INSTRUCTIONS GEI-98305C UNDERVOLTAGE RELAY D-C. Type NGV18A GENERAL ELECTRIC

Similar documents
INSTRUCTIONS HAA 15A / 15B / 15C / 15D / 15E / 15F / 15G / 15H AUXILIARY CURRENT RELAYS

GEK41931B INSTRUCTIONS MULTI-CONTACT AUXILIARY RELAYS TYPE HFA73K. GE Protection and Control 205 Great Valley Parkway Malvern, PA

INSTRUCTIONS. GEI-38974A Supersedes GEI INSTANTANEOUS CURRENT RELAY TYPE PJC2OA GENERALS ELECTRIC

GEK 45484B INSTRUCTIONS MULTI-CONTACT AUXILIARY RELAY HFA151 TYPE. GE Protection and Control 205 Great Valley Parkway Malvern, PA

INSTRUCT IONS GEH-1 793J INSTANTANEOUS AUXILIARY RELAY TYPES HGA11A, C, H, J, K, P, S, T, V, W, X GENERAL ELECTRIC AUILIARV P A GENERALS ELECTRIC

INSTRUCTIONS HAA 15A/15B/15C/15D/15E/15F/15G/15H AUXILIARY CURRENT RELAYS. Iso9ooo. GE Power Management

INSTRUCTION S GEK 7354J AUXILIARY VOLTAGE RELAY TYPE HAA16B, HAA16C GENERAL ELECTRIC

INSTRUCTIONS. GE Protection and Control. 205 Great Valley Parkway Malvern, PA UNDERVOL TAGE RELAYS TYPES: IAV54E IAV55C IAV54F IAV55F

INSTRUCTIONS SYNCHRONISM-CHECK RELAYS. GE Meter and Control. 205 Great Valley Parkway Malvern, PA Types IJS51A.

GENERAL ELECTRIC INSTRUCTIONS GEK- 2M42. Insert Rooklet GEH 1793 INSTANTANEOUS AUXILIARY RELAY TYPE HGA MODEL 12HGAI1E(-)A I NTRODUCT ION

INSTANTANEOUS UNDERVOLTAGE RELAY

Type CRN-1 Reverse Power Relay 50 and 60 Hertz

THERMAL OVER CURRENT RELAY

Test Cabinet (Inspection Box) Instructions. for Testing Accessories on Manually and Electrically Operated EntelliGuard G Low Voltage Circuit Breakers

TYPE KF UNDER-FREQUENCY RELAY A. Figure 1: Type KF Relay for 60 Hertz without Case. (Front & Rear View.) Front View Rear View

P. Sub 4 184A404. Sub 3 876A220

A - Add New Information C - Change Existing Information D - Delete Information. Page 7. Delete the fourth paragraph beginning CAUTION

GENERAL ELECTRIC INSTRUCTIONS. GE I Supersedes GEI-28802E INSTANTANEOUS VOLTAGE RELAYS TYPES

ABB ! CAUTION. Type KRV Directional Overcurrent Relay E 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION. Instruction Leaflet

COM Overcurrent Relay

C. Figure 1. CA-16 Front View Figure 2. CA-16 Rear View

3.0 CHARACTERISTICS E Type CO-4 Step-Time Overcurrent Relay

HGA. Hinged Armature Auxiliary. Hinged armature auxiliary relay to perform auxiliary functions in AC and DC circuits.

2.0 CONSTRUCTION AND OPERATION 3.0 CHARACTERISTICS K. CO (HI-LO) Overcurrent Relay

INSTRUCTIONS GEI-10190L DC AUXILIARY RELAYS TYPE HGA17A TO F, H, M, R, S, T GENERAL ELECTRIC

Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) E

INSTRUCTIONS. GE Protection and Control. 205 Great Valley Parkway Malvern, PA GEK-49826D INSTANTANEOUS OVERCURRENT RELAYS TYPES:

INSTRUCTIONS GEK G HIGH-SPEED DIFFERENTIAL RELAYS TYPES CFD22A AND CFD22B. GE Protection and Control

4.0 OPERATION Type ITH-T Relay

B CW POWER RELAY

ABB. Type CRQ Directional Negative Sequence Relay for Ground Protection B 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION CAUTION

