Specifications, Applications, Service Instructions & Parts. HCK1, HCK1W PISTON-TYPE CHECK VALVE ¾" thru 6" (20 thru 150 mm)

Similar documents
ISO 9002 Hansen Technologies Corp. Burr Ridge, IL Cert. # Orlando, FL Cert. #

Specifications, Applications, Service Instructions & Parts. Flanged and Weld-in 3/4" thru 4" Port (20 mm thru 100 mm) for Refrigerants

DIFFERENTIAL PRESSURE RELIEF REGULATOR TYPE A4AL Port Size 3/4"- 4" (20-100mm) For Ammonia, R-22, R134a, R404a, R507 and other common refrigerants.

Hand Expansion Valves Built Stronger to Last Longer Sizes: 6mm (¼ ) to 305mm (4 )

Specifications, Applications, Service Instructions & Parts. Butt Weld Shut-off valves

Refrigerating Specialties Division 1. BULLETIN DN23-05B Type A4A-DN, A4AK-DN, A4AE-DN, A4AR-DN. January 2007 Installation and Service Information

Specifications, Applications, Service Instructions & Parts BUTT WELD SHUT-OFF VALVES

Specifications, Applications, Service Instructions & Parts. Socket Weld Shut-off valves

Hand Shut-Off Valves for Standard and Extended Bonnets

BULLETIN Type A4AM. March 2002 Installation, Service and Parts Instruction. Refrigerating Specialties Division Fig.

Specifications, Applications, Service Instructions & Parts SEALED MOTOR VALVE & CONTROLLERS

Specifications, Applications, Service Instructions & Parts MOTORIZED CONTROL VALVE & CONTROLLERS

Industrial Refrigeration Control Valves. Catalog C12

ADAPTOMODE INLET PRESSURE REGULATORS Types: A4AS, A4AB, A4AD, A4AZ

Parker Weld-in Valve Stations

SECTION PIPING SPECIALTIES PART 1 GENERAL 1.1 SUMMARY

CV Control Valves Installation and Operation Manual

DO NOT INSULATE BELOW THIS LINE. * For sizes 1/2" to 1 1/2" add 2 1/2" to 'C' dimension.

Operator Installation & Instructions HERMETIC LIQUID REFRIGERANT PUMPS CAM AND CNF SERIES

2017 LIST PRICE SCHEDULE & PARTS LIST PRICING

Installation, Operation & Maintenance Manual

t EVAPORATOR PRESSURE REGULATING VALVES

Valve Station ICF 20-40

Installation, Operation and Maintenance Manual

MAINTENANCE MANUAL FOR THERMOSTATIC TEMPERATURE REGULATING VALVE TRAC STYLE P

Pilot operated main valves for regulating pressure and temperature, type PM

Installation, Operation and Maintenance Instructions

EVAPORATOR PRESSURE REGULATORS

OPERATING INSTRUCTIONS & SERVICE MANUAL BLUE MAX II HYDROSTATIC TEST PUMP

611H Flo-Con Pressure Regulators & Valves

Pilot-operated servo valve Type ICS

LEAD FREE * LFF113RFP Flood Protection Shut Down Valve

Shut-off Check valves and regulating valves for for Industrial Refrigeration

Valve Station in stainless steel ICF SS 20 and ICF SS 25

NEECO INDUSTRIES INC. INSTRUCTION MANUAL 7 1/16 10K SLAB GATE BODY

MODEL 5540 CONTENTS. Installation, Operation and Maintenance Instructions 1.0 GENERAL

Crispin Valves Operating Guide. Crispin

Hansen Introduction Stop And Regulating Valves Pressure Regulators Control Valve Pilots

Technical Data P3 PISTON POWER PUMP NON-ELECTRIC CONDENSATE PUMP SD 9952B

NECO Pumping Systems

Type 644 and 645 Differential Pressure Pump Governors

Flowrite VF 599 Series Two-Way Valves 2-1/2 to 6-inch Flanged Iron Body

Check Valves Check Valves are the simplest form of directional control valves, but they can also be used as pressure controls.

