SEN and SEN Outdoor Air Temperature Sensors

Similar documents
TM-9100 Series Room Command Module

TE-6300 Series Temperature Sensors

A25 Series Warm Air Control with Manual Reset

TE-6300 Series Temperature Sensors

TE-6100 Series Temperature Sensors and Completed Sensor/Hardware Assemblies

R1000 Series Relays. Features and Benefits. Enclosed Relay Contacts Delivers maximum durability and extends life; inhibits corrosion and dust build-up

System 350 P352AB Electronic Pressure Control Series

VA-8020 Floating Valve Actuator

P66 Series Electronic Fan Speed Controls

AV-8020 Series Floating Control Actuated Valve

D-4070 Two Stage Pneumatic Actuator

TE-6300 Series Temperature Sensors Catalog Page

EP-8000 Series Electro-Pneumatic Transducers

Barbara, Here is the list of items. I numbered the attachments to match with the numbers below.

TS Temperature Sensor and Transducers. Product Bulletin. Wide range of mounting types and signal outputs

Damper Actuator Installation

Series Y63, Y64, Y65, Y66, and Y69 Transformers

System 350 S350P Proportional Plus Integral Temperature Stage Module

M9206-Bxx-2S Series On/Off Electric Spring Return Actuators

M100F Incremental Motor Actuator R81F Interface Board

A419ABG-3C Electronic Temperature Control

M9106-AGx-2N0x Series Electric Non-spring Return Actuators

D-70, D-140, D-210, and D-280 Series Electric Non-Spring Return Actuators

VA-715x Electric Valve Actuator

RA-1250 Thermal Dispersion Fan Inlet Sensors Airflow Measuring System

P445 Series Electronic Lube Oil Control

TS Series TS Series

BAPI-Stat 4 Room Humidity Sensor (BA/ B4 -H200 Series)

AD-1251 Probe with Differential Pressure Transducer

BAPI-Com, Two Wire Multifunction Sensor BA/BS4SCOM Temperature/Humidity Sensor Installation and Operating Instructions

D24-53 Series Electric Non-Spring Return Actuators 53 lb in Models (6 N m)

A91 Series Thermistor Temperature Sensors For Duct, Immersion and Space Sensing

TE-6100 Series Temperature Sensors and Completed Sensor/Hardware Assemblies

M9216 Series Electric Spring Return Actuators

VA2202-xxx-2 Series Electric Spring Return Valve Actuators

TE-6001 Hardware Assemblies for TE-6000 Temperature Elements

M9116, M9124, and M9132 Series Electric Non-spring Return Actuators

MicroTech III Water Source Heat Pump Wall-Mounted Room Temperature Sensors

G76x Direct Spark Ignition Controls

TM-11x1 Series Room Temperature Module

YCCS TE-6800 Series Temperature Sensors

VA-7450 Series. Electric Valve Actuators

V46 Series Pressure-Actuated Water-Regulating Valves

M Damper Mount Linkage Kit Installation. Item Description Quantity Item Description Quantity Nuts 2

A11 Series Low Temperature Cutout Control

Digital Room Thermostats with Touch Screen LCD

M9000-3xx Series Weather Shield Enclosures

User's Manual: Series 270I Model 270I Process Current Loop-Powered Isolator

VA-715x Electric Valve Actuator

VA9104-xGA-1S Series Electric Non-Spring Return Valve Actuators

R81EAA Type Plug-In Electronic Circuit Board Kit For Series M100 Motor Actuators

SetPoint 501 and 501s Controllers Installation and Operation Manual

M x Series Valve Linkage Kits

Q35 Series Automatic Vent Damper System

F61 Series Standard Flow Switches

BAPI-Com, Two Wire Multifunction Sensor with Setpoint Slider (BA/BS4SCOM) Temperature/Humidity Sensor

A419 Series Electronic Temperature Controls with NEMA 1 or NEMA 4X Watertight Enclosures

R81EAA-2 Economizer Circuit Board

G72x Series Direct Spark Ignition Controls

P70, P72, and P170 Controls for Low Pressure Applications

Universal Packaging Module (UPM)

INSTALLATION MANUAL. Melink Corporation (513) Revision

AD-1250 Airflow Measuring Station

VA-4233-GGx Series Electric Valve Actuators

M9210-xxx-3 Electric Spring Return Actuators

G600 Series Replacement Intermittent Pilot Ignition Controls

S-2300 Pneumatic Selector Switch

M9300 Series Potentiometer Kits

M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications

TS , -850 Series TS , -850 Series TS-57031, TS

BAPI-Stat Quantum Temperature Sensor with Display and Slider Setpoint

MP461SC Flex Probes* Installation Instructions

Metasys Zoning Package

BAPI-Stat Quantum Temperature Sensor with Display, Button Setpoint, Fan or System Mode Control

