PSAT Model- Based Voltage Stability Analysis for the Kano 330KV Transmission Line

Similar documents
COMPARISON OF STATCOM AND TCSC ON VOLTAGE STABILITY USING MLP INDEX

Computation of Sensitive Node for IEEE- 14 Bus system Subjected to Load Variation

Power Flow Simulation of a 6-Bus Wind Connected System and Voltage Stability Analysis by Using STATCOM

TRANSMISSION LOSS MINIMIZATION USING ADVANCED UNIFIED POWER FLOW CONTROLLER (UPFC)

An Approach for Formation of Voltage Control Areas based on Voltage Stability Criterion

Optimal Placement of Distributed Generation for Voltage Stability Improvement and Loss Reduction in Distribution Network

Simulation of Voltage Stability Analysis in Induction Machine

Computer Aided Transient Stability Analysis

Voltage Sag Mitigation in IEEE 6 Bus System by using STATCOM and UPFC

Implementation SVC and TCSC to Improvement the Efficacy of Diyala Electric Network (132 kv).

Enhancement of Power Quality in Transmission Line Using Flexible Ac Transmission System

Contingency Ranking and Analysis using Power System Analysis. Toolbox (PSAT)

Maintaining Voltage Stability in Power System using FACTS Devices

INTRODUCTION. In today s highly complex and interconnected power systems, mostly made up of thousands of buses and hundreds of generators,

Performance Analysis of 3-Ø Self-Excited Induction Generator with Rectifier Load

Statcom Operation for Wind Power Generator with Improved Transient Stability

POWER FLOW SIMULATION AND ANALYSIS

VOLTAGE STABILITY IMPROVEMENT IN POWER SYSTEM BY USING STATCOM

Performance Analysis of Transient Stability on a Power System Network

Wind Power Plants with VSC Based STATCOM in PSCAD/EMTDC Environment

Multi-Line power Flow Control Using Interline Power Flow Controller (IPFC) in Power Transmission system

CHAPTER 3 TRANSIENT STABILITY ENHANCEMENT IN A REAL TIME SYSTEM USING STATCOM

Implementation of FC-TCR for Reactive Power Control

STABILITY ANALYSIS OF DISTRIBUTED GENERATION IN MESH DISTRIBUTION NETWORK IN FREE AND OPEN SOURCE SOFTWARE

Power Quality Improvement Using Statcom in Ieee 30 Bus System

Modelling and Loading Limits for Kenya Coast Power Network Using Continuation Power Flow

Adaptive Power Flow Method for Distribution Systems With Dispersed Generation

Power Flow Control through Transmission Line with UPFC to Mitigate Contingency

Enhancement of Voltage Stability Margin Using FACTS Controllers

Identification of Best Load Flow Calculation Method for IEEE-30 BUS System Using MATLAB

Available Transfer Capacity with Renewable Energy

Enhancement of Transient Stability Using Fault Current Limiter and Thyristor Controlled Braking Resistor

Electric Power System Under-Voltage Load Shedding Protection Can Become a Trap

United Power Flow Algorithm for Transmission-Distribution joint system with Distributed Generations

Simulation of real and reactive power flow Assessment with UPFC connected to a Single/double transmission line

Steady State Voltage Stability Enhancement Using Shunt and Series FACTS Devices

Fuzzy based STATCOM Controller for Grid connected wind Farms with Fixed Speed Induction Generators

Master of Engineering

ELG4125: Flexible AC Transmission Systems (FACTS)

Wind Farm Evaluation and Control

Journal of American Science 2015;11(11) Integration of wind Power Plant on Electrical grid based on PSS/E

Islanding of 24-bus IEEE Reliability Test System

CHAPTER 6 DESIGN AND DEVELOPMENT OF DOUBLE WINDING INDUCTION GENERATOR

ECEN 667 Power System Stability Lecture 19: Load Models

Voltage Control Strategies for Distributed Generation

Performance Analysis of Transmission Line system under Unsymmetrical Faults with UPFC

Complex Power Flow and Loss Calculation for Transmission System Nilam H. Patel 1 A.G.Patel 2 Jay Thakar 3

CHAPTER 5 FAULT AND HARMONIC ANALYSIS USING PV ARRAY BASED STATCOM

VOLTAGE STABILITY CONSTRAINED ATC COMPUTATIONS IN DEREGULATED POWER SYSTEM USING NOVEL TECHNIQUE

OPTIMAL Placement of FACTS Devices by Genetic Algorithm for the Increased Load Ability of a Power System

