TotalPac 3 Deluge, Electric release Remote controlled system

Similar documents
TotalPac 3 Deluge system Pneumatic release

TotalPac 3 Firecyle III Wet pipe Remote controlled system

TotalPac 3 Double interlock Preaction, Electric/PneuLectric release Remote controlled system

TotalPac 3 Non interlock Preaction system Pneumatic release

TotalPac 3 Double interlock Preaction, Electric/Pneumatic release Remote controlled system

TotalPac 3 Non interlock Preaction, Electric release Remote controlled system

TotalPac 3 Double interlock Firecyle III Preaction Remote controlled system

FireFlex DUAL Single Interlock, Remote controlled system

TECHNICAL DATA. Q= C v P S

TECHNICAL DATA. Q= C v P Cv = Flow Factor (GPM/1 PSI P)

TECHNICAL DATA 1-1/2 (dn40)

TECHNICAL DATA. Inlet Type Outlet Type OBSOLETE 6 (DN150)

TECHNICAL DATA. Trimpac 244a. April 15, 2011

TECHNICAL DATA. Trimpac 249a. September 16, 2013

Q= C. v P S Refer to Table 1 for part numbers and shipping weights. Accessories: Table 1: Valve Part Numbers and Specifications

TECHNICAL DATA TRIMPAC MODEL B-4, B-4B & B-4S SINGLE INTERLOCK PREACTION SYSTEM WITH PNEUMATIC RELEASE

TECHNICAL DATA CONCENTRATE CONTROL VALVE APPLICATIONS, PRIMING CONNECTIONS, AND TRIMS 1. GENERAL DESCRIPTION 2. LISTINGS AND APPROVALS.

Instructions for Installation, Operation, Care and Maintenance

DV-5a Automatic Water Control Valve Single Interlock Preaction Fire Protection Systems 1-1/2 Inch to 8 Inch (DN40 to DN200) General Description

Instructions for Installation, Operation, Care and Maintenance

TECHNICAL DATA. Q= C v P S FLOW CONTROL VALVE MODEL J-2 HALAR COATED 1-1/2 & 2 (DN40 & DN50) 1. DESCRIPTION

Q= C v P S. Flow control valve Model j-2 Halar coated

TECHNICAL DATA. Viking Technical Data may be found on Style: 90 Degree Pattern (inlet to outlet)

Model DV-5 Deluge Valve, Diaphragm Style, 1-1/2 thru 8 Inch (DN40 thru DN200), Deluge System Electric Actuation

DELUGE VALVE MODEL: SD-DVA TECHNICAL DATA : VALVE OPERATION TRIM DESCRIPTION DESCRIPTION PRESSURE THREADED OPENING

30.85 FireLock NXT Actuated Valve with LPCB Approved Preaction Trim

Series 758 FireLock Actuated System Valve

DV-5a Automatic Water Control Valve Double Interlock Preaction Fire Protection Systems 1-1/2 Inch to 8 Inch (DN40 to DN200) General Description

DELUGE VALVE DATA SHEET

FireLock NXT Deluge Valve. With Deluge Trim Grooved x Grooved. System No. Submitted By Spec Sect Para Location Date Approved Date

TECHNICAL DATA P S. Q= Cv MODEL E-2 DELUGE VALVE HALAR COATED ANGLE STYLE

Features 1. Differential Latch-type, lightweight, dependable

Section O Preaction Systems

Section R Foam Systems

Section R Foam Systems

TECHNICAL DATA 2-1/2-8 (dn65 - dn200)

Wet pipe low flow foam/water manifold system

TECHNICAL DATA. Q= C v P S. Table 1 - Valve Part Numbers and Specifications

Model DDX Deluge Valves 4" (100 mm), 6" (150 mm) and 165 mm Sizes

APPLICATION FOR OSHPD SPECIAL SEISMIC CERTIFICATION PREAPPROVAL (OSP)

Model DDX Deluge Valve 8 (200mm) Features

TECHNICAL DATA. Q= C v P S FLOW CONTROL VALVE MODEL H-2 HALAR COATED 2 (DN50) - 6 (DN150)

Series 769 FireLock NXT Deluge Valve

DV-5 Deluge Valve, Diaphragm Style, 1-1/2 thru 8 Inch (DN40 thru DN200), Deluge System Wet Pilot Actuation General Description

MODEL RCW NON-INTERLOCK PREACTION SYSTEM

Section M Dry Pipe Systems

TECHNICAL DATA CAUTION

Instructions for Installation, Operation, Care and Maintenance

Series 756 FireLock Dry System Check Valve

Preaction System with DV-5 Deluge Valve Double Interlock Electric/Electric Actuation. General Description. Page 1 of 14 DECEMBER 2014 TFP1465

Section N Deluge Systems

TECHNICAL DATA OBSOLETE. Inlet Type Outlet Type in mm. Thread Thread in. ANSI B Flanged Flanged in.

