Current Ratings. Standards & codes note 1. Introduction. interest. By Steve Hansen Sr. Field Engineer

Similar documents
Advanced Guide To Understanding Assembly Short-Circuit Current Rating WITH ENGINEERING SOLUTIONS AND OVERCURRENT PROTECTION DEVICES TO ENHANCE SCCR

Simplified Guide To Understanding Short-Circuit Current Rating FIND IT, FIX IT, FORGET IT

Evaluating Selective Coordination Between

Selective Coordination Enforcement:

Evaluating Selective Coordination Between Current-Limiting Fuses And Non Current-Limiting Circuit Breakers

Reducing. with Current. arc flash note 2. points of interest. Why Use Current Limiting Fuses. By mike lang, Principal field engineer

BRANCH CIRCUIT PROTECTION FUSED COORDINATION PANELBOARD

Devices for Branch Circuits and Feeders

ACHIEVING MAXIMUM BENEFITS WITH A FUSE PROTECTED MOTOR CONTROL CENTER

Secondaries. arc flash note Introduction. By Mike Lang, engineer and. Services Supervisor

Fused Coordination Panelboard

A case study in solving SCCR issues

What's New with UL508A Codes & Standards Presented by Jeff Woolfolk Manufacturing in America March 14-15, 2018

Design Standards NEMA

Panel SCCR 50kA RMS Symmetrical 480V Maximum

3.2. Current Limiting Fuses. Contents

Suggestion on How to Use

KT7. Methods. of Applying. & Molded Case Circuit Breakers F119. Motor Circuit Controllers

Compact Circuit Protector (CCP) Application Note

Electrical Safety and Overcurrent Protection

Protectors. Manual motor. Types MS116, MS132, MS45x, MS49x. MS Series. Manual motor protectors. Type MS116. Type MS132. Type MS45x.

Selective Coordination Requirements

Electrical Safety and Reliability: Short-Circuit Current Rating (SCCR) Equipment SCCR made easy

Selective Coordination

the National PhotoVoltaic protection note 5 I rated Introduction points of interest When to Fuse, When Not to Fuse

Understanding National Electric Code (NEC) tap rules How do they apply to circuit breaker terminals?

Fused Coordination Panelboard

YOUR ELECTRICAL SYSTEM IS YOUR LIFELINE AMP-TRAP 2000 FUSES

TERMS AND DEFINITIONS

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

2000 Cooper Bussmann, Inc. Page 1 of 9 10/04/00

FUSES VERSUS CIRCUIT BREAKERS FOR LOW VOLTAGE APPLICATIONS

Service Entrance Methods

Design Considerations to Enhance Safety and Reliability for Service Entrance Switchboards

ECET Circuit Design Motor Loads. Branch Circuits. Article 210

ETAP Implementation of Mersen s Medium Voltage Controllable Fuse to Mitigate Arc Flash Incident Energy

Amp-Trap 2000 Fuses FOR TYPE 2, NO DAMAGE CIRCUIT PROTECTION IN ALL THE CONFIGURATIONS YOU NEED. Class J / AJT...A2. AJT Reducer Fuses...

Arc Fault Circuit Interrupter (AFCI) FACT SHEET

A Look at the 2017 NEC Significant Changes

IN2 Enclosed Switches and Circuit Breakers

MOLDED CASE CIRCUIT BREAKER BASICS. David Castor, P.E.

The easiest and fastest way to select and specify the right fuse

Low-Peak 600V Class RK1

Industrial Generator Set Accessories. Standard Features. Line Circuit Breakers kw

Equipment Protection. Transformers 600V or Less

6/4/2017. Advances in technology to address safety. Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton

FUSES. Safety through quality

ECET Distribution System Protection. Overcurrent Protection

Selecting Protective Devices

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

Now - Up To 400A Mains!