A-C Fire Pump. Fitting and Accessories A-C 100A

Guide Specification SECTION HYDRONIC PIPING SPECIALTIES PART 1 - GENERAL 1.1 SUMMARY

Pilot-operated servo valve Type ICS

E8 Mini-Matic 3/8" Bolted Plastic Pumps Operating Instructions

Standard Valves Series Globe Valves Series Angle Valves Series Way-Valves

Pilot controlled servo valves Type ICS - Solenoid Valves Pressure Regulating Valves. Technical leaflet MAKING MODERN LIVING POSSIBLE

Pressure control valve Type KDC

LEAD FREE * LFF113RFP Wireless Smart Flood Protection Shut Down Valve with SentryPlus Alert Technology

I & M Mark 78 Series. Ideal Installation. Start-Up. Installation & Maintenance Instructions for Mark 78 Control Valves (1-1/2-2 )

GT-200 GATE VALVES PN16, Screwed end

INSTALLATION, OPERATION AND MAINTENANCE MANUAL (IOM)

Versa-Matic. Operating Manual. 3/8" Bolted Plastic Pumps. Polypropylene Kynar

Direct-Operated Pressure & Temperature Regulating Valves

I & M Mark 78 Series. Ideal Installation. Start-Up. Installation & Maintenance Instructions for Mark 78 Control Valves (1/2-1 )

Series 867 Reduced Pressure Zone Assemblies

CONTENTS. VIKING PUMP, INC. A Unit of IDEX Corporation Cedar Falls, IA USA SECTION TSM 710.1

Pilot-operated servo valve Type ICS

Solenoid valves, type EVRA 3 40 and EVRAT REFRIGERATION AND AIR CONDITIONING. Technical leaflet

SECTION Pressure & Temperature Control

Check & stop valve, SCA-X Check valve, CHV-X

SECTION METERS AND GAGES FOR PLUMBING PIPING

SERIES 270A HIGH SIDE FLOAT VALVES BULLETIN 270A-SB11-02 SERVICE BULLETIN

PRESSURE REDUCING VALVE

GP-2000 : Trouble Shooting. Cause of problems

MODEL 900 IMPELLER-TYPE FLOW METER

Anderson Greenwood Series 5100 Pilot Operated Pressure Relief Valves

High Temperature Chemical Process Inline Pumps

MODEL 200 MULTI-JET FLOW METER

PRESSURE REDUCING CONTROL VALVE

Colt Series C400, C500

Farval. Dualine Installation System Start-Up. Bulletin DL300 BIJUR DELIMON INTERNATIONAL

Specifications, Applications, Service Instructions & Parts VPIF VALVE POSITION INDICATOR. for use with Sealed Motor Valves VPIF INTRODUCTION

Shut-off Check valves and regulating valves for for Industrial Refrigeration

Installation Instructions

Mustang Series PRESSURE REDUCING CONTROL VALVE. M115 (Globe) M1115 (Angle) Schematic. Standard Components. Options & Accessories.

Condensed Catalog 410A January 2008

Solenoid valves type EVRA 3 to 40 and EVRAT 10 to 20

THIS WARRANTY IS IN LIEU

Solutions beyond products...

CIRCLE SEAL CONTROLS

AUTOMATIC FLOW CONTROL VALVE. INSTRUCTIONS Installation - Operation - Inspection - Maintenance

Cla-Val. Service Training Manual. Simple solutions plus learning with a purpose

MODEL 200 MULTI-JET FLOW METER

Vickers. Overhaul Manual. Vane Pumps. Small and Large Series Combination Pumps VC(K)(S)-**-(*)*D*-6(1) VC(K)(S)-**-(*)-*-*D*-5(1)

3. Installation and Commissioning 4. Maintenance 5. Spares

Parts List. Item # Part # # Reqd. Description

CIRCLE SEAL CONTROLS

CHECK VALVES. Flare to Flare. Solder to Solder. Solder to Solder - Extended Ends. Shipped loosely assembled.

6200 Series. Specifications. Fluid End Power End Models 6211, 6212, 6221, & 6222 Models 6241 & 6242 Part Material Part Material Part Material

SINGLE ACTING ALTITUDE VALVE

MODEL NUMBER: MEDIUM DUTY ONBOARD AIR SYSTEM

Hydraulic Motors Repair Instructions

Mercy Hospital of Buffalo Catholic Health System 2 nd Floor Patient Holding Center 3 rd Floor Locker Rooms Shaflucas Architects, PC Project No.

