PRESSURE RELIEF / SURGE ANTICIPATOR CONTROL VALVE

Similar documents
PRESSURE RELIEF / SUSTAINING CONTROL VALVES

PRESSURE REDUCING CONTROL VALVES

FLOAT CONTROL VALVES

ALTITUDE CONTROL VALVES FOR ONE WAY FLOW

COMBINATION PRESSURE REDUCING AND SOLENOID SHUTOFF CONTROL VALVES 2.01 COMBINATION RESSURE REDUCING AND SOLENOID SHUTOFF CONTROL VALVE

MODULATING FLOAT CONTROL VALVE

SOLENOID CONTROL VALVE

SECTION ELECTRONIC ACTUATED PRESSURE REDUCING VALVES AND ACCESSORIES

PRESSURE REDUCING CONTROL VALVE

PRESSURE REDUCING VALVE

PRESSURE REDUCING VALVE

PRESSURE REDUCING VALVE

Mustang Series PRESSURE REDUCING CONTROL VALVE. M115 (Globe) M1115 (Angle) Schematic. Standard Components. Options & Accessories.

LEAD FREE * LFF115 (Globe) LFF1115 (Angle)

LEAD FREE * LFM115 (Globe) LFM1115 (Angle)

50-01 (Full Internal Port) (Reduced Internal Port) Pressure Relief. & Pressure Sustaining Valve MODEL

Check Valve MODEL. Schematic Diagram. Product Dimensions Data:

PROJECT TITLE PROJECT NO: CONTRACT TITLE GRANT NO: UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA

LEAD FREE * LFF113RFP Wireless Smart Flood Protection Shut Down Valve with SentryPlus Alert Technology

SECTION VIII. (Sub-section 430) Wastewater Valves and Appurtenances. 1. General thru Gate Valves thru 430-3

LEAD FREE * LFF113RFP Flood Protection Shut Down Valve

NYLON & PVC VALVES MINING DIVISION PRESSURE REDUCING VALVES ENSURE DOWNSTREAM PRESSURE PVC NYLON

HYDRAULIC CONTROL VALVES

Electronic Control Valves

Deluge Valves. Model 68 DE\ HM-MR. Hydraulically Actuated Manual-Reset Deluge Valve. Dorot Fire Protection Division

Deluge Valves. Model 68 DE\ HRV-MR. Hydraulically Actuated, Anti-Columning, Manual-Reset Deluge Valve. Dorot Fire Protection Division

BERMAD Waterworks. Pressure Relief/Sustaining Valve. Model: WW Series. Features and Benefits. Major Additional Features

BERMAD Waterworks. Booster Pump Control Valve Active Check Valve. 700 Series. Model 740. Features and Benefits. Major Additional Features

Mark 5108 Series. Back Pressure Regulating Valves Mark 5108 Series. Back Pressure Regulating Valves. Valve Features. Operation

Deluge Pressure Reducing Valves. Model 68 DE\ EL\ PORV\ PR. Electrically and Pneumatically Actuated, Pressure Reducing, Remote-Reset, Deluge Valve

700 LARGE SIZE SERIES

Mark 6127 Series. Pressure Regulators Mark 6127 Series. Pressure Reducing Valves. Valve Features. Operation

MODEL 106/206-PG POWER OPERATED GLOBE VALVE Sizes 1/2" to 8" (106-PG) 3" to 10" (206-PG) Installation, Operating and Maintenance Instructions

UPDATE LOG FOR TECHNICAL PROVISIONS DIVISION 4 Date Item(s) Changed Page # 10/1/13 TECHNICAL PROVISIONS DIVISION 4 VALVE SPECIFICATIONS

SECTION MISCELLANEOUS VALVES

SECTION GENERAL-DUTY VALVES FOR PLUMBING PIPING

Deluge Pressure Reducing Valves. Model 68 DE\ RCL\ PR. Electrically Actuated, Manual-Reset, Pressure Reducing, Deluge Valve

BERMAD Waterworks. BERMAD 700 Large Size Series. 700 Series. Features and Options. Model: 700-M5, 700-M6, 700-M5L

Automatic Control Valves

Available End Connections & Size Range

Deep Well Pump Control Valve

MODEL 106-PT / 106-PTC / S106-PT / S106-PTC DOUBLE CHAMBER HYDRAULICALLY OPERATED VALVE

BERMAD Fire Protection

FLOOD PROTECTION SHUT DOWN VALVE (3 and smaller)

