In-line rectangular fans. Technical Catalogue

Similar documents
IN-LINE RECTANGULAR FANS IRB / IRBS IRB

ROOF FAN ROOFMASTER STEC NON-INSULATED VERSION TECHNICAL CATALOGUE

Slot diffusers, Round duct diffusers. IMP Klima

IN-LINE DUCT FANS MIXVENT-TD Fan Systems

SLOT DIFFUSERS, ROUND DUCT DIFFUSERS

IN-LINE MIXED FLOW DUCT FANS MIXVENT-TD Fan Systems

Sound attenuators. Sound attenuators, Sound attenuating louvres. Sound attenuators. Rectangular sound attenuators DZ-2, DZ-3

Device can only be used indoors. Not suitable for polluted air or volatile and explosive gases. Single phase speed controller.

TD-MIXVENT Series IN-LINE MIXED FLOW DUCT FANS TD-MIXVENT. In-Line duct fans

7/S6 FIRE DAMPER FDC40. v 2.9 (en)

CAV controllers. Type EN-Ex. For the precise control of normal and high constant volume flows in potentially explosive atmospheres (ATEX)

7/S5 FIRE DAMPER FD40. v 2.9 (en)

VAV terminal units. Type TVM. For dual duct systems PD TVM 1

JVR CONTENTS. Page Introduction 2 Models and dimensions 3 Technical data. Selection tables 4 Technical data. Selection charts 5 Product codes 6

Single-inlet centrifugal fans

Vent-Axia Sabre Sickle Roof Fans (VSR)

ROOFMASTER STEF-HT ROOF FAN

hore PRODUCT CATALOGUE nd Offsh arine an ms for Ma & Refrig CENTRIFUGAL FANS HV VAC &

Sentinel D-Box Single Fan

Twin and Single Inline Fans. Offers a range of flexible installation and application options, including auto-changeover on the Twin range

Shut-off dampers. Type AK-Ex. For low-leakage shut-off of volume flows in potentially. explosive atmospheres (ATEX) PD AK-Ex 1.

Sentinel D-Box Twin Fan

GigaBox centrifugal fans Product specific information

VENT Series CENTRIFUGAL IN-LINE FANS VENT. In-Line duct fans. Mounting foot

Bifurcated Case Axial Fans (BIFA)

COMFORT AIR CURTAIN. SensAir

VKAP 100 MD/LD 3.0 Product version Motor power level (M higher power level, L lower power level) Diameter Product name. Guard grille.

CAV controllers. Type EN. For the precise control of normal and high constant volume flows. 01/2017 DE/en PD EN 1

CENTRIFLOW 3D WITH AC MOTOR >> Technical catalouge

MegaBox Product-specific information

NEW Slimpak EC Box Fan (SLPT EC)

CAV controllers. Type VFL. Volume flow limiter for insertion into ducting K

Centrifugal fan with highly efficient EC drive motor

Series VENTS KSK. Centrifugal kitchen fan in sound-insulated casing with air flow up to 8138 m 3 /h

DIRECT-AIR ILB / ILT Series Rectangular duct fans

Axial-flow Fan AFC. Model numbering system AF C / T. Accessories Three phase. Power rate 1.

CAV controllers. Type VFL. Volume flow limiter for insertion into ducting PD VFL 1

CAV controllers. Type RN-Ex. For the precise control of constant volume flows in potentially explosive atmospheres (ATEX) PD RN-Ex 1

FIRE DAMPERS, FIRE PROTECTION VALVES, SMOKE DAMPERS

HXBR / HXTR Series PLATE MOUNTED SICKLE BLADE AXIAL FANS WITH EXTERNAL ROTOR MOTOR. Plate mounted axial flow fans HXBR/HXTR. Corrosion resistance

The Straight Way. Rectangular Cabinet Fan. Fans Air Handling Units Air Distribution Products Fire Safety Air Curtains and heating Products Tunnel Fans

COMFORT AIR CURTAIN. SensAir

ACOUSTIC CABINET FANS CVAB / CVAT Series

QUOTATION BLADE 7 LX. Product code GEAL6S2BAA

Thermo fans. Systemair range Systemair thermo fans are available in three different executions. The Multibox MUB-K ASF/KB. Flexible connection

Category 1 (zone 0) covers areas, where there is a permanent or long lasting occurrence

CENTRIFLOW 3D WITH AC MOTOR >> Technical catalogue

CVAB / CVAT Series ACOUSTIC CABINET FANS CVAB / CVAT. Acoustic cabinet fans. Backward curved centrifugal impellers.

BACKWARD CURVE CENTRIFUGAL FANS KABB / KABT Series

Centrifugal performance characteristics with axial flow pattern: RADAX VAR

Explanation of AR Series Ventilator Products. Fan type code D S AR AE

Device can be connected to pull air directly from ventilated room or air duct system. Not suitable for polluted air or volatile and explosive gases.

Circular Silencer. Rigid and flexible construction Type CA CB CF CS. TROX GmbH Telephone +49/28 45/ Telefax +49/28 45/

Sound attenuators, Sound attenuating louvres

GmbH Lufttechnik Dresden USER INFORMATION ROOF FANS SERIES VRV. vertical outlet. Issue 07/02

VAV terminal units. Type TVA. For extract air systems with demanding acoustic requi rements K

HPR. Heat recovery units. from 700 to m³/h R410A HIGH EFFICIENCY WITH ENTHALPY EXCHANGER AND BUILT-IN HEAT PUMP SYSTEM

For installation into ductwork

CAV controllers. Type RN. For the precise control of constant volume flow rates PD RN 1

AC Commercial Fans Edition. ErP ready

KV sileo 100 M. Circular duct fans. Circular duct fans

CENTRIFUGAL IN-LINE FANS VENT Series

IN-LINE CENTRIFUGAL DUCT FANS VT Series

ROOF FAN ROOFMASTER STEC

Sabre Sickle Fan Assisted Roof Cowls (VSR)

Electrical data Nominal voltage AC V / DC V Nominal voltage frequency

CENTRIFLOW 3D WITH EC MOTOR >> Technical catalogue

CONSTANTFLOW Volume Flow Controllers

CMRT Series BACKWARD CURVED CENTRIFUGAL FANS. Backward curved centrifugal fans CMRT 80 C

NEW Acoustic In-Line Fans (ACQ)

COMFORT AIR CURTAIN. SensAir

In-Line Fans. Roof Fans. Fans ATEX. Centrifugal Fans. Chip Extractors. Domestic Fans. Accessories. Electric Diagrams. General Information.

Ultra-quiet circular duct fans TD-SILENT ECOWATT Series

ROOFMASTER STEF ROOF FAN

SINGLE DUCT TERMINAL UNITS

IN-LINE MIXED FLOW DUCT FANS TD-MIXVENT Series

Long Throw Nozzle WDA

VAV terminal units. Type TVZ. For supply air systems with demanding acoustic requirements PD TVZ 1

Type AK-Ex FOR LOW-LEAKAGE SHUT-OFF OF VOLUME FLOWS IN POTENTIALLY EXPLOSIVE ATMOSPHERES (ATEX)

WGA Long throw nozzle grille

Mechanical mixing box MBM

Type MSA. Splitter thickness 200 mm FOR INCREASED INSERTION LOSS AND BROADBAND ATTENUATION EVEN IN THE LOW FREQUENCY RANGE

USER S MANUAL VENTS OV/ OVK/ OV1/ OV1 R/ OVK1/ VKF/ VKOM / OVP

Square Duct Fans - ESTOC Range. Estoc Features. Electrical Supply. Product Code. Sizes 355, 400, 450, 500, 560, 630 and 710.

CK, LPK, LPKB. Duct fans with circular connection.

VKAP 100 MD/LD 3.0 Product version Motor power level (M higher power level, L lower power level) Diameter Product name. Guard grille.