PRESSURE REDUCING VALVE

Purging Air From Divider Block Lubrication Systems

ONYX VALVE CO QUICK START INSTRUCTION. Changing Instruments on an Onyx Isolator Ring

PRESSURE REDUCING VALVE

Transcription:

Bulletin Specifications, Applications, Service Instructions & Parts HCK1, HCK1W PISTON-TYPE CHECK VALVE ¾" thru (20 thru 150 mm) d ¾" thru FPT, SW, WN, ODS for refrigerants Piston-Type Check Valve: HCK1 INTRODUCTION These flanged, heavy-duty, piston-type check valves control the flow of refrigerant. Valves open wide for flow in the direction of the arrow on the valve body. Valves close tight when flow reversals occur. The piston design minimizes pulsations. KEY FEATURES Valves open when inlet pressure exceeds outlet pressure (1 psid [.07 bar] minimum), thereby lifting the piston/seat assembly and allowing flow through the valve. When inlet pressure and outlet pressure are equalized, the weight of the piston/seat assembly causes the valve to close. If outlet pressure exceeds inlet pressure, the outlet pressure acting on top of the piston/seat also helps seat the valve closed. Also available, Type HCK4 in-line check valves and Type SCK combination stop/check valves; contact Hansen ADVANTAGES This normally closed valve requires very little pressure drop to operate. Valve sizes ¾" thru 1¼" have spring-assisted closing. Valve sizes 1½" thru have a special, spool-type, dirt-resistant piston/ seat. A manual opening stem allows positive opening during servicing or troubleshooting the system. The flange-to-flange dimension and flange pattern are the same as the Parker R/S allowing this valve to be dropped in without main line piping changes (exception: 1¼"). APPLICATIONS The HCK1 piston-type check valve prevents reverse flow of refrigerant in liquid, discharge, suction, and hot gas lines. It is an ideal valve where constant pulsating of gas or liquid is present, or where a manual opening of the valve is desirable. This valve is suitable for ammonia, R22, R134a, and other common refrigerants.

MATERIAL SPECIFICATIONS Body: ¾" thru : Ductile iron ASTM A536. & : Cast steel : ¾" thru 1¼": Stainless steel with Teflon seat 1½" thru : Ductile iron, ASTM A536 Closing Spring: Stainless steel (¾" thru 1¼" only) s: Nonasbestos, graphite composite Stem: Plated steel : Steel Stem Seal: O-ring plus graphite composite packing Companion s: Forged steel Safe Working Pressure: 400 psig (27 bar) Operating Temperature: 25F to +250F ( 32 to +121 C) INSTALLATION Protect the interior of the valve from dirt and moisture during storage and installation. The valve must be installed upright in a horizontal line. The arrow on the valve body should be in the normal direction of refrigerant flow. The system should be free of dirt, weld slag, and rust particles. Install the valve in an accessible location for servicing. Do not install a check valve at the inlet of a solenoid valve or regulator with electric shut-off. Do not install a check valve at the inlet of an outlet regulator where liquid may be trapped between the valves. Check valves in general, when installed, should be at the outlet of control valves to avoid trapping refrigerant between the valves. SIZING The same care should be taken when sizing check valves as with any other type of control valve. Check valves should be sized so that the valve is fully open under all normal operating conditions. Also, the check valve port size is not always the same as the line size. This is particularly true for gas flow in compressor discharge lines and hot gas lines. Under some conditions, the port size of a properly-selected check valve can be one or two sizes smaller than the line. The pressure drop across the HCK1 check valve should normally be 2 to 5 psi under full load conditions. In addition, the pressure drop across the check valve at normal minimum load should be determined. For the Hansen HCK1 check valve, a minimum of 1 psi at minimum load is required to ensure that the valve is fully open during all normal flow conditions. CAPACITIES (Tons) (1 Ton= 12,000 Btu/hr= 3.517 kw= 3042 kcal/hr) REFRIG. R717 R22 2 psi = 0.14 bar 5 psi = 0.35 bar 1 U.S. GPM (gallons per minute) = 0.227124 m 3 /hr Discharge line capacities based on +86F (+30 C) condenser, +140F (+60 C) discharge, and +15F ( 9.4 C) evaporator. Compressor sideport capacities based on +20F ( 6.7 C) economizer and +86F (+30 C) condensing. Liquid line capacities based on +20F ( 6.7 C) liquid and +5F ( 15 C) evaporator, with no flashing through valve. To convert to +86F (+30 C) liquid, multiply values in table by 0.9. To convert R22 capacities to R134a, multiply tons in table by 0.92 (accuracy within 8%). GPM correction factors for temperatures between 40F ( 40 C) and +40F (+4.4 C) are negligible. A PPLICATIONS PORT SIZE (mm) Discharge Line Compressor Sideport Liquid Line TONS GPM Discharge Line Compressor Sideport Liquid Line Cv (Kv) TONS GPM P ¾" (32) (32) 1¼" (32) 2 1½" (40) (50) 2½" (65) (80) (100) 2 psi 22 29 44 128 150 242 343 50 (125) 5 (150) 122 7 9 2 4 5 psi 34 45 69 200 234 378 535 1173 1487 1912 2 psi 12 16 25 72 84 136 193 5 psi 19 25 38 110 129 209 296 2 psi 209 274 425 1227 1435 2322 3289 7203 2 psi 14 18 29 83 97 157 222 486 2 psi 7. 5 9. 8 15 44 52 83 118 259 328 422 5 psi 12 16 24 70 82 133 189 414 525 675 2 psi 4. 7 6. 2 9. 6 27 32 52 74 5 psi 7. 2 9. 5 15 42 50 80 114 2 psi 48 63 97 282 330 534 756 1656 2 psi 9. 9 13 20 58 68 110 156 342 8 (7) 10.5 (9) 16.3 (14) 47 (40) 55 (47) 89 (76) 126 (108) 276 (236) 350 (300) 450 (385)

