TotalPac 3 Firecyle III Wet pipe Remote controlled system

Similar documents
TotalPac 3 Deluge, Electric release Remote controlled system

TotalPac 3 Deluge system Pneumatic release

TotalPac 3 Double interlock Firecyle III Preaction Remote controlled system

TotalPac 3 Non interlock Preaction system Pneumatic release

TotalPac 3 Double interlock Preaction, Electric/PneuLectric release Remote controlled system

TotalPac 3 Non interlock Preaction, Electric release Remote controlled system

TotalPac 3 Double interlock Preaction, Electric/Pneumatic release Remote controlled system

FireFlex DUAL Single Interlock, Remote controlled system

TECHNICAL DATA. Q= C v P S

TECHNICAL DATA. Q= C v P Cv = Flow Factor (GPM/1 PSI P)

TECHNICAL DATA. Trimpac 244a. April 15, 2011

TECHNICAL DATA. Trimpac 249a. September 16, 2013

TECHNICAL DATA 1-1/2 (dn40)

TECHNICAL DATA TRIMPAC MODEL B-4, B-4B & B-4S SINGLE INTERLOCK PREACTION SYSTEM WITH PNEUMATIC RELEASE

TECHNICAL DATA. Inlet Type Outlet Type OBSOLETE 6 (DN150)

Q= C. v P S Refer to Table 1 for part numbers and shipping weights. Accessories: Table 1: Valve Part Numbers and Specifications

Instructions for Installation, Operation, Care and Maintenance

TECHNICAL DATA CONCENTRATE CONTROL VALVE APPLICATIONS, PRIMING CONNECTIONS, AND TRIMS 1. GENERAL DESCRIPTION 2. LISTINGS AND APPROVALS.

TECHNICAL DATA. Viking Technical Data may be found on Style: 90 Degree Pattern (inlet to outlet)

DV-5a Automatic Water Control Valve Single Interlock Preaction Fire Protection Systems 1-1/2 Inch to 8 Inch (DN40 to DN200) General Description

DELUGE VALVE MODEL: SD-DVA TECHNICAL DATA : VALVE OPERATION TRIM DESCRIPTION DESCRIPTION PRESSURE THREADED OPENING

TECHNICAL DATA. Q= C v P S FLOW CONTROL VALVE MODEL J-2 HALAR COATED 1-1/2 & 2 (DN40 & DN50) 1. DESCRIPTION

Instructions for Installation, Operation, Care and Maintenance

Q= C v P S. Flow control valve Model j-2 Halar coated

Model DV-5 Deluge Valve, Diaphragm Style, 1-1/2 thru 8 Inch (DN40 thru DN200), Deluge System Electric Actuation

Series 758 FireLock Actuated System Valve

DELUGE VALVE DATA SHEET

30.85 FireLock NXT Actuated Valve with LPCB Approved Preaction Trim

FireLock NXT Deluge Valve. With Deluge Trim Grooved x Grooved. System No. Submitted By Spec Sect Para Location Date Approved Date

Features 1. Differential Latch-type, lightweight, dependable

TECHNICAL DATA 2-1/2-8 (dn65 - dn200)

Model DDX Deluge Valves 4" (100 mm), 6" (150 mm) and 165 mm Sizes

Model DDX Deluge Valve 8 (200mm) Features

DV-5a Automatic Water Control Valve Double Interlock Preaction Fire Protection Systems 1-1/2 Inch to 8 Inch (DN40 to DN200) General Description

Section O Preaction Systems

Series 769 FireLock NXT Deluge Valve

TECHNICAL DATA. Q= C v P S. Table 1 - Valve Part Numbers and Specifications

TECHNICAL DATA. Q= C v P S FLOW CONTROL VALVE MODEL H-2 HALAR COATED 2 (DN50) - 6 (DN150)

Wet pipe low flow foam/water manifold system

MODEL RCW NON-INTERLOCK PREACTION SYSTEM

1-1/2 Inch (DN40) 9 lb (4,1 kg) Groove Groove 1 8 lb (3,6 kg) Flange Groove 1 N/A N/A. Flange Flange N/A N/A

