner s Manual

AJAX PUMPS PUMPS AJAX. ~Pli~r. on s SYDNEY BRISBANE ADELAIDE PERTH. ~Pli~[ ODS ~ISTON PURPOSES

4 - Way Control 4 - Way Control 4 - Way Control with lock

PB18 SERIES PORTABLE PUMPS

TC Series Cooling Systems

Maintenance. Daily. Shutdown Procedure. Periodically. During Freezing Temperatures

M-1115S Series Fuel Pump

CH.4 Basic Components of Hydraulic and Pneumatic System/16 M HAP/17522/AE5G

NECO Pumping Systems

3" & 4" Cast Iron Self-Priming Centrifugal Pump Instruction Manual

barmesapumps.com IB SERIES & 3500 RPM Installation, Operation & Maintenance Manual End Suction Centrifugal Pumps

Under Axle Jack Max. Capacity: 25 Tons

Troubleshooting 3Z8 038 Rev B

One Step CAF System Operation and Maintenance Instructions

Service Manual #67. Installation and Service Instructions 6000, 7000 & 8000 Series Magnetically Coupled Pumps

TYPE E Main Valve Sizes 3 /8 through 12

Operating and Maintenance Manual Gas & Diesel Engine Powered Self-Priming Trash Pumps Series

COYOTE ENTERPRISES, INC. 9/10 BLAST WHEEL MAINTENANCE & ASSEMBLY MANUAL

1 Green Pressure Regulator Spring Automatic transmissions operate at temperatures between 150ºF and

Troubleshooting the Transmission Hydraulic System


Installation Vertical Pump: Installation 'CM' and 'CDM' Style: Operation:

P-200 Plastic Utility Pump for Petroleum Products

Cla-Val. Service Training Manual. Simple solutions plus learning with a purpose

D/G-35 Maintenance. Shutdown Procedure During Freezing Temperatures. Daily. Periodically

PO Box 645, Stockton, Missouri, FAX superiorgearbox.com W D0446-A 4/1/05 1

COLT 2310, 2510, AND 2712 COM PACT TRACTORS CHAPTER 9 TROUBLESHOOTING AND ANALYSIS

Instruction Manual. Maximum Operating Pressure 510 bar

INSTRUCTION MANUAL INTERNAL GEAR PUMP TITAN G-4124A SERIES=> FLANGED TITAN G-124A SERIES => FLANGED MODELS:

OPERATING INSTRUCTIONS & SERVICE MANUAL BLUE MAX II HYDROSTATIC TEST PUMP

barmesapumps.com CD SERIES RPM Installation, Operation & Maintenance Manual End-Suction Centrifugal Stainless Steel Pumps

Medium and high pressure pumps

Transcription:

Priming Systems Installation Priming Systems Operation & Maintenance Form No. F 1031 Section 2312 Issue Date 10/07/94 Rev. Date 02/27/06 Table of Contents Illustrations Principals of Operation........................... 1 Rotary Vane Priming Pump VPE and VPES.......... 2 Rotary Vane Priming Pump VPO and VPOS......... 3 Priming Valve..................................... 4 Operating Instructions............................ 6 Models VPE, VPES, VPO, VPOS (Electric Operation).. 6 Manual Hand Primer............................... 6 Maintenance Instructions......................... 7 Priming Pump..................................... 7 Priming Valve..................................... 7 Priming Tank...................................... 7 Manual Controls................................... 7 Testing........................................... 7 Rotor Clearance Adjustment........................ 7 Vanes............................................ 7 Service Suggestions.............................. 8 Models VPE, VPES, VPO, VPOS.................... 8 Wiring Diagrams................................. 10 1.. Priming System........................ 1 2. Rotary Vane Priming Pump.............. 2 3. VPES Priming Pump................... 2 4. Rotary Vane Priming Pump.............. 3 5. VPOS Priming Pump................... 3 6. Priming Valve (Manual Electric).......... 4 7. Solenoid Actuated Priming Valve......... 4 8. Manual Electric Priming Valve........... 5 9. Solenoid.............................. 8 10. Wiring Diagram........................ 10 Tables 1. Switch and Solenoid Wires............... 10 2. Wire from Battery to Motor............... 10 Waterous Company 125 Hardman Avenue South, South St. Paul, Minnesota 55075 USA (651) 450 5000 Instructions subject to change without notice. All content in this instruction is property of the Waterous Company. Instructions subject to change without notice.