TECHNICAL DATA. Notes: For use with Trim Charts on Pages 2-4

Instructions for Installation, Operation, Care, and Maintenance

Section P Flow Control and Pressure Regulation

Worldwide Contacts.

DV-5A Automatic Water Control Valve Remote-Resetting Deluge Fire Protection Systems 1-1/2 Inch to 8 Inch (DN40 to DN200) General Description

1-1/2 Inch (DN40) 9 lb (4,1 kg) Groove Groove 1 8 lb (3,6 kg) Flange Groove 1 N/A N/A. Flange Flange N/A N/A

Instructions for Installation, Operation, Care and Maintenance

Model CV-1FR Grooved-End Riser Check Valves 2 Inch to 12 Inch (DN50 to DN300) General Description. Installation. Technical Data

Technical Data. UL Listing is based on the following criteria:

MODEL RCW DELUGE SYSTEM ELECTRIC, WET PILOT, AND DRY PILOT ACTUATION

Section P Flow Control and Pressure Regulation

AGCX Bulletin 519 C/Alfoz de Bricia nº4 P.l. Villalonquéjar Burgos (Spain) Tlfno: PAG 1 de 50

Instructions for Installation, Operation, Care and Maintenance

LEAD FREE * LFF113RFP Flood Protection Shut Down Valve

Sl. No. Description Pages

Section L Wet Pipe Systems

TECHNICAL DATA. model f-1 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA. Page 1 of 11

FireLock NXT Actuated Valve with Preaction Trim. System No. Submitted By Spec Sect Para Location Date Approved Date

TECHNICAL DATA. Table 1: Model F1 Dry Valve Part Numbers and Specifications

GW MKIII DELUGE VALVE - ALUBRONZE EXTERNAL RESET, PNEUMATIC

Table Summary of Sprinkler System Inspection, Testing, and Maintenance. Reference. Inspection , ,

Grooved Piping System for Fire Protection Services

Easy Riser swing check valve Models E-1 & F-1

LEAD FREE * LFF113FP. Wireless Smart Flood Protection Shut Down Valve with SentryPlus Alert Technology. Materials NOTICE NOTICE ES--LFF113FP

FIRE PROTECTION EQUIPMENT 2017 DATA SHEETS BSP FIRE RESERVES THE RIGHT TO ALTER INFORMATION CONTAINED IN THIS CATALOGUE AT ANY TIME.

NMSU FIRE DEPARTMENT FIRE PUMP ACCEPTANCE TEST

Instructions for Installation, Operation Care and Maintenance

Valves & Flow Control Components Valves & Flow Control Components

Model QRS Electronic Accelerator (Quick Opening Device) For Dry Pipe or Preaction Systems General Description

LEAD FREE * PVS-7000 Engineered Flood Protection Valve Station with SentryPlus Alert

TECHNICAL DATA OBSOLETE

Instructions for Installation, Operation, Care and Maintenance

Instructions for Installation, Operation, Care and Maintenance 2 PSI (0,14 bar) Pneumatic Supervising Pressure with Electric Actuation

Grooved Piping System for Fire Protection Services

SHORTER. LIGHTER. MORE VERSATILE. 1 VALVE 10 TRIM CONFIGURATIONS 4" AND 6" MODEL RCW WATER CONTROL VALVE FOR DRY, PREACTION AND DELUGE APPLICATIONS

FLOOD PROTECTION SHUT DOWN VALVE (3 and smaller)

70.03 Victaulic Vortex TM

LEAD FREE * LFF113RFP Wireless Smart Flood Protection Shut Down Valve with SentryPlus Alert Technology

ALARM CHECK VALVE 3", 4" & 6" MODEL H-1 FLANGE/FLANGE 3" & 4" MODEL H-2 GROOVE/GROOVE 3", 4" & 6" MODEL H-3 FLANGE/GROOVE

Automatic Changeover Medical Manifold Installation, Operation and Maintenance Manual

