Features: Electronically Commutated (EC) fan motor Specific Fan Power of 0.16 to 0.34 at NR Insignificant fan heat gain Designed to operate below NR at External Static Pressures of up to 50Pa Variable speed Fan adjustment Ceiling and Underfloor installation Low surface temperature on electric element Low Maintenance Highline 260i EC Waterside Fan Coil Unit
Highline 260i EC Waterside Fan Coil Unit Fan Coil Unit The most popular waterside control fan coil unit in the UK for the past 15 years, now available with EC fans having low Specific Fan Powers. Initially designed to be fitted into a ceiling void, the flexibility also allows the unit to be installed underfloor. Furthermore an alternative to the standard design is the Highline 260d, which incorporates a detachable discharge plenum and enables a more flexible discharge arrangement. Chassis Units are manufactured from 1.0-1.6mm hot dipped galvanised steel and are constructed without the use of self tapping screws. All thermal and acoustic lining is CFC and HCFC free and class O fire rated. All bearings and moving surfaces will operate without requiring further lubrication. All electrical components and electrical wiring comply with the current edition of the I.E.E. regulations. Each unit is factory tested to ensure that it will continue to meet its specified performance with the minimum of maintenance, throughout its life. Fans The fans are of the double inlet, double width centrifugal type. The scrolls are manufactured from galvanised mild steel, complete with forward curved aluminium or galvanised steel bladed impellers. All fan and motor assemblies are statically and dynamically balanced to prevent the transmission of vibration to the fan coil unit casing. Each fan and motor assembly has thermal overload protection fitted, via imbedded thermistors or the commutation electronics. The motors comply to BS 5000-11 and BS EN 60034. The motor frame is totally enclosed and fitted with maintenance free sealed for life ball bearings. Motors are insulated to BS 2757 class B (minimum) and tested to BS EN 61000-3-2 for Harmonic Distortion and BS EN 61000-3-3 for Flicker. Heat Exchangers Coils are manufactured from 0. mm thick solid drawn copper tubes, mechanically expanded into accurately pre-formed collars in rippled aluminium fins. The coils are arranged for single or multicircuit operation via headers. Each coil is fitted with a manual air vent and drain point. All coils are factory tested to a minimum of bar and are suitable for operating pressures of up to 12 bar static head. Coils are fitted with 15 mm o/d plain copper tails. Condensate Drip Tray The condensate drip tray is manufactured from hot dipped galvanised steel, welded at each corner. The tray is then degreased before anti-condensation insulation is applied to all internal and external surfaces. The tray is fitted with 15 mm o/ d plain brass connection (22 mm o/d optional). The tray has a built in gradient to ensure correct drainage of condensate. Temperature Controls (WATERSIDE) Temperature control shall be by modulation of the control valves allowing either chilled or heated water to flow through the appropriate coil. Air Filter Options Mesh Filter - The filter is permanent and is manufactured from a fine woven mesh of galvanised steel wire, welded to a rigid galvanised steel frame. It can be vacuum cleaned in-situ, or periodically removed for washing when necessary Media type filter - Filters are EU2 to Eurovent 4/5 and manufactured from a synthetic media secured to a wire metal frame and fitted with handles for ease of cleaning and replacement. Discharge/ Inlet Plenum The discharge and inlet plenums are attenuated and thermally lined with a CFC and HCFC free class O fire retardant non-migratory foam, which is both vermin and rot proof. The density of the foam is 11 kg/m³ thereby helping to reduce the total weight of the fan coil unit. Electric Heat Element (if required) The element is manufactured from stainless steel sheath with spiral wound stainless steel fins to minimise surface temperature. It is located upstream of the fan(s) to evenly distribute the heat to the final discharge spigots. Each unit shall incorporate a manual reset high temperature cut-out and a Pressure Differential Switch or Current Switch, wired to prevent operation in the event of a fan failure.