Principles of Operation Before any centrifugal pump can be operated, it must be primed. Priming is the process of replacing air in the intake lines and portions of the pump with water. If the pump is to be operated from draft, priming must be done by means of a positive displacement pump, or some other device for creating a partial vacuum. Also, when pumping from a water tank, priming will be accomplished more quickly and positively if a priming device is used. Priming will occur naturally when pumping from hydrants or in relay, because inlet water pressure is high enough to force air out of the pump and intake lines, providing a discharge line is opened to permit the air to escape. A Waterous priming system consists of a priming pump and a priming valve. The priming pump draws air out of the centrifugal pump through the priming valve. The priming valve must be open when priming the pump and then closed when the pump is fully primed (pumping water with all air removed). On some models, a lubricant is needed to help seal and lubricate the priming pump. Pumping from Draft To obtain a quick prime & maintain pump performance: a.) Position pump as near as possible to water supply. b.) Avoid humps or sharp bends in intake hose. Make sure no part of hose is higher than pump intake inlet. (Air pockets in intake hose may cause loss of prime or erratic pump action and may reduce pump capacity.) c.) Make sure all intake connections are tight and discharge valves are closed. d.) Always use an intake strainer or screen. e.) Immerse intake strainer at least two feet below water surface to prevent pump from drawing air. (Whirlpools forming above intake strainer indicate that strainer is too close to surface of water.) f.) Make sure intake strainer is far enough from bottom to prevent pumping sand, gravel or other foreign matter. Figure 1. Priming System Note: If pump fails to prime or loses prime, refer to the troubleshooting guide in form F 1031, Section 1000. IL2130 Page 1 of 10

Rotary Vane Priming Pump VPE and VPES Rotary vane priming pumps are available separately mounted (model VPES) or transmission mounted (model VPE). The VPE and VPES models are driven by an electric motor. The VPE and VPES models each contain one eccentric rotor with three vanes that slide in and out of the rotor. On the VPE and VPES models, during operation, lubricant from the auxiliary priming tank provides lubrication and an air tight seal between the vanes and pump casing. As the rotor turns, air is drawn from the priming valve inlet due to the vacuum created behind the priming pump. As the priming pump evacuates the air from the lines and the main pump, atmospheric pressure forces water into the pump. A check valve in the tubing line prevents possible back flow of water into the priming tank. An orifice controls the lubricant flow from the priming tank. Figure 2. Rotary Vane Priming Pump Figure 3. Model VPES Priming Pump INLET FROM PRIMING VALVE Motor Ground Post from DPL82082 OUTLET TO ATMOSPHERE This electric motor driven rotary vane primer is used for separately mounted applications. With the priming valve and lubricant supply tank, it forms a complete, dependable priming system. 1044 Page 2 of 10

Rotary Vane Priming Pump VPO, VPOS Models Rotary vane priming pumps are available separately mounted (model VPOS) or transmission mounted (model VPO). The VPO and VPOS models are driven by an electric motor. The VPO and VPOS models each contain one eccentric rotor with four vanes that slide in and out of the rotor. As the rotor turns, air is drawn from the priming valve inlet due to the vacuum created behind the priming pump. As the priming pump evacuates the air from the lines and the main pump, atmospheric pressure forces water into the pump. An optional lubricant tank is available for use with VPO/VPOS models to provide additional lubrication and sealing. Figure 4. Rotary Vane Priming Pump Figure 5. Model VPOS Priming Pump Motor Ground Post (24 V Model) Motor Ground Post (12 V Model) from DPL82082 This electric motor driven rotary vane primer is used for separately mounted applications. With the priming valve, it forms a complete, dependable priming system. IL2067 Page 3 of 10