Analysis of Grid Connected Solar Farm in ETAP Software

Available Transfer Capability Calculation Using ACPTDF & DCPTDF on IEEE-24 bus System Under Deregulated Environment

APPLICATION OF VARIABLE FREQUENCY TRANSFORMER (VFT) FOR INTEGRATION OF WIND ENERGY SYSTEM

The Effect Of Distributed Generation On Voltage Profile and Electrical Power Losses Muhammad Waqas 1, Zmarrak Wali Khan 2

INSTALLATION OF CAPACITOR BANK IN 132/11 KV SUBSTATION FOR PARING DOWN OF LOAD CURRENT

POWER QUALITY IMPROVEMENT BASED UPQC FOR WIND POWER GENERATION

Possibilities of Distributed Generation Simulations Using by MATLAB

Analysis of Interline Power Flow Controller (IPFC) Location in Power Transmission Systems

Grid Stability Analysis for High Penetration Solar Photovoltaics

Electric Drives Lab PCC 8 EE-456C Electrical Simulation Lab PCC 9 EE-468C Project Workshop SEC

APPLICATION OF STATCOM FOR STABILITY ENHANCEMENT OF FSIG BASED GRID CONNECTED WIND FARM

Dynamic Control of Grid Assets

Dynamic Behaviour of Asynchronous Generator In Stand-Alone Mode Under Load Perturbation Using MATLAB/SIMULINK

Transient Stability Assessment and Enhancement in Power System

Steady-State Power System Security Analysis with PowerWorld Simulator

A Transient Free Novel Control Technique for Reactive Power Compensation using Thyristor Switched Capacitor

A Novel GUI Modeled Fuzzy Logic Controller for a Solar Powered Energy Utilization Scheme

EFFECT OF WIND TURBINE GENERATORS ON THE SMALL SIGNAL STABILITY OF POWER SYSTEMS. Kamel A. Shoush, Member, IEEE

EPE97 OPTIMIZED DESIGN OF VARIABLE-SPEED DRIVES BASED ON NUMERICAL SIMULATION

J.-J.Simond*, A.Sapin**, B.Kawkabani*, D.Schafer***, M.Tu Xuan*, B.Willy***

FAULT ANALYSIS OF AN ISLANDED MICRO-GRID WITH DOUBLY FED INDUCTION GENERATOR BASED WIND TURBINE

ENHANCEMENT OF ROTOR ANGLE STABILITY OF POWER SYSTEM BY CONTROLLING RSC OF DFIG

Islanding of 24-bus IEEE Reliability Test System

Hamdy S. K. El-Goharey, Walid A. Omran, Adel T. M. Taha

CHAPTER I INTRODUCTION

Research on Transient Stability of Large Scale Onshore Wind Power Transmission via LCC HVDC

CONTROL AND PERFORMANCE OF A DOUBLY-FED INDUCTION MACHINE FOR WIND TURBINE SYSTEMS

Experience on Technical Solutions for Grid Integration of Offshore Windfarms

SPEED CONTROL OF THREE PHASE INDUCTION MACHINE USING MATLAB Maheshwari Prasad 1, Himmat singh 2, Hariom Sharma 3 1

PERFORMANCE ANALYSIS OF SQUIRREL CAGE INDUCTION GENERATOR USING STATCOM

ECE 740. Optimal Power Flow

WESTERN INTERCONNECTION TRANSMISSION TECHNOLGOY FORUM

Fuzzy Based Unified Power Flow Controller to Control Reactive Power and Voltage for a Utility System in India

A Variable Speed Wind Generation System Based on Doubly Fed Induction Generator

Induction Generator: Excitation & Voltage Regulation

IMPACT OF THYRISTOR CONTROLLED PHASE ANGLE REGULATOR ON POWER FLOW

Modeling and Simulation of TSR-based SVC on Voltage Regulation for Three-Bus System

Implementation of Steady-State Power System Visualizations Using PowerWorld Simulator. Dr. Jung-Uk Lim, Department of Electrical Engineering

DC Voltage Droop Control Implementation in the AC/DC Power Flow Algorithm: Combinational Approach

Index Terms: Dynamics, reactive power capability, time domain simulation, voltage stability,

Enhancement of Voltage Stability Through Optimal Placement of TCSC

Power System Stability Analysis on System Connected to Wind Power Generation with Solid State Fault Current Limiter

POWER DISTRIBUTION SYSTEM ANALYSIS OF URBAN ELECTRIFIED RAILWAYS

COMPARISON BETWEEN ISOLATED AND GRID CONNECTED DFIG WIND TURBINE

Review paper on Fault analysis and its Limiting Techniques.