DIAC DIFC DSFC Digital Self Powered Overcurrent Protection

L. Photo. Figure 2: Types CA-16 Relay (rear view) Photo. Figure 1: Types CA-16 Relay (front view)

Installation Sheet January, 2016 Supersedes February, 2013

GE K D IN ST RU CT ION S INSTANTANEOUS AUXILIARY RELAY TYPE HGA111 GENERAL ELECTRIC

GE CONSUMER & INDUSTRIAL

CR193 Vacuum Limitamp* Contactors

GEK 65513D INSTRUCTIONS AUXILIARY LOCKOUT RELAY HAND RESET WITH TARGET. GE Meter and Control 205 Great Valley Parkway Malvern, PA

ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA

INSTRUCTIONS. GE Protection and Control 205 Great Valley Parkway Malvern, PA GLK 34117G

Installation Sheet January, 2016 Supersedes June 2013

Low Voltage WavePro TM and EntelliGuard TM Circuit Breakers Remote Racking Operator

[ These instruction: do not purport to cover all details or variations eqiipment GENERAL ELECTR INSTRUCTIONS. Insert Book t Ci[ V.

Vacuum Circuit Breakers (Vehicle)

Type SOQ Negative Sequence Time Overcurrent Relay

INSTANTANEOUS CURRENT RELAYS

41-747G. Figure 1: Type DGF Relay without case (Photo)

SecoVac * Ground & Test Device

Operation and Maintenance Manual

GENERALS ELECTRIC INSTRUCTIONS. GEK Insert Booklet- GEI SYNCHRONISM CHECK RELAY IJS52F INTRODUCTION

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

3. OPERATION 2.1. RESTRAINT CIRCUIT 2.6. INDICATING CIRCUIT 2.2. OPERATING CIRCUIT 2.7. SURGE PROTECTION CIRCUIT 2.3.

INSTRUCT ION S GEK A. Supersedes GEK TIME OVERCURRENT RELAY TYPE IAC66S GENERAL ELECTRIC

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065

INSTRUCTIONS GEH 2056F POWER RELAYS. Types ICW51A ICW52A ICW52B GENERALJ ELECTRIC

UNION SERVICE SPECIFICATION NUMBER SU A

Florham Park, NJ USA Call (ASCO) for sales or service

INSTRUCTIONS TIME OVERCURRENT RELAY TYPE IAC 12IAC77S(-)A INTRODUCTION

2.0 CONSTRUCTION 3.0 OPERATION. SA-1 Generator Differential Relay - Class 1E 2.5 TRIP CIRCUIT

TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS

PROCESS ELECTRONICS CORPORATION

Vacuum Circuit Breakers (Vehicle)

Vacuum Circuit Breaker (Vehicle)

BBC. Renewal Parts. I-T-E Low-Voltage Power Circuit Breakers

Florham Park, NJ USA Call (ASCO) for sales or service

www. ElectricalPartManuals. com Operator s Manual

GEK 65602B INSTRUCTIONS RECLOSING RELAYS TYPES HGA18M, HGA18N. GE Protection and Control. 205 Great Valley Parkway. Malvern, PA

600 D 220 E 230 J Hanover Road, Florham Park, New Jersey USA For sales or service call (ASCO)

50 Hanover Road, Florham Park, New Jersey USA For sales or service call (ASCO)

www. ElectricalPartManuals. com MAGNETIC TIME RELAYS GENERAL. ELECTRIC INSTRUCTIONS *IC *Also identified with prefix CR instead of IC.

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

Vacuum Circuit Breakers (Vehicle) Type HKR 7.5kV to 15kV. Instructions Installation Operation Maintenance SGIM-9928C

A. Submit manufacturer's literature and technical data before starting work.

GE Industrial Solutions. DEH Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

N1233 Series Troubleshooting Guide for N Alternator

INSTRUCTIONS GEH-1789B GEH-1789A SUPERSEDES BALANCED-CURRENT RELAYS. Types. IJCSlB IJCSlC IJC53A. www. ElectricalPartManuals. com. GENERAL f) ELECTRIC

GEI-90802E INSTRUCTIONS SYNCHRONISM CHECK RELAY TYPE 1J552D. GE Protection and Control 205 Great Valley Parkway Malvern, PA

Operator s Manual Series ADTS Automatic Delayed Transition Transfer Switches, amps

GP/GPA GROUND FAULT PROTECTION

ABB Power T&D Company Inc. Relay Division Coral Springs, FL Allentown, PA. Non-Directional, Single Phase Adjustable Time Delay Device No.

Operator s Manual Series ACTS Automatic Closed Transition Transfer Switches 150 through 4000 amps A. Rating Label.