TYPICAL APPLICATIONS DISCHARGE LINE COMPRESSOR SIDEPORT INTERMEDIATE PRESSURE GAS TO COMPRESSOR SUCTION HCK1 PISTON-TYPE CHECK VALVE ECONOMIZER COOLER PUMP DISCHARGE LINE TRANSFER SYSTEM PUMP ACCUMULATOR VENT/BYPASS LINE LIQUID RELIEF HCK1 PISTON-TYPE CHECK VALVE The above are schematic drawings of fictional refrigeration systems to show Hansen product applications in a system. These drawings should not be used for design or construction. 3

INSTALLATION DIMENSIONS ¾" thru (20 mm thru 100 mm) & (125 mm & 150 mm) 20.40" (518 mm) PORT SIZE (mm) ¾ ", (20), (25) 1¼" (32) 1½ ", (40), (50) 2½" (65) (80) (100) (125) (150) HCK1 -to-flange dimensions (L) are the same as the Parker R/S Type CK1, except 1¼",, and. *L1 is the flange face-to-face dimension. DIMENSIONS (mm) L H 1 H 4 FPT, SW WN, ODS 4.2 (107) 4.2 (107) 7.1 (182) 8.0 (205) 8.38" (213) 9.88" (251) 12.1 (308) 12.1 (308) 4.30" (108) 4.30" (108) 5.3 (136) 6.10" (155) 6.5 (167) 7.38" (187) 14.3 (364) 14.3 (364) 8.20" (208) 8.20" (208) 12.39" (315) 13.0 (330) 15.38" (391) 17.0 (432) 8.9 (227) 8.9 (227) 13.39" (340) 14.0 (356) 16.40" (417) 20.5 (521) L 1 * L W ** 4 6.19" (157) 6.19" (157) 9.88" (251) 9.88" (251) 12.2 (311) 14.1 (359) 7.20" (183) 7.20" (183) 10.89" (277) 11.0 (280) 13.38" (340) 15.0 (381) 4.50" (114) 4.50" (114) 4.50" (114) 5.6 (143) 6.50" (165) 8.0 (205) 12.7 (324) 12.7 (324) **W dimension is the maximum width of the valve. 4

