Guideline No.: E-07(201712) E-07 TRANSFORMERS. Issued date: December 26, China Classification Society

Similar documents
Guideline No.: E-07(201610) E-07 TRANSFORMERS. Issued date: October 28,2016. China Classification Society

Guideline No.: E-07(201501) E-07 TRANSFORMERS. Issued date: October 20,2015. China Classification Society

Guideline No.: E-03(201806) E-03 MOTORS. Issued date: June 7, China Classification Society

Guideline No.: E-03(201610) E-03 MOTORS. Issued date: October 28,2016. China Classification Society

Guideline No.: E-04(201610) E-04 GENERATORS. Issued date: October 28,2016. China Classification Society

Guideline No.: E-04(201510) E-04 GENERATORS. Issued date: October 20,2015. China Classification Society

E-15 Uninterruptible Power Systems (UPS)

E-15 Uninterruptible Power Systems (UPS)

N-03 STEERING GEAR CONTROL SYSTEMS

K-03 CRUDE OIL TANK WASHING MACHINES

E-12 Low-voltage Switchboard

Guideline No.M-10(201510) M-10 Marine Diesel Engine Fuel Injection Pump

M-11 MARINE DIESEL ENGINE FUEL INJECTOR

E-12 Low-voltage Switchboard

M-22 DUAL FUEL ENGINE

M-24 OUTBORD ENGINES

M-18 Controllable-Pitch Propeller

Unified requirements for systems with voltages above 1 kv up to 15 kv

M-14 Stern Shaft Sealing Apparatus

M-04 TRANSMISSION GEARS

TECHNICAL REQUIREMENTS FOR ELECTRICAL EQUIPMENT

ABB PTTR SPAIN. Zaragoza. The product: Cast coil transformers

EU RO Mutual Recognition Technical Requirements

Green T.HE. High efficiency Transformers. THE Global specialist in electrical and digital building infrastructures

DNVGL-CP-0110 Edition March 2016

CAST RESIN TRANSFORMERS

Technical Specification of GECOL. Packaged Transformers

CAST RESIN DISTRIBUTION TRANSFORMERS 2016 EDITION

شركة كهرباء محافظة القدس المساهمة المحدودة

AIR LUBRICATION SYSTEM INSTALLATION

EU Mutual Recognition Technical Requirements

tests Partial discharge level from day 1 10 pc Insulation 24 kv : impulse tested at 125 kv Insulation 36 kv : impulse tested at 170 kv, 200 kv indeed.

AF series contactors (9 2650)

Technical Specification for 12kV Powder Filled Current Limiting Fuse-Links for Use in Switchgear (In Oil)

MV Air Insulated Switchgear TAP17. Technical Data TGOOD

Transforming Energy.. For Advanced Technology

Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear

Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated Medium-Voltage Switchgear.

INTER PLANT STANDARD STEEL INDUSTRY SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION)

AF series contactors (9 2650)

INTERNATIONAL STANDARD

NB/T Translated English of Chinese Standard: NB/T ENERGY INDUSTRY STANDARD

Presented to the IAPMO Standards Review Committee on December 9, 2013

INSTRUCTION MANUAL BR 25 FOR RAILWAY APPLICATION 5COR BR25AT REV00

--> Buy True-PDF --> Auto-delivered in 0~10 minutes. GB/T

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)

P2 : About Us. P3 : Elsewedy Transformers. P4 : Why Elsewedy Dry Type Transformer? P6 : Cast Resin Dry Transformers. P7 : Technical Data Sheets

Technical Specification for 12kV and 24kV Powder Filled Current Limiting Fuse Links for Use in Switchgear (In Air)

INTERNATIONAL STANDARD

Lloyd s Register Type Approval System Test Specification Number GT04

Test report. Type VRLTC load tap changer VRLTC 1500A Type test summary report

Technical Specification for 12kV and 24kV Powder Filled Fuse-Links and Fuse Holders

Certified for best-in-class performance, reliability, and safety. Trihal sets a new standard for dry-type cast resin transformers

Resin Impregnated Paper Bushing, Oil to Air, Type GSB Technical guide

TGK Prefabricated Substation Technical Data

MT/T Translated English of Chinese Standard: MT/T COAL INDUSTRY STANDARD

Characteristics of LV circuit breakers Releases, tripping curves, and limitation

MEDIUM POWER TRANSFORMER

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

FUSES. Safety through quality

ISO INTERNATIONAL STANDARD

This standard covers the requirements of lighting chains. This standard covers only the safety requirements.