AMERICAN FLOW CONTROL 3-16 SERIES 2100 RESILIENT SEATED CHECK VALVE

SECTION VALVES PART 1 -GENERAL

Innovation + Quality. Valves, controls + systems Balancing and Control Valves

SERIES 300 PLUNGER VALVES

Wafer and Globe Style Silent Check Valve. Operation, Maintenance and Installation Manual

Distributed By: M&M Control Service, Inc KO/650-01KO

Series 800 AWWA Butterfly Valves

The Ideal Solution for Protecting People and Property From the Ravages of Fire. SingerValve.com

A. American National Standards Institute: 1. ANSI Z Relief Valves for Hot Water Supply Systems.

Val-Matic 3-Way Tapered Plug Valve

MO\ RC Remote Hydraulic Actuated Monitor Valve. MO\ EL Electrically Actuated Monitor Valve. Local & Remote Actuated Monitor Valves

T he -A900 series of automatic control

SAN ANTONIO WATER SYSTEM SPECIFICATIONS FOR RUBBER-SEATED BUTTERFLY VALVES 3 INCHES THROUGH 72 INCHES ANSI/AWWA C504 Class 150/250 December 2012

SECTION GENERAL-DUTY VALVES FOR HVAC PIPING. A. Contents of Division 23, HVAC and Division 01, General Requirements apply to this Section.

SURGEBUSTER! BUILT WITH ADVANCED TECHNOLOGY TO WITHSTAND YOUR TOUGHEST APPLICATIONS. Air Release Air Valves. Air/Vacuum Air Valves

KEY FEATURES. Product Overview. Product Line Drawing

P r o d u c t c a t a l o g u e

BERMAD BERMAD BERMAD WW M

SWING CHECK VALVES SERIES 52-SC SERIES 600

WATERWORKS. Reach Optimum Efficiency with OCV Control Valves.

The SWL Series Swing Check Valves Meets AWWA C Standards (Full Waterway) Accepts Air Cushions Cost-effective Swing Check Valve Solution

Typical Applications. Installation

Differential Piston Control Valves Pressure, Level and Flow Control

Bourdon Tube Pressure Gauge

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION HVAC&R VALVES

PRESSURE RELIEF VALVE CONTROL VALVE

BERMAD Irrigation. IR-300 Basic Valve. 300 Series. ??????? Basic Valve

MILLCENTRIC FULL/100% POR T ECCENTRIC PLUG VALVE

Suggested Specifications

SECTION 1019 VALVES AND APPURTENANCES GENERAL: Valves shall have manufacturer's name and pressure rating cast in raised letters.

BERMAD Waterworks. Electronic Control Valve. 700 Series. Model Features and Benefits. Major Additional Features

PACIFIC. for Agricultural Irrigation Applications. exceptional quality unparalleled performance

Valve Selection. 1. Function and service considerations

Suggested Specifications

2-12 Grooved End Dual Disc Check Valve. Operation, Maintenance and Installation Manual

CUSTOM COMBINATION AIR VALVE

T e n c a n Backflo w Specialties

INSTALLATION, OPERATION AND MAINTENANCE MANUAL

CLOW CANADA - M-67 HERITAGE BRIGADIER FIRE HYDRANT SPECIFICATION

DWS 41. Installation Data 44 Performance Specs DWS & DW-PRV Series

VRX Plunger. Advanced Control Valve

Ballcentric Plug Valve

1. Valves shall conform to the latest version of AWWA Standard C-509 covering Resilient Seated gate Valves for Water Supply Service.

T he -A900 series of automatic control valves

ECCENTRIC PLUG VALVES

DOROT CONTROL VALVES CATALOGUE

LEAD FREE * LFF113FP. Wireless Smart Flood Protection Shut Down Valve with SentryPlus Alert Technology. Materials NOTICE NOTICE ES--LFF113FP

BERMAD Irrigation. 300 Series. Basic Valve. ??????? IR-300 Basic Valve.

SECTION VALVES AND OPERATORS

Crispin Valves Operating Guide. Crispin

A. This Section includes general duty valves common to several HVAC piping systems.

Butterfly Valve. Product Training Presentation Danfoss Flomatic Corporation

SECTION VALVES PART 1 - GENERAL

SECTION PIPING SPECIALTIES PART 1 GENERAL 1.1 SUMMARY

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES

Model DV-5 Deluge Valve, Diaphragm Style, 1-1/2 thru 8 Inch (DN40 thru DN200), Deluge System Electric Actuation

Transcription:

PROJECT NAME LOCATION PRESSURE RELIEF / SURGE ANTICIPATOR CONTROL VALVE INTRODUCTION This specification covers the design, manufacture, and testing of 2-1/2 in. (65 mm) through 18 in. (450 mm) Control Valves PART 1 - GENERAL 1. Standard products - use the same manufacturer for multiple units of same type. 2. "Tying" of equipment into packages for the purpose of thwarting competition shall be considered to be in non-compliance with these specifications. 3. Manufacturers shall price items under different subsections or sections separately. PART 2 - PRODUCTS 2.01 PRESSURE RELIEF / SURGE ANTICIPATOR CONTROL VALVE A. FUNCTION The Pressure Relief / Surge Anticipator Control Valve shall control high pressures and power failure surges by bypassing system pressure that exceeds the high pressure control setting and also by opening a preset amount when sensed pressure decreases below a preset minimum in anticipation of a surge. B. MATERIALS 1. Material Specification for the Pressure Relief/Surge Anticipator Control Valves Main Valve as follows: Component Material Body & Cover Ductile Iron-ASTM A536 (standard) Cast Steel or Bronze (optional) Main Valve Trim Other Materials Available (optional) Disc Retainer Cast Iron Diaphragm Washer Cast Iron Seat Other Materials Available (optional) Stem, Nut and Spring Seal Disc Buna-N Rubber Diaphragm Nylon Reinforced Buna-N Rubber Internal Trim Parts : Bronze; Brass End Detail Flanged (2 18 ) Threaded (2 3 ) Grooved (2 8 ) Pressure Rating Class 150 lb. (250psi Max.) Class 300 lb. (400psi Max.) Temperature Range Water to 180ᵒF Any other wetted metallic parts ; Bronze; Brass Coating (optional) Fusion Bonded Epoxy Coating (Interior and Exterior); ANSI / NSF 61 Approved / AWWA coating specifications C116-03. Optional Accessories Anti-Cavitation Trim.

C. MANUFACTURE 1. Main Valve: a. The main valve shall be hydraulically operated, single diaphragm actuated, globe or angle pattern. The valve shall consist of three major components; the body with seat installed, the cover with bearing installed and the diaphragm assembly. The diaphragm assembly shall be the only moving part and shall form a sealed chamber in the upper portion of the valve, separating the operating pressure from line pressure. Packing glands, stuffing boxes and/or rolling diaphragm technology will not be permitted and there shall be no pistons operating the main valve or pilot controls. No fabrication or welding shall be used in the manufacturing process. Y-pattern valves shall not be permitted. Main valve shall comply with NSF/ANSI Standard 61 and certified lead free to NSF/ANSI 372 as a safe drinking water system component. 2. Main Valve End Connections: a. End Connections for control valve shall be flanged per ASME/ANSI B16.42, Class 150 or Class 300 (2-1/2 thru 18 ) or Threaded End Connections (2-1/2 thru 3 ) or Grooved End Connections (2-1/2 thru 8 ). 3. Main Valve Body: a. No separate chamber(s) below the diaphragm shall be allowed between the main valve cover and body. No fabrication or welding shall be used in the manufacturing process. b. The valve shall contain a resilient, synthetic rubber disc with a rectangular cross-section contained on three and one half sides by a disc retainer and forming a tight seal against a single removable seat insert. No O-ring type discs (circular, square, or quad type) shall be permitted as the seating surface. The disc guide shall be of the contoured type to permit smooth transition of flow and shall hold the discs firmly in place. The disc retainer shall be of a sturdy one-piece design capable of withstanding opening and closing shocks. It must have straight edge sides and a radius at the top edge to prevent excessive diaphragm wear as the diaphragm flexes across this surface. No hours-glass shaped disc retainers shall be permitted and no V-type or slotted-type disc guides shall be used. c. The diaphragm assembly containing a non-magnetic 303 stainless steel stem; of sufficient diameter to withstand high hydraulic pressures and shall be fully guided at both ends by a bearing in the main valve cover and an integral bearing in the valve seat. The valve seat shall be a solid, one-piece design and shall have a minimum five-degree taper on the seating surface for a positive, drip-tight shut off. No center guides shall be permitted. The stem shall be drilled and tapped in the cover end to receive and affix such accessories as may be deemed necessary. The diaphragm assembly shall be the only moving part and shall form a sealed chamber in the upper portion of the valve, separating the operating pressure from the line pressure. No bolts or cap screws shall be permitted for use in the construction of the diaphragm assembly. d. The flexible, non-wicking, FDA approved diaphragm shall consist of nylon fabric bonded with synthetic rubber compatible with the operating fluid. The diaphragm s center hole for the main valve stem must be sealed by the vulcanized process or a rubber grommet sealing the center stem hole from the operating pressure. The diaphragm must withstand a Mullins Burst Test of a minimum of 600 X per layer of nylon fabric and shall be cycled tested 100,000 times to insure longevity. The diaphragm shall not be used as the seating surface. The diaphragm shall be fully supported in the valve body and cover by machined surfaces which support no less than one-half of the total surface area of the diaphragm in either the fully opened or fully closed position. Bellofram type rolling diaphragms shall not be permitted. e. The main valve seat and stem bearing in the valve cover shall be removable. The cover bearing and seat in the 6 and smaller size valve shall be threaded into the cover and body. The valve seat in the 8 and larger size valves shall be retained by flat head machine screws for ease of maintenance. The lower bearing of the valve stem shall be contained