Electropneumatic Timing Relays Series 7000 Industrial

Operator s Manual Series ATS Automatic Transfer Switches 600 through 1200 amps

section-page Table 1. Transfer switching device ratings. Conditional short circuit current

TABLE I 60 CYCLE BURDEN OF THE CVD RELAY AT CONTINUOUS RATING

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

Operator s Manual Series ATB Automatic Transfer & Bypass Isolation Switches 150, 260, and 400 amp sizes A. Rating Label.

Model HEA Multicontact Auxiliary

www. ElectricalPartManuals. com Instructions for Load Break Air Switch, Type LBF, for Power Centers

Operator s Manual Series ADTS Automatic Delayed Transition Transfer Switches 150 through 4000 amp. Rating Label. Nameplate A

C.E. Niehoff & Co. C653/C653A and C625 Alternators Troubleshooting Guide NOTICE. Hazard Definitions. Battery Charge Volt and Amp Values

STARTING SYSTEMS 8B - 1 STARTING SYSTEMS CONTENTS

GE Industrial Solutions. User/Installation Manual for 4.76kV -15kV SecoBloc

50 Hanover Road, Florham Park, New Jersey USA For sales or service call (ASCO)

GEK 41880D INSTRUCTIONS MACHINE FIELD GROUND DETECTOR RELAY TYPE PJG12B. GE Protection and Control. 205 Great Valley Parkway Malvern, PA

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod

Service Instructions. Syntron Light-Capacity Electromagnetic Model: F-T01-A DF-T01-A

RELAYS HAVING NO KS DESIGNATIONS WARD LEONARD COMPANY, ALLEN-BRADLEY COMPANY AND WESTINGHOUSE CORPORATION REQUIREMENTS AND ADJUSTING PROCEDURES

Transcription:

INSTRUCTIONS GEI-98305C D-C UNDERVOLTAGE RELAY Type NGV18A GENERAL ELECTRIC

2 Fig (8035275) NOV18A Relay Removed From Case (Rear View) GEI-98305 D-C Undervoltage Relay Type NOV Fig. 1 (8035274) NGVI&L e1ey Removed From Case (Front Viev) RI

specifically to be used to monitor the d-c charging undervoltage relay with extra high dropout designed The NGV18A relay is an instantaneous d-c DESCRIPTION The resistors are supplied as a and each relay is calibrated with TABLE A listed on Fig. 3. its resistors. part of the relay 3 but no such assurance is given with respect to local codes and ordinances because they vary greatly. RATINGS NGV18A relay coil ratings and the resistors are delay dropout HFA65D relay which provides a time Figure 5 shows the NGV18A used with a time This arrangement will sound an alarm not only when a prolonged d-c undervoltage occurs but also when delay of about two seconds and at the same time voltage to decay. fully charged open circuit voltage of the battery. Table A gives detailed information on the either a lead-acid or a nickel-cadmium battery, it is suggested that the dropout be set about 98% of the For example, the fully charged open circuit voltage battery charger output. the relay must pickup at the lowest acceptable the a-c power is lost without waiting for the battery the suggested NGV18A setting about 121 volts. Also of a 60 cell lead-acid battery will be 123 volts and When the NGV18A relay is used to monitor monitors the a-c supply to the battery charger. * The inductive rating is based on the indictive of an To the extent required the products described herein meet applicable ANSI, IEEE and NEMA standards; the purchasers purposes, the matter should be referred to the General Slectric Company. further information be desired or should particular problems arise which are not covered sufficiently for every possible contingency to be met in connection with installation, operation or maintenance. Should These instructions do not purport to cover all details or variations in equipment nor to provide for BURDEN in Table A. OPERATING PRINCIPLES The NGV18A is a hinged armature type relay which operates by electromagnetic attraction. The The NGV1SA relay pick up can be adjusted by The resistances of the d-c windings are given means of the variable resistor Ri. The relay will droput feature results from the characteristic of pick up at 105% or less of dropout voltage. the zener diode regulator. average tripping coil. contacts are opened and closed by the movement spring and operated by the D.C. solenoid. The high of an armature which is restrained by an opening CHARACTERISTICS delay auxiliary relay to prevent false alarms. alarm. Since some operating conditions may temporarily lower the d-c voltage, It is suggested station battery undervoltage and to provide an Usually the NGV18A relay is used to detect Because the NGV18A picks up at 105% of drop high-speed, extra high dropout, d-c relay Is re quired. that the NGV18A be used in conjunction with a time 230 0.5 1.5 250 0.25 1.0 115 0.75 2.0 125 0.5 1.5 48 1.0 3.0 A-C VOLTS D-C VOLTS AMPS INDUCTWE* NON-INDUCTIVE APPLICATION out voltage or less, It finds application wherever a TABLE B INTERRUPTING RATINGS target. It is packaged in a S-i drawout case, for mally open and one normally closed contact but no In series with the operating coil and the fixed and telephone-type voltage unit with a zener regulator The relay undervoltage element consists of a this supply falls. either flush or surface mounting. It is normally auxiliary relay. adjustable resistors. Also the relay has one nor used in conjunction with one time delay dropout seconds. ratings. These contacts will make and carry three amperes continuously or 30 amperes for two Table B gives the relay contact interrupting NGV18A3 200 48 NGVL8A2 2500 I 125 NGV18A1 2500 250 OHMS RELAY MODEL RESISTANCE VOLTAGE D.C. COIL D.C. supply for a station battery to sound an alarm if TYPE NGV18A D.C UNDERVOLTAGE RELAY