RA-2000 Airflow Measuring System

SLC-811X Series. Single Loop Proportional Temperature Controller General Instructions APPLICATION SPECIFICATIONS

M9109 Series Electric Non-spring Return Actuators

DPT-2015 Differential Pressure Transmitter for VAV Box Applications

G861 Series Integrated Function. Direct Spark Ignition Control

M9300 Series Switch Kits

EDA-8100 Electric Damper Actuator

System 350 S350C Temperature Slave Stage Module

VSD Series II Variable Speed Micro Drives

A419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures

Manual Flushing. I nspection and Service

M9220-xxx-3 Electric Spring Return Actuators

C3000 SIGNAL TRANSMITTER. Introduction

VA-720x Electric Valve Actuator

D-3240 Series Pneumatic Piston Actuators

M x Cast Iron Flanged Valve Linkage Kit for Mounting a Single M9000 Series Electric Actuator

M Valve Actuator Weather Shield Kit

IMC SOLAR EAGLE 2 DIFFERENTIAL TEMPERATURE CONTROLLERS

AD592/592-10K Non-Room Sensors in BAPI-Box, BAPI-Box 2 or BAPI-Box 4 BA/592-x-(BB, BB2, BB4) Temperature Sensor Instructions & Operation

Introduction. Series A99 Temperature Sensors. Features and Benefits

Metal Enclosure. Application Note: Metal Enclosure Page 3

VA9104-xGA-2S Series Electric Non-Spring Return Valve Actuators

System 350 A350E Electronic Cooling Control

IMC SOLAR EAGLE 2 DIFFERENTIAL TEMPERATURE CONTROLLERS

ASSA ABLOY Series Power Operator Installation and Instruction ASSA Manual ABLOY ASSA ABLOY

VOC Duct and Rough Service Sensor

Transcription:

FANs 216, 1628.3 Product/Technical Bulletin SEN-500-2, SEN-500-3 Issue Date 0996 SEN-500-2 and SEN-500-3 Outdoor Air Temperature Sensors The SEN-500-2 and SEN-500-3 Outdoor Air Temperature Sensors offer economical solutions to outdoor air temperature measurement in applications with the T500 Series of programmable and non-programmable thermostats. The sensors consist of either a duct mount sensor (SEN-500-3) or an outdoor air sensor (SEN-500-2) and a communication module that provides a digital interface between the sensor and a T500 thermostat. Figure 1: Outdoor Air Temperature Communication Module and Sensors Features and Benefits Single Assembly Ordering Application Diversity Digital Communication Interface Simplifies ordering; provides complete assembly (including communication module, sensor, and all hardware) in one box T500 thermostat can be located up to 300 feet from the communication module, and the sensor can be located up to 500 feet from the communication module Eliminates wire resistance variability associated with 2-wire passive sensors 1996 Johnson Controls, Inc. 1 Part No. 24-4034-131, Rev. A Code No. LIT-216179

O utdoor Air Sensors Overview SEN-500-2 for outdoor air mounting includes: 3 in. 10K thermistor sensor outdoor air shield conduit enclosure with cover wire nuts (2) remote communication module screws and anchors (2) 4.46 113.3 3.47 88.1 1.38 35.0 6.0 max. 152.4 2.54 64 3.50 89 0.81 21 Figure 4: Communication Module Dimensions (in./mm) 0.67 17.0 45 Figure 2: Outdoor Air Sensor Dimensions (in.\mm) SEN-500-3 for duct mounting includes: 8 in. 10K thermistor sensor quick mount sensor holder and retainer metal mounting plate with screws (4) and locknut conduit enclosure with cover wire nuts (2) remote communication module screws and anchors (2) 2.75 69.9 7.5 max. 190.5 Location Considerations Avoid areas subject to excessive vibration or electrical noise. Mount the sensor in an area where it will not be influenced by air currents, radiated heat, or conducted heat. Air currents and heat could adversely affect the temperature at the sensor. Do not exceed the temperature range given in the Specifications table. 6.0 max. 152.4 Plate Dimensions: 3 in. x 3 in. (76 mm x 76 mm) 1.72 43.7 Figure 3: Duct Mount Sensor Dimensions (in./mm) 2 SEN-500-2 and SEN-500-3 Outdoor Air Temperature Sensors Product/Technical Bulletin