Section N Deluge Systems

Section R Foam Systems

Section R Foam Systems

APPLICATION FOR OSHPD SPECIAL SEISMIC CERTIFICATION PREAPPROVAL (OSP)

DV-5 Deluge Valve, Diaphragm Style, 1-1/2 thru 8 Inch (DN40 thru DN200), Deluge System Wet Pilot Actuation General Description

TECHNICAL DATA P S. Q= Cv MODEL E-2 DELUGE VALVE HALAR COATED ANGLE STYLE

TECHNICAL DATA CAUTION

Model CV-1FR Grooved-End Riser Check Valves 2 Inch to 12 Inch (DN50 to DN300) General Description. Installation. Technical Data

Series 756 FireLock Dry System Check Valve

AGCX Bulletin 519 C/Alfoz de Bricia nº4 P.l. Villalonquéjar Burgos (Spain) Tlfno: PAG 1 de 50

Instructions for Installation, Operation, Care, and Maintenance

Worldwide Contacts.

TECHNICAL DATA. Notes: For use with Trim Charts on Pages 2-4

Sl. No. Description Pages

LEAD FREE * LFF113RFP Flood Protection Shut Down Valve

TECHNICAL DATA OBSOLETE. Inlet Type Outlet Type in mm. Thread Thread in. ANSI B Flanged Flanged in.

MODEL RCW DELUGE SYSTEM ELECTRIC, WET PILOT, AND DRY PILOT ACTUATION

Technical Data. UL Listing is based on the following criteria:

Section M Dry Pipe Systems

Preaction System with DV-5 Deluge Valve Double Interlock Electric/Electric Actuation. General Description. Page 1 of 14 DECEMBER 2014 TFP1465

Tekleen GB6 & GB7 USERS AUTOMATIC FILTERS, INC. MANUAL

FIRE PROTECTION EQUIPMENT 2017 DATA SHEETS BSP FIRE RESERVES THE RIGHT TO ALTER INFORMATION CONTAINED IN THIS CATALOGUE AT ANY TIME.

Instructions for Installation, Operation, Care and Maintenance

FireLock NXT Actuated Valve with Preaction Trim. System No. Submitted By Spec Sect Para Location Date Approved Date

To ensure proper installation, digital pictures with contact information to before startup.

DV-5A Automatic Water Control Valve Remote-Resetting Deluge Fire Protection Systems 1-1/2 Inch to 8 Inch (DN40 to DN200) General Description

Instructions for Installation, Operation, Care and Maintenance

Valves & Flow Control Components Valves & Flow Control Components

Table Summary of Sprinkler System Inspection, Testing, and Maintenance. Reference. Inspection , ,

TECHNICAL DATA. model f-1 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA. Page 1 of 11

Section P Flow Control and Pressure Regulation

Grooved Piping System for Fire Protection Services

Instructions for Installation, Operation, Care and Maintenance

Easy Riser swing check valve Models E-1 & F-1

SHORTER. LIGHTER. MORE VERSATILE. 1 VALVE 10 TRIM CONFIGURATIONS 4" AND 6" MODEL RCW WATER CONTROL VALVE FOR DRY, PREACTION AND DELUGE APPLICATIONS

TECHNICAL DATA. Table 1: Model F1 Dry Valve Part Numbers and Specifications

Section P Flow Control and Pressure Regulation

Automatic Changeover Medical Manifold Installation, Operation and Maintenance Manual

70.03 Victaulic Vortex TM

January 2007 Approval Guide Fixed Extinguishing Systems 5-57

Instructions for Installation, Operation, Care and Maintenance 2 PSI (0,14 bar) Pneumatic Supervising Pressure with Electric Actuation

GW MKIII DELUGE VALVE - ALUBRONZE EXTERNAL RESET, PNEUMATIC

LEAD FREE * LFF113FP. Wireless Smart Flood Protection Shut Down Valve with SentryPlus Alert Technology. Materials NOTICE NOTICE ES--LFF113FP