Missing recessed or flush escutcheons, concealed cover plates with deflector and operating element in correct position

TECHNICAL DATA. Notes: For use with Trim Charts on Pages 227b - d

FIRE PROTECTION PRODUCTS

Model RM-1 Riser Manifold Commercial and Residential General Description

FIRE SPRINKLER SYSTEM

Technical Data Sheet SEVO 1230 Clean Agent Cylinders

Cla-Val. Service Training Manual. Simple solutions plus learning with a purpose

TECHNICAL DATA OBSOLETE

Transcription:

(Optional) DESCRIPTION This TOTALPAC 3 integrated fire protection system by FireFlex Systems Inc. consists of a deluge system trim totally preassembled, pre-wired and factory tested. All electrical and mechanical components of the system are contained in one single unit TOTALPAC 3 deluge systems are built around the Viking trim using deluge valves model F-1. Electrically controlled deluge systems require an electric normally closed solenoid valve controlled by an approved system releasing control panel (supplied by others) with compatible detection devices. In fire condition, when the detection condition is satisfied the system releasing control panel energizes the solenoid valve, causing the deluge valve to open allowing water to enter the system piping. Water will flow from any open sprinklers and/or spray nozzles on the system Activation of a releasing device alone or operation of a sprinkler alone will sound an alarm but will NOT cause the system to fill with water. All the valves are rated up to a maximum of 250 psi WWP (1724 kpa) max. and are available in the following diameters: 1½" (40 mm) 2" (50 mm) 3" (80 mm) 4" (100 mm) 6" (150 mm) 8" (200 mm) Standard features culus Listed & FM Approved as an assembled unit Factory assembled, programmed and tested under ISO-9001 standards Prewired to a terminal block Easy and compact installation Viking conventional trim rated at 250 psi (1724 kpa) Galvanized trim piping Serial number for easy reference Corrosion resistant cabinet with flush type handle and lock No open drain cup inside the unit numerous modular options to meet the most demanding jobsite requirements Four styles of modular air supply options Inlet & outlet hydrostatic test ports User-friendly standardized operation & installation manual Free interactive simulator 1 of 12 FM-076D-0-82F

Cabinet The TOTALPAC 3 cabinets are made of sturdy 14 gauge steel, they are available in four (4) sizes; 23" x 25" x 77" (58.4 x 63.5 x 195.6 cm) for 1½",and 2" systems, 36" x 25" x 77" (91.4 x 63.5 x 195.6 cm) for 3" and 4" system, 46" x 25" x 77" (116.8 x 63.5 x 195.6 cm) for 6" system 54" x 31" x 81" (137.2 x 78.7 x 205.7 cm) for 8" system All surfaces are rust proof coated, inside and outside, with fire red, oven baked polyester powder on phosphate base. Cabinet is provided with one or two doors, all provided with a neoprene gasket to absorb vibrations. A field wiring electrical junction boxes is integrated with the cabinet for connection of all electrical components in the trim. Pressure switches, supervisory switches, etc. are all factory wired to a terminal strip (TBA) for contractor's field wiring. Gauges to indicate water supply pressure and priming water pressure are all visible through clear Lexan windows. IMPORTANT: TOTALPAC 3 units are NOT designed to be installed where they will be subjected to outdoors and/or freezing conditions. Refer to environmental data for additional details. Subjecting the unit to conditions outside these limitations might tamper the normal operation of the system. Cabinet doors are provided with hinges that can easily be disassembled on site to remove the door assemblies for servicing. The cabinet assembly is pre-assembled, pre-wired, and factory tested under ISO-9001 conditions. Multiple unit installations are easily achieved by manifolding units together at their water inlets but drains shall remain separate and open. Sequence of operation (see trim diagram) In a fire condition, when the detection condition is satisfied, system releasing control panel (supplied by others) activates an alarm and energizes normally closed solenoid valve (F1) open. Pressure is released from the priming chamber of the deluge valve (A1) to the open drain manifold faster than it is supplied through the restricted orifice (B3). The Deluge Valve clapper opens to allow water to flow into the system piping and alarm devices, causing the alarm pressure switch (C1) and optional water motor alarm (C2) to activate. Water will flow from all the open sprinklers and/or nozzles in the system. When the deluge valve operates, the sensing end of the PORV (B9) is pressurized, causing the PORV to open. When the PORV opens, it drains the priming water pressure to the priming chamber, preventing the deluge valve (A1) from resetting, even if the open releasing devices close. The deluge valve can only be reset after the system is taken out of service, and the outlet chamber of the deluge valve and associated trim piping is depressurized and drained. Systems hydraulic limitations WARNING The information contained herewith is for estimation and evaluation purposes only. Its use remains the responsibility of the designer. Designers should refer to the appropriate NFPA Standards and any other applicable codes for their final design. Also refer to FireFlex Systems Inc. appropriate user manuals and to manufacturer's data sheets for additional details. Systems limitations indicated below are nominal flow limitations. Piping Equivalent Lengths w/o Piping Equivalent Lengths c/w Usage Range shut off valve shut off valve (gpm) (m.) (ft.) (m.) (ft.) GPM 1½ 0 210 6.77 22.2 6.98 22.9 272 2 0 360 9.2 30.2 9.42 30.9 272 3 100-700 13.75 45.1 17.28 56.7 762 4 200 1400 17.92 58.8 21.37 70.1 1597 6 400-3500 27.17 89.15 31.18 102.3 1597 8 750-5250 34.14 112.0 37.7 123.7 1597 System size (in.) Drain flow @ 250 PSIG w.p. FM-076D-0-82F 2 of 12