Communication Module and Sensor Installation! WARNING: Shock Hazard. Disconnect power supply before wiring connections are made to prevent electrical shock or possible damage to the equipment. Prior to installing the communication module, install the T500 thermostat following the instructions provided with the unit. Note: The maximum wiring run between the thermostat and communication module is 300 feet (91.5 m), and the maximum wiring run between communication modules is 300 feet (91.5 m). The maximum wiring run between the outdoor air communication module and its sensor is 500 feet (152.4 m). Install the communication module and sensor as follows: IMPORTANT: When using shielded wire to ensure proper communications, the total distributed capacitance of the wire run between the T500 thermostat and the communication module must not exceed 15 nf. 1. Install 3-wire 18 AWG cable from the T500 thermostat to the outdoor air communication module location. Unshielded wire is normally recommended. Shielded cable, Belden number 8770 or equivalent, is recommended for applications in electrically noisy environments. Tape the shield at the communication module and terminate the shield at the 24V(c) terminal of the T500 thermostat. 2. Install the outdoor air sensor and 2-wire 18 AWG cable from the sensor location to the outdoor air communication module location. Unshielded wire is recommended on wiring runs less than 20 feet (6.1 m). Shielded cable, Belden number 8760 or equivalent, is recommended for wiring runs longer than 20 feet (6.1 m). Tape the shield at the sensor and terminate the shield at Terminal 2 of the communication module. 3. Using a 3/8 in. (9.5 mm) screwdriver, open the communication module by pushing the cover latch located on the bottom of the module case. (See Figure 5.) 4. Carefully remove the circuit board from the communication module by disengaging the tab that holds the circuit board in place. (See Figure 6.) 5. Using the base as a template, mark the location of the two mounting holes. Drill two 3/16 in. (5 mm) holes at the marked locations, and tap nylon anchors flush to wall surface. Pull the wire cables through the opening in the base and fasten the base to the wall using the supplied screws. (See Figure 7.) 6. Connect the 3-wire cable wires between Terminals RS1, RS+V, and RS2 on the T500 thermostat and communication module. Connect the sensor wires to Terminals 1 and 2 on the communication module. See Figures 8 and 9. 7. Snap the circuit board back into place and replace the cover on the communication module. 8. Press the Outdoor button on the T500 thermostat to verify that the sensor is functioning. Cover Latch Press with screwdriver to open. Figure 5: Opening the Communication Module SEN-500-2 and SEN-500-3 Outdoor Air Temperature Sensors Product/Technical Bulletin 3

To Sensor 0.38 9.5 To Thermostat 2.54 64 0.38 9.5 0.70 18 AVG RS2 RS+V RS1 2 1 Circuit Board Tab 0.65 17 2.45 62 Figure 6: Removing the Circuit Board Figure 8: Outdoor Sensor/Communication Module Wiring Diagram (in./mm) Note: The maximum wiring run between the thermostat and communication module is 300 feet (91.5 m), and the maximum wiring run between communication modules is 300 feet (91.5 m). The maximum wiring run between the outdoor air communication module and its sensor is 500 feet (152.4 m). T500 Thermostat RS1 RS+V RS2 1 2 SEN-500-1 Indoor Sensor 1 (optional) RS1 RS+V RS2 AVG Figure 7: Mounting the Communication Module Base 1 2 RS1 SEN-500-1 Indoor Sensor 2 (optional) RS+V RS2 AVG Outdoor Sensor Wiring If an SEN-500-1 is used for remote indoor sensing, or if a series of SEN-500-1 sensors are used for averaging, the outdoor air communication module can be wired with the remote indoor sensor(s) as shown in Figure 9. Wire the sensor to the outdoor air communication module as shown in Figures 8 and 9. 1 2 RS1 RS+V RS2 AVG SEN-500-2 or 3 ODA Communication Module Outdoor Air or Duct Temperature Sensor Figure 9: Outdoor Sensor/Communication Module Wiring Schematic 4 SEN-500-2 and SEN-500-3 Outdoor Air Temperature Sensors Product/Technical Bulletin

Sensor Installation Step 1: Drill a 1-3/8 in. (35 mm) diameter hole at the desired mounting plate location. Using the mounting plate as a template, drill four 1/8 in. (3 mm) holes for the screws. Sensor Holder Step 2: Mount probe assembly to duct. Retainer Step 3: Insert wires and sensor holder into conduitbox. Ensure that the sensor holder snaps in place. Slide theretainer inside sensor holder. Step 4: Attach conduit box to conduit. Step 5: Wire the sensor to Terminals 1 and 2 of the communications module. Step 6: Close conduit box cover and firmly tighten screws. Figure 10: Duct Mount Sensor Step 3: Close conduit box cover and firmly tighten screws. Step 2: Connect the sensor wires to the wires connected to Terminals 1 and 2 of the communication module using wire nuts provided. Note: The outdoor air sensor may be secured to a flat surface by drilling screws through the back of the conduit box. Step 1: Secure conduit box to conduit and pull wires from the communication module to the conduit box. Figure 11: Outdoor Air Sensor SEN-500-2 and SEN-500-3 Outdoor Air Temperature Sensors Product/Technical Bulletin 5