concentrically within the seat and shall be exposed to the flow on all sides to avoid deposits. To insure proper alignment of the valve stem, the valve body and cover shall be machined with a locating lip. No pinned covers to the valve body shall be permitted. Cover bearing, disc guide and seat shall be made of the same material. All necessary repairs and/or modifications other than replacement of the main valve body shall be possible without removing the valve from the pipeline. The valve shall be designed such that both the cover assembly and internal diaphragm assembly can be disassembled and lifted vertically straight up from the top of a narrow opening/vault. Y-pattern valves shall not be permitted. The seat shall be of the solid one piece design. Two piece seats or seat inserts shall not be permitted. Packing glands and/or stuffing boxes shall not be permitted. 4. Pilot Control System: a. High Pressure Surge Relief Pilot: The pressure relief/sustaining pilot shall be a direct-acting, adjustable, spring-loaded, diaphragm valve designed to permit flow when controlling pressure exceeds the adjustable spring setting. The pressure relief pilot control is normally held closed by the force of the compression in the spring above the diaphragm and it opens when the pressure acting on the underside of the diaphragm exceeds the spring setting. Pressure relief pilot control sensing shall be upstream of the pilot system strainer so accurate control may be maintained if the strainer is partially blocked. Pilot shall comply with NSF/ANSI 61 and certified lead free to NSF/ANSI 372 as a safe drinking water system component. b. Low Pressure Pilot: The pressure reducing pilot control shall be a direct-acting, adjustable, spring-loaded, normally open, diaphragm valve designed to open when the sensed pressure falls below the control setting and close when pressures are normal. The pilot control is held open by the force of the compression on the spring above the diaphragm and it closes when the delivery pressure acting on the underside of the diaphragm exceeds the spring setting. The pilot control system shall include a fixed orifice. The pilot control shall have a second downstream sensing port which can be utilized to install a pressure gauge. Pilot shall comply with NSF/ANSI 61 and certified lead free to NSF/ANSI 372 as a safe drinking water system component. c. Flow Limiter: The pilot system shall contain an adjustable flow limiter to limit main valve travel during low pressure opening without affecting high pressure relief valve travel. This unique hydraulically operated flow limiter has two calibrated orifices, each positioned proportional to valve position, to vary main valve cover control chamber operating pressure. The hydraulically operated flow limiter regulates flow through main valve pilot systems based on valve position to prevent main valve exceeding predetermined flow. A manually adjustable orifice provides reference valve position. Valve position is linked to an integral sensor orifice. When valve position is below reference set-point of the hydraulically operated flow limiter, it allows unhindered pilot system flow. As valve position rises and approaches the reference control setting, the hydraulic flow limiter limits pilot system outward flow to build pressure in the main valve control chamber. Pressure continues to build until flow equals and hydraulically locks the valve at the flow limiters valve position set-point. Mechanical flow limiters shall not be permitted. d. The pilot controls shall be hard piped or bracket mounted to the main valve. e. The pilot control system shall include a strainer, an adjustable closing speed and all required control accessories, equipment, control tubing and fittings. The pilot system shall include isolation ball valves on sizes as standard equipment. A full range of spring settings shall be available in ranges of 0 to 400 psi. Pilots to be manufactured by control valve manufacturer. f. The Pressure Relief / Surge Anticipating Control Valve shall include a visual position indicator assembly on all sizes, as standard equipment. 5. Material Specification for Pilot Control System: Component Material Flow Limiter