Standard equipment Deluge valve The Viking Model deluge valve is a quick-opening, differential diaphragm, flood valve with one moving mechanism. The deluge valve is used to control water flow in deluge and preaction sprinkler systems. The valve is held closed by system water pressure trapped in the priming chamber, keeping the outlet chamber and system piping dry. In fire conditions, when the releasing system operates, pressure is released from the priming chamber. The deluge valve clapper opens to allow water to flow into the system piping. Solenoid valve The high pressure solenoid valve is a two-way type with one inlet and one outlet. It is a packless, internal pilot operated valve, suitable for use in releasing water pressure from the priming chamber of Viking deluge valves. The solenoid valve has floating diaphragm construction, which requires a minimum pressure drop across the valve to operate properly. IN OUT Releasing circuit disable switch The releasing circuit disable switch is used to disable the releasing solenoid. When the key is set to Disable, the releasing solenoid will be disconnected from the control panel s releasing circuit, causing a trouble signal and preventing accidental discharge during maintenance or inspection. Water supply control valve The water inlet control valve is a supervised, indicating butterfly valve. Purpose of this vale is to manually shutoff the preaction system. Alarm pressure switch The alarm pressure switch monitors the water flow within the sprinkler piping. Should the Deluge Valve clapper opens to allow water to flow into the sprinkler piping. The alarm pressure switch will activate, indicating a water flow signal. POTTER PS10-1A 3 of 12 FM-076D-0-82F

Optional mechanical equipment Shut-off valve & sight glass option The Shut-off valve & sight glass option is intended to be used for applications where testing of the system operation without filling the sprinkler piping network is desirable and where it is critical that all functions of the system being tested under actual discharge conditions. Examples of such applications are freezers, ovens, museums, data processing and other hazards where the possibility of water leaking from the piping system is to be avoided at all costs. Warning: Shut-off valve & sight glass option is not available on 8" systems. Fire department connection The fire department connection option consists of a grooved tee fitting installed at the outlet of the deluge valve (A1). An access hole of the proper diameter is factory pre-drilled on the side of the TOTALPAC 3 enclosures for connection of the piping going to the fire department connection. Note: The fire department connection hardware itself (drain, Siamese, etc.) is NOT provided with this option and shall be provided by the installing contractor. Refer to NFPA- 13 Standard for additional information about the equipment layout and installation. Warning: Shut-off valve is not available combined with Fire department connection on 6" systems. Warning: Fire department connection is not available on 8" systems. Main Drain Valve (D3) Sight Glass Assembly (D5) Supervised Shut-off Valve (D4) Grooved Tee Fitting with Coupling & Cap To Fire Dep't Connection (hardware by Contractor) Point flash light here Supervised Water Supply Control Valve (D1) FM-061H-0-79B FM-061H-0-78B FM-076D-0-82F 4 of 12