FLOOD PROTECTION SHUT DOWN VALVE (3 and smaller)

Instructions for Installation, Operation, Care and Maintenance

LEAD FREE * PVS-7000 Engineered Flood Protection Valve Station with SentryPlus Alert

LEAD FREE * LFF113RFP Wireless Smart Flood Protection Shut Down Valve with SentryPlus Alert Technology

NMSU FIRE DEPARTMENT FIRE PUMP ACCEPTANCE TEST

TECHNICAL DATA OBSOLETE

PATTERSON PUMP COMPANY

Grooved Piping System for Fire Protection Services

DV-5 Deluge Valve Aluminium Bronze Diaphragm Style General Description

ALARM CHECK VALVE 3", 4" & 6" MODEL H-1 FLANGE/FLANGE 3" & 4" MODEL H-2 GROOVE/GROOVE 3", 4" & 6" MODEL H-3 FLANGE/GROOVE

Model QRS Electronic Accelerator (Quick Opening Device) For Dry Pipe or Preaction Systems General Description

FIRE PROTECTION PRODUCTS

FIRE SPRINKLER SYSTEM

DWS 41. Installation Data 44 Performance Specs DWS & DW-PRV Series

SECTION HVAC CONTROL SYSTEM PART 1 GENERAL 1.01 SUMMARY. A. Section Includes:

Section L Wet Pipe Systems

Transcription:

(Optional) DESCRIPTION This TOTALPAC 3 integrated fire protection system by FireFlex Systems Inc. consists of a Firecycle III system trim totally preassembled, pre-wired and factory tested. All electrical and mechanical components of the system are contained in one single unit TOTALPAC 3 Firecycle III systems are built around the Viking trim using flow control valves model J-1. Firecycle III Wet preaction system uses closed automatic sprinklers in the sprinkler piping. A detection network is used in parallel with the automatic sprinkler system and is designed to operate before a sprinkler head fuses. This network is electric and may be actuated by normally closed rate compensated heat detectors, or normally open manual pull station. The detection system operates before the sprinkler fuses and gives an alarm. When the detection system operates it gives an alarm and activates the flow control valve. In addition to automatically detecting a fire and turning the system on, Firecycle III has the added ability to sense when the fire has been controlled, and automatically turn off the water flow once a preprogrammed "Soak Timer" has been satisfied. Should the fire rekindle, the releasing control panel will initiate the sequence again. This unique Firecycle III feature will repeat as long as power is available to the panel, helping to minimize water usage, water damage, and the danger of pollution to surrounding areas. A special features offer perfect fail-safe modes, Firecycle III preaction systems provide protection with or without electrical power. If a condition occurs that removes both the primary and secondary power supplies, the pneumatic actuator becomes the release mechanism and the system will operate as a dry pipe system. The Firecycle III preaction system requires a VIKING VFR-400 releasing control panel All the valves are rated up to a maximum of 250 psi WWP (1724 kpa) max. and are available in the following diameters: 1½" (40 mm) 2" (50 mm) 3" (80 mm) 4" (100 mm) 6" (150 mm) 8" (200 mm) Standard features culus Listed & FM Approved as an assembled unit Factory assembled, programmed and tested under ISO-9001 standards Prewired to a terminal block Easy and compact installation Viking conventional trim rated at 250 psi (1724 kpa) Galvanized trim piping Serial number for easy reference Corrosion resistant cabinet with flush type handle and lock No open drain cup inside the unit numerous modular options to meet the most demanding jobsite requirements Four styles of modular air supply options Inlet & outlet hydrostatic test ports User-friendly standardized operation & installation manual Free interactive simulator 1 of 12 FM-076D-0-75C