Plate mounted axial flow fans HXBR / HXTR Series

PVHRU Max Quiet. Engineering Solutions. Packaged Void Heat Reclaim Unit. Acoustic Testing Laboratory College of Science & Technology

CSXRT: Single inlet, belt-driven centrifugal fans fitted with electric motors. CJSXR: Ventilation units with a backward-curved impeller

Homepage > Products > External louvres - louvre blades > Mechanically self-powered dampers > Non-return dampers > Type KUL.

Technical documentation

Square Duct Fans - ESTOC TARGE Range. Estoc Targe Features. Electrical Supply. Sizes 355, 400, 450, 500, 560 and 630.

TD-SILENT Series (160 to 1000 models)

Particle Filter Box FKU

ACOUSTIC CABINET FANS Centribox CVB-CVT Series, Forward Curved Centrifugal Fans

Kitchen exhaust fan GLEB

Acoustic Twin Fans (ATQ)

Mixed Flow Roof Fans (RMH)

VENTS KSB K2. Series. Inline centrifugal fans in heat- and sound-insulated casing with air flow up to 7000 m 3 /h SOUND-INSULATED FANS

Ceiling Swirl Diffuser DQJ

Transcription:

In-line rectangular fans Technical Catalogue

Overview IN-LINE RECTANGULAR FANS IRB / IRBS IRB and IRBS are a compact series of centrifugal type exhaust and supply in-line duct fans for air conditioning systems. They are specifically designed for installation where space is limited and allow installation directly at any angle and any location along the duct system. Due to their silent operation, they can be used for direct air exhaust from the room or for air supply into the room. IRB Characteristics of IRB/IRBS in-line rectangular fans Duct fans are designed in nine nominal connection dimensions. IRBS: sound isolated housing for all nominal dimensions. Nominal connection dimensions from 3 x 15 mm to 1 x 5 mm Single phase fans from nominal dimension 3 x 15 mm to 6 x 35 mm Three phase fans in all nominal dimensions. Air flow up to 17. m 3 /h. Static pressure up to 1.25 Pa. Direct installation into air duct systems with housing connection flanges; Housing is entirely made of galvanized sheet steel; Motor with centrifugal backward curved impeller is mounted on a swing out door, enabling easy servicing access; Impellers with backward curved blades and high hydraulic efficiency; Efficient, quality and user-friendly regulation. IRBS 2

Content IN-LINE RECTANGULAR FANS IRB/IRBS 4 In-line rectangular fans IRB/IRBS General Information 4 Technical data 6 Accessories 19 Wiring diagrams and regulation 24 Ordering key 31 Installation and maintenance 32 Page Legend of symbols AI Element is made of aluminium profiles, aluminium sheet or aluminium casting. Element is intended to be built in the wall. Element is suitable for the supply of cool air (cooling). St Element is made of steel sheet. Element is intended to be built in the ceiling or in the wall. M Element allows regulation by electric motor (Belimo electric motors). RAL 91 Element is powder painted in standard RAL 91 colour. Other desired colour is to be specified in the order. Element for air conditioning of rooms with floor to ceiling heights room up to 4 m. F EU... Element is intended for air filtration. The filter of class is built in. Shady symbol means possibility of optional material, surface protection, motor version, Element is intended to be built in the floor. Element for air conditioning of rooms with floor to ceiling heights from 6 to 15 m. Element is suitable for the supply of warm air (heating). CD INOX The possibility of the automatic selection and calculation of the technical characteristics of grilles and difusers in regard to the given conditions with the assistance of the Klima ADE program. The element is made of stainless sheet steel AISI 34. 3

In-line rectangular fans irb/irbs In-line rectangular fans irb/irbs Application IRB/IRBS is a compact series of centrifugal type exhaust and supply in-line duct fans for air conditioning systems. They are specifically designed for installation where space is limited and allow installation directly at any angle in any point along the duct work. All fans are designed with a non overloading backward curved impeller with external rotor motor. IRBS fans with sound attenuated housing can be used where quiet operating is needed. Description Main advantages of all IRB and IRBS duct fans: direct installation into air ducts with housing connecting flanges, IRB housing is made of galvanized sheet steel, IRBS sound absorbing casing is made from galvanized sheet steel and filled with highly efficient absorption material, motor with centrifugal backward curved impeller is mounted on a swing out door for free service access, stepless voltage and frequency or 5 step controllable external rotor motor, high efficient impellers with backward curved blades, quiet operating. IRB IRB Typical Specifications for IRB/IRBS Fan Housing IRB/IRBS housings are constructed in nine sizes of galvanized sheet steel. IRBS housing is completely filled with highly efficient absorption material. The construction of sound isolated housing attains very high degree of attenuation. Housing connecting flanges are made of galvanized rolled steel quick-coupling elements with 2 mm edges, joined by means of angle pieces. That allows installation connections directly to or within rectangular duct work. Fan housing includes swing out door on which the motor is mounted providing free service access. Electrical Motors and Impellers Electrical motors are external-rotor type mounted directly into the impeller. All single phase fans are protected by thermal limiter (WS). It is a special version of internal thermal switch, which stops the motor 4

In-line rectangular fans irb/irbs if it is overheated or blocked. User has to switch power supply off for restarting after eliminating cause of overheating. All three phase fans are protected by thermal overload protection brought out (TK). They must be connected to the external protective equipment: speed controllers with TK leads or motor protection switches with TK leads. Impellers are centrifugal type made of backward curved blades, which make impellers run smoothly with high static pressure output, low noise level and very high hydraulic efficiency. Impellers are made of polyamide PA 6.6, aluminium or sheet steel (galvanised or coated). Fans are dynamically balanced in two planes according to DIN ISO 194 to provide vibration free performance. Both the motor and the impeller are cooled with optimal efficiency, being positioned directly in the centre of the air stream they generate, which increases service life. IRBS Speed Control and Electrical Connections Mono phase IRB/IRBS can be speed controlled by the Transformer with 5-step adjustable voltage output or continuously by the thyristor from 8 to 23 V output. Three phase IRB/IRBS can be controlled by the Transformer with 5 step adjustable voltage output or can be controlled by the Frequency controller from to 1% of maximum fan speed. All three phase power supply regulators have leads for TK. When there is no speed control required, IRB/IRBS three phase fans must be connected on motor protection switches with TK: ZSK 25 T (/H). Fans are supplied with an external electrical wiring box and are pre-wired with motor connections leads. Measurements of Characteristics Acoustic performances of all IRB and IRBS fans are measured in reverberation room according to ISO 3741. Air flow and static pressure characteristics for all IRB and IRBS fans are measured according to ISO 581. 5

Technical data Tehnical data D B3 B2 B1 H1 H2 H3 C3 IRB Characteristic (page 8 and 9) Nominal Dimensions in mm Construction Size Type B H B1 B2 B3 H1 H2 H3 C3 D Maximum Air flow Pressure Performances Speed Noise level (at 1 m) Power Voltage Q max p max n L pa P U (m³/h) (Pa) (min -1 ) (db(a)) (W) (V) 1 IRB 315 2SM IRB 315 2ST 1 2 3 15 298 32 335 148 17 185 41 248 525 49 38 2 235 48 55 45 23 2 IRB 42 2SM IRB 42 2ST IRB 42 2HM IRB 42 2HT 3 4 5 6 2 398 42 435 198 22 235 51 287 331 92 82 135 129 55 44 76 655 25 245 245 234 5 5 47 49 85 8 15 21 23 23 3 IRB 525 4SM IRB 525 4ST IRB 525 2HM IRB 525 2HT 7 8 9 1 5 25 498 52 535 248 27 285 54 49 372 155 138 197 165/128 35 24 85 82/625 132 125 225 268/226 45 45 51 53/49 11 1 22 3/185 23 23 IRB 53 6SM 11 179 19 86 45 65 23 4 IRB 53 4HM IRB 53 4HT 12 13 5 25 498 52 535 298 32 335 61 462 23 242 43 44 135 138 48 49 175 225 23 5 IRB 63 4SM IRB 63 4ST 14 15 6 3 598 62 635 298 32 335 65 466 324 35 47 45 1 132 53 54 24 275 23 6 IRB 635 4SM IRB 635 4ST IRB 635 4HM IRB 635 4HT 16 17 18 19 6 35 598 62 635 348 37 385 726 56 336 316 41 42 47 45 58 58 1 132 1325 134 52 53 56 56 24 275 47 48 23 23 7 IRB 74 4ST 2 7 698 72 735 398 42 435 796 586 56 6 13 59 7 8 IRB 85 4ST 21 636 7 74 1355 63 145 8 5 798 82 835 498 52 535 921 IRB 85 4HT 22 676 16 11 135 66 235 9 IRB 15 4ST 23 18 11 1355 65 235 1 5 998 12 135 498 52 535 126 676 IRB 15 4HT 24 127/97 11/8 1285/88 85/77 41/233 * 2-2 poles 4-4 poles 6-6 poles ** S - standard power at nominal dimension H - higher power at nominal dimension *** M - mono phase motor T - 3-phase motor 6