4 by a test plug. The cover, which is attached to the Relay Type NGV18A (Front View) * 0 connected by removing the connection plug which when desired. To do this, the relay Is first die assembly which is latched into a drawout case whes completes the electrical connections between the case block and the cradle block. To test the relay front bf the relay case, contains an interlock arm 0 lock circuits. CONSTRUCTION in its case this connection block can be replaced GEI-98305 D-C Undervoltage Type NGV18A The relay components are mounted in a cradle the relay is in operation but It can be easily removed ment. These relays, when not included as part of a from rough handling is evident, file a damage claim control panel, will be shipped in cartons designed promptly notify the nearest General Electric Apparatus Sales Office. at once with the transportation company and tained in transit. If injury or damage resulting receipt of a relay, examine it for any damage sus to protect them against damage. Immediately upon RECEIVING, HANDLING AND STORAGE 5+ I2NGV1HA1 OOO 12GVThA2 OOO v -!O6T EICEP Fig. 3 (D165A7720-3) Internal Connections, (C pressure to prevent the opening of important inter makes contact as Indicated in FIg. 4 with adequate it is especially Important that the auxiliary brush with shorting bars (see Fig. 3). On these circuits, adequate overlap when the connecting plug is with drawn or inserted. Some circuits are equipped auxiliary brush, as shown in Fig. 4, to provide Fig. 6. Every circuit In the drawout case has an included. For outilne and drilling dimensions, see relay order to insure that proper hardware will be However, panel thickness must be indicated on the The relay case Is suitable for either semiflush or surface mounting on all panels up to 2 inches thick and appropriate hardware is available. which prevents the cover from being replaced until the connection plugs have been inserted. indicates revision TESTS, the relay is held In storage before shipment to the job site, it is recommended that the visual If alter the performance of the ACCEPTANCE INSTALLATION PROCEDURE before the residual screw strikes the shim. With closed contacts should be.ol0 to.020. The wipe on each normally open contact should and the pole piece and operating the armature by the armature picked up, the gap on jhe normally hand. The normally open contacts should make inserting a.002 5 shtm between the residual screw be approxiniit*iv.005. This can be checked by mately.005. contact by deflecting the station contact member towards the frame. Wipe should be approxi Observe the wipe on each normally closed contact should have a gap of.015 or more. 2. WIth the relay de-energized each nqrmally open parts are free from friction or binds. hand and allow it to reset to insure that all 1. Operate the armature of the voltage unit by adjustments be checked; It is recommended that thefollowingmechanical * MECHANICAL INSPECTION damage, and that all screws are tight. visual inspection that there are no broken or cracked molded parts or other signs of physical Remove the relay from its case and check by the relay received agree with the requisition. Check the nameplate stamping to insure that the model number, rating and calibration range of VISUAL INSPECTION Insure that no damage has been sustained in ship Immediately upon receipt of the relay an in spection and acceptance test should be made to ACCEPTANCE TESTS of the relay. cover is removed and cause trouble in the operation outside of the case may find its way Inside when the cartons in a place that is free from moisture, dust ing the relay. If the relays are not to be Installed and metallic chips. Foreign matter collected on the Reasonable care should be exercised in unpack immediately, they should be stored in their original