NXPLUS C Single busbar. Maintenance-free for lifetime

Bus bar Bushings up to 1.1kV and from 1.6kA to 4kA for Liquid Filled Transformers:

Product presentation CPT tech Jason Evershed, ABB Transformer Components, May 21st Dry-type transformers Innovative Technology

C. System Design and Performance Requirements

MIRUS International Inc. TYPICAL SPECIFICATION ULLTRA & ULLTRA-H1E 31 Sun Pac Blvd., Brampton, Ontario, Canada L6S 5P6

YOUR KEY ENERGY EFFICIENCY PARTNER CAST RESIN DRY-TYPE TRANSFORMERS

RESOLUTION MEPC.205(62) Adopted on 15 July GUIDELINES AND SPECIFICATIONS FOR ADD-ON EQUIPMENT FOR UPGRADING RESOLUTION

THE ISRAEL ELECTRIC CORPORATION LTD. GENERATION DIVISION SPECIFICATION GD1/16

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS

DRY TYPE TRANSFORMERS

NZQA registered unit standard version 3 Page 1 of 5. Demonstrate and apply knowledge of electrical machines

INSTRUCTION MANUAL CRS Combined insulation bushing

INSTRUCTION MANUAL RELAY FOR ON LOAD TAP CHANGER APPLICATIONS OR-25 5COR OR25 REV03

Menu. Home About this portal Latest updates. Print Save Resource detail Citations. Table of Contents

Product Specification Guide. Title: Southern States 362 kv RLSwitcher Vertical Interrupter Style Reactor Switcher

GB/T / IEC :2007

Issue Title Remarks. Instrument transformers See IEC 61869

Drive Duty Transformer Specification Virginia Transformer Corp. Power Up! Selecting the Right Transformer

Electrical network protection VIP30, VIP35. User s manual 12/2008

The construction features of EdM transformers

Annex to the Accreditation Certificate D-PL according to DIN EN ISO/IEC 17025:2005

Approved for use as fixed fire extinguishing system for machinery spaces and cargo pump rooms.

RULES PUBLICATION NO. 4/P IC ENGINES AND ENGINE COMPONENTS SURVEY AND CERTIFICATION July

H-02 Hydraulic Cylinder

DISTRIBUTION TRANSFORMERS CATALOGUE

Product Specification Guide. Title: Southern States 72 kv RLSwitcher Vertical Interrupter Style Reactor Switcher

General. Main electric circuits Fuses compartment Operating mechanisms Cables connection compartment

AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE

AS/NZS AS/NZS

Contact us. Catalog Low voltage generators for diesel and gas engines Industrial Marine applications - series Standard series

BHARAT ALUMINIUM COMPANY LTD. SPECIFICATIONS FOR SYNCHRONOUS GENERATOR GENERAL Make : Jinan Power Equipment Factory Type : WX2

SECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS

SECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS

Technical Specification for 12kV and 24kV Current Limiting Fuse- Links for Overhead Applications

Overhead transmission lines Spacers

TANZANIA BUREAU OF STANDARDS

Transcription:

Guideline No.: E-07(201712) E-07 TRANSFORMERS Issued date: December 26, 2017 China Classification Society

Foreword: This Guide is a part of CCS Rules, which contains technical requirements, inspection and testing criteria related to classification and statutory survey of marine products. This Guide is published and updated by CCS and can be found through http://www.ccs.org.cn. Comments or suggestions can be sent by email to ps@ccs.org.cn. Historical versions and release date : E-07(201510) October 20,2015 E-07(201610) October 28,2016 E-07(201705) May 9,2017 Main changes: 1. Table 5.1.5 (temperature rise limit) requirements for dry type transformers, revision and specification table 3.6.4. 2. Make clear article 7.2: Unit/batch inspection requirements for 50kVA and above transformers

CONTENTS 1 Application... 4 2 Normative references... 4 3 Definitions... 5 4 Plans and documents... 5 5 Design and technical requirements... 6 6 Type test... 9 7 Unit/batch inspection... 11 3 / 12