Troubleshooting Table 1: Troubleshooting Symptom Possible Cause Corrective Action Thermostat has no outdoor air temperature display... Temperature displayed at the T500 does not correlate with temperature at the outdoor air sensor... Incorrect wiring. Outdoor air sensor or communication module are not correctly connected. T500, communication module, or outdoor air sensor failure. Incorrect voltage. Communication module failure. Check wiring between outdoor air sensor, communication module, and thermostat. Check wiring connections at thermostat terminal blocks, between thermostat and communication module, and between communication module and outdoor air sensor. Short the sensor by jumpering Terminals 1 and 2 at the communication module. Reading at the T500 thermostat should read the maximum. If the reading at the T500 thermostat does not read the maximum, check the communication module. If the reading at the T500 does read the maximum, measure the resistance of the sensor with the wires removed from the terminals of the communications module. The resistance should be 10,000 ohm at 77 F. If resistance is not correct, replace the sensor. Measure the voltage across Terminals RS2 and RS+V. Voltage should be 20 to 30 VAC. If the voltage is not within this range, check and correct the voltage at the T500. Note: The voltage reading across Terminals RS2 and RS+V should be the same as the voltage reading across Terminals 24V and 24C of the T500. Measure the voltage across Terminals RS2 and RS1. Voltage should be a pulsed 18 to 20 VDC signal. If the voltage is not within this range, replace the communications module. Ordering Table 2: Ordering Information Item Outdoor Air Temperature Communication Module with Outdoor Air Sensor Outdoor Air Temperature Communication Module with Duct Mount Sensor Product Code Number SEN-500-2 SEN-500-3 6 SEN-500-2 and SEN-500-3 Outdoor Air Temperature Sensors Product/Technical Bulletin

Replacement and Repair Parts The SEN-500 Series of products allows for easy replacement of the sensor. For a replacement sensor, contact the nearest Johnson Controls Table 3: Replacement Parts Item representative and order using the information from the Replacement Parts and Repair Parts tables. Product Code Number Replacement Outdoor Air Temperature Communication Module Replacement Outdoor Air Temperature Sensor (including mounting hardware) Replacement Duct Mount Temperature Sensor (including mounting hardware) Table 4: Repair Parts Item SEN-500-603 SEN-500-604 SEN-500-605 Product Code Number 3 in. Sensor Probe (use with outdoor air sensor) SEN-500-601 8 in. Sensor Probe (use with duct mount sensor) SEN-500-602 SEN-500-2 and SEN-500-3 Outdoor Air Temperature Sensors Product/Technical Bulletin 7

Specifications Product Power Requirements Sensor Temperature Coefficient Reference Resistance Sensor Accuracy Communication Module Ambient Operating Conditions Communication Module Ambient Storage Conditions Sensor Ambient Storage and Operating Conditions T500 Temperature Display Range when Used with the SEN-500-2 or SEN-500-3 SEN-500-2 Outdoor Air Temperature Communication Module with Outdoor Air Sensor SEN-500-3 Outdoor Air Temperature Communication Module with Duct Mount Sensor Supplied by T500 Thermostat Nonlinear, Negative Temperature Coefficient 10K ohm at 77 F (25 C) ±4 F from -4 to 86 F; ±2 C from -20 to 30 C 32 to 122 F (0 to 50 C); 5 to 90% RH noncondensing -30 to 122 F (-34 to 50 C) Sensor Probe: Conduit Box: -55 to 118 F (-48 to 48 C) -50 to 220 F (-46 to 104 C) -50 to 122 F (-46 to 50 C) Sensor Construction Sensor: 1/4 in. O.D. Stainless Steel Probe Conduit Access Box: Rigid PVC Plastic Sensor Holder: Gray LEXAN Sensor Lead Wires Communication Module Dimensions (H x W x D) 22 Gauge Wire 2.54 x 0.81 x 3.50 in. (64 x 21 x 89 mm) Shipping Weight SEN-500-2: 0.5 lb (0.23 kg), Includes Outdoor Air Temperature Sensor and Outdoor Air Communication Module SEN-500-3: 0.4 lb (0.19 kg), Includes Duct Mount Sensor and Outdoor Air Communication Module The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. Controls Group 507 E. Michigan Street P.O. Box 43 Milwaukee, WI 53201 M3643 Printed in U.S.A. 8 SEN-500-2 and SEN-500-3 Outdoor Air Temperature Sensors Product/Technical Bulletin