Technical data D B4 B3 B2 B1 H1 H2 H3 H4 C3 IRBS Characteristic (page 8 and 9) Nominal Dimensions in mm Construction Size Type B H B1 B2 B3 B4 H1 H2 H3 H4 C3 D Maximum Air flow Pressure Performances Speed Noise level (at 1 m) Power Voltage Q max p max n L pa P U (m³/h) (Pa) (min -1 ) (db(a)) (W) (V) 1 IRBS 315 2SM IRBS 315 2ST 1 2 3 15 298 32 335 46 148 17 185 255 41 197 525 49 38 2 235 45 44 55 45 23 2 IRBS 42 2SM IRBS 42 2ST IRBS 42 2HM IRBS 42 2HT 3 4 5 6 2 398 42 435 56 198 22 235 35 51 236 28 92 82 135 129 55 44 76 655 25 245 245 234 46 46 43 45 85 8 15 21 23 23 3 IRBS 525 4SM IRBS 525 4ST IRBS 525 2HM IRBS 525 2HT 7 8 9 1 5 3 498 52 535 66 248 27 285 355 54 358 321 155 138 197 165/128 35 24 85 82/625 132 125 225 268/226 42 42 47 49/45 11 1 22 3/185 23 23 IRBS 53 6SM 11 179 19 86 42 65 23 4 IRBS 53 4HM IRBS 53 4HT 12 13 5 3 498 52 535 66 298 32 335 45 61 411 23 242 43 44 135 138 44 45 175 225 23 5 IRBS 63 4SM IRBS 63 4ST 14 15 6 3 598 62 635 76 298 32 335 45 65 415 324 35 47 45 1 132 48 49 24 275 23 6 IRBS 635 4SM IRBS 635 4ST IRBS 635 4HM IRBS 635 4HT 16 17 18 19 6 35 598 62 635 76 348 37 385 455 726 455 336 316 41 42 47 45 58 58 1 132 1325 134 47 48 49 49 24 275 47 48 23 23 7 IRBS 74 4ST 2 7 698 72 735 86 398 42 435 55 796 535 56 6 13 52 7 8 IRBS 85 4ST 21 585 7 74 1355 54 145 8 5 798 82 835 96 498 52 535 65 921 IRBS 85 4HT 22 625 15 92 135 58 235 9 IRBS 15 4ST 23 16 92 1355 61 235 1 5 998 12 135 116 498 52 535 65 126 625 IRBS 15 4HT 24 127/97 11/8 1285/88 81/74 41/233 * 2-2 poles 4-4 poles 6-6 poles ** S - standard power at nominal dimension H - higher power at nominal dimension *** M - mono phase motor T - 3-phase motor 7

Technical data Selection diagram for Mono phase fans. ps (Pa) 9 8 5 7 9 6 5 1 3 3 12 18 2 11 7 14 16 1 8 12 16 2 2 28 32 36 2 6 1 1 18 22 26 3 3 38 42 Q (m 3 /h) For corresponding fan type see pages 6 and 7. Selection diagrams for 3-phase fans. ps (Pa) 9 8 7 1-6 6 5 3 2 4 2 1-Y 15 19 1 8 13 17 8 12 16 2 2 28 32 36 2 6 1 1 18 22 26 3 3 38 42 Q (m 3 /h) Legend: 1-Δ: delta wiring ;1-Y: star wiring 8

Technical data Selection diagrams for 3-phase fans. ps [Pa] 13 12 11 1 9 8 7 24-6 5 21 22 3 2 24-Y 23 2 1 1 2 3 5 6 7 8 9 1 11 12 13 1 15 16 17 5 15 25 35 45 55 65 75 85 95 15 115 125 135 145 155 165 175 Q (m 3 /h) For corresponding fan type see pages 6 and 7. 9

Technical data Size 1 Nominal Rectangular Duct Dimensions 3x15 Type IRB 315 2SM / IRBS 315 2SM IRB 315 2ST/ IRBS 315 2ST Duct width (mm) 3 Duct height (mm) 15 Max. Air flow: Q max (m³/h) 525 49 Temperature of transported Air and of Ambient ( C) -25 5-25 7 Power (W) 55 45 Voltage/Frequency (V/Hz) 23/5 /5 Current (A).25.9 Speed/rpm (min -1 ) 2 235 Motor: Insulation class B B Motor: Type of protection IP 44 IP 44 Motor: Wiring diagram No.1 page: 24 No.2 page: 24 Weight (kg) 8/14 8/14 Sound pressure level at 1 m according to ISO 3741 IRB: (db(a)) 48 47 IRBS: (db(a)) 45 44 IRB 315 2SM/T Installation dimensions in (mm) IRBS 315 2SM/T Installation dimensions in (mm) 197 46 335 32 298 148 17 185 255 248 335 32 298 148 17 185 41 41 IRB/IRBS 315 2SM and IRB/IRBS 315 2ST Characteristics: ps (Pa) 45 35 3 25 2 15 1 5 1 2 3 5 6 IRB/IRBS 315 2SM IRB/IRBS 315 2ST Q (m 3 /h) IRB/IRBS 315 2SM IRB/IRBS 315 2ST Regulation - pg: 25-3 Stepless controller BR 1 M page: 25 / 5-step controller SR 1,5 M page: 26 SRK 1,5 T page: 27 ON/OFF switch RS 3 P page: 3 RS 6 P page: 3 Motor protection switch / ZSK 25 T(/H) page: 3 Frequency controller / FR,37 M page: 28 1