Priming Valve The valve consists of a stainless steel sliding plunger in a bronze valve body that contains three inlet ports and an outlet. A rubber insert in the plunger is forced against the seat in the body when the valve is closed, assuring a tight seal between the inlets and the outlet. A relief groove in the valve body connects one inlet port to the area behind the plunger. When the main pump is operating, pressure at the rear of the plunger is at least equal to that on the opposite end of the plunger. This feature prevents the priming valve from opening accidentally. When the valve is opened during priming operation, it allows a uniform air flow from the various main pump passages to the priming pump. After the main pump is primed, the priming valve is closed to prevent air from leaking into the pump. Figure 6. Priming Valve (Manual Electric Shown) Control Rod to Panel PULL PUSH Bronze Valve Body Rubber Plunger Insert Stainless Steel Sliding Plunger Operating Arm Outlet Port to Priming Pump Relief Groove Inlet Port (3) TO PRIMING PUMP MOTOR OR CLUTCH Switch PUMP INTAKE PASSAGE 1165 Page 4 of 10

Figure 7. Solenoid Actuated Priming Valve Figure 8. Manual Electric Priming Valve Switch Cover from DPL82083 from DPL82083 This valve is identical to the manual electric valve except the switch on the end of the valve is replaced with a solenoid. Priming with this valve is fully automatic. Pressing a push button switch on the control panel actuates a solenoid on one end of the priming valve to open it, and at the same time starts the priming pump. Releasing the switch closes the priming valve and stops the priming pump. This valve has a switch on one end enclosed in a housing. As the valve is manually opened, an internal plunger closes the switch to start the priming pump. Releasing the valve control opens the switch to stop the priming pump. Page 5 of 10

Operating Instructions Models VPE, VPES, VPO, VPOS (Electric Operation) 1. Close discharge valves, drain valves and all other openings. 2. Make sure all intake connections are tight. 3. Open priming valve as described below. (As valve opens, the priming pump starts automatically.) Manual Electric Valve A rod leading out to the control panel operates this valve. As the rod is pulled (or pushed, if so installed), it closes a switch mounted on the valve to start the priming pump. Solenoid Actuated Valve Depressing the priming switch button on the control panel simultaneously opens the solenoid operated valve, and starts the priming pump motor. (If the solenoid should fail to open the valve, it can be opened manually.) If a manual override control is installed for solenoid actuated priming valve, make sure it moves out (or in) when you press the switch button. If it does not move, then operate the manual control while pushing the switch button. As soon as possible after operation, determine why it did not operate, clean and lubricate or repair as necessary. Manual (Hand) Primer 4. Operate priming pump until it discharges a solid stream of water through its discharge outlet. NOTE: If priming pump does not prime main pump and discharge a steady stream of water within 30 seconds (1250 gpm or smaller) or 45 seconds (1500 gpm or larger), stop pump and determine cause of problem. (An additional 15 seconds may be required if the truck is equipped with a 4 inch or larger front or rear intake pipe.) CAUTION Operating the priming pump for more than one minute continuously may damage the electric motor and/or motor solenoid. 5. After main pump is primed, release valve control. NOTE: The motor and solenoid are NOT rated for continuous duty. If possible, allow primer to be OFF for a minimum of one minute between uses. 1. Close discharge valve(s), drain valves and all other openings. 2. Make sure all intake connections are tight. 3. Open priming valve. 4. Start main pump and immediately begin pumping the primer handle (to minimize time the pumps runs dry) until water begins exiting the primer outlet. 5. Close priming valve and open main pump discharge valve(s). Page 6 of 10