Optional mechanical equipment (continued) Semi and full flanged option When required by the user, TOTALPAC 3 units can be provided in either a semi-flanged of full flanged configuration. The semi flanged option provides flanged fittings only on the water inlet pipe (side needs to be specified at the time of order) and on the system riser outlet. The drain manifold is then provided with a threaded end that also needs to have its side specified (left or right). The rest of the fittings are the same as usual with the main components being provided in the standard grooved -grooved configuration. The full flanged option is the same as above but goes a step further with the main components being also provided with a flanged-flanged configuration. When provided, the face of the flanges will always be situated 6 inches from the outside face of the mounting base or cabinet surface. OSHPD option Pre-approved construction, under OSP-0341-10, using specific components. Flanged fitting outside cabinet (when provided) Threaded end Field Connection to Open Drain (specify side) Flanged fitting outside cabinet (when provided) Field connection to Water Supply (specify side) FM-061H-0-208B 5 of 12 FM-076D-0-82F

Details & field wiring diagrams Cabinet with main components - Configuration without releasing control panel Cable Entry Release Solenoid Disconnect Switch Junction box TBA & TBB Riser Outlet to Sprinklers Network Straight Through Deluge Valve Water Supply Control Valve Drain Outlet (either side) Water Inlet (either side) FM-061H-0-173B FM-076D-0-82F 6 of 12

Trim diagram FIELD CONNECTION TO SPRINKLER PIPING NETWORK C1 D3 A1 F1 B8 C2 B5 B6 B11 B10 D1 B7 B9 B13 FIELD CONNECTION TO OPEN DRAIN (on both sides) B12 B3 B4 B2 B1 FIELD CONNECTION TO WATER SUPPLY (on both sides) TotalPac Base (shown without enclosure) CONTRACTOR'S HYDROSTATIC TEST PORT (water supply side) FM-061H-0-111C Trim Components: A1 B1 B2 B3 B4 B5 B6 B7 B8 B9 B10 B11 B12 B13 Deluge valve Priming valve Strainer 1/16" Restricted orifice Spring loaded check valve Alarm test valve Flow test valve Drip check valve Drain check valve Pressure operated relief valve (PORV) Emergency release valve Priming pressure water gauge & valve Water supply pressure gauge & valve Clapper check valve C1 C2 D1 D3 F1 Alarm pressure switch Connection to water motor gong (strainer supplied by contractor) Water supply control valve Main drain valve N.C. solenoid valve 24 Vdc 7 of 12 FM-076D-0-82F

Field wiring diagrams: CHICAGO OPTION OPTIONAL LOS ANGELES OPTION WATER FLOW EOL MAIN VALVE EOL SOLENOID VALVE 13 14 15 16 17 18 SHUT-OFF VALVE EOL 9 10 11 12 MAIN VALVE OPTIONAL TBA 1 2 3 4 TBC 1 2 3 4 5 6 C NO NC C NO NC BYBASS SWITCH SUPERVISORY EOL 24 VDC Needed for keyswitch LEDs operation SHUT-OFF VALVE 19 20 21 22 WATER FLOW SWITCH MAIN VALVE SUPV SWITCH 5 6 7 8 S N.C. SOLENOID VALVE (see table below for ratings) LED POWER DISCHARGE BYPASS SWITCH SHUT-OFF VALVE SUPV SWITCH MAIN VALVE SUPV SWITCH SHUT-OFF VALVE SUPV SWITCH NOTE: Contacts provided for connection to the building's central Fire Alarm Panel. NOTES: All devices are factory wired. All devices are shown in their normal supervisory state. Contacts are rated: Pressure switches: 2A, 30VDC 10A, 125/250VAC Supervisory switches: 0.5A, 125VDC 0.25A, 250VDC 5A, 1/6HP, 125/250VAC Use dry contacts with power limited circuits only. EOL devices (not included) must be compatible with the Release Control Panel used. FM-061H-0-97B SOLENOID VALVE ELECTRICAL RATINGS Viking P/N Description Pressure Voltage Watts DC Amps (De-energized) Rating 11591 NC 24 VDC 10.0 DC 416 ma 300 psi (2 068 kpa) Notes: 1. Solenoid Valve is UL Listed as Fire Protection Special System Water Control Release Service (UL 429A Product category VLTR). 2. Voltage Drop: For proper operation, make sure that voltage at the solenoid valve is at least 85% of nameplate rating. FM-076D-0-82F 8 of 12

Dimensions Figure 1 Cabinet dimensions: D E P TBA, TBB & TBC Q TBB TBA & TBC F CONTROL PANEL (except for Remote Controlled Unit) SPRINKLER RISER SCH.40 GROOVED OUTLET CONTROL PANEL SPRINKLER RISER SCH.40 GROOVED OUTLET ØB OPTIONAL SHUT-OFF VALVE OPTIONAL FIRE DEP'T CONNECTION OUTLET (DRILLED ONLY WHEN ORDERED) S (W) R (V) J L N DRAIN - SCH.40 GROOVED OUTLET N ØC T ØA M WATER INLET SCH.40 GROOVED OUTLET M K H G U FM-061H-0-129A Dimensions are nominal and may vary ±¼". Dimensions V and W are with the optional Fire Department Connection System Size A B C D E F G H J K L M N P Q R S T U V W 1½" 2" 1½" 2" 23 25 77¼ 4 8¾ 11½" 13¾ 3¾ 2¾ 2¾ 8 11½" 37½" 44¾" 47½" 27 43 50¼ 2" 2" 2" 2" 23 25 77¼ 4 8¾ 11½" 13¾ 3¾ 2¾ 2¾ 8 11½" 37¾" 45 47¾" 27 43¼ 50½ 3" 4" 3" 2" 35¾ 25 77¼ 4 10 11½" 13¾ 3¾ 2¾ 2¾ 11¾ 11½" 44 47¾" 51¼ 39¾" 51 54¾" 4" 4" 4" 2" 35¾ 25 77¼ 4 10 11½" 13¾ 3¾ 2½ 2½ 12 11½" 48½" 53 59 39¾" 56½ 61 6" 6" 6" 2" 46 25 77¼ 4 11 11½" 13¾ 3¾ 5¼ 5¼ 17¾ 11½" 59¼ 65 70½" 50 70¼ n/a 8" 8" 8" 2" 54 31 81¼ 4 12 13¼ 17 3¾ 9 6¾ 27 13¼ 70 75½ n/a 58 n/a n/a SYSTEMS WEIGHTS Cabinets without control panel System Description Weight (lbs) Weight (Kg) 1½" Preaction cabinet unit 450 204 2" Preaction cabinet unit 455 206 3" Preaction cabinet unit 690 313 4" Preaction cabinet unit 705 320 6" Preaction cabinet unit 1010 458 8" Preaction cabinet unit 1470 667 9 of 12 FM-076D-0-82F

Figure 2 Anchoring dimensions: Figure 3 Cabinet clearance dimensions A B min. 5" B ¾" TOP VIEW TOTALPAC UNIT TYPICAL MECHANICAL ROOM 1" FRONT FM-061H-0-128A System Size A B 1½ 25 15" 2 25 15" 3 37¾ 15" 4 37¾ 15" 6" 48" 15" 8" 56" 21" B min. FM-061H-0-130A System Size A min. A B 1½ 24" 12 2 24" 12 3 24" 12 4 24" 12 6" 24" 12 8" 32" 12 Figure 4 Knockouts detail Top of Cabinet High voltage 2½" Low voltage 8½" 3¾" 2½" Typ. 3" FM-061H-0-68B-12 FM-076D-0-82F 10 of 12

Figure 5: Open drain details for single unit: (See dimensions in table below) TotalPac Unit Shown Without Front Door Unit Drain Pipe (dia. = C) Air Gap Water Supply Pipe 4'' min. B A Single Unit Detail Drain Pipe (pipe diameter per drain flow calculation) FM-061H-0-139A Figure 6: Open drain details for multiple units: (See dimensions in table below) 12'' min. Water Supply Pipe (Can Be Manifolded) TotalPac Unit Shown Without Front Door TotalPac Unit Shown Without Front Door Unit Drain Pipe (dia. = C) DO NOT MANIFOLD! Typical Air Gap B 4'' min. A Drain Collector running between wall and units (pipe diameter per drain flow calculations) Multiple Units Detail FM-061H-0-140A Dimension table Unit Size: 1½" 2" 3" 4" 6" 8" A 8¾" 8¾" 10" 10" 11" 12" B 13¾" 13¾" 13¾" 13¾" 13¾" 17" C 2" 2" 2" 2" 2" 2" Notes: 1. Supply and drain pipes can be connected on either sides of cabinet. 2. All pipes and fittings should meet applicable codes. 3. Actual drain collector diameter shall be determined with detailed hydraulic calculations and is the responsibility of the system designer. 11 of 12 FM-076D-0-82F

1935, Lionel-Bertrand Blvd. Boisbriand QC Canada J7H 1N8 Tel.: 450-437-3473 Fax: 450-437-1930 Toll Free: 866-347-3353 Email: info@fireflex.com Web: www.fireflex.com FM-076D-0-82F 12 of 12