Technical data Size 2 Nominal Rectangular Duct Dimensions x2 Type IRB 42 2SM/ IRBS 42 2SM IRB 42 2ST/ IRBS 42 2ST IRB 42 2HM/ IRBS 42 2HM IRB 42 2HT/ IRBS 42 2HT Duct width (mm) Duct height (mm) 2 Max. Air flow: Q max (m³/h) 92 82 135 129 Temperature of transported Air and of Ambient ( C) -25 55-25 7-25 7-25 7 Power (W) 85 8 15 21 Voltage/Frequency (V/Hz) 23/5 /5 23/5 /5 Current (A),38,12,7,34 Speed/rpm (min -1 ) 25 245 245 234 Motor: Insulation class B B F F Motor: Type of protection IP 44 IP 44 IP 44 IP 44 Motor: Wiring diagram/page No.1 page: 24 No.2 page: 24 No.1 page: 24 No.2 page: 24 Weight (kg) 13/21 13/21 14/23 14/23 Sound pressure level at 1 m according to ISO 3741 IRB: (db(a)) 5 5 47 49 IRBS: (db(a)) 46 46 43 45 IRB 42 2SM/T, IRB 42 2HM/T Installation dimensions in (mm) IRBS 42 2SM/T, IRBS 42 2HM/T Installation dimensions in (mm) 287 (331) 435 42 236 (28) 56 435 42 398 398 198 22 235 198 22 235 35 51 51 * The value in bracket ( ) is given for versions IRB 42 2HM and IRB 42 2HT. IRB/IRBS 42 2SM, IRB/IRBS 42 2ST Characteristics: **The value in bracket ( ) is given for versions IRBS 42 2HM and IRBS 42 2HT. IRB/IRBS 42 2HM, IRB/IRBS 42 2HT Characteristics: ps (Pa) 6 55 5 ps (Pa) 8 7 45 6 35 5 3 25 2 3 15 2 1 5 1 1 2 3 5 6 7 8 9 1 2 6 8 1 12 1 16 IRB/IRBS 42 2SM IRB/IRBS 42 2ST Q (m 3 /h) IRB/IRBS 42 2HM IRB/IRBS 42 2HT Q (m 3 /h) IRB/IRBS 42 2SM IRB/IRBS 42 2ST IRB/IRBS 42 2HM IRB/IRBS 42 2HT Regulation - pg: 25-3 Stepless controller BR 1 M page: 25 / BR 1 M page: 25 / 5-step controller SR 1,5 M page: 26 SRK 1,5 T page: 27 SR 1,5 M page: 26 SRK 1,5 T page: 27 ON/OFF switch RS 3 P page: 3 RS 6 P page: 3 RS 3 P page: 3 RS 6 P page: 3 Motor protection switch / ZSK 25 T(/H) page: 3 / ZSK 25 T(/H) page: 3 Frequency controller / FR,37 M page: 28 / FR,37 M page: 28 11

Technical data Size 3 Nominal Rectangular Duct Dimensions 5x25 Type IRB 525 4SM / IRBS 525 4SM IRB 525 4ST / IRBS 525 4ST IRB 525 2HM / IRBS 525 2HM IRB 525 2HT / IRBS 525 2HT Duct width (mm) 5 Duct height (mm) 25 Max. Air flow: Q max (m³/h) 155 138 197 165/128 Temperature of transported Air and of Ambient ( C) -25 7-25 7-25 4-25 7 Power (W) 11 1 22 3/185 Voltage/Frequency (V/Hz) 23/5 /5 23/5 /5 Current (A).44.3.97.5 Speed/rpm (min -1 ) 132 125 225 268/226 Motor Insulation class B B F F Motor Type of protection IP 44 IP 44 IP 44 IP 44 Motor wiring diagram/page No.1 page: 24 No.3 page: 24 No.1 page: 24 No.4 page: 24 Weight (kg) 18/29 18/19 17/28 17/28 Sound pressure level at 1 m according to ISO 3741 IRB: (db(a)) 45 45 51 53/49 IRBS: (db(a)) 42 42 47 49/45 IRB 525 4SM/T, IRB 525 2HM/T Installation dimensions in (mm) IRBS 525 4SM/T, IRBS 525 2HM/T Installation dimensions in (mm) 49 (372) 535 52 498 358 (321) 66 635 52 498 248 27 285 248 27 285 355 54 54 * The value in bracket ( ) is given for versions IRB/IRBS 525 4SM, IRB/IRBS 525 4ST Characteristics: **The value in bracket ( ) is given for versions IRBS 525 2HM and IRBS 525 2HT. IRB/IRBS 525 2HM, IRB/IRBS 525 2HT Characteristics: ps (Pa) 35 ps (Pa) 9 8 3 7 25 6 2 5 15 3 1 2 5 1 2 6 8 1 12 1 16 3 6 9 12 15 18 21 IRB/IRBS 525 4SM IRB/IRBS 525 4ST Q (m 3 /h) IRB/IRBS 525 2HM IRB/IRBS 525 2HT: connection IRB/IRBS 525 2HT: Y connection Q (m 3 /h) Regulation - pg: 25-3 IRB/IRBS 525 4SM IRB/IRBS 525 4ST IRB/IRBS 525 2HM IRB/IRBS 525 2HT Stepless controller BR 1 M page: 25 / BR 1,5 M page: 25 / 5-step controller SR 1,5 M page: 26 SRK 1,5 T page: 27 SR 1,5 M page: 26 SRK 1,5 T page: 27 ON/OFF switch RS 3 P page: 3 RS 6 P page: 3 RS 3 P page: 3 RS 9 P page: 3 Motor protection switch / ZSK 25 T(/H) page: 3 / ZSK 25 T(/H) page: 3 Frequency controller / FR,37 M page: 28 / FR,37 M page: 28 12

Technical data Size 4 Nominal Rectangular Duct Dimensions 5x3 Type IRB 53 6SM / IRBS 53 6SM IRB 53 4HM / IRBS 53 4HM IRB 53 4HT / IRBS 53 4HT Duct width (mm) 5 Duct height (mm) 3 Max. Air flow: Q max (m³/h) 179 23 242 Temperature of transported Air and of Ambient ( C) -25 7-25 6-25 7 Power (W) 65 175 225 Voltage/Frequency (V/Hz) 23/5 23/5 /5 Current (A).3.75.53 Speed/rpm (min -1 ) 86 135 138 Motor: Insulation class F F F Motor: Type of protection IP 44 IP 44 IP 44 Motor: Wiring diagram No.1 page: 24 No.1 page: 24 No.2 page: 24 Weight (kg) 29/42 3/42 3/42 Sound pressure level at 1 m according to ISO 3741 IRB: (db(a)) 45 48 49 IRBS: (db(a)) 42 44 45 IRB 53 6SM, IRB 53 4HM/T Installation dimensions in (mm) IRBS 53 6SM, IRBS 53 4HM/T Installation dimensions in (mm) 411 66 535 52 498 298 32 335 42 462 535 52 498 298 32 335 61 61 IRB/IRBS 53 6SM Characteristics: IRB/IRBS 53 4HM, IRB/IRBS 53 4HT Characteristics: ps (Pa) 2 175 ps (Pa) 45 15 35 125 3 25 1 2 75 15 5 1 25 5 25 5 75 1 125 15 175 2 5 1 15 2 25 IRB/IRBS 53 6SM Q (m 3 /h) IRB/IRBS 53 4HM IRB/IRBS 53 4HT Q (m 3 /h) IRB/IRBS 53 6SM IRB/IRBS 53 4HM IRB/IRBS 53 4HT Regulation - pg: 25-3 Stepless controller BR 1 M page: 25 BR 1 M page: 25 / 5-step controller SR 1,5 M page: 26 SR 1,5 M page: 26 SRK 1,5 T page: 27 ON/OFF switch RS 3 P page: 3 RS 3 P page: 3 RS 6 P page: 3 Motor protection switch / / ZSK 25 T(/H) page: 3 Frequency controller / / FR,37 M page: 28 13

Technical data Size 5 Nominal Rectangular Duct Dimensions 6x3 Type IRB 63 4SM / IRBS 63 4SM IRB 63 4ST / IRBS 63 4ST Duct width (mm) 6 Duct height (mm) 3 Max. Air flow: Q max (m³/h) 324 35 Temperature of transported Air and of Ambient ( C) -25 5-25 7 Power (W) 24 275 Voltage/Frequency (V/Hz) 23/5 /5 Current (A) 1.1.55 Speed/rpm (min -1 ) 1 132 Motor: Insulation class F F Motor: Type of protection IP 44 IP 44 Motor: Wiring diagram/page No.1 page: 24 No.3 page: 24 Weight (kg) 35/49 35/49 Sound pressure level at 1 m according to ISO 3741 IRB: (db(a)) 53 54 IRBS: (db(a)) 48 49 IRB 63 4SM/T Installation dimensions in (mm) IRBS 63 4SM/T Installation dimensions in (mm) 466 635 62 598 298 32 335 415 76 635 62 598 298 32 355 42 65 65 IRB/IRBS 63 4SM, IRB/IRBS 63 4ST Characteristics: ps (Pa) 5 45 35 3 25 2 15 1 5 5 1 15 2 25 3 35 IRB/IRBS 63 4SM IRB/IRBS 63 4ST Q (m 3 /h) IRB/IRBS 63 4SM IRB/IRBS 63 4ST Regulation - pg: 25-3 Stepless controller BR 1,5 M page: 25 / 5-step controller SR 1,5 M page: 26 SRK 1,5 T page: 27 ON/OFF switch RS 3 P page: 3 RS 6 P page: 3 Motor protection switch / ZSK 25 T(/H) page: 3 Frequency controller / FR,37 M page: 28 14