THERMAL PERFORMANCE ELECTRIC DATA/ FAN PERFORMANCE WH6CH Model & Size Air Vol. l/s Speed Sens. Duty Watts Total Duty Watts CHW Flow Rate l/s Hyd. Res kpa Heat Duty Watts LPHW Flow Rate l/s Hyd. Res. kpa Running Current (A) Power Absorbed (W) Specific Fan Power (SFP) W/I/s 109 Extra low 1494 1895 0.075 3.63 815 0.018 0. 0.17 23 0.21 122 Low 1667 2112 0.084 4.42 898 0.02 0.34 0.23 31 0.25 143 Low + 1911 2392 0.095 5.55 984 0.022 0.4 0.27 41 0.29 162 Medium 2129 2642 0.105 6.65 1060 0.024 0.46 0.4 55 0.34 167 Medium + 2186 2707 0.107 6.95 1080 0.024 0.47 0.44 59 0. 175 High 2277 12 0.112 7.45 1112 0.025 0.5 0.5 66 0.38 WH9CH 152 Extra low 2093 2662 0.106 4.19 1200 0.027 0.7 0.23 0.20 190 Low 2586 69 0.13 6.1 1422 0.0 0.96 0.3 42 0.22 221 Low + 2951 93 0.147 7.62 1556 0.0 1.14 0.39 55 0.25 274 Medium 84 4438 0.176 10.67 1798 0.04 1.49 0.57 80 0.29 2 Medium + 75 4541 0.18 11.13 1829 0.041 1.54 0.62 86 0. 4 High 3923 48 0.192 12.45 1914 0.043 1.67 0.74 104 0.34 WH12CH 216 Extra low 91 4016 0.159 9.92 1699 0.038 1.5 0. 42 0.19 2 Low 36 4295 0.17 11.21 1784 0.04 1.65 0.4 54 0.23 262 Low + 59 4687 0.186 13.16 1904 0.042 1.86 0.5 67 0.26 7 Medium 4210 5343 0.212 16.72 2102 0.047 2.23 0.7 93 0. 6 Medium + 4463 5658 0.225 18.57 2206 0.049 2.44 0.82 113 0. 3 High 4569 5783 0.229 19.33 2243 0.05 2.52 0.89 121 0. WH13CH 2 Extra low 33 4338 0.172 7.86 1934 0.043 2.15 0.34 45 0.19 265 Low 38 4817 0.191 9.52 2103 0.047 2.51 0.4 54 0.20 317 Low + 46 5572 0.221 12.45 2340 0.052 3.06 0.51 70 0.22 3 Medium 49 6239 0.248 15. 2547 0.057 3.58 0.7 99 0.27 381 Medium + 5184 6552 0.26 16.77 2658 0.059 3.87 0.78 110 0.29 431 High 5774 7241 0.7 20.16 63 0.064 4.45 1.06 143 0.33 WH15CH 246 Extra low 3475 4480 0.178 6.57 2057 0.046 2.78 0. 42 0.17 0 Low 3980 5151 0.204 8.5 23 0.052 3.52 0. 49 0.18 4 Low + 4589 5927 0.2 11.01 2625 0.058 4. 0.47 65 0.20 380 Medium 52 6749 0.268 14 86 0.064 5.2 0.64 90 0.24 415 Medium + 5714 7265 0.8 16.04 47 0.068 5.75 0.77 111 0.27 440 High 6021 7633 0.3 17.57 3163 0.07 6.15 0.88 124 0. WH18CH 0 Extra low 4901 68 0.25 8.75 2971 0.066 6.61 0.47 60 0.17 382 Low 58 6921 0.275 10.46 39 0.072 7.74 0.51 67 0.18 449 Low + 62 7966 0.316 13.59 99 0.08 9.4 0.65 90 0.20 538 Medium 7333 9277 0.8 18.06 4020 0.089 11.52 0.9 129 0.24 585 Medium + 7910 9966 0.395 20.65 4241 0.094 12.71 1.01 142 0.24 647 High 8703 109 0.434 24.55 4566 0.102 14.55 1.24 177 0.27 Based on following Design Condition: Return Air Temperature(summer): 23 o C db and 16.4 o C wb Chilled Water Temperature: 6/12 o C Return Air Temperature(winter): 21 o C LPHW Temperature: 82/71 o C External Static Pressure: Pa Electric heat is available on all units. For further information please contact us. For any alternative design conditions please contact the Cooling Department at Diffusion.