Maintenance Instructions Priming Pump During operation of VPE model and VPO model with optional lubricant tank, lubricant from the priming tank lubricates the priming pump. The priming pump should be operated weekly to cycle fresh lubricant through the primer. This cycling is of particular importance when using biodegradable lubricant, since the biodegradable properties allow it to break down quickly and lose its lubricating qualities. On rotary vane primers only, an orifice is in the lubricant line where it enters the priming pump head, to prevent excessive amounts of lubricant entering the pump and reducing its performance. Make sure clean lubricant is used in the priming tank and make sure the orifice is always open. Priming Valve After long service, normal wear of plunger insert, quad ring or O ring may prevent air sealing of the valve. Replace O rings and plunger insert if any signs of leakage are discovered. A repair kit is available from the Waterous Company. Priming Tank A vent hole is located in the elbow on top of the priming tank to break the syphon and stop the flow of lubricant after priming. The hole should be kept open at all times, but do not enlarge it. Refill priming tank as needed with lubricant. If dispensing priming lubricant into the environment, always use a biodegradable or non toxic lubricant. Biodegradable / non toxic Prime Safe is available from Waterous. NOTE: If 30 weight motor oil is used, it is recommended that a catch pan be used under the primer to collect the used oil so it can be disposed of properly. Manual Controls If priming valve has manual controls, check them monthly to make sure they operate freely. If rust or dirt cause them to bind, clean and lubricate them. Testing Once a month, perform the following vacuum test. Remove all caps except openings without valves. Close all discharge, intake, drain valves and other similar openings. Operate priming device to create a vacuum of about 22 in. Hg in pump, then stop primer and engine. Watch pressure gage; if vacuum drops more than 10 in. Hg in 5 minutes, listen for air leaks around packing glands, gaskets, valves, etc. Replace gaskets, repack or otherwise repair source of trouble. Rotor Clearance Adjustment All Waterous priming pumps are factory tested and will draw a minimum of 22 In. Hg vacuum. After prolonged service, the rotor to pump clearance may increase because of wear, resulting in lower vacuum. On VPE models, if maximum vacuum falls below 22 In. Hg., readjust rotor end clearance to 0.008 to 0.011 inches (VPE) by removing shims from between head and body. On VPO models, if maximum vacuum falls below 22 In. Hg., inspect primer for wear of the housing, vanes, rotor and seals. Replace as needed. Vanes Use of rotary vane primers will cause vane wear. If wear is excessive, vacuum levels will decrease. Periodic replacement of vanes and seals is required to maintain acceptable vacuum levels. Contact Waterous service for replacement kits. Page 7 of 10

Service Suggestions Models VPE, VPES, VPO, VPOS If the priming system fails to operate properly, refer to the troubleshooting guide in F 1031, Section 1000 for the possible cause and suggested remedy. If the cause of the failure cannot be determined using the troubleshooting guide, the following Service Suggestions should help locate the cause of the malfunction. Go through each step in sequence to check out all the components of the priming system, or until the cause of the malfunction is located. 1. Make sure battery is properly charged. If battery is in low state of charge, it may be difficult to operate the priming pump at proper speed. 2. Check all wiring to the priming pump and valve for loose terminals, damaged insulation, or broken wire strands especially near terminals. 3. Check that the correct cable size is used (see Table 1 and Table 2). 4. Check for proper grounding of the motor. On newer VPE and VPO models, there is a ground stud on the side of the motor that should be connected with a ground cable to the truck chassis. Older model primers rely on grounding through the primer body; corrosion and/or dirt build up may cause a loss of ground. 5. If priming pump still does not operate, remove priming motor. Step 6 will help troubleshoot the priming pump, and step 7 will help troubleshoot the motor. a.) VPE models The priming pump can be removed as a subassembly. b.) VPO models There are two cast parts that make up the priming pump, the part attached to the motor should not be removed from the motor. 6. For proper function of the priming system, always follow the Maintenance Instructions section of this document. The following are possible priming pump related causes of low vacuum levels or a non functioning priming pump: a.) No lubricant in the primer. VPE models must have lubricant in order to achieve vacuum levels of 22 in. Hg. or higher. VPO models can achieve vacuum levels of 22 in. Hg. without lubricant, but for higher vacuum levels or as the primer wears, the use of lubricant helps maintain desired vacuum levels. b.) Corrosion inside the priming pump. VPE primers are more susceptible to corrosion if not used regularly; weekly operation is recommended to help keep internal components coated with fresh lubricant. VPO primers are made of corrosion resistant materials, but abrasives passing through the primer can damage the corrosion resistant surfaces. Clean the priming pump surfaces to remove corrosion, or replace worn parts. c.) Stuck or broken vanes. If primer is not used regularly, corrosion and/or the breakdown of biodegradable lubricants can cause vanes to stick; foreign objects can enter the primer and cause a vane to break; or sand can damage the rotor and inside walls of the primer, not allowing the vanes to slide freely. Clean the inside of the primer and replace vanes or worn parts as needed. d.) Inside walls of primer damaged from sandy water. A tight fit between the vanes and smooth primer walls are required for high vacuum levels. Damage to this smooth surface (and smooth vane edges) causes a loss of the required tight fit. Replacement of damaged parts is usually required. 7. Check for primer motor function in the following manner: a.) With the motor disassembled from the priming pump, manually rotate the motor shaft to make sure it turns freely. If it does not, replace the motor. b.) Using the correct battery (12V or 24V) for the application, attach a ground cable (6 AWG or heavier) from the negative,, battery terminal to the ground post on the primer motor (see Figure 3 or 5). Connect the positive, +, battery terminal to the solenoid HOT terminal, again using a 6 AWG or heavier cable.! WARNING Solenoid Motor Testing Hazard. Improper wiring may cause the jumper wire to become very hot, resulting in burns to fingers or hands. To prevent the jumper wire from overheating on 24V motors, DO NOT place the jumper wire on the solenoid ground terminal (small terminal with wire attached). c.) Check for motor solenoid function by connecting a jumper between center (small) and hot terminals of solenoid (see Figure 9); the motor should run. Disconnect the jumper. If the motor ran with the jumper installed, go to step 8. Page 8 of 10