Technical data Size 6 Nominal Rectangular Duct Dimensions 6x35 Type IRB 635 4SM/ IRBS 635 4SM IRB 635 4ST / IRBS 635 4ST IRB 635 4HM / IRBS 635 4HM IRB 635 4HT/ IRBS 635 4HT Duct width (mm) 6 Duct height (mm) 35 Max. Air flow: Q max (m³/h) 336 316 41 42 Temperature of transported Air and of Ambient ( C) -25 5-25 7-4 7-25 6 Power (W) 24 275 47 48 Voltage/Frequency (V/Hz) 23/5 /5 23/5 /5 Current (A) 1.1.55 2.35 1.27 Speed/rpm (min -1 ) 1 132 1325 134 Motor: Insulation class F F F F Motor: Type of protection IP 54 IP 54 IP 54 IP 54 Motor: Wiring diagram/page No.1 page: 24 No.3 page: 24 No.1 page: 24 No.3 page: 24 Weight (kg) 39/55 39/55 44/59 44/59 Sound pressure level at 1 m according to ISO 3741 IRB: (db(a)) 52 53 56 56 IRBS: (db(a)) 47 48 49 49 IRB 635 4SM/T, IRB 635 4HM/T Installation dimensions in (mm) IRBS 635 4SM/T, IRBS 635 4HM/T Installation dimensions in (mm) 56 635 62 455 76 635 62 598 598 348 37 385 348 37 385 455 726 726 IRB/IRBS 635 4SM, IRB/IRBS 4ST Characteristics: IRB/IRBS 635 4HM, IRB/IRBS 635 4HT Characteristics: ps (Pa) 5 45 ps (Pa) 6 55 5 45 35 3 35 25 3 2 25 15 2 15 1 1 5 5 5 1 15 2 25 3 35 5 1 15 2 25 3 35 45 IRB/IRBS 635 4SM IRB/IRBS 635 4ST Q (m 3 /h) IRB/IRBS 635 4HM IRB/IRBS 635 4HT Q (m 3 /h) IRB/IRBS 635 4SM IRB/IRBS 635 4ST IRB/IRBS 635 4HM IRB/IRBS 635 4HT Regulation - pg: 25-3 Stepless controller BR 1,5 M page: 25 / BR 4 M page: 25 / 5-step controller SR 1,5 M page: 26 SRK 1,5 T page: 27 SR 3,5 M page: 26 SRK 1,5 T page: 27 ON/OFF switch RS 3 P page: 3 RS 6 P page: 3 RS 3 P page: 3 RS 6 P page: 3 Motor protection switch / ZSK 25 T(/H) page: 3 / ZSK 25 T(/H) page: 3 Frequency controller / FR,37 M page: 28 / FR,75 M page: 28 15

Technical data Size 7 Nominal Rectangular Duct Dimensions 7x Type IRB 74 4ST/ IRBS 74 4ST Duct width (mm) 7 Duct height (mm) Max. Air flow: Q max (m³/h) 56 Temperature of transported Air and of Ambient ( C) -4 7 Power (W) 7 Voltage/Frequency (V/Hz) /5 Current (A) 1.34 Speed/rpm (min -1 ) 13 Motor: Insulation class F Motor: Type of protection IP 54 Motor: Wiring diagram No.3 page: 24 Weight (kg) 63/93 Sound pressure level at 1 m according to ISO 3741 IRB: (db(a)) 59 IRBS: (db(a)) 52 IRB 74 4ST Installation dimensions in (mm) IRBS 74 4ST Installation dimensions in (mm) 586 735 72 698 398 42 435 535 86 735 72 698 398 42 435 53 796 796 IRB/IRBS 74 4ST Characteristics: ps (Pa) 6 5 3 2 1 1 2 3 5 6 IRB/IRBS 74 4ST Q (m 3 /h) IRB/IRBS 74 4ST Regulation - pg: 25-3 Stepless controller / 5-step controller SRK 1,5 T page: 27 ON/OFF switch RS 6 P page: 3 Motor protection switch ZSK 25 T(/H) page: 3 Frequency controller FR,75 M page: 28 16

Technical data Size 8 Nominal Rectangular Duct Dimensions 8x5 Type IRB 85 4ST / IRBS 85 4ST IRB 85 4HT / IRBS 85 4HT Duct width (mm) 8 Duct height (mm) 5 Max. Air flow: Q max (m³/h) 7 16 Temperature of transported Air and of Ambient ( C) -25 65-4 6 Power (W) 145 235 Voltage/Frequency (V/Hz) /5 /5 Current (A) 2.69 4.96 Speed/rpm (min -1 ) 1355 135 Motor: Insulation class F F Motor: Type of protection IP 54 IP 54 Motor: Wiring diagram/page No.3 page: 24 No.3 page: 24 Weight (kg) 9/13 95/135 Sound pressure level at 1 m according to ISO 3741 IRB: (db(a)) 63 66 IRBS: (db(a)) 54 58 IRB 85 4ST, IRB 85 4HT Installation dimensions in (mm) IRBS 85 4ST, IRBS 85 4HT Installation dimensions in (mm) 636 (676) 835 82 798 498 52 535 585 (625) 96 835 82 798 498 52 535 66 921 921 * The value in bracket ( ) is given for versions IRB 85 4HT. **The value in bracket ( ) is given for versions IRBS 85 4HT. IRB/IRBS 85 4ST Characteristics: IRB/IRBS 85 4HT Characteristics: ps (Pa) 8 7 ps (Pa) 12 11 1 6 9 5 8 7 6 3 5 2 3 1 2 1 1 2 3 5 6 7 8 2 6 8 1 12 IRB/IRBS 85 4ST Q (m 3 /h) IRB/IRBS 85 4HT Q (m 3 /h) IRB/IRBS 85 4ST IRB/IRBS 85 4HT Regulation - pg: 25-3 Stepless controller / / 5-step controller SRK 4 T page: 27 SRK 6 T page: 27 ON/OFF switch RS 6 P page: 3 RS 6 P page: 3 Motor protection switch ZSK 25 T(/H) page: 3 ZSK 25 T(/H) page: 3 Frequency controller FR 1,5 M page: 28 FR 2,4 T page: 28 17

Technical data Size 9 Nominal Rectangular Duct Dimensions 1x5 Type IRB 15 4ST / IRBS 15 4ST IRB 15 4HT / IRBS 15 4HT Duct width (mm) 1 Duct height (mm) 5 Max. Air flow: Q max (m³/h) 18 127/97 Temperature of transported Air and of Ambient ( C) -4 6-4 6 Power (W) 235 41/233 Voltage/Frequency (V/Hz) /5 /5 Current (A) 4.98 7.4/4.23 Speed/rpm (min -1 ) 1355 1285/88 Motor: Insulation class F F Motor: Type of protection IP 54 IP 54 Motor: Wiring diagram No.3 page: 24 No.4 page: 24 Weight (kg) 114/163 119/17 Sound pressure level at 1 m according to ISO 3741 IRB: (db(a)) 65 85/77 IRBS: (db(a)) 61 81/74 IRB 15 4ST, IRB 15 4HT Installation dimensions in (mm) IRBS 15 4ST, IRBS 15 4HT Installation dimensions in (mm) 676 135 12 998 625 (625) 116 135 12 998 498 52 535 498 52 535 66 126 126 IRB/IRBS 15 4ST Characteristics: IRB/IRBS 15 4HT Characteristics: ps (Pa) 12 11 ps [Pa] 1 1 12 9 8 1 7 6 8 5 6 3 2 1 2 2 6 8 1 12 2 6 8 1 12 1 16 18 IRB/IRBS 15 4ST Q (m 3 /h) IRB/IRBS 15 4HT ; connection Q [m 3 /h] IRB/IRBS 15 4HT ; Y connection Regulation - pg: 25-3 IRB/IRBS 15 4ST IRB/IRBS 15 4HT Stepless controller / / 5-step controller SRK 6 T page: 27 SRK 8 T page: 27 ON/OFF switch RS 6 P page: 3 RS 6 P page: 3 Motor protection switch ZSK 25 T(/H) page: 3 ZSK 25 T(/H) page: 3 Frequency controller FR 2,4 T page: 29 FR 4 T page: 29 18