Load Side PV Connections

Recommended Procedures

Equipment Protection. Transformers 600V or Less

File E47705 Project 97ME August 21, 1997 REPORT. MOTOR CONTROLLERS, MANUAL Amberg, FED REP Germany

Motor Protection. Presented By. Scott Peele PE

INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY

Overcurrent Protection According to the 2011 NEC

1. Division 26 Section "Elevator Shunt-Trip Fused Disconnect Switches".

Busway. Siemens STEP 2000 Course. STEP 2000 Courses distributed by

Alternator protection, part 1: Understanding code requirements

For Type 2, No Damage circuit protection in all the configurations you need. A Amp-Trap 2000 Fuses

Application note Compact Circuit Protector (CCP2) Smaller, better... the Power of Space

Power System Solutions (PSS)

Fuseology. Dual-Element, Time-Delay Fuse Operation

Code Compliance. Perspectives on PV. Back to the Grid, Designing PV Systems for

FUSE TECHNOLOGY Ambient temperature

Engineering Dependable Protection

SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL

www. ElectricalPartManuals. com Engineering Dependable Protection

Applying Interrupting Rating: Circuit Breakers

Industry Automation Control Components

Applying More Than One ArmorStart Motor Controller in a Single Branch Circuit on Industrial Machinery

Applying Interrupting Rating: Circuit Breakers

A member-consumer with a QF facility shall not participate in the Cooperative s electric heat rate program.

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

Optimizing Emergency Power Systems for Health Care Applications

Low Voltage Fuses For Motor Protection

1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces.

WARREN COUNTY, N.Y. M/E REFERENCE

HVAC and Refrigeration Circuit Protection Solutions. Compact and safe HVAC/R circuit protection

Open-Style Power Distribution Blocks

File E47705 Vol. 7 Sec. 9 Page 1 Issued: and Report Revised:

UL248 North American Low Voltage Fuses

OUTPUT SHORT-CIRCUIT CURRENT BEARABLE BY THE UPS

General Purpose US Fuses

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

Type E/F Simplex & Duplex Pump Controllers

LPSRK100SP 100A 600V TD Dual Elem Class RK1 Low Peak Fuse

SOLAR PV STANDARD PLAN - COMPREHENSIVE Central/String Inverter Systems for One and Two Family Dwellings

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES

2006 IEEE PES General Meeting June 2006, Montreal, Canada Paper 06GM0613. Fault Current Limiters - Report on the Activities of Cigre WG A3.

4-Day Power System Analysis, Coordination, System Studies

FUSE: SAFE & RELIABLE

Product Selection Guide

University of Houston Master Construction Specifications Insert Project Name

Source-Side Fuse/Load-Side Recloser Coordination

Technical data OT16E3 OT160E3 UL & CSA

ECET 211 Electric Machines & Controls Lecture 1-3 (Part 2) Electrical Safety in the Workplace Electrical Safety in the Workplace

Selection Guide Motor Control Device Solutions

Transcription:

Achieving Higher Short Circuit Current Ratings for Industrial Control Panels Standards & codes note 1 By Steve Hansen Sr. Field Engineer Introduction Articles 9.1 and. in the National Electrical Code require industrial control panels to be clearly marked with a Short Circuit Current Rating (SCCR). NEC recognizes UL 8A, the Supplement SB as an approved method for determining panel SCCR. As of April, 6, UL 8 Listed panels must be marked with SCCRs. NEC 1. requires that the overcurrent protective devices [and] component SCCRs shall be so selected and coordinated to permit the circuit protective devices used to clear a fault to do so without extensive damage to the electrical components of the circuit. In order to comply with NEC 1., an industrial control panel must have an SCCR equal to or greater than the available fault current of the system where the panel is to be installed. An SCCR marking on a panel facilitates compliance with NEC 1. during initial and future installations, should the panel need to be relocated. points of interest The NEC requires panel SCCR markings Class J and Class CC fuses provide high panel SCCRs UL 8A provides an analytical method for determining panel SCCR and allows an increase in the panel short circuit current rating if properly selected currentlimiting fuses are installed in the panel. This issue of Tech Topics will explain how UL 8A Supplement SB is used to determine panel SCCR and how the use of typetested components and currentlimiting fuses can increase panel SCCR. The following definitions will be helpful: Available Fault Current the maximum short circuit current that can flow in an unprotected circuit. Branch Circuit 1 the conductors and components following the last overcurrent protective device protecting a load. CurrentLimiting Fuse a fuse which will limit both the magnitude and duration of current flow under short circuit current conditions.

Feeder Circuit 1 the conductors and circuitry on the supply side of the branch circuit overcurrent protective device. Interrupting Rating the maximum current a fuse can safely interrupt. OverCurrent Protective Device (OCPD) a fuse or a breaker used to protect downstream equipment. Peak Let Through Current (I p ) The maximum instantaneous current passed by a currentlimiting fuse when clearing a fault current of a specified magnitude. Short Circuit Current Rating 1 The prospective symmetrical fault current at a nominal voltage to which an apparatus or system is able to be connected without sustaining damage exceeding the defined acceptance criteria. 1 Glossary; UL Standard for Safety for Industrial Control Panels, UL8A. Revision through and including September 1,. Disclaimer This paper has been written to demonstrate the concept of panel SCCR and to illustrate how high panel SCCRs can be obtained with currentlimiting fuses. The author has attended the UL University training session on UL 8A, studied the standard in detail, and have firsthand field experience. The reader should understand that UL 8A has undergone numerous changes and will likely continue to evolve. At times there have been interpretation disagreements among experts on this subject. In no event will Mersen or the author of this paper be held liable for any direct or indirect damages arising from the use of the interpretations set forth in this paper. Methods For Determining Industrial Control Panel SCCR There are two generally accepted approaches to determining panel SCCR. The first is to test the assembled panel to an existing standard with a third party witness, such as UL. Assuming the test results are acceptable, the panel is marked with the appropriate SCCR. This approach is common when the panel is relatively simple and panel volume is high. The second method of determining the short circuit current rating of a panel is to use the requirements of UL 8A Supplement SB. Supplement SB allows the panel manufacturer to assign an SCCR to a panel without testing the assembled panel. This approach is particularly attractive for low volume or oneofakind panels where the cost of testing the assembled panel would be prohibitive. The method set forth in Supplement SB is commonly referred to as the weakest link approach. In other words, the panel SCCR is limited to the SCCR of the lowest rated component or the lowest rated branch circuit protective device in the panel. If the panel contains a currentlimiting feeder OCPD the currentlimiting effects may be factored into the SCCR evaluation. Supplement SB can be utilized to determine the SCCR of panels ranging from the simple to the complex. SB4.1.1 of UL 8A states, The short circuit current rating of the overall industrial control panel shall be determined based upon:

1. First, establishing the short circuit current ratings of individual power circuit components as specified in SB4.;. Second, modifying the available short circuit current within a portion of a circuit in the panel due to the presence of current limiting components as specified in SB4., when applicable; and. Third, determining the overall panel short circuit current rating as specified in SB4.4. To illustrate this method consider the panel shown in Figure 1. Industrial control panel SCCR can be determined by testing the assembled panel or by using an analytical method such as that described in Supplement SB of UL 8A. Step 1 Determine SCCR of Power Circuit Components Begin by determining the SCCR of each power component in each branch and feeder circuit contained within the panel. UL 8A requires that all power components (with the exception of power transformers, reactors, current transformers, drytype capacitors, resistors, varistors, and voltmeters) have short circuit current ratings. Component SCCRs are established by UL during the Listing or Component Recognition process. There are several ways to determine component SCCR. The SCCR may be marked on the component or on the instruction sheet packaged with it. Component SCCR values are often available on manufacturers web sites. If the Per UL 8A manufacturer has not provided...establish the an SCCR and the component short circuit is UL Listed or Component current rating Recognized, the SCCR may be of individual determined by referring to UL power circuit 8A Supplement SB, Table components. SB4.1. A copy of this table is shown on the top of page 8 as Table SB4.1. The matrix shown in Figure lists the components in the sample panel from Figure 1, the component SCCRs and the source of the rating information. Once the SCCR of the components in the power circuit have been established, the effects of currentlimiting devices can be considered. Step Consider the Effects of Current Limiting OverCurrent Protective Devices Considering the effects of currentlimiting devices in reducing available short circuit current allows for higher panel ratings. Quoting from UL 8A, SB4.1.1 b), this step consists of modifying the available short circuit current within a portion of a circuit in the panel due to the presence of currentlimiting components as specified in SB4., when applicable This means UL has determined that it is appropriate to apply a component in a circuit, provided the peak current passed by an upstream OCPD (I p ) does not exceed the component s SCCR. This approach is appropriate with three prerequisites. First, the upstream OCPD must be a UL Class CC, G, J, L, RK1, RK, or T fuse or a listed circuit breaker Figure 1: Control Panel Circuit Component Component SCCR Source of SCCR Feeder Fusible Switch ka Product Marking Feeder Fuses, A ka Product Marking Feeder PDB ka UL8A Table SB4.1 Branch #1 Fuse Holder ka Product Marking Branch #1 Fuses, 1A ka Product Marking Branch #1 Starter ka Product Marking Branch # Fuse Holder ka Product Marking Branch # Fuses, 1A ka Product Marking Branch # VFD, HP 0kA Instruction Sheet Branch # MCCB, A 6kA Product Marking Branch # Starter ka UL8A Table SB4.1 Figure : Component SCCRs of Control Panel of Figure 1

4 marked currentlimiting. Second, the currentlimiting fuse or circuit breaker must be in the feeder circuit position (not the branch circuit) and must be located within the panel. Third, the I p passed by the currentlimiting OCPD in the feeder circuit must not be greater than the SCCR of the protected component. To facilitate fuse selection, UL 8A contains Supplement SB, Table SB4. (Table, page 8) which shows fuse I p as a function of available short circuit current. For example, a A, Class J fuse will have an I p of no more than ka for available short circuit currents up to 0kA. Consider the panel shown in Figure 1 to illustrate this method. The feeder circuit in the panel contains a Component Recognized power distribution block not marked with an SCCR. Using Table SB4.1 (top of page 8), the PDB is assigned an SCCR of ka. Class J, A fuses placed in the feeder circuit will limit I p to ka at available currents up to 0kA, as shown by Table SB4. (bottom of page 8). Thus, the ka rated PDB is suitable, provided the available short circuit current on the line side of the feeder fuses is 0kA or less. The feeder circuit can now be assigned an SCCR of 0kA. Continue with this approach by evaluating other components in the panel with low SCCRs. The motor starter in Branch #1 has a ka SCCR. Given that the available fault current on the line side of the feeder fuses is 0kA or less, the ka rated starter is appropriate for use. As with the feeder circuit, the A, Class J fuses have effectively increased the SCCR of Branch #1 to 0kA. If the panel contains a currentlimiting feeder circuit OCPD, the currentlimiting effects of this device may be factored into the evaluation. Figure : Adjusted component SCCRs The A, Class J fuses in the feeder will not impact the SCCR of the VFD in Branch #. The instruction sheet assigns the VFD a 0kA SCCR, provided the component is protected by Class J fuses rated 1A or less. The 1A, Class J branch circuit fuses shown in Figure 1 satisfy listing requirements. Branch # contains a starter with no SCCR marked on the device or its instruction sheet. This starter is assigned an SCCR of ka, based upon Table SB4.1 (top of page 8). The Class J fuses in the feeder circuit do not limit I p to ka under short circuit condition. The starter in branch # remains the weak link and limits the panel SCCR to ka. UL 8A does not contain a table showing I p values for circuit breakers, because the circuit breaker standard, UL 489, does not contain specific maximum allowable Ip values for currentlimiting circuit breakers. Circuit breaker performance varies by manufacturer while by comparison, the UL 48 series of fuse standards specifies maximum acceptable I p values for Class CC, G, J, L, RK1, RK, and T fuses at available short circuit currents of ka, 0kA, and ka. Thus, if using currentlimiting circuit breakers, one must refer to the I p graphs published by the circuit breaker manufacturer. Step Assigning Overall Panel SCCR The final step is to assign an SCCR to the overall panel. This rating will be marked on the panel and will facilitate compliance with NEC 1. and NEC 9.1. Begin by adjusting the matrix developed in Step 1 to reflect the currentlimiting effects evaluated in Step. The new matrix is shown below in Figure. Circuit Component Component SCCR Source of SCCR Feeder Fusible Switch ka Product Marking Feeder Fuses, A ka Product Marking Feeder PDB ka UL8A Table SB4.1 Branch #1 Fusible Switch ka Product Marking Branch #1 Fuses, 1A ka Product Marking Adjusted SCCR 0kA Branch #1 Starter ka Product Marking 0kA Branch # Fusible Switch ka Product Marking Branch # Fuses, 1A ka Product Marking Branch # VFD, HP 0kA Instruction Sheet Branch # MCCB, A 6kA Product Marking No Change Branch # Starter ka UL8A Table SB4.1 No Change

Following the weakest link approach, identify the lowest component SCCR rating in the panel power circuits. In this example, the starter SCCR in Branch # is ka. Therefore, the short circuit current rating of this panel is ka. Control Circuit SCCR A low SCCR for the control circuit can limit panel SCCR. The control circuit SCCR is equal to the interrupting rating of the OCPD protecting the control circuit (SB. of UL 8A). This potential weak link can be eliminated by protecting the control circuit with Class CC timedelay fuses, which allow a ka SCCR. How Much SCCR Is Enough? Panel SCCR must be greater than the available short circuit current at the point where the panel receives power. How much SCCR is enough? That will, of course, depend on the facility, the location in plant and the installation. Keep in mind that changes in the power system affect short circuit current levels. Panels located in one area of the plant may later move to another area, changing the available short circuit current. In today s industrial and commercial facilities a panel with a ka SCCR is just not adequate. As an example, a single kva transformer with a 4V secondary and a utility primary capability of MVA will have a secondary short circuit current (including motor contribution) approaching ka. A panel with a 0kA SCCR is suitable for virtually all industrial and commercial installations. Strategies For Increasing Panel SCCR The panel in Figure 4 demonstrates strategies for increasing panel SCCR, including: Upgrading to components with higher SCCRs Considering the use of typetested components Taking advantage of the high degree of currentlimitation provided by Class J timedelay and Class CC timedelay fuses to protect low rated components Upgrading Components Can Increase Panel SCCR Consider the example panel in Figure 4, which shows component SCCR adjusted for the currentlimiting effects of the feeder fuses. The starter in Branch # is the weakest link and limits the panel SCCR to ka. What happens if the starter in Branch # is upgraded to a starter marked with a ka SCCR? After adjusting for the I p of the currentlimiting feeder fuses, the new starter has a modified SCCR of 0kA. At this point, the A MCCB in Branch # is the weak link and limits the panel SCCR to 6kA. Using High Fault Current Tested Components The UL 8 Standard allows the component manufacturer to test components with specific OCPDs at higher current levels to establish what UL refers to as high fault short circuit current ratings. This process is called typetesting. Rather than use the minimum SCCR levels given by Table Panel SCCR cannot be higher than the lowest branch circuit overcurrent protective device interrupting rating. Figure 4: Panel shown with component SCCRs adjusted for the currentlimiting effects of the A Class J fuses in the feeder circuit