Flow Limiter Body Flow Limiter Adjustment Tube Flow Limiter O-Rings Flow Limiter Stem Brass Brass Buna-N Pilots (High & Low) Body & Cover Bronze, Low Lead CuZn21Si3P or UNS C87850 (optional) Pilot Trim Brass & 303 Pilot(s) rubber Buna-N Pilot(s) Connections FNPT Pressure rating 400 psi Max. Temperature Range Water to 180ᵒF Max. Control Tubing Control Fittings Copper (optional) Flexible Braided (optional) Polyethylene (optional) Brass (optional) 6. Factory Assembly: a. Each control valve shall be factory assembled. b. The Quality Management System of the factory shall be certified in accordance with ISO 9001: 2008. c. For all control valves, the factory assembly shall include the complete main valve, pilot valve(s), and all associated accessories and control equipment. d. During factory assembly the control valve manufacture shall make all necessary adjustments and correct any defects. 7. Nameplates: a. Each Control Valve and associated pilot(s) shall be provided with an identifying nameplate. b. Nameplates, depending on type and size of control valve, shall be mounted in the most practical position possible, typically on the inlet side of the valve body. c. Nameplates shall be brass and a minimum of 3/32 thick, ¾ high and 2-3/4 long. d. Pertinent control valve data shall be etched or stamped into the nameplate. Data shall include control valve Catalog number, function, size, material, pressure rating, endconnection details, type of pilot controls used and control adjustment range. 8. Factory Testing: a. Each control valve shall be factory tested. b. The Quality Management System of the factory shall be certified in accordance with ISO 9001: 2008 c. Tests shall conform to approved test procedures. d. The standard factory tests shall include a valve body and cover leakage test, seat leakage test and a stroke test. Control valves and pilot valves, in the partially open position, with both ends closed off with blind flanges (valves) and pipe plugs (pilots), shall be subject to an air test. The applied air pressure shall be 90 psi minimum. All air pressure tests shall be applied for a minimum of 15 minutes. No visible leakage is permitted through the valve seat,

the pressure boundary walls of the valve body, valve cover, pilot body, pilot cover or the body-cover joint. e. Control valve manufacturer shall, upon request, offer additional testing, such as high pressure hydrostatic testing, positive material inspection testing, ferrite testing, liquid penetration inspection testing, magnetic particle examination testing and radiographic examination testing. D. PRODUCT DATA PART 3 - EXECUTION 1. The following information shall be provided: a. Control Valve manufacturer s technical product data. b. Control Valve manufacturer s Installation, Operation and Maintenance manual (IOM). 2. Provide specific information on all optional features specified above and confirm that these items are provided. 3. The valve manufacturer shall be able to supply a complete line of equipment from 2-1/2 through 16 sizes and a complete selection of complementary accessories and equipment. 4. The control valve manufacture shall provide a computerized cavitation analysis report which shows flow rate, differential pressure, and percentage of valve opening. Cv factor, system velocity, and if there will be cavitation damage. A. DELIVERY, STORAGE AND HANDLING 1. Delivery a. The Manufacture shall deliver the control valves to: Address, City, State, Zip. Attention: Phone number: Call 48 hours prior to delivery. b. Upon delivery, control valves to be unloaded and stored by the Owner, district or municipality. 2. Packing and Shipping a. Control valves specified herein shall be factory assembled. Any control valve appurtenances, accessories, parts and assemblies that are shipped unassembled shall be packaged and tagged in a manner that will protect the equipment from damage and facilitate the final assembly in the field. b. Care shall be taken in loading, transporting and unloading to protect control valves, appurtenances, or coatings from damage. Equipment shall not be dropped. All control valves and appurtenances shall be examined before installation and no piece shall be installed which is found to be defective. Any damage(s) shall be repaired. c. Prior to shipping, the control valves and all associated accessories shall be acceptably packaged and covered to prevent entry of foreign material. d. All packaged control valves shall be shipped, remain covered and stored on site until they are installed and put into use. B. FIELD TESTING

1. A direct factory representative shall be made available by the equipment supplier for start-up service, inspection and necessary adjustments. The Control Valve manufacturer shall warrant the valve to be free of defects in material and workmanship for a period of three years from date of shipment provided the valve is installed and used in accordance with all applicable instructions. Electrical components shall have a one-year warranty. The control valve shall be CLA-VAL Company Model No. 52-03, Pressure Relief / Surge Anticipator Control Valve, as manufactured by Cla-Val Co., Newport Beach, CA 92659-0325. END OF SECTION