Figure 9. Solenoid Center (Small) Terminal (24V Motor) Center (Small) Terminal (12V Motor) Motor HOT Post Solenoid Buss Bar CAUTION Solenoid COLD Terminal Solenoid HOT Terminal Wherever jumper wire is used, do not leave the wire connected after making the desired test. Failure to disconnect the jumper before proceeding with subsequent tests may cause serious damage to the electrical equipment. 8. If the priming motor operated with jumper connected between center (small) and hot terminals of solenoid, control switch or switch wiring may be defective. To check switch, connect a jumper to its terminals. If priming motor operates with switch bypassed, switch is defective and should be replaced. If priming motor does not operate with switch bypassed, check wiring from switch to solenoid. NOTE: To expose control switch on manual electric priming valve (Figure 8), remove two round head screws attaching cover to valve. 9. If pump is equipped with solenoid actuated priming valve (Figure 7), and other components of priming system operate properly, then check priming valve. To do so, depress push button switch and watch valve. If priming motor operates but valve does not, run a jumper from hot post of priming motor solenoid to terminal of priming valve solenoid. If valve operates with jumper connected, then power cable is defective and should be replaced. If valve still does not operate, then replace its solenoid. d.) If motor does not run, temporarily place a heavy jumper (6 AWG or heavier) firmly across hot and cold terminals of solenoid. If the motor then runs, check that the buss bar connections are tight. If connections are good, the solenoid is probably defective and should be replaced. e.) If priming motor still does not run, connect a heavy jumper directly between positive +, battery terminal and HOT post of motor. f.) If motor does not run, replace or rebuild it. If motor does run with jumper connected, check cable between battery and priming motor solenoid. Page 9 of 10

Table 1. Switch and Solenoid Wires Amps Length of Wire, Feet 20 or less 30 40 50 100 3 20 Ga. 20 20 18 16 4 20 20 18 16 14 5 20 18 16 16 12 No. Description 1 Normally Open Push Button Switch 2 Motor Solenoid 3 Priming Pump Motor 4 Priming Valve Solenoid 5 Dual Batteries 6 Selector Switch 7 Manual Electric Priming Valve Table 2. Wire from Battery to Motor Amps Length of Wire, Feet (at.2 Volt Drop) 10 20 30 40 50 100 4 Ga. 1/0 3/0 4/0 2@2/0 125 2 2/0 4/0 2@2/0 2@3/0 150 1 3/0 2@2/0 2@3/0 2@4/0 175 1 3/0 2@2/0 2@3/0 2@4/0 200 1/0 4/0 2@3/0 2@4/0 225 1/0 4/0 2@3/0 2@4/0 250 2/0 2@2/0 2@4/0 270 2/0 2@2/0 2@4/0 300 3/0 2@3/0 2@4/0 350 4/0 2@4/0 Figure 12. Wiring Diagram Models VPE, VPES, VPO, VPOS, HHE and HHEB Priming Pumps IL2124 On 24V primers, there is an extra #10 stud on the solenoid. Make sure it is wired to the 5/16 ground stud on the motor frame. The 5/16 ground stud, on both 12V and 24V models, should be connected to the truck chassis. Page 10 of 10