6 SB4.1 (top of page ), the manufacturer may be contacted to determine whether higher ratings have been established for a specific component. Refer again to Figure 4. The starter manufacturer offers a comparable starter that has been successfully tested at 0kA with 1A Class CC fuses. Replacing the ka starter with the 0kA starter and the A MCCB with Class CC fuses rated 1A or less, the two weakest links in the original panel have been eliminated. The panel can now be labeled with a 0kA SCCR. If the fuseholder in which the class CC fuses are installed will accept fuses having a larger continuous current rating than the maximum rating proven by the typetesting, a label must be mounted next to the fuseholder specifying the current rating of the replacement fuses. Increase Panel SCCR Using Class J or Class CC Fuses Panel designers using RK fuses or OCPDs that are not currentlimiting, as shown in Figure, may unnecessarily limit the panel SCCR and restrict the range of applications. Figure 6 illustrates the results possible with an allfuse panel. Class J or Class CC timedelay fuses are chosen for their high degree of currentlimitation. The result is a panel with a high SCCR, which is more likely to provide NEC compliance, installation flexibility and enhanced safety. Figure : Panel with a low SCCR Figure 6: Panel with Class J fuses

Table SB4.1 UL Standard for Safety, UL8A Supplement SB. Assumed maximum short circuit current rating for unmarked components. Table SB4.1 effective April, 6. Component Bus bars Circuit breaker (including GFCI type) Current meters Current shunt Fuseholder Industrial control equipment a. Auxiliary devices (overload relay) b. Switches (other than mercury tube type) c. Mercury tube switches Rated over amperes or over volts Rated volts or less, amperes or less, and over kva Rated volts or less and kva or less Motor controller rated in horsepower (kw) a. 0 (0.) b. 1 (8 149) c. 1 (1 98) d. 1 0 (99 44) e. 1 900 (448 61) f. 901 (6 119) Meter socket base Miniature or miscellaneous fuse Receptacle (GFCI type) Receptacle (other than GFCI type) Supplementary protector Switch unit Terminal block or power distribution block a b c Short circuit current rating, ka a. 1 c c 18 c c 4 c 8 c b 0. A short circuit current rating is not required when connected via a current transformer or current shunt. A directly connected current meter shall have a marked short circuit current rating. The use of a miniature fuse is limited to volt circuits. Standard fault current rating for motor controller rated within specified horsepower range.

8 Table SB4. UL Standard for Safety, UL8A Supplement SB. Peak let through currents, I p, and clearing, I t, for fuses. Table SB4. effective April, 6. Fuse Types Class CC 1 Class G 1 0 Volt Class T 0 0 0 1 Class J and 0 Volt Class T 0 0 0 Fuse Rating Amperes Between Threshold and ka 0 ka ka 1 t x I p x 1 t x I p x 1 t x I p x 4 4 6.. 1 1 0 00 00 9 1 9 6 8.8. 1 1 00 0 10 4. 9 8 6. 14 4. 1 1 00 0 10 Class L 0 1 10 0 00 00 00 000 10 0 0 1 000 10 0 00 0000 00 00 00 0 0 1 000 0 000 0 00 0000 00 00 0000 0 1 1 0 Class R RK1 RK RK1 RK RK1 RK RK1 RK RK1 RK RK1 RK 0 0 0 10 00 000 0 10 00 000 6 14 18 4 11 6 0 1 00 0 10 00 000 11 1 11 0 10 0 0 00 10 9 46 6 4 0 0 14 6 0 Contact USA 4 Merrimac Street, Newburyport, MA 019 T 98 46 666 F 98 46 0181 info.nby@mersen.com CANADA 6 Kestrel Road, Mississauga, ON LT 1Z1 T 90 9 00 F 90 9 8 technicalservices.mis@mersen.com Additional Resources Standards & Codes Note : Understanding SPD Codes and Standards, and TPMOV Technology Standards & Codes Note : Major Changes to NFPA 0E Standard 1 Edition These and other Tech Topics are available on. TTSCN0 PDF 6. Mersen