International Journal of Advanced Research in Electrical, Electronics and Instrumentation Engineering. (An ISO 3297: 2007 Certified Organization)

Transient Stability Improvement of Squirrel Cage Induction Wind Turbine Generator using Plugging Mode

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements

ENHANCEMENT OF TRANSIENT STABILITY OF SMART GRID

Okelola, M. O. Department of Electronic & Electrical Engineering, Ladoke Akintola University of Technology, P.M.B. 4000, Ogbomoso, Nigeria

Transcription:

SAT Model- Based Voltage Stability Analysis for the Kano 330KV Transmission ne S.M. Lawan Department of Electrical Engineering, Kano University of Science and Technology, Wudil Nigeria Abstract Voltage instability problems increasing day by day because of demand increase. It is very important to analyze the power system with respect to voltage stability. This paper investigates the voltage stability analysis of Kano 330KV Transmission line. The test system network consisting of 11 buses, 4 generating stations, 4 transmission lines and 1 control centres, ower System Analysis Toolbox (SAT) software was used to carried out simulation analysis, using the relevant data as obtained from power holding company of Nigeria [HCN], to determine bus voltages, real and reactive power flows and losses of the transmission lines and generators The results obtained showed that the Maximum Loading oint is max λ = 3.97 p.u. Also load active powers are in base and maximum cases are base = 7.00 p.u. and max = 7.189 p.u. respectively. The weakest bus also is identified bus8 with voltage 0.948 p.u. Also load active powers are in base and maximum cases are base = 9.67p.u. and max = 17.67 p.u. respectively. The weakest bus also is identified bus8 with voltage 0.948 p.u This paper demonstrates how singularity in the Jacobian can be avoided by slightly reformulating the power flow equations and applying a formulation will be implemented in the ATC Toolbox with MATLAB and tested on 330kv buses to determine power flow solution using OWERSAT (SAT) technique [2]. II. Continuation ower Flow The conventional power flow has a problem in the Jacobian matrix which becomes singular at the voltage stability limit. This problem can be overcome by using continuation power flow [3].Figure 1 shows the predictor corrector scheme used in the continuation power flow. Key words: SAT, 330KV Transmission ne, Voltage Stability, ower Flow I. Introduction As power systems become more complex and heavily loaded, voltage stability becomes an increasing serious problem. Voltage problems have been a subject of great concern during planning and operation of power systems due to the significant number of serious failures believed to have been caused by this phenomenon. It is therefore necessary to develop Voltage Stability Analysis (VSA) tools in today s Energy Management Systems (EMS). [1] Indeed, numerous authors have proposed voltage stability indexes based upon some type of power flow analysis. A particular difficulty being encountered in such research is that the Jocobian of a Newton-Raphson power flow becomes singular at the steady state voltage stability limit. In fact, this stability limit, also called the critical point, is often defined as the point where the power flow Jacobian is singular. As a consequence, attempts at power flow solutions near the critical point are prone to divergence and error. Figure1. An illustration of the Continuation power flow [3] From the Newton-Raphson, load flow equations can be written as: (1) (2) The new load flow equations consists of load factor can be expressed as: i0 ( K 0 (3) ( K S base S base cos ) i sin ) i 969 a g e