ACOUSTIC PERFORMANCE SOUND POWER LEVELS Model & Size Air Volume l/s Speed Acoustic Measuring Position OCTAVE BAND FREQUENCY 63 125 250 500 1K 2K 4K NR WH6CH 109 Extra low 122 Low 143 Low + 162 Medium 167 Medium + 175 High 42 48 43 45 34 25 47 46 38 31 22 21 41 49 45 47 31 29 48 48 39 34 24 23 43 51 47 49 40 34 48 50 43 34 27 26 46 52 49 51 41 51 52 45 39 29 29 45 53 49 51 42 50 52 46 41 47 54 52 54 44 39 52 56 49 38 42 31 31 33 WH9CH 152 Extra low 190 Low 221 Low + 274 Medium 2 Medium + 4 High 47 48 43 44 34 27 21 46 46 41 29 19 17 46 49 45 47 25 47 48 43 21 20 49 51 47 49 39 33 48 50 45 34 23 23 46 53 50 52 43 38 34 49 53 48 38 39 46 54 51 53 44 39 51 53 49 38 40 29 29 47 55 53 54 45 40 51 54 50 39 41 31 WH12CH 216 Extra low 2 Low 262 Low + 7 Medium 6 Medium + 3 High 45 48 43 45 33 27 22 47 47 40 31 18 17 48 49 46 48 26 45 48 42 33 22 20 45 51 48 50 39 33 29 49 50 44 24 22 47 52 51 51 41 34 49 53 48 38 39 27 48 54 53 53 44 38 51 54 49 39 41 29 29 48 54 53 54 44 39 51 54 50 39 41 33 WH13CH 2 Extra low 265 Low 317 Low + 3 Medium 381 Medium + 431 High 48 49 45 45 34 27 22 45 47 41 18 18 47 50 46 47 29 24 47 49 43 20 19 48 52 48 49 38 48 50 44 34 33 23 22 48 54 51 52 42 49 53 47 27 26 51 55 53 53 43 34 50 54 48 38 38 27 52 56 54 54 45 39 52 56 50 41 41 31 WH15CH 246 Extra low 0 Low 4 Low + 380 Medium 415 Medium + 440 High 45 50 45 45 33 26 21 46 47 42 31 29 19 17 44 51 46 46 34 22 46 48 43 34 31 20 18 44 52 48 49 26 46 49 46 34 22 21 46 53 49 50 40 31 27 51 53 49 26 25 52 55 53 53 43 34 52 54 50 39 40 27 52 56 53 54 44 38 51 55 51 40 41 38 WH18CH 0 Extra low 382 Low 449 Low + 538 Medium 585 Medium + 647 High 52 48 46 44 26 20 46 47 41 33 22 18 52 49 47 45 22 48 49 43 29 23 20 50 50 49 47 31 25 50 50 45 29 21 20 52 53 52 51 41 31 50 52 48 33 24 25 51 55 53 52 42 33 52 53 48 39 26 26 51 55 54 53 44 38 53 55 50 41 38 29 29 OCTAVE BAND FREQUENCY 63 125 250 500 1K 2K 4K CORRECTIONS FOR INDUCT 8 4 1 0 0 0 0 Correction to be added to Discharge only, to convert to Discharge Induct. The discharge sound power levels shown above are based on all front spigots connected directly to an unlined plenum/grilles and measurements taken 1.5m from grille at 45 o. The NR levels shown above are for guidance only and are based on a typical office layout. We would recommend that advice is taken from an Acoustic Consultant to verify actual project noise levels. To achieve guide NR it is recommended that a maximum velocity of 2.5m/s per outlet is not exceeded.
Highline 260i EC Waterside Fan Coil Unit UNIT A SPIGOTS (No Off) 6 855 4 9 1075 5 12 12 5 13 1408 5 15 1655 6 18 2040 7 RECTANGULAR SPIGOTS ALSO AVAILABLE
Options Underfloor installation available Electric Heat(Stainless Steel sheathed element) with Thermal Cut-out Differential Pressure Switch for heating element protection(standard) Current Switch for heating element protection(optional) Power Correction Module Speed Controller/ Speed Limiter 24v Transformer Condensate pumps DIFFUSION Unit Coding System UNIT MODEL FAN TYPE CONTROL APPLICATION OPTIONS UNIT SIZE Chassis - Electronically commutated A - Airside H - Horizontal E - ELECTRIC 06 CH W - Waterside UF - Underfloor CO - COOLING ONLY 09 e.g. -W-H-09-CH HIGHLINE 260i, with EC fans, Waterside Horizontal, 4 pipe, size 9, chassis -W-UF-CO-09-CH HIGHLINE 260i, with EC fans, Waterside Underfloor, Cooling Only, size 9, chassis -W-H-E-09-CH HIGHLINE 260i, with EC fans, Waterside Horizontal, 2 pipe, Electric Heat, size 9, chassis 12 13 15 18 Established in 1960, Diffusion has over 40 years experience in producing environmental solutions via the manufacture of heating, air conditioning and ventilating products. Diffusion Environmental Systems 47 Central Avenue, West Molesey, Surrey KT8 2QZ Tel: (+44) 020 8783 0033 Fax: (+44) 020 8783 0140 Email: diffusion@etenv.co.uk www.diffusion-group.co.uk Diffusion Environmental Systems have a policy of continuous development. We therefore reserve the right to alter information contained in this leaflet, without prior notice.