Maximum temp. rise in oil by 40 thermometer above design ambient (deg C) specified time Short circuit rating (Sec) for As per IS 2026

Similar documents
BHARAT ALUMINIUM COMPANY LTD. SPECIFICATIONS FOR SYNCHRONOUS GENERATOR GENERAL Make : Jinan Power Equipment Factory Type : WX2

TGK Prefabricated Substation Technical Data

TRANSFORMERS UP TO 750 kv

PART C: GUARANTEED TECHNICAL PARTICULARS OF 33 KV, 2x5/6.67 MVA RURAL TYPE SUB-STATION MATERIALS

7.0 Technical Guarantee Specification of 60MVA, 132/33kV Mobile Substation. TECHNICAL DATA SCHEDULE 60MVA, 132/33 kv MOBILE SUBSTATION

Drive Duty Transformer Specification Virginia Transformer Corp. Power Up! Selecting the Right Transformer

MEDIUM POWER TRANSFORMER

CAST RESIN DISTRIBUTION TRANSFORMERS 2016 EDITION

Technical Specification of GECOL. Packaged Transformers

Minera. Oil distribution transformers up to kva. eco design. Minera at a glance. Standards

WESTERN ELECTRICITY SUPPLY COMPANY OF ORISSA, WESCO. GUARANTEED TECHNICAL PARTICULARS 1 of 2

R07 SET - 1

COMPACT SUBSTATION GUIDE

www. ElectricalPartManuals. com WeSTinghouse Secondary Unit Substation Transformers (Power Centers) Descriptive Bulletin Page 1

DISTRIBUTION TRANSFORMER

tests Partial discharge level from day 1 10 pc Insulation 24 kv : impulse tested at 125 kv Insulation 36 kv : impulse tested at 170 kv, 200 kv indeed.

Make : BHEL / Siemens Type : THDF 115/ Reference Standard : IEC 60034

Cast resin transformers

ABB Transformers Egypt

ABB PTTR SPAIN. Zaragoza. The product: Cast coil transformers

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT

Regulation: R16 Course & Branch: B.Tech EEE

Package Price for Grid Connected 6.0 MW Synchronized Electricity: Please Call For Details Price

Package Price for Grid Connected 3.3 MW Synchronized Electricity: Please Call For Details Price

GROUP OF INSTITUTIONS :: PUTTUR UNIT I SINGLE PHASE TRANSFORMERS

Resin Impregnated Paper Bushing, Oil to Air, Type GSB Technical guide

1500 kva Pad Mount Transformer GRDY/14400V Primary - 208Y/120 Wye Secondary - Oil Cooled

AC/DC Arc Furnace and Ladle Furnace Transformers

2014 ELECTRICAL TECHNOLOGY

OLIVER ONLINE VOLTAGE REGULATION

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

Guideline No.: E-07(201501) E-07 TRANSFORMERS. Issued date: October 20,2015. China Classification Society

Guideline No.: E-07(201712) E-07 TRANSFORMERS. Issued date: December 26, China Classification Society

Guideline No.: E-07(201610) E-07 TRANSFORMERS. Issued date: October 28,2016. China Classification Society

Product Description: Objective and Certification: Test Samples and Test Cable:

Distribution transformers Efficiency over life-cycle

CAST RESIN DISTRIBUTION TRANSFORMERS 2017 EDITION

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS

Unit Substation Transformers 5 and 15 KV Class

Fuji Electric. Oil immersed. Transformer FTU08A1-E-0024

A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system.

INTRODUCTION. The plug-in connection on the cables and lightning arrestors, allows for easy installation and replacement.