Cabinet The TOTALPAC 3 cabinets are made of sturdy 14 gauge steel, they are available in four (4) sizes; 23" x 25" x 77" (58.4 x 63.5 x 195.6 cm) for 1½",and 2" systems, 36" x 25" x 77" (91.4 x 63.5 x 195.6 cm) for 3" and 4" system, 46" x 25" x 77" (116.8 x 63.5 x 195.6 cm) for 6" system 54" x 31" x 81" (137.2 x 78.7 x 205.7 cm) for 8" system All surfaces are rust proof coated, inside and outside, with fire red, oven baked polyester powder on phosphate base. Cabinet is provided with one or two doors, all provided with a neoprene gasket to absorb vibrations. A field wiring electrical junction boxes is integrated with the cabinet for connection of all electrical components in the trim. Pressure switches, supervisory switches, etc. are all factory wired to a terminal strip (TBA) for contractor's field wiring. Gauges to indicate air, water supply pressure and priming water pressure are all visible through clear Lexan windows. IMPORTANT: TOTALPAC 3 units are NOT designed to be installed where they will be subjected to outdoors and/or freezing conditions. Refer to environmental data for additional details. Subjecting the unit to conditions outside these limitations might tamper the normal operation of the system. A field wiring electrical junction boxes is integrated with the cabinet for connection of all electrical components in the trim. Pressure switches, supervisory switches, etc. are all factory wired to a terminal strip (TBA) for contractor's field wiring. Multiple unit installations are easily achieved by manifolding units together at their water inlets but drains shall remain separate and open. Sequence of operation (see trim diagram) In a fire condition, when the detection condition is satisfied, system releasing control panel (supplied by others) activates an alarm and energizes normally closed solenoid valve (F2) open and normally open solenoid valve (F1) closed. Pressure is released from the priming chamber of the flow control valve (A1) to the open drain manifold faster than it is supplied through the restricted orifice (B3). The flow control valve clapper opens to allow water to flow into the system piping and alarm devices, causing the alarm pressure switch (C1) and optional water motor alarm (C2) to activate. When a sprinkler head opens, water will flow from the system. Water discharges until all Firecycle III detectors have reset (cooled below their set point). After all detectors have reset, the Firecycle III releasing control panel activates the soak timer, allowing the system to flow water for a pre-determined period of time. When the soak timer has elapsed, the releasing control panel de-energizes the normally closed solenoid valve (F2), allowing the flow control valve to re-primes and closes, stopping the flow of water through the piping system. Should a Firecycle III detector go into alarm, the releasing control panel reenergizes the normally closed solenoid valve (F2) open, and the entire cycle repeats. Systems hydraulic limitations WARNING The information contained herewith is for estimation and evaluation purposes only. Its use remains the responsibility of the designer. Designers should refer to the appropriate NFPA Standards and any other applicable codes for their final design. Also refer to FireFlex Systems Inc. appropriate user manuals and to manufacturer's data sheets for additional details. Systems limitations indicated below are nominal flow limitations. Piping Equivalent Lengths w/o Piping Equivalent Lengths c/w Usage Range shut off valve shut off valve (gpm) (m.) (ft.) (m.) (ft.) GPM 1½ 0 210 8.3 27.2 8.5 27.9 272 2 0 360 11.65 38.2 11.85 38.9 272 3 100-700 19.84 65.1 23.38 76.7 762 4 200 1400 21.89 71.8 25.33 83.1 1597 6 400-3500 33.28 109.15 37.28 122.3 1597 8 750-5250 41.15 135 44.71 146.7 1597 System size (in.) Drain flow @ 250 PSIG w.p. FM-076D-0-75C 2 of 12

Standard equipment Flow control valve The Viking flow control valve is a quick opening, differential type flood valve with a spring loaded rolling diaphragm clapper. The flow control valve can be used to facilitate manual or automatic on/off control. The Viking flow control valve is an integral part of the Viking Firecycle System. The valve is held closed by system water pressure trapped in the priming chamber, keeping the outlet chamber and system piping dry. In fire conditions, when the releasing system operates, pressure is released from the priming chamber. The flow control valve clapper opens to allow water to flow into the system piping. Solenoid valve The high pressure solenoid valve is a two-way type with one inlet and one outlet. It is a packless, internal pilot operated valve, suitable for use in releasing water pressure from the priming chamber of Viking flow control valves. The solenoid valve has floating diaphragm construction, which requires a minimum pressure drop across the valve to operate properly. IN OUT Alarm water flow switch The alarm water flow switch monitors the water flow within the sprinkler piping. Should an automatic sprinkler open to allow water to flow into the sprinkler piping. The alarm water flow switch will activate, indicating a water flow signal. Water supply control valve The water inlet control valve is a supervised, indicating butterfly valve. Purpose of this vale is to manually shutoff the preaction system. Releasing circuit disable switch The releasing circuit disable switch is used to disable the releasing solenoid. When the key is set to Disable, the releasing solenoid will be disconnected from the control panel s releasing circuit, causing a trouble signal and preventing accidental discharge during maintenance or inspection. 3 of 12 FM-076D-0-75C

Optional mechanical equipment Shut-off valve & sight glass option The Shut-off valve & sight glass option is intended to be used for applications where testing of the system operation without filling the sprinkler piping network is desirable and where it is critical that all functions of the preaction system be tested under actual discharge conditions. Examples of such applications are freezers, ovens, museums, data processing and other hazards where the possibility of water leaking from the piping system is to be avoided at all costs. Warning: Shut-off valve & sight glass option is not available on 8" systems. Fire department connection The fire department connection option consists of a grooved tee fitting installed in lieu of the 90 degree elbow at the outlet of the deluge valve (A1). An access hole of the proper diameter is factory pre-drilled on the side of the TOTALPAC 3 enclosures for connection of the piping going to the fire department connection. Note: The fire department connection hardware itself (drain, Siamese, etc.) is NOT provided with this option and shall be provided by the installing contractor. Refer to NFPA- 13 Standard for additional information about the equipment layout and installation. Warning: Shut-off valve is not available combined with Fire department connection on 6" systems. Warning: Fire department connection is not available on 8" systems. Main Drain Valve (D3) Sight Glass Assembly (D5) Supervised Shut-off Valve (D4) Grooved Tee Fitting with Coupling & Cap To Fire Dep't Connection (hardware by Contractor) Point flash light here Supervised Water Supply Control Valve (D1) FM-061H-0-79B FM-061H-0-78B FM-076D-0-75C 4 of 12

Optional mechanical equipment (continued) Semi and full flange option When required by the user, TOTALPAC 3 units can be provided in either a semi-flanged of full flanged configuration. The semi flanged option provides flanged fittings only on the water inlet pipe (side needs to be specified at the time of order) and on the system riser outlet. The drain manifold is then provided with a threaded end that also needs to have its side specified (left or right). The rest of the fittings are the same as usual with the main components being provided in the standard grooved -grooved configuration. The full flanged option is the same as above but goes a step further with the main components being also provided with a flanged-flanged configuration. When provided, the face of the flanges will always be situated 6 inches from the outside face of the mounting base or cabinet surface. OSHPD option Pre-approved construction, under OSP-0341-10, using specific components. Flanged fitting outside cabinet (when provided) Threaded end Field Connection to Open Drain (specify side) Flanged fitting outside cabinet (when provided) Field connection to Water Supply (specify side) FM-061H-0-208B 5 of 12 FM-076D-0-75C

Details & field wiring diagrams Cabinet with main components - Configuration without releasing control panel, shown with air style "A" Cable Entry Release Solenoid Disconnect Switch Junction box TBA & TBB Riser Outlet to Sprinklers Network Straight Through Flow Control Valve Water Supply Control Valve Drain Outlet (either side) Water Inlet (either side) FM-061H-0-195A FM-076D-0-75C 6 of 12

Trim diagram FIELD CONNECTION TO SPRINKLER PIPING NETWORK C3 B13 F2 D3 F1 A2 B10 B6 B11 B4 B3 D1 B2 B12 FIELD CONNECTION TO OPEN DRAIN (on both sides) FIELD CONNECTION TO WATER SUPPLY (on both sides) TotalPac Base (shown without enclosure) CONTRACTOR'S HYDROSTATIC TEST PORT (water supply side) FM-061H-0-110A Trim Components: A2 B2 B3 B4 B6 B10 B11 B12 B13 Flow control valve Strainer 1/8" Restricted orifice Spring loaded check valve Flow test valve Emergency release valve Priming pressure water gauge & valve Water supply pressure gauge & valve System water pressure gauge & valve C3 D1 D3 F1 F2 Alarm water flow switch Water supply control valve Main drain valve N.O. solenoid valve 24Vdc N.C. solenoid valve 24Vdc 7 of 12 FM-076D-0-75C

Field wiring diagram: CHICAGO OPTION OPTIONAL LOS ANGELES OPTION WATER FLOW EOL MAIN VALVE EOL SOLENOID VALVE BYBASS SWITCH SUPERVISORY EOL 24 VDC Needed for keyswitch LEDs operation SOLENOID VALVE SHUT-OFF VALVE EOL MAIN VALVE OPTIONAL TBA 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 TBC 1 SHUT-OFF VALVE 23 24 25 26 2 3 4 5 WATER FLOW SWITCH 6 C NO NC MAIN VALVE SUPV SWITCH C NO NC S N.C. SOLENOID VALVE (see table below for ratings) LED POWER DISCHARGE BYPASS SWITCH S N.O. SOLENOID VALVE (see table below for ratings) SHUT-OFF VALVE SUPV SWITCH NOTE: MAIN VALVE SUPV SWITCH SHUT-OFF VALVE SUPV SWITCH Contacts provided for connection to the building's central Fire Alarm Panel. NOTES: All devices are factory wired. All devices are shown in their normal supervisory state. Contacts are rated: Pressure switches: 2A, 30VDC 10A, 125/250VAC Supervisory switches: 0.5A, 125VDC 0.25A, 250VDC 5A, 1/6HP, 125/250VAC Use dry contacts with power limited circuits only. EOL devices (not included) must be compatible with the Release Control Panel used. FM-061H-0-94B SOLENOID VALVE ELECTRICAL RATINGS Viking P/N Description Pressure Voltage Watts DC Amps (De-energized) Rating 11591 NC 24 VDC 10.0 DC 416 ma 300 psi (2 068 kpa) 11595 NO 24 VDC 10.0 DC 416 ma 300 psi (2 068 kpa) Notes: 1. Solenoid Valve is UL Listed as Fire Protection Special System Water Control Release Service (UL 429A Product category VLTR). 2. Voltage Drop: For proper operation, make sure that voltage at the solenoid valve is at least 85% of nameplate rating. Note: This unit has been provided without the Integrated Release Releasing control panel. Due to Listings and Approvals specific to the Firecycle System, no other release releasing control panel other than the Firecycle III Model VFR-400 Releasing control panel can be used with this unit. Use of any other releasing control panel is not recommended and will void the unit's Listings & Approvals and may prevent the system from operating normally. FM-076D-0-75C 8 of 12

Dimensions Figure 1 Cabinet dimensions: D E P TBA, TBB & TBC Q TBB TBA & TBC F CONTROL PANEL (except for Remote Controlled Unit) SPRINKLER RISER SCH.40 GROOVED OUTLET CONTROL PANEL SPRINKLER RISER SCH.40 GROOVED OUTLET ØB OPTIONAL SHUT-OFF VALVE OPTIONAL FIRE DEP'T CONNECTION OUTLET (DRILLED ONLY WHEN ORDERED) S (W) R (V) J L N DRAIN - SCH.40 GROOVED OUTLET N ØC T ØA M WATER INLET SCH.40 GROOVED OUTLET M K H G U FM-061H-0-129A Dimensions are nominal and may vary ±¼". Dimensions V and W are with the optional Fire Department Connection System Size A B C D E F G H J K L M N P Q R S T U V W 1½" 2" 1½" 2" 23 25 77¼ 4 8¾ 11½" 13¾ 3¾ 2¾ 2¾ 8 11½" 37½" 44¾" 47½" 27 43 50¼ 2" 2" 2" 2" 23 25 77¼ 4 8¾ 11½" 13¾ 3¾ 2¾ 2¾ 8 11½" 37¾" 45 47¾" 27 43¼ 50½ 3" 4" 3" 2" 35¾ 25 77¼ 4 10 11½" 13¾ 3¾ 2¾ 2¾ 11¾ 11½" 44 47¾" 51¼ 39¾" 51 54¾" 4" 4" 4" 2" 35¾ 25 77¼ 4 10 11½" 13¾ 3¾ 2½ 2½ 12 11½" 48½" 53 59 39¾" 56½ 61 6" 6" 6" 2" 46 25 77¼ 4 11 11½" 13¾ 3¾ 5¼ 5¼ 17¾ 11½" 59¼ 65 70½" 50 70¼ n/a 8" 8" 8" 2" 54 31 81¼ 4 12 13¼ 17 3¾ 9 6¾ 27 13¼ 70 75½ n/a 58 n/a n/a SYSTEMS WEIGHTS Cabinets without control panel System Description Weight (lbs) Weight (Kg) 1½" Preaction cabinet unit 460 209 2" Preaction cabinet unit 465 211 3" Preaction cabinet unit 740 336 4" Preaction cabinet unit 755 342 6" Preaction cabinet unit 1035 469 8" Preaction cabinet unit 1485 674 9 of 12 FM-076D-0-75C

Figure 2 Anchoring dimensions: Figure 3 Cabinet clearance dimensions A B min. 5" B ¾" TOP VIEW TOTALPAC UNIT TYPICAL MECHANICAL ROOM 1" FRONT FM-061H-0-128A System Size A B 1½ 25 15" 2 25 15" 3 37¾ 15" 4 37¾ 15" 6" 48" 15" 8" 56" 21" B min. FM-061H-0-130A System Size A min. A B 1½ 24" 12 2 24" 12 3 24" 12 4 24" 12 6" 24" 12 8" 32" 12 Figure 4 Knockouts detail Top of Cabinet High voltage 2½" Low voltage 8½" 3¾" 2½" Typ. 3" FM-061H-0-68B-12 FM-076D-0-75C 10 of 12

Figure 5: Open drain details for single unit: (See dimensions in table below) TotalPac Unit Shown Without Front Door Unit Drain Pipe (dia. = C) Air Gap Water Supply Pipe 4'' min. B A Single Unit Detail Drain Pipe (pipe diameter per drain flow calculation) FM-061H-0-139A Figure 6: Open drain details for multiple units: (See dimensions in table below) 12'' min. Water Supply Pipe (Can Be Manifolded) TotalPac Unit Shown Without Front Door TotalPac Unit Shown Without Front Door Unit Drain Pipe (dia. = C) DO NOT MANIFOLD! Typical Air Gap B 4'' min. A Drain Collector running between wall and units (pipe diameter per drain flow calculations) Multiple Units Detail FM-061H-0-140A Dimension table Unit Size: 1½" 2" 3" 4" 6" 8" A 8¾" 8¾" 10" 10" 11" 12" B 13¾" 13¾" 13¾" 13¾" 13¾" 17" C 2" 2" 2" 2" 2" 2" Notes: 1. Supply and drain pipes can be connected on either sides of cabinet. 2. All pipes and fittings should meet applicable codes. 3. Actual drain collector diameter shall be determined with detailed hydraulic calculations and is the responsibility of the system designer. 11 of 12 FM-076D-0-75C

1935, Lionel-Bertrand Blvd. Boisbriand QC Canada J7H 1N8 Tel.: 450-437-3473 Fax: 450-437-1930 Toll Free: 866-347-3353 Email: info@fireflex.com Web: www.fireflex.com FM-076D-0-75C 12 of 12