HCK1 PARTS LIST, ¾" thru 1¼" (20 mm thru 32 mm) ITEM Q TY PART NO. Kit ¾", 70-1019 Kit 1¼" 70-1021 Above kits consist of: 1a xxpiston/sea t ¾ ", 1 70-0163 1b xx 1¼" 1 70-0167 2 xxclosing Spring 1 70-0155 3 xx O-ring, Lower 1 70-0130 4 xx O-ring, Upper 1 70-0131 Kit ¾",, 1¼" 70-1017 Above kit consists of: 3 xx O-ring, Lower 1 70-0130 4 xx O-ring, Upper 1 70-0131 5 xxstem O-ring 1 70-0010 6 xxstem Washer 1 70-0026 7 xxpackin g 1 70-0025 8 xxpacking Nut 1 70-0019 9 xxseal Cap O-ring 1 70-0011 14 xx 2 70-0132 11 xxseal Cap 1 50-0411 9 xxseal Cap O-ring 1 70-0011 10 xxstem 1 70-0128 12 1 70-0307 13a Body ¾ ", 1 70-0369 13b Body 1¼" 1 70-0369 15 (various) 2 FACTOR Y 16 Bolt ( 5 /8"-11 x 2 3 /) 4 70-0339 17 Nut ( 5 /8"-11) 4 70-0136 5

HCK1 PARTS LIST, 1½" thru (40 mm thru 100 mm) ITEM Q TY PART NO. Kit 1½", 75-1004 Kit 2½" 75-1005 Kit 75-1006 Kit 75-1018 Above kits consist of: 1a xx 1½ ", 1 75-0282 1b xx 2½ ", 1 75-0281 1c x x 1 75-0244 2a xx 1½ ", 1 75-0196 2b xx 2½ ", 1 75-0128 2c x x 1 75-0234 Kit 1½", 75-1007 Kit 2½" 75-1008 Kit 75-1009 Kit 75-1017 Above kits consist of: 2a xx 1½ ", 1 75-0196 2b xx 2½ ", 1 75-0128 2c x x 1 75-0234 3a xxback-up Washer 1½",, 2½ ", 1 75-0245 3b x xback-up Washer 1 50-0351 4a xxstem O-ring 1½",, 2½ ", 1 50-0179 4b x xstem O-ring 1 50-0253 5a xxstem Washer 1½",, 2½ ", 1 50-0046 5b x xstem Washer 1 50-0247 6a xxpacking 1½",, 2½ ", 1 50-0045 6b x xpacking 1 50-0248 7a xxpacking Nut 1½",, 2½ ", 1 50-0013 7b x xpacking Nut 1 50-0251 8a xxseal Cap O-ring 1½",, 2½ ", 1 50-0432 8b x xseal Cap 1 50-0270 14a xx 1½ ", 2 75-0138 14b xx 2½ " 2 75-0125 14c x x 2 75-0137 14d x x 2 75-0253 ITEM 9a Stem 1½,, 2 9 b tem 9 c tem 10a Seal Cap 1½",, 2½, 10b eal Cap 11a 1½, 11b 2½, 11c over 12a Bolts 1½, 12b Bolts 2½, 12c over Bolts 13a ody 1 13b ody 13c ody 2 13d ody 13e ody 15 lange (various) 16a Bolt 1½ ", ( 5 /8"-11 x 3 1 /4 ) 16b Bolt 2½ ", ( ¾" -10 x 3¾ ) 16c Bolt ( 7 /8-9 x ) 17a Nut 1½ ", ( 5 /8-11) 17b Nut 2½ ", ( ¾ -10) 17c Nut ( 7 /8-9) Q TY PART NO. " ½" 1 75-0118 S 1 75-0135 S 1 75-0242 " 1 75-0139 S 1 50-0260 " 1 75-0107 " 1 75-0121 C 1 75-0243 " 4 75-0175 " 4 65-0057 C 4 75-0291 B ½" 1 75-0197 B 1 75-0197 B ½" 1 75-0221 B 1 75-0198 B 1 75-0238 F 2 FACTOR Y " 8 70-0135 " 8 75-0202 " 8 75-0279 " 8 70-0136 " 8 75-0210 " 8 75-0280 6

HCK1W PARTS LIST, & (125 mm & 150 mm) ITEM a b QTY PART NO 1 x 1 75-0686 1 x 1 75-0608 2 x O-ring, Inner, & 1 75-0605 3 x O-ring, Outer, & 1 75-0606 4 xback-up Washer 1 50-0324 5 xstem Seal O-ring 1 50-0293 6 xstem Washer 1 50-0299 7 xpackin g 1 50-0290 8 xpacking Nut 1 50-0292 9 xseal Cap 1 50-0315 10 xstem 1 75-0584 11 xseal Cap 1 50-0304 12 x 1 75-0583 13 x Bolts 4 75-0604 14a x Body 1 75-0638 14b x Body 1 75-0639 7