Where the following definitions are made; 0, 0 original load at bus i, active and reactive respectively. K - multiplier to designate the rate of load change at bus i as λ changes. Ψ i - power factor angle of load change at bus i. III. SAT METHOD SAT is a Matlab toolbox for electric power system analysis and control. The command line version of SAT is also GNU Octave compatible. SAT includes power flow, continuation power flow, optimal power flow, and small signal stability analysis and time domain simulation. All operations can be assessed by means of graphical user interfaces (GUIs) and a Simulinkbased library provides a user friendly tool for network design. SAT core is the power flow routine, which also takes care of state variable initialization. Once the power flow has been solved, further static and/or dynamic analysis can be performed. These routines are: 1. Continuation power flow; 2. Optimal power flow; 3. Small signal stability analysis; 4. Time domain simulations; 5. hasor measurement unit (MU) placement. In order to perform accurate power system analysis, SAT supports a variety of static and dynamic component models, as follows: ower Flow Data: bars, transmission lines and transformers, slack buses, V generators, constant power loads, and shunt admittances. CF and OF Data: ower supply bids and limits generator power reserves, generator ramping data, and power demand bids and limits. Switching Operations: Transmission line faults and transmission line breakers. Measurements: frequency and phasor measurement units (MU). Loads: Voltage dependent loads, frequency dependent loads, ZI (impedance, constant current and constant power) loads, exponential recovery loads, thermostatically controlled load, Jimma's loads, and mixed loads. Machines: Synchronous machines (dynamic order from 2 to 8) and induction motors (dynamic order from 1 to 5). Controls: Turbine Governors, Automatic Voltage Regulators, ower System Stabilizer, Over-excitation limiters and Secondary Voltage Regulation (Central Area Controllers and Cluster Controllers). Regulating Transformers: Load tap changer with voltage or reactive power regulators and phase shifting transformers. FACTS: Static Var Compensators, Thyristor Controlled Series Capacitors, Static Synchronous Source Series Compensators, Unified ower Flow Controllers, and High Voltage DC transmission systems. Wind Turbines: Wind models, Constant speed wind turbine with squirrel cage induction motor, variable speed wind turbine with doubly fed induction generator, and variable speed wind turbine with direct drive synchronous generator. Other Models: Synchronous machine dynamic shaft, dynamic phasor RLC series circuit, sub-synchronous resonance model, Solid Oxide Fuel Cell, and sub transmission area equivalents. Besides mathematical routines and models, SAT includes a variety of utilities, as follows: 1. one-line network diagram editor (Simulink library); 2. GUIs for settings system and routine parameters; 3. User defined model construction and installation; 4. GUI for plotting results; 5. Filters for converting data to and from other formats; 6. Command logs. Finally, SAT includes bridges to GAMS and UWFLOW programs, which highly extend SAT ability of performing optimization and continuation power flow analysis [4] IV. Under Study Network Our test system is Kano 330KV Transmission system. Stimulated diagram of System with the following components and statistics as shown in table 1and 2 below: Table 1: Network Statistics es 11 nes 8 Transformers 4 Generators 4 Loads 2 Table2: Solution Statistics Number of Iterations 4 Maximum mismatch [p.u.] 0 Maximum mismatch [p.u.] 0 ower rate [MVA] 0 970 a g e

V phase gen gen load load [p.u.] [rad] [p.u.] [p.u.] [p.u.] [p.u.] 01 1.030 0.353 7.000 1.825 0.000 0.000 02 1.0 0.183 7.000 2.284 0.000 0.000 03 1.030-0.119 7.189 1.724 0.000 0.000 04 1.0-0.296 7.000 1.936 0.000 0.000 05 1.0 0.241 0.000 0.000 0.000 0.000 0.979 0.5 0.000 0.000 0.000 0.000 0.963-0.2 0.000 0.000 9.670-1.000 0.948-0.323 0.000 0.000 0.000 0.000 0.974-0.560 0.000 0.000 17.670-2.500 Fig. 2 Kano 330KV Transmission system In this system generation unit are modeled as standard V buses and loads are represented as constant loads. The and load powers are not voltage dependent and are assumed to change as follows: l (1 ) l l 0 (4) (1 l 0 ) Where L0 and L0 are the active and reactive base loads, whereas L, and L, are the active and reactive loads at bus L for the current operating point as defined by λ, table 2 V. Simulation Results To analyze of static voltage stability to survey contingencies of power system (like the line outages and/or generation unit outages) with sat software [5]. The continuation power flow for normal system manner is done that all generation units and lines are in the network and in fact no contingencies has occurred in system. Maximum Loading oint is max λ = 3.97 p.u. Also load active powers are in base and maximum cases are base = 7.00 p.u. and max = 7.189 p.u. respectively. The weakest bus also is identified bus8 with voltage 0.948 p.u. Also load active powers are in base and maximum cases are base = 9.67p.u. and max = 17.67 p.u. respectively. The weakest bus also is identified bus8 with voltage 0.948 p.u A. The results of simulation for the network with CF method Table 3, 4,5 and 6 shows the results of single generation units applying continuation power flow. B. Table 3: ower Flow Results 0.985-0.414 0.000 0.000 0.000 0.000 11 1.0-0.234 0.000 0.000 0.000 0.000 Table 4: ne Flows Fro m To ne [p.u. ] Flow [p.u.] 05 11 Flow [p.u.] Lo ss [p.u.] Lo ss [p.u.] 1 7.000 1.002 0.123 1.191 2 13.87 7 1.2 0.202 2.0 3 2.002 0.9 0.048 0.303 4 1.954-0.224 0.047 0.382 5 1.954-0.268 0.047 0.293 6 7.189 0.866 0.129 1.245 7 13.85 6 0.177 0.204 2.026 8 2.002 0.123 0.048 0.391 971 a g e

01 05 02 04 03 11 9 7.000 1.825 0.000 0.822 7.000 2.284 0.000 0.886 11 7.000 1.936 0.000 0.862 12 7.189 1.724 0.000 0.859 Table 5: General Summary Report ower Total Generation Total Load Total Loses Real ower 28.19 27.34 0.85 [p.u] Reactive ower [p.u] 7.77-3.50 11.27 Table 6: Newton-Raphson Method for ower Flow Computation Iteration Convergence 1 0.048618 2 0.00322 3 1.7363e-005 4 4.4468e-0 Table 7: State Matrix Eigen values Summary Dynamic Order 24 Number of Eigen values with Re(MU) < 0 19 Number of Eigen values with Re(MU) >0 0 Number of real Eigen values 16 Number of Complex airs 4 Number of Zero Eigen values 6 VI. CONCLUSION The Study 330KV network has a relatively low voltage drop in the transmission lines though, there was an obvious improvement over the existing case, some buses and generators of high reactive power values need to be compensated using either the conventional compensators such as reactors, capacitor banks, and tap changing transformers or the use of FACTS devices. This however will enable the 330KV transmission network to be used very close to its thermal limit, yet still remain very stable, reduce transmission line congestion and maintain grid stability and effective interconnectivity. Reference [1] X. Wang, G.C. Ejebe, J. Tong, & J.G. Waight reventive/corrective Control for Voltage Stability Using Direct Interior oint Method IEEE Transaction on ower Systems, Vol. 13, No. 3, August 1998, pp. 878 883. [2] Werner C. Rheiboldt, & John V. Burkardt sat Toolbox in Matlab ACM Trans. On Mathematical Software, Vol. 9, no. 2, 1983, pp 215-235 [3] Venkataramana Ajjarapu, Colin Christy,1992. The continuation power flow a tool for steady state voltage stability analysis, IEEE Transactions on ower Systems, Vol.7, No. 1. February. [4] A.. Lerm, C. A. Canizares, and A. S. Silva, Multi-parameter bifurcation analysis of the South Brazilian power system, IEEE Trans. ower [5] F. Milano, "ower System Analysis Toolbox," Version 1.3.4, Software and Documentation, July 14, 2005. [6] Operation Technology Inc, Electrical Transient Analyzer rogram (ETA) 2001. [7] IEEE Standards Board Approved by American National Standard Institute IEEE Recommended ractice for Industrial and Commercial ower Systems Analysis (IEEE Std 399 1991) [8] HCN 2011 report on generation profile of the country. [9]. Komolafe,O.A And Omoigui M.O An Assessment Of Reliability Of Electricity Supply In Nigeria., Conference roceedings Of The 4th International Conference On ower Systems Operation And lanning (ICSO),ACCRA,Ghana, July 31-August 3,2000,p 89-91 [] A.. Lerm, C. A. Canizares, and A. S. Silva, Multi-parameter bifurcation analysis of the South Brazilian power system, IEEE Trans. owersyst., vol. 18, pp. 737 746, May 2003. [11] W. Marszalek and Z. W. Trzaska, Singularity-induced bifurcations in electrical power systems, IEEE Trans. ower Syst., vol. 20, pp. 312 320, Feb. 2005. [12] T. Gou and R. A. Schlueter, Identification of generic bifurcation and stability problems in power system differentialalgebraic model, IEEE Trans. ower Syst., vol. 9, pp. 32 44, May 1994. [13] Y. V. Makarov, D. J. Hill, and Z.-Y. Dong, Computation of bifurcation boundaries for power systems: A new _-plane method, IEEE Trans. Circuits Syst. I, vol. 47, pp. 536 544, Apr. 2000. 972 a g e

973 a g e