Stray Losses in Power Transformers

INESING GROUP. Power System Solution

Transformers for Power Applications

DC CIRCUITS ELECTROMAGNETISM

YOUR KEY ENERGY EFFICIENCY PARTNER CAST RESIN DRY-TYPE TRANSFORMERS

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications

ÒÌÃ TRANSFORMERS. ÒÌÃ 1250 kv.a

CONTENTS 1 GENERAL 2 STANDARDS. 3 TECHNICAL FEATURES 3.1 Basic Technical Data 3.2 Standard Accessories 3.3 Tolerances

P2 : About Us. P3 : Elsewedy Transformers. P4 : Why Elsewedy Dry Type Transformer? P6 : Cast Resin Dry Transformers. P7 : Technical Data Sheets

33 KV STATIC SHUNT CAPACITOR WITH ALLIED EQUIPMENT

Resin Impregnated Paper Bushing, Oil to SF 6. , Type GSBK

Product presentation CPT tech Jason Evershed, ABB Transformer Components, May 21st Dry-type transformers Innovative Technology

25 kv Apparatus Bushings

023 : 2006 CEB STANDARD. 12kV & 36kV LOAD BREAK SWITCHES CEYLON ELECTRICITY BOARD SRI LANKA

Syllabus for the Trade of Electrician Duration : Six Month Second Semester Semester Code: ELE: SEM II

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING

Medium Voltage Metal-Enclosed Switches

ABB Ltd. FACTORY IN HANOI

500 kva Pad Mount Transformer V Delta Primary - 208Y/120 Secondary - NEMA 4X - Oil Cooled

Power IT RESIBLOC Dry Type Distribution Transformers. 250 kva up to 40,000 kva

@Perkins. Technical Data Series TAG1A TAG2A TAG3A. Diesel Engine - Electropak. Basic technical data

ABB Transformadores para aplicaciones solares y eolicas

A VIETNAMESE MEMBER OF A WORLD - WIDE FAMILY

1 Low-voltage Power-factor Correction capacitors KNK APPLICATION DESIGN

On-Load Tap changer Type V

(Under Two Part Bid System) Tender No: NFV/ PUR/ BEC K for VCB

Sr. No. Details Page No. 1 MV Capacitor Unit Drawings 3. 2 Technical Perticular for Capacitor Unit 4. 3 MV Surge Capacitor Unit Drawings 6

Small wonder. Station service voltage transformers for small power requirements

694 Electric Machines

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents

Large Power Transformers

MOBILE SUBSTATION DESIGN Brad Bozich & Vitor Vieira 2755 Northwoods Parkway Norcross, Georgia

UniPack compact secondary substations (CSS) upto 36 kv For safe, reliable and space saving power distribution solutions

1ZSE EN, REV. 4. Wall bushings type GSA-AA Technical guide

Medium Voltage Metal-Enclosed Switches

ELECTRICAL PART OF EPR DESIGN, APPLIED STANDARDS AND POSSIBILITY OF COOPERATION WITH POLISH INDUSTRY SUPPLIERS

Pretest Module 21 Units 1-4 AC Generators & Three-Phase Motors

2-marks question bank UNIT I - TRANSFORMERS UNIT II: AC MACHINES

1ZSE en, Rev. 7. Transformer bushings, type GOB Technical guide

SECTION PADMOUNT TRANSFORMER - OIL FILLED

HPS EnduraCoil. Cast Resin Transformer

Powering industry since 1947.

35-kV Thru-Bushings F Series (bolt-in) for Air-Insulated to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

Contact us. Catalog Low voltage generators for diesel and gas engines Industrial Marine applications - series Standard series

Certified for best-in-class performance, reliability, and safety. Trihal sets a new standard for dry-type cast resin transformers

Scheme - I. Sample Question Paper

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS

750 kva Transformer V Delta Primary Voltage - 480Y/277 Wye-N Voltage Secondary - NEMA 3R

DEPARTMENT OF ELECTRICAL ENGINEERING DIT UNIVERSITY HIGH VOLTAGE ENGINEERING

1ZSE EN, REV. 7. Oil SF 6. bushings type GOEK Technical guide

Excitation system is of Static Silicon Excitation System, including excitation transformer, thyristors, and AVR.