SERVICE AND MAINTENANCE Failure to Close: The manual opening stem is turned in, mechanically holding the piston/seat open. Dirt may be lodged between the piston/seat and the valve piston wall. Failure to Open: The pressure difference is not high enough. Inlet pressure must be at least 1 psi above outlet pressure. Adjacent shut-off valves or control valves are not open. Dirt may be lodged between the piston/seat and valve piston wall. Manual Operation: If it is necessary to manually hold open the HCK1 valve, remove the seal cap cautiously. There may be a small amount of refrigerant trapped in it. Turn the manual opening stem inward (clockwise) as far as possible. The piston/seat is then mechanically held open. The valve cannot close until the manual opening stem is turned out (counter-clockwise). If it is necessary to remove or disassemble the valve for servicing, be sure it is completely isolated from the refrigeration system and all refrigerant is removed (pumped out to zero pressure). Be sure to follow refrigeration system safety procedures and read the Caution section in this bulletin. To inspect valve interior, slowly loosen the screwed cover or four cover bolts equally, being careful to avoid any refrigerant which may still remain. Remove the piston/ seat. Then clean and inspect for burrs and damage to the seating surfaces. Slight marks and burrs can often be removed by hand with emery paper or by power lapping. Damaged parts should be replaced. Lightly lubricate the main valve interior bore with refrigerant oil, and install the piston/seat and closing spring (a closing spring is used in ¾" - 1¼" valves only). Replace the cover, gasket and bolts (1½" - ). Carefully check the entire valve for leaks before restoring the valve to service. CAUTION Hansen valves are only for refrigeration systems. These instructions and related safety precautions must be completely read and understood before selecting, using, or servicing these valves. Only knowledgeable, trained refrigeration mechanics should install, operate, or service these valves. Stated temperature and pressure limits should not be exceeded. The valve cover or pilot line should not be removed from valves unless the system has been evacuated to zero pressure. See also Safety Precautions in the current List Price Bulletin and the Safety Precautions Sheet supplied with the product. Escaping refrigerant might cause injury, particularly to the eyes and lungs. ORDERING INFORMATION, PISTON-TYPE CHECK VALVES PORT SIZE (mm) STD FLANGE STYLE AND SIZES CONNECTIONS AVAILABLE SW, WN, FPT ALSO ODS STD ¾"x ( 20) ¾", 1¼" 7 /8" x ( 25) ¾", 1¼" 1 1 /8" 1¼"x ( 32) * 1¼", ¾" 1 3 /8" 1½"x ( 40) 1½" 1 5 /8" x ( 50) 1½" 2 1 /8" 2 ½"x ( 65) 2½" 2 5 /8" x ( 80) 3 1 /8" x ( 100) 4 1 /8" x ( 125) ** BW x ( 150) ** BW * ¾",, and 1¼" valves are 2-bolt design. ** & are integral butt weld only, Type HCK1W. To Order: Specify Type HCK1 (or HCK1W), port size, flange connection style and size. TYPICAL SPECIFICATIONS Piston-type check valves shall be ductile iron or steel bodied, normally closed, with a manual opening stem, as manufactured by Hansen Technologies Corporation or approved equal. OTHER PRODUCTS Ammonia Pressure-Relief Valves Gauge, Purge, and Needle Valves Shut-off Valves Expansion Valves (Regulators) Refrigerant Solenoid Valves Refrigerant Pressure Regulators Small Pressure Regulators Refrigerant Check Valves Strainers Gas-Powered Valves Refrigerant Float Switches Float Regulators (High Side) Refrigerant Liquid Pumps AUTO-PURGER Non-condensable Gas Purgers Vari-Level Adjustable Level Controls Techni-Level Transducer Probes Frost Master Defrost Controllers SEE-LEVEL Refrigerant Liquid Indicators WARRANTY Hansen valves are guaranteed against defective materials or workmanship for one year F.O.B. factory. No consequential damages or field labor is included. Teflon is a registered trademark of DuPont 8 6827 High Grove Boulevard Burr Ridge, Illinois 60527 USA Tel: (630) 325-1565 Fax: (630) 325-1572 Toll: (800) 426-7368 http://www.hantech.com 2004 Hansen Technologies Corporation