TRANSFORMERS 1 Application 1.1 This Chapter applies to approval and inspection of transformers for power and lighting (including single phase transformers rated at 1 kva or more and three-phase transformers rated at 5 kva or more) installed and used on ships and offshore installations. 2 Normative references 2.1 The approval and inspection of transformers in this Chapter are to be based on the following documents: (1) IEC 60092-303(1980-1) Electrical installations in ships Part 303: Equipment - Transformers for power and lighting (2) IEC 60092-303-am1 (1997-9) Amendment 1-Electrical installations in ships Part 303: Equipment - Transformers for power and lighting (3) IEC 60076-1(2011-04) Power transformers Part 1: General (4) IEC 60076-2(2011-02) Power transformers Part 2: Temperature rise (5) IEC 60076-3(2013-07) Power transformers Part 3: Insulation levels, dielectric tests and external clearances in air (6) IEC 60076-4(2002-06) Power transformers Part 4: Guide to the lightning impulse and switching impulse testing - Power transformers and reactors (7) IEC 60076-5(2006-02) Power transformers Part 5: Ability to withstand short circuit (8) IEC 60076-10: (2016-03) Power transformers Part 10: Determination of sound levels (9) IEC 60076-10-1: (2016-03) Power transformers Part 10-1: Determination of sound levels - Application guide (10) IEC 60076-11(2004-05) Power transformers Part 11: Dry-type transformers (11) IEC 60076-12: (2008-11) Loading guide for dry-type power transformers (12) IEC 60529 (2013-08) Degrees of protection provided by enclosures (IP Code) 4 / 12

(13) IEC 60068-2-30(2005-08) testing Part 2-30: Tests - Test Db: Damp heat, cyclic (12 h + 12 h cycle) (14) IEC 60068-2-11(1981-01) Environmental testing Part 2: Tests - Test Ka: Salt mist (15) CCS Rules for Classification of Sea-going Steel Ships (16) Guideline on Type Approval Test of Electrical and Electronic Products (current valid version) 3 Definitions 3.1 The terms and definitions used in this Chapter are consistent with those of IEC 60076. 4 Plans and documents 4.1 The following plans and documents are to be submitted to CCS for approval: (1) General plans; (2) Drawings of main parts including frame, coils, iron cores, terminal boxes, enclosures (if applicable); (3) Technical specifications of the products; (4) Type test programme. 4.2 The following plans and documents are to be submitted to CCS for information: (1) Operation instructions for the products; (2) Process flow diagram indicating quality control points; (3) Documents of manufacturing procedures, covering winding, sheet metal processing, painting (if applicable), lamination, insertion, vacuum dipping coating (if applicable), drying (if applicable), welding, polyester casting (if applicable) and various calculation sheets (tables); (4) List of types (trade marks) and suppliers of main raw materials (e.g. magnetic wires, silicon steel sheets, insulation paper and insulating paints); (5) Drawing of external wiring. 5 / 12

5 Design and technical requirements 5.1 Marine transformers are to comply with IEC 60092-303 and in addition, the following requirements: 5.1.1 All transformers, except those used for motor starting, are to be double wound or have multiple windings, with no electrical connections between primary and secondary windings. 5.1.2 In general, transformers are to be of dry, air-cooled type. Proposals for the use of liquid-immersed transformers are to comply with the following requirements: (1) Cooling fluids are to be non-toxic and of low flammability. Liquid-immersed transformers are to be provided with a pressure release device with alarms and there is to be a suitable means provided to contain any liquid which may leak from the system due to the release of alarms or breakage of transformers; (2) Where forced cooling is used, there is to be temperature monitoring of the heated cooling medium and coils with an alarm being given when the temperature exceeds a preset value which can be recovered by reducing load. 5.1.3 The voltage drop (voltage regulation) in the secondary voltage between no load and rated load, under resistive load, is not to exceed the following: (1) 2.5% for single phase transformers rated more than 5 kva or 3-phase transformers rated more than 15 kva; (2) 5% for single phase transformers rated up to 5 kva or 3-phase transformers rated up to 15 kva. 5.1.4 Transformers arranged for parallel operation are to comply with the following requirements: (1) their winding connections are to be compatible; (2) their rated voltage ratios are to be equal (with tolerances within permissible limits); (3) their short-circuit impedance values are to be equal (if expressed in percentage, a ratio within 0.9 to 1.1 may be allowed); (4) when transformers are intended for operation in parallel, the rated output of the smallest transformer in the group is not be less than 50% of the rated output of the largest 6 / 12

transformer in the group. 5.1.5 The temperature rise of transformers at any part is not to exceed the values given in Table 5.1.5 during continuous operation at rated output, where the ambient air temperature is based on 45. Transformer type Limit of Temperature Rise Table 5.1.5 Method of Temperature rise limit of windings (K) measurement Class A insulation Windings 55 Dry type Oil-immersed Class E insulation Windings 70 Class B insulation Windings 75 Class F insulation Windings 95 Class H insulation Windings 120 Not to exceed the External surface of the magnetic core and structural components Defined as ON or OF in IEC60092-303 permissible temperature rise of the insulating material in contact Resistance method Thermometer or thermocouple 65 Thermometer or thermocouple Defined as OD in IEC60092-303 70 method 5.1.6 All transformers are to be capable of withstanding, without damage, the thermal and mechanical effects of a short-circuit at the terminals of any windings for 2 s. 5.1.7 Transformers are to be subjected to high voltage test by applying a test voltage between primary and secondary windings and between windings and the frame. The test is to be made according to Table 5.1.7 and maintained for 1 min without breakdown and flashover. Voltage of High Voltage Test Table 5.1.7 Maximum voltage (root mean square value) kv Rated short-time withstand voltage (root mean square value) kv 1.1 3 3.6 10 7.2 20 12.0 28 17.5 38 24.0 50 36.0 70 5.1.8 Transformers are to withstand an induced high voltage test with a voltage twice the rated voltage and the duration of the test is to be 1 min for a frequency less than or equal to twice the 7 / 12

rated frequency, or t (t = 60 2 rated frequency/test frequency (s)), but not less than 15 s for an increased frequency greater than twice the rated frequency. For transformers subject to temperature rise test, the induced high voltage test is to be carried out immediately after the temperature rise test. 5.1.9 Proper terminals and clear marks should be provided for outside wirings. The terminals should be protected and isolated from each other to avoid accidental grounding, short circuit or being touched. 5.1.10 Transformers should have a grounding terminal for protection use. All the metal parts which are not electrically charged should have structural method to be connected to the grounding terminal. 5.2 Marine transformers with metal enclosures are to comply with the above-mentioned standards an in addition, the following requirements. 5.2.1 Metal enclosures are to be of sufficient mechanical strength for mechanical protection, normal operation and safe handling of transformers. 5.2.2 Metal enclosures are to have sufficient space to maintain enough air clearance and creepage distance between conducting parts and between conducting parts and non-conducting parts of transformers inside metal enclosures. When a transformer mounted in the metal enclosure is in normal operation, the temperature rise is to comply with the requirements of Table 5.1.5 for Classification of Sea-going Steel Ships. 5.2.3 Degree of protection provided by metal enclosures is to be appropriate to the ambient conditions of the location where transformers are installed. 5.3 For transformers with voltage rating higher than 1kV, following requirements are to be complied with: 5.3.1 The enclosure protection class should be at least IP23. If installed in locations which can be accessed by unprofessional personnel, the enclosure protection class should be at least IP4X, the installation should comply with CCS Rules Part Four 2.14.7.1. 5.3.2 Dry-type transformers should comply with acceptable standards (See IEC60076-11 Dry-type transformers or other equivalent standards), oil-immersed transformers should also comply with acceptable standards (See IEC60076 power transformers or other equivalent standards). 8 / 12

5.3.3 Oil-immersed transformers should have following alarms and protections: (1) Low oil level alarm; (2) High oil temperature alarm; (3) Low oil level tripping or load decrease; (4) High oil temperature - tripping or load decrease; (5) High air pressure relay tripping. 6 Type test Marine transformers are to be subjected to type test according to the following requirements. 6.1 Unless otherwise specified, all tests are to be carried out under the following ambient conditions: (1) ambient temperature: 15 to 40, cooling water temperature should be no higher than 25 if applicable; (2) relative humidity: 30%RH to 90%RH; (3) air pressure: 86 to 106 kpa. 6.2 Type test of marine transformers is at least to be in accordance with Table 6.2. Type Test Items Table 6.2 No. Test item Technical requirements Test method 1. Exterior inspection Visual inspection 2. 3. 4. 5. Measurement of winding resistance Measurement of voltage ratio and check of phase displacement Measurement of no-load loss and current Measurement of short-circuit impedance and load loss IEC 60076-1 para. 11.2 IEC 60076-1 para. 11.2 IEC 60076-1 para. 11.3 IEC 60076-1 para. 11.3 IEC 60076-1 para. 11.5 IEC 60076-1 para. 11.5 IEC 60076-1 para. 11.4 IEC 60076-1 para. 11.4 9 / 12

6. Voltage withstand 7. Induced voltage withstand 8. Insulation resistance test Lightning impulse test 9. (applicable for rated voltage higher than 1kV) Partial discharge measurement 10. (applicable for Um> 3.6 kv dry-type ) Measurement of 11. zero-sequence impedance(s) on three-phase transformers Continued Table 6.2 3.6.6.3, Chapter 3, PART FOUR of CCS Rules IEC 60076-3 para. 11 3.6.6.4, Chapter 3, PART FOUR of CCS Rules IEC 60076-3 para. 12.2.1 3.6.7.5, Chapter 3, PART FOUR of CCS 3.6.7.5, Chapter 3, PART FOUR Rules of CCS Rules IEC 60076-11 para. 21 IEC 60076-3 para. 13 IEC 60076-11 para. 22 IEC60270, IEC60076-3Appendix A IEC 60076-1 para. 11.6 IEC 60076-1 para. 11.6 12 Sound level measurement IEC 60076-10 IEC 60076-10 13 Voltage regulation test 14 Short-circuit test (when necessary) 15 Temperature rise 16 Damp heat test 17 Degree of protection (for transformers with enclosures) 3.6.3.1, Chapter 3, PART FOUR of CCS Rules for Classification of Sea-going Steel Ships 3.6.6.7, Chapter 3, PART FOUR of CCS Rules for Classification of Sea-going Steel Ships 3.6.6.2, Chapter 3, PART FOUR of CCS Rules CCS Guidelines for Type Approval Test of Electric and Electronic Products (current valid version) 2.10, 6 period 3.6.7.6, Chapter 3, PART FOUR of CCS Rules for Classification of Sea-going Steel Ships IEC 60076-5 IEC60076-2(for oil-immersed ), IEC60076-11 para.23(for dry-type) IEC 60068-2-30 IP IEC 60529 18 Salt mist test (for open deck) Ka IEC 60068-2-11 19 Function test of components (If applicable, PT100, cooling fans, protection devices, etc.) 6.3 Selection of typical samples 6.3.1 Type test samples are to be taken from qualified products by CCS Surveyor at the manufacturer. 6.3.2 At least one marine transformer is to be taken as test sample (more may be taken if necessary), if the capacity of the product applying for approval is not larger than 200kVA, the capacity of which is to be the maximum in the products to be approved. If the capacity of the product applying for approval is larger than 200kVA, then the test sample can be chose between range 50%~100%, but it is needed to confirm that the manufacturer has the ability to produce the 10 / 12

maximum capacity. Where different insulation levels and constructions are to be covered by approval, related products are to be sampled respectively. 6.3.4 If environmental tests are restricted by test equipment (such as damp heat test), a smaller transformer of the same type may be taken as test sample. 6.4 Test organization 6.4.1 The initial type test is to be carried out by a competent test organization holding CCS Product Inspection and Test Organization Approval Certificate. 6.4.2 For renewal of the type approval certificate, type test may be carried out at the manufacturer s laboratory in the presence of CCS Surveyor, subject to agreement of CCS and provided that the manufacturer has required test environment and equipment as well as competent inspection and test personnel. 7 Unit/batch inspection 7.1 The manufacturers holding a CCS Type Approval B Certificate are still to carry out unit/batch inspection for all transformers and submit relevant certification documents and test reports. 7.2 For 50kVA and above transformers,the unit/batch inspection is required.the number of transformers to be inspected by CCS is to be 10% of the total number of submitted ones, but not less than 2 sets, unless the inspection is requested for one transformer only.unit/batch inspection items are at least to include items: (1) visual examination and processing examination (visual); (2) measurement of winding resistance (IEC60076-1 para.11.2); (3) measurement of voltage ratio and check of phase displacement (if applicable) (IEC 60076-1 para. 11.3); (4) measurement of short-circuit impedance and load loss (IEC 60076-1 para. 11.4); (5) measurement of no-load loss and no-load current (IEC 60076-1 para. 11.5); (6) withstand voltage test (IEC 60076-3 para. 11); (7) induced withstand voltage test (IEC 60076-3 para. 12.2.1); (8) measurement of insulation resistance (3.6.6.5, Chapter 3, PART FOUR of CCS Rules for 11 / 12

Classification of Sea-going Steel Ships); (9) partial discharge test (for Um 3.6 kv dry-type) (IEC60076-11 para. 22); (10) voltage regulation test (may be omitted when impractical at the manufacturer, subject to agreement of CCS) (3.6.6.6, Chapter 3, PART FOUR of CCS Rules for Classification of Sea-going Steel Ships); (11) temperature rise test (may be required only for the first product of batch products of the same type) (3.6.6.1~3.6.6.2, Chapter 3, PART FOUR of CCS Rules for Classification of Sea-going Steel Ships). (12) function test of components(if applicable, PT100, cooling fans, protection devices, etc.). 12 / 12