Technical data Sound Attenuator DZ Sound attenuators installation dimensions in (mm) Sound attenuators are designed to attenuate fan noises. Based on numerous practical calculations it has been established that the said systems require maximum sound attenuation in the 25 Hz octave band. In other frequency bands, attenuation performances of the attenuators are also well adapted to ventilation systems acoustic requirements. The attenuators are equipped with splitter guide rails at inlet and outlet for low pressure losses. H1+2 H2 H3 B1+2 B2 B3 Sound attenuators dimensions in (mm) B1 B2 B3 H1 H2 H3 Length DZ 315 298 32 335 148 17 185 85 DZ 42 398 42 435 198 22 235 85 DZ 525 498 52 535 248 27 285 11 DZ 53 498 3 52 298 32 335 11 DZ 63 598 62 635 298 32 335 11 DZ 635 598 62 635 348 37 385 85 DZ 74 698 72 735 348 42 435 11 DZ 85 798 82 835 498 518 535 11 DZ 15 998 12 135 498 52 535 11 Sound attenuation capacity D (db) Frequency (Hz) 63 125 25 5 1 2 8 Sound absorbing rate (db(a)) IRB/IRBS version S IRB/IRBS version H IRB/IRBS version S Pressure drop (Δp) DZ 315 4 8 14 22 27 27 2 14 33 / 23 / DZ 42 2 6 1 16 18 13 11 8 15 22 5 15 DZ 525 5 9 14 23 29 28 2 15 24 29 16 26 DZ 53 5 9 14 23 29 28 3 15 23 3 14 27 DZ 63 5 1 19 28 34 33 23 17 36 / 57 / DZ 635 4 8 14 22 27 27 2 14 36 4 52 79 DZ 74 4 8 13 22 27 22 18 14 32 / 3 / DZ 85 3 7 13 2 23 16 14 1 27 36 17 31 DZ 15 3 7 13 2 23 16 14 1 32 44 21 57 Pressure drop in attenuator is given for 2/3 of maximum air flow volume. IRB/IRBS version H 19

Accessories Steel overpressure dampers JNŽ-4, JNŽ-4/3, JNŽ-6, JNŽ-6/3 They can be applied where the automatic break of the supply and exhaust air is required after IRB or IRBS fan has been turned off. Steel overpressure dampers JNŽ-4 and JNŽ-6 consist of supporting frame made of galvanized sheet steel, and horizontal swinging vanes of sheet aluminium. The horizontal vanes are inserted into plastic bearings, temperature resistant up to 8 C. Sealing stripe, attached on lower part of vanes reduces noise. Ordering key: page 31 JNŽ-4 JNŽ-6 9 12 9 12 H1+2/B1+2 H1+2/B1+2 H2/B2 H3/B3 H1+2/B1+2 H1+2/B1+2 H2/B2 H3/B3 JNŽ-4 JNŽ-6 JNŽ-4/3 Overpressure damper is fastened in built-in frame of angle steel. Designation: JNŽ-4/3 JNŽ-6/3 Overpressure damper is fastened in built-in frame of angle steel. Designation: JNŽ-6/3 Steel overpressure dampers dimensions in (mm) B1 B2 B3 H1 H2 H3 Pressure drop (Δp) IRB/IRBS version S JNŽ-4 315, JNŽ-4/3 315, JNŽ-6 315, JNŽ-6/3 315. 298 32 335 148 17 185 34 / JNŽ-4 42, JNŽ-4/3 42, JNŽ-6 42, JNŽ-6/3 42. 398 42 435 198 22 235 31 48 JNŽ-4 525, JNŽ-4/3 525, JNŽ-6 525, JNŽ-6/3 525. 498 52 535 248 27 285 34 45 JNŽ-4 53, JNŽ-4/3 53, JNŽ-6 53, JNŽ-6/3 53. 498 3 52 298 32 335 32 47 JNŽ-4 63, JNŽ-4/3 63, JNŽ-6 63, JNŽ-6/3 63. 598 62 635 298 32 335 51 / JNŽ-4 635, JNŽ-4/3 635, JNŽ-6 635, JNŽ-6/3 635. 598 62 635 348 37 385 42 53 JNŽ-4 74, JNŽ-4/3 74, JNŽ-6 74, JNŽ-6/3 74. 698 72 735 348 42 435 55 / JNŽ-4 85, JNŽ-4/3 85, JNŽ-6 85, JNŽ-6/3 85. 798 82 835 498 518 535 37 71 JNŽ-4 15, JNŽ-4/3 15, JNŽ-6 15, JNŽ-6/3 15. 998 12 135 498 52 535 57 93 Pressure drop is given for 2/3 of maximum air flow volume. IRB/IRBS version H 2

Accessories Volume control dampers RŽ-1 Volume control dampers are designed are designed for regulation of air flow and pressure in ventilating ducts and air conditioning devices. They are installed as independent device or combined with protection- or overpressure louvers. They are made of galvanised sheet steel. Volume control dampers consist of supporting frame and interconnected blades which are inserted into PVC bearings. Blades can be moved manually or by electric actuator. Ordering key: page 31 Manual control with handle mechanism for locking selected position Type RŽ-1/R Motor control with electric actuator control via electric actuator (15 Nm) 75 Power driven by electric actuator CODE BELIMO, JOVENTA, Regulation Torque Electrical power Voltage Hidria Catalogue B7 SM 24 J7 DA 1 B8 SM 23 J8 DA 2 B9 MOTOR (/) (Nm) (W) (V) SM 24 SR J9 DM 1.1 B1 SM 22 SR J1 DM 2.2 ON/OFF 15 1.8 DC 24 ON/OFF 15 1.6 AC 23 CONTINUOUS 15 3. DC 24 CONTINUOUS 15 3.6 AC 23 Wiring diagrams 45 214 12 3 End position control a - opened OPEN b - opened CLOSED 75 21

Accessories Installation types 18 18 Steel overpressure dampers dimensions in (mm) B1 B2 B3 H1 H2 H3 RŽ-1B 315 298 32 335 148 17 185 RŽ-1B 42 398 42 435 198 22 235 RŽ-1B 525 498 52 535 248 27 285 RŽ-1B 53 498 3 52 298 32 335 RŽ-1B 63 598 62 635 298 32 335 RŽ-1B 635 598 62 635 348 37 385 H1+2/B1+2 H2/B2 H3/B3 H1+2/B1+2 H2/B2 H3/B3 RŽ-1B 74 698 72 735 348 42 435 RŽ-1B 85 798 82 835 498 518 535 RŽ-1B 15 998 12 135 498 52 535 RŽ-1B, RŽ-1B/G RŽ-1B/3, RŽ-1B/G/3 Overpressure damper is fastened in builtin frame of angle steel. Designation: RŽ-1B/3, RŽ-1B/G/3 Pressure drop air flow direction p H/B Pressure drop Δp(Pa) RŽ-1B Blade angle 8 7 6 5 4 15 1 5 3 2 1 5 2 1 WA L (db (A )) 4 5 6 7 8 9 3 2 1 5.5 1 2 3 4 5 1 15 Air velocity (m/s) a ( ) Blade inclination Δp (Pa) Pressure drop L WA (db (A)) Sound power level 22