/ I S S : / S T S I

NITIN CORPORATION 402, 4 th Floor, Bezzola Commercial Complex, Sion Trombay Road, Chembur, Mumbai , India.

Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 25 kw to 10 MVA or less)

Voltage Regulators PHENIX. Column-Type Variable Transformers, kva. Toroidal Variable Transformers, kva

DRY TYPE TRANSFORMERS

Alstom Grid provides smart, efficient and environmentally-friendly solutions to deliver electricity reliably across the world GRID

Transcription:

TECHNICAL PERTICULAR FOR 1.6 MVA 6.6/0.433 KV SERVICE TRANSFORMER 1.00.00 GENERAL 1.01.00 Service SERVICE 1.02.00 Make ASHOK/VOLTAMP/DANKE/CGL 1.03.00 Type CORE 1.04.00 Location OUTDOOR 1.05.00 Specification and Standards 1.06.00 Type of cooling ONAN 1.07.00 Fitting and accessories included as per specification 1.08.00 Design and ambient temp. 50 DEG CENTEGRADE (Deg C.) 1.09.00 System particulars 2.00.00 RATING 2.01.00 Rated KVA at design 1.6 MVA ambient on ONAN cooling 2.02.00 Rated voltage of HV(KV) 6.6 2.03.00 Rated voltage of LV(KV) 0.433 2.04.00 Rated frequency (Hz) 50 2.05.00 Maximum temp. rise above design ambient of winding by resistance method on ONAN cooling ((deg C.) 50 2.06.00 Maximum temp. rise in oil by 40 thermometer above design ambient (deg C) 2.07.00 Overload capacity for As per IS 2026 specified time 2.08.00 Short circuit rating (Sec) for As per IS 2026 time 3.00.00 WINDING 3.01.00 Connections 3.01.01 HV winding DELTA

3.01.02 LV winding STAR 3.01.03 Vector group Dyn11 3.02.00 Tapping on HV winding 3.02.01 Number 6 3.02.02 Range +/-7 ½ % 3.02.03 Value of each step 2 ½ % 3.03.00 Current density 3.03.01 HV winding (A/mm 2 ) 3 A/mm 2 3.03.02 LV winding (A/mm 2 ) 3 A/mm 2 3.04.00 Conductor area 3.04.01 HV winding (mm 2 ) To be furnished 3.04.02 LV winding (mm 2 ) To be furnished 4.00.00 Losses 4.01.00 No Load losses at rated frequency 4.01.01 100% rated voltage To be furnished 4.01.02 110% rated voltage To be furnished 4.02.00 Copper losses at current,frequency,75degre e centigrade 4.02.01 OFAF NA 4.02.02 ONAF NA 4.03.00 ONAN To be furnished 5.00.00 Efficiency 5.01.00 Efficiency at 75 degree centigrade and Unity P.F / 0.8P.F 5.01.01 100% 98.91% / 98.64% * 5.01.02 75% 99.09% / 98.87% * 5.01.03 50% 99.22% / 98.87% * 5.02.00 MAXIMUM EFFICIENCY % 99.02% * 5.03.00 Load at which maximum efficiency occurs 0.64 * Note:- Efficiency values shall be nearer or higher as mentioned above.

6.00.00 Constructional Detail 6.01.00 Type of construction CORE 6.02.00 Insulation between INORGANIC laminations 6.03.00 Type of joint between core Mitred type limb and yoke 6.04.00 Bolt insulation test voltage 2 KV one minute 6.05.00 Type of winding 6.05.01 Hv winding LAYER 6.05.02 Lv winding LAYER 6.06.00 Winding insulation 6.06.01 Hv winding (kv UNIFORM uniform/graded category 6.06.02 Lv winding (kv uniform) UNIFORM 6.07.00 Insulation material 6.07.01 Hv winding turn insulation PAPER 6.07.02 Lv winding turn insulation PAPER 6.07.03 Between HV and LV winding PAPER BOARD 6.07.04 Between LV winding and PAPER BOARD Core 6.08.00 Type of joint in winding BRAZED 6.09.00 Minimum clearance 6.09.01 Between phases 1. in oil (mm) 2. out of oil (mm) 6.09.02 HV tolv 1.in oil (mm) 2.out of oil (mm) 6.09.03 HV to Earth 1.in oil (mm) 2.out of oil (mm) 6.09.04 LV to Earth 1.in oil (mm) 4 10 MIN 178 MIN 9 NOT APPLICABLE 25 115

2.out of oil (mm) 25 6.10.00 Terminal Arrange ment 6.10.01 High Voltage CABLE BOX 6.10.02 Low voltage CABLE BOX 7.00.00 Transformer constants 7.01.00 Positive sequence To be furnished percentage impedance at principle tap, rated frequency and seventy-five degree centigrade temperature on rated MVA base 7.02.00 Maximum flux density in core at rated frequency 7.02.01 Hundred percent rated volts To be furnished 7.02.02 Hundred ten percent rated To be furnished volts 7.03.00 Noise level maximum 65 7.04.00 Test voltage 7.04.01 Impulse (1.2/50 microsecond wave)withstand voltage 1.HV winding (KV peak) 2.LVwinding (KV peak) 7.04.02 One minute power frequency withstand 1.HV winding (KV peak) 2.LVwinding (KV peak) 7.05.00 No load current at rated frequency and 7.05.01 100% rated voltage TO BE SUBMITTED (= or < 2%) Amp 7.05.02 110% rated voltage TO BE SUBMITTED (= or < 7%) Amp 7.06.00 No load power factor at rated voltage and frequency 60-22 3 TO BE SUBMITTED

7.07.00 Percentage impendence at rated current, rated frequency and seventy five degree centigrade on rated MVA base 7.07.01 Positive sequence at 8 maximum tape +/-10 % 7.07.02 Positive sequence at 7.6 minimum tape +/-10 % 7.08.00 Percentage resistance and reactance at rated current and frequency on rated MVA base 7.08.01 HV to LV reactance % 7.9 7.08.02 Resistance HV winding % 0.5 7.08.03 Resistance LV winding % 0.4 7.09.00 Percentage regulation at full load, seventy five degree centigrade and 7.09.01 Unit power factor % 1.2 7.09.02 0.8 lag power factor % 5.6 8.00.00 Bushings 8.01.00 Type Indoor Indoor Indoor 8.02.00 Voltage class KV HV LV LVN 7.2 1.0 1.0 8.03.00 Rated current 250 2500 2500 8.04.00 Momentary power frequency -- -- -- dry withstand voltage 8.05.00 Visible discharge power 5.5 - - frequency voltage 8.06.00 One minute power frequency withstand voltage 8.06.01 Dry (kv) 27 3 3

8.06.02 Wet (kv) 27 3 3 8.07.00 Under oil flash over or NOT APPLICABLE puncture withstand power frequency voltage 8.08.00 Full wave (1.2/50 microsecond) withstand impulse voltage 8.08.01 Positive(kv peak) 60 8.08.02 Negative (kv peak) 60 8.09.00 Under oil flashover or puncture(1.2/50microseco nd) withstand impulse voltage 8.09.01 Positive(kv peak) NOT APPLICABLE 8.09.02 Negative (kv peak) NOT APPLICABLE 8.10.00 Creep age distance in air 8.10.01 Total (mm) 115 8.10.02 Protected(mm) NOT APPLICABLE 8.11.00 Recommended tap setting NOT APPLICABLE 8.12.00 Weight of assembled TO BE FURNISHED bushing (kg) 9.00.00 Details of tank and materials 9.01.00 Thickness of side plates 5 (mm) 9.02.00 Thickness of bottom plates 6 (mm) 9.03.00 Thickness of cover plates 6 (mm) 9.04.00 Thickness of radiator (pipes TO BE SUBMITTED or sheets) 9.05.00 Material of tank plates MILD STEEL 9.06.00 Material of cooling tubes - 9.07.00 Material of radiator PRESSED STEEL

9.08.00 Material and thickness of CRGO-0.028 core sheet 9.09.00 Are the following designed for filling under full vacuum? 9.09.01 Tank YES 9.09.02 Radiator YES 9.09.03 Conservator YES 9.09.04 Bushings YES 10.00.00 On load tape changer NA 10.01.00 Make 10.02.00 Type 10.03.00 Descriptive Bulletin no (attached) 10.04.00 Connected to 10.05.00 Rating 10.05.01 Rated voltage 10.05.02 Rated current 10.05.03 Tap voltage 10.05.04 Number of steps 10.06.00 Control function provided 10.06.01 Local manual mechanical operation 10.06.02 Non automatic local electrical independent control 10.06.03 Non automatic remote electrical independent control 10.06.04 Non automatic remote electrical simultaneous parallel control 10.06.05 Automatic voltage control 10.07.00 Auxiliary supply(v)

10.08.00 Protective devices 10.09.00 Approximate overall weight (kg) 10.10.00 Approximate overall dimensions 10.11.00 Approximate overall qty of oil (liters) 11.00.00 Off circuit tap switch 11.01.00 Make TO BE FURNISHED 11.02.00 Type MANUALLY,EXTERNALLY,GANG OPERATED 11.03.00 Descriptive Bulletin no (attached) 11.04.00 Connected to CENTRE OF WINDING 11.05.00 Rating 11.05.01 Rated voltage 7200 V 11.05.02 Rated current 100 A 11.05.03 Tap voltage 165 11.05.04 Number of steps 6 12.00.00 Cooling equipment for NOT APPLICABLE OFAF/ONAF/ONAN Type transformer 12.01.00 Number of group of coolers 12.02.00 Number of group of spare coolers 12.03.00 Capacity of each group of coolers (%) 12.04.00 Power consumption per cooler (kw) 12.05.00 Fan and pump details 12.05.01 Number 1.Total : 2. Running: 3. Standby:

12.05.02 Type 12.05.03 Rating (kw) 12.05.04 Speed(rpm) 12.05.05 Motor details 12.06.00 Input (kw) 12.07.00 supply 12.08.00 Type of cooling equipment control 12.09.00 Temperature range over which control is adjustable 12.10.00 Total surface area of each cooler 13.00.00 Weight and dimensions To be furnished 13.01.00 Net weight of core(kg) To be furnished 13.02.00 Net weight of copper To be furnished 13.02.01 HV winding To be furnished 13.02.02 LV winding To be furnished 13.03.00 Net untanking weight (cover To be furnished with core and winding) (Tm) 13.04.00 Net weight of insulating oil To be furnished ( ) 13.05.00 Volume of insulating To be furnished oil(liters) 13.06.00 Total weight of To be furnished transformer 13.06.01 With out oil (Tm) To be furnished 13.06.02 With oil (Tm) To be furnished 13.07.00 Total weight of cooling To be furnished equipment i.e. Radiators 13.08.00 Total weight of transformer To be furnished and ancillary equipment (Tm) 13.09.00 Shipping weight of largest To be furnished

package (Tm) 13.10.00 Crane lift(excluding slings To be furnished for untanking cover with core and windings) 13.11.00 Crane lift(excluding slings To be furnished for removal of HV bushings 13.12.00 Overall dimensions of the transformer 13.12.01 Under base to the top most point (mm) 13.12.02 Under base to bushing mounting flange (mm) 13.12.03 Overall width (mm) 13.12.04 Overall length (mm) 13.13.00 Overall shipping dimensions To be furnished of the largest package 13.14.00 Gross shipping weight to be To be furnished handled 13.15.00 Gross shipping volume to be To be furnished handled 13.16.00 Parts detached for transport To be furnished * Note : - Drawings must be approved prior to order commencement. AS PER DRAWING APPROVED * AS PER DRAWING APPROVED * AS PER DRAWING APPROVED *