Also the relay should be set at the dropout the lowest acceptable battery charger outputvoltage. The ratio of pickup to dropout can be changed by value to be used and it should be checked. When droput is set, check that the relay will pick up at in its permanent location and preheated. After the making this check, the relay should be installed stallation. setting of the variable resistor Ri, (see Fig. 3.) on ACCEPTANCE TESTS be repeated before in and mechanical inspection described in the section D-C Undervoltage Relay Type NGV GEI-98305 The pickup voltage is adjusted by changing the observed in restoring them. to be out of limits, the following points should be points described in the previous sections are found If any of the mechanical or electrical check SERVICING. sary to make adjustments, refer to the section on age. A voltmeter with at least 1000 ohms per volt should be used for making the test. If it Is neces voltage should be 106% or less of the dropout volt rate and check the pickup and dropout. The pickup Set the battery charger at Its lowest charging tarnishing or corrosion. Examine the contact surfaces for signs of Check that the contact gap andwtpe values agree with those given in the ectien under ACCEPTANCE TESTS. or tendency to bind. reset to make sure thatthere is no excessive friction Manually operate the armature and allow it to MECHANICAL CIECKS Showing P sition of Auxiliary Brush and Shorting Bar Fig. 4 (8025039) Cross Section of Drawout Case THE TERMINAL BLOCK TRAVELS /4 INCH BEFORE ENGAGING THE MAIN BRUSH ON NOTE. AFTER ENRAGING AUXILIARY BRUSH CONNECTING PLUG SHORTING BAR AUXILIARY BRUSHJ TERMILL BLOCK select the test interval best suited to his individual requirements, it is suggested that the following will vary depending upon environment, type of relay recognized that the interval between periodic checks that a periodic test program be followed, It Is points be checked at an Interval of from one to two years. the operation of a power system it is important and the user s experience with periodic testing. Until the user has accumulated enough experience to In view of the vital role of protective relays In MAINTENANCE PERIODIC CHECKS AND ROUTINE 5 for Type NGV18A Relay with Type HFA65D for Low Battery Indicator Fig. 5 (01781o9003 (2])Exrernal Connection Diagrwn Th eoooo 111 NO 27 NG11 wr,.e. -c041 000000. 0001: 000 41 10100 F 10 Cl 0-4) OFC0700N. IOU)FC FOR R4. 0. 0 74 000 Olf fir 0-101 00 0-1 N4F+A.LLY 0 011-0 N0 A1._Y 01OL7i d IN 1 C oo roost: 104 f 1L1 t1l 1Z 11L j 101007 Ill 147V 047010 number on which the relay was furnished. possible, give the General Electric requisition wanted, and give complete nameplate data. If pany, specify quantity required, name of the part nearest Sales Office of the General Electric Com When ordering renewal parts, address the damaged. prompt replacement of any that are worn, broken or renewal parts be carried in stock to enable the It is recommended that sufficient quantities of RENEWAL PARTS tool as described above can be obtained from the paper or cloth to clean relay contacts. A burnishing superfine file which removes corroded material bility of the tool insures the cleaning of the actual roughened strip of flexible metal, resembling a quickly without scratching the surface. The flexi ing tool should be used. This consists of an etched For cleaning relay contacts, a flexible burnish points of contact. Never use knives, files, abrasive factory. voltage unit. The minimum gap must be 0.002 inch between armature and pole face. turning the residual screw of the telephone-type SERVICING

tnches 5/16 18 STUD CASE 9 125 1 L 168MM 6. 625 1. 125 PANEL DRILLING (TYPICAL).500 CU ThU T 5. 687 4. 08642 00000 00000 97531 PANEL LOCATION SEMI FLUSH SURFACE PANEL DRILLING.218 172MM 218 2.843 1. 468 --;--- SURFACE MTG. CUTOUT MAY REPLACE 1 09MM.1,156 (2) 5/16 18 STUDS 6. * Indicates revision LYICAL DIM. 232MM 4 HOLES 6MM GLASS 29MM BACK VIEW 144MM FUR SEMI-FLUSH MOUNTING FRONT VIEW 12MM FOR SURFACE MOUNTING FRONT VIEW * Fig. 6 (6209271 [8]) Outline and Panel Drilling Dimensions for Type NGV18A Relay 10 HOLES P3/4 DRILL DRiLLED HOLES 1/4 DRILL STUD NUMBER ING 29MM 37MM 4. 281 5MM 5MM PANEL 19MM MM VIEW FOR GEI-98305 DC Undervoltage Re ay Type NGV

GE Power Management 215 Anderson Avenue Markham, Ontario Canada L6E 1B3 Tel: (905) 294-6222 Fax: (905) 201-2098 wwwgeindustrial.com/pm