Accessories Protection Grill ZM B1 B3+2 H1 H3+2 Dimensions in (mm) B1 B3 H1 H3 ZM 315 298 335 148 185 ZM 42 398 435 198 235 ZM 525 498 535 248 285 ZM 53 498 52 298 335 ZM 63 598 635 298 335 ZM 635 598 635 348 385 ZM 74 698 735 348 435 ZM 85 798 835 498 535 ZM 15 998 135 498 535 Flexible Connector FS B1+2 B2 B3 H1+2 H2 H3 Dimenzije (mm) B1 B2 B3 H1 H2 H3 FS 315 298 32 335 148 17 185 FS 42 398 42 435 198 22 235 FS 525 498 52 535 248 27 285 FS 53 498 3 52 298 32 335 FS 63 598 62 635 298 32 335 FS 635 598 62 635 348 37 385 FS 74 698 72 735 348 42 435 FS 85 798 82 835 498 52 535 FS 15 998 12 135 498 52 535 23

Accessories Wiring diagrams for mono phase IRB/IRBS fans without speed controllers Wiring diagram 1 IRB/IRBS 315 2SM, IRB/IRBS 42 2SM, IRB/IRBS 42 2HM, IRB/IRBS 525 4SM, IRB/IRBS 525 2HM, IRB/IRBS 53 6SM, IRB/IRBS 53 4HM, IRB/IRBS 63 4SM, IRB/IRBS 635 4SM and IRB/IRBS 635 4HM: N L 1 2 3 4 IRB/IRBS C 1. blue 2. black 3. white 4. brown green/yellow Wiring diagrams for three phase IRB/IRBS fans without speed controllers Wiring diagram 2 IRB/IRBS 315 2ST, IRB/IRBS 42 2ST, IRB/IRBS 42 2HT, IRB/IRBS 53 4HT: L1 1 L2 2 L3 3 TK 4 IRB/IRBS TK 5 1. black 2. blue 3. brown 4. grey: thermal overload protection contacts of the fan 5. grey: thermal overload protection contacts of the fan green/yellow Wiring diagram 3 IRB/IRBS 525 4ST, IRB/IRBS 63 4ST, IRB/IRBS 635 4ST, IRB/IRBS 635 4HT, IRB/IRBS 74 4ST, IRB/IRBS 85 4ST, IRB/IRBS 85 4HT, IRB/IRBS 15 4ST: L1 L2 L3 TK 1 3 5 2 4 6 7 IRB/IRBS Y connection only! TK 8 1. black 2. yellow 3. blue 4. green 5. brown 6. white 7. grey: thermal overload protection contacts of the fan 8. grey: thermal overload protection contacts of the fan green/yellow Wiring diagram 4 IRB/IRBS 525 2HT, IRB/IRBS 15 4HT: L1 L2 L3 TK TK 1 2 3 4 5 6 7 8 IRB/IRBS Y connection L1 L2 L3 TK TK 1 2 3 4 5 6 7 8 IRB/IRBS Δ connection 1. U1 black 2. W2 yellow 3. V1 blue 4. U2 green 5. W1 brown 6. V2 white 7. grey: thermal overload protection contacts of the fan 8. grey: thermal overload protection contacts of the fan green/yellow 24

Wiring diagrams and regulation Stepless speed controllers: BR 1 M, BR 1,5 M, BR 4 M Manual voltage controllers for mono phase fans (23 V, 5 Hz) for speed and air flow control. The controllers regulate output voltage from 14 to 23 V. Suitable for inset as well as for surface mounting. The splash-proved housing allows use in demanding (moist) environments like kitchens, bathrooms etc. Inset mounting gives splash proof IP 44, surface mounting with the mounting case gives splash proof IP 54. Several fans can be controlled by BR 1 M, BR 1,5 M or BR 4 M parallel as long as the current limit is not exceeded. They can be used only with motors with built-in overheating protection. BR 1 M BR 1,5 M BR 2,5 M Current rating (A) 1, 1,5 4 Current fuse (A) F 1.25 A H F 2. A H F 5. A H 2` Supply (V/Hz) 23/5 23/5 23/5 Extra output (V/Hz) 23/5 23/5 23/5 Weight (kg),25,29,36 N N infinitely variable speed control from minimum to maximum built-in temperature cut-off fuse spare fuse included minimum speed by trimmer inset mounting: IP44, surface mounting: IP54 plastic enclosure, ABS, RAL 91 maximum ambient temperature: 35 C L N 1` M 23V Stepless mono phase controller with TK: BRK 3 M BRK 3 M is electronic speed controller, which control the speed of mono phase fans by varying the supplied voltage. Controller starts the motor at the highest speed for about 6-7 seconds, after this, the motor speed will descend to the required speed, following the position of the potentiometer. Its IP 54 case allows the use in demanding environments. BRK 3 M controller fitted out with TK provides an excellent protection for motors with thermal cut-out contacts. They switch off power supply to the motor when thermal contact in the motor windings is tripped. BRK 3 M has NO automatic restart! After elimination of the cause of the overheating, the fan can be restarted by putting the switch in OFF-position for a few moments. This alarm situation is indicated by the red telltale and can be branched off through the terminals N-A. BRK 3 M also offers non regulated 23 V/5 Hz output. 1` non regulated output 23 V 2` fuse box with spare fuse BRK 3 M BRK 3 M Current rating (A) 3, Current fuse (A) F 5, A H Supply (V/Hz) 23/5 Extra output (V/Hz) 23/5 variable speed control from maximum to minimum minimum setting by trimmer motor protection by connection thermal overheating contacts of the motor ON/OFF switch plastic enclosure, ABS, RAL 92 IP 54 minimum speed by trimmer not regulated 23 V/5 Hz output maximum ambient temperature: 35 C 25

Wiring diagrams and regulation 5 step mono phase controller: SR 1,5 M and SR 3,5 M SR 1,5 M and SR 3,5 M are a mono phase transformers with voltage output in five fixed steps (11 14 17 19 23 V). They are applicable with fans for 5-step air flow control. The fan speed can be chosen manually with control knob on the front panel. They can regulate two or more fans parallel as long as the current limit is not exceeded. They can be used only with motors with built-in overheating protection. SR 1,5 M and SR 3,5 M regulators also have not regulated 23 V/5 Hz output. SR 1,5 SR 3,5 M Maximum Current (A) 1.5 3.5 Current fuse (A) 2. 5 Supply (V/Hz) 23/5 23/5 Extra output (V/Hz) 23/5 23/5 Weight (kg) 3.4 4.7 plastic enclosure IP54 5 positions switch with OFF position indicator lamp current fuse ready mounted cable glands maximum ambient temperature: 35 C L N F L N Pe L1 N Pe N U 23 Vac output F Fuse N L1: 23 V unregulated output M 23V 5 step mono phase controller with TK: SRK 3,5 M SRK 3,5 M is a mono phase transformer with voltage output in five fixed steps (11 14 17 19 23 V). It is applicable with fans for 5-step air flow control. The fan speed can be chosen manually with control knob on the front panel. It can regulate two or more fans parallel as long as the current limit is not exceeded. It is fitted out with TK contacts for motor overload protection. Single phase motors which have thermal overload protector (TOP) brought out must be connected to the their thermo contacts. They switch off power supply to the motor when thermal contact in the motor windings is tripped. It has NO automatic restart! The fan can be manually restarted by turning the switch into the position for a few seconds after the fault is eliminated and the temperature of motor winding is dropt down. SRK 3,5 M speed controller is equipped with not regulated 23 V/5 Hz output. SRK 3,5 M Maximum Current (A) 3,5 Current fuse (A) 5, Supply (V/Hz) 23/5 Extra output (V/Hz) 23/5 Weight (kg) 5, plastic enclosure IP54 5 positions switch with OFF position motor protection by connecting thermal overheating contacts of the motor indicator lamp current fuse ready mounted cable glands maximum ambient temperature: 35 C L N F L N Pe N U Pe N L1 TK TK M 23V izhod: 23 V / 5Hz F Fuse N L1: 23 V unregulated output TK motor overload protection contacts for the fan s motor 26

Wiring diagrams and regulation 5 step three phase controllers with TK: SRK 1,5 T, SRK 4 T, SRK 6 T, SRK 8 T They are a three phase transformers with voltage output in five fixed steps (13 18 23 3 V). They are applicable with fans for 5-step speed and air flow control. The fan speed can be chosen manually with control knob on the front panel. They can regulate two or more fans parallel as long as the current limit is not exceeded. Their (TK) contacts for thermal motor protection switches off power supply to the motor when thermal contact in the motor windings is tripped. They have NO automatic restart! The fan can be manually restarted by turning the switch into the position for a few seconds after the fault is eliminated and the temperature of motor winding is dropt down. Not regulated 23 V/5 Hz outputs offer possibility to connect any other mono phase accessories. SRK 1,5 T SRK 4 T SRK 6 T SRK 8 T Maximum Current (A) 1.5 4. 6. 8. Supply (V/Hz) /5 /5 /5 /5 Extra output (V/Hz) 23/5 23/5 23/5 23/5 Weight (kg) 12.2 18.5 24.6 28. sheet steel IP54 5 positions switch with OFF position indicator lamp motor protection by connection thermal overheating contacts of the motor ready mounted cable glands maximum ambient temperature: 35 C Pe R S T N Pe U V W Pe N L1 TK TK Pe R S T N Pe U V W Pe N L1 TK TK L1 L2 L3 N M 3~ V 23 Vac output L1 L2 L3 N M 3~ V 23 Vac output For fans without TK Pe N L1: 23 V unregulated output TK motor overload protection contacts for the fan s motor must be wired together! For fans with TK Pe N L1: 23 V unregulated output TK motor overload protection contacts for the fan s motor 27

Wiring diagrams and regulation Frequency controllers with mono phase inlets and three phase outlets: FR,37 M, FR,75 M, FR 1,5 M FR,37 M, FR,75 M, FR 1,5 M are stepless frequency controllers with mono phase power supply. They provide speed and air flow control by adjusting output frequency for three phase motors. They are full of useful features including pre-programmed applications all designed to simplify set-up, installation and operation. They can be controlled locally using keys on front panel or can be controlled by remote mode. Several fans can be controlled by FR,37 M, FR,75 M, FR 1,5 M parallel as long as the drive power limit is not exceeded! They also have TK contacts with no automatic restart. They allow setting the maximal current draw with no automatic restart when application of use needs overload protection and the fan s motor does not have TK. Frequency controllers allow to set maximal current draw. When the limit of the maximum current is reached, controller switch off power supply to the fan with no automatic restart. Maximum Power output Power Supply (V/Hz) 22-24V ± 1% 5-6Hz ± 5% Ambient Temperature FR,37 M FR,75 M FR 1,5 M (W).37.75 1.5 22-24V ± 1% 5-6Hz ± 5% 22-24V ± 1% 5-6Hz ± 5% ( C) 4 C 4 C 4 C Weight (kg).85.85 1. compact housing with LCD display IP 2 local or Remote mode operation support for RS485 and Modbus RTU comms protocols SELV control terminals (Safe Extra Low Volts) intelligent monitoring strategy to avoid nuisance tripping in-built protection of the unit against overloads, excessive voltages, phase-to-phase and phase-to-earth short circuits an internal RFI filter is fitted as standard motor protection by connection thermal overheating contacts of the motor max. current draw can be set no automatic restart when motor is overloaded and cooled down quiet operation RL1 TH1 A B A B Pe L1 L2/N M1/U M2/V M3/W Pe RL1 TH1 A B A B Pe L1 L2/N M1/U M2/V M3/W Pe L N TK TK M 3~ V L N M 3~ V For fans with TK TH1 (A) motor overload protection contacts for the fan s motor TH1 (B) motor overload protection contacts for the fan s motor For fans without TK TH1 (A) and TH1 (B) motor overload protection contacts for the fan s motor must be wired together! 28

Wiring diagrams and regulation Frequency controllers with three phase inlets and three phase outlets: FR 2,4 T, FR 4 T FR 2,4 T, FR 4 T are stepless frequency controllers with three phase supply. They provide speed and air flow control by adjusting output frequency for three phase motors. They are full of useful features including pre-programmed applications all designed to simplify set-up, installation and operation. They can be controlled locally using keys on front panel or can be controlled by remote mode. Several fans can be controlled by FR 2,4 T or FR 4 T parallel as long as the drive power limit is not exceeded! They also have TK contacts with no automatic restart. They allow setting the maximal current draw with no automatic restart when application of use needs overload protection and the fan s motor does not have TK. Frequency controllers allow to set maximal current draw. When the limit of the maximum current is reached, controller switch off power supply to the fan with no automatic restart. FR 2,4 T Maximum Power output Power Supply (V/Hz) 38-46V ± 1% 5-6Hz ± 5% FR 4 T (W) 2.4 4. 38-56V ± 1% 5-6Hz ± 5% Ambient Temperature ( C) 4 C 4 C Weight (kg) 2.7 2.7 compact housing with LCD display IP 2 local or Remote mode operation support for RS485 and Modbus RTU comms protocols SELV control terminals (Safe Extra Low Volts) intelligent monitoring strategy to avoid nuisance tripping in-built protection of the unit against overloads, excessive voltages, phase-to-phase and phase-to-earth short circuits an internal RFI filter is fitted as standard an internal dynamic brake switch for connection to an external resistor motor protection by connection thermal overheating contacts of the motor max. current draw can be set no automatic restart when motor is overloaded and cooled down quiet operation RL1 TH1 A B A B Pe L1 L2 L3 DC- DBR DC+ M1/U M2/V M3/W Pe RL1 TH1 A B A B Pe L1 L2 L3 DC- DBR DC+ M1/U M2/V M3/W Pe L1 L2 L3 M 3~ V L1 L2 L3 M 3~ V For fans with TK TH1 (A) motor overload protection contacts for the fan s motor TH1 (B) motor overload protection contacts for the fan s motor For fans with TK TH1 (A) and TH1 (B) motor overload protection contacts for the fan s motor must be wired together! 29

Wiring diagrams and regulation Motor protection switches with TK: ZSK 25 T (/H) Motor protection switch ZSK 125 T with thermal contact (TK) switches off power supply to the motor when thermal contact in the motor windings is tripped. It has NO automatic restart! The fan can be manually restarted by pressing the black button when the fault is eliminated and the temperature of the motor is dropped down. It can be rail mounted according to EN 6 715. Motor protection switch can be used in combination with 5-step transformers. Caution: The screw on control panel must be on position 5! Without housing ZSK 25 T With housing ZSK 25 T/H Maximum Current (A) 25. Supply (V/Hz) /5 Weight (kg).465 (.615) plastic enclosure for wall mounted IP 55 rail mounted according to EN 6 715 motor protection by connection thermal overheating contacts of the motor ZSK 25 T (/H) L1 L2 L3 max. 8 A 1 3 5 TK TK 2 4 6 TK TK U V W M 3~ V TK motor overload protection contacts for the fan s motor Revision ON/OFF switches: RS 3 P, RS 5 P, RS 6 P, RS 9 P Type Number of pole Imax for each lead RS 3 P 3 1A RS 5 P 5 1A RS 6 P 6 1A RS 9 P 9 1A Application ON/OFF function for mono phase fans without TK ON/OFF function for mono phase fans with TK ON/OFF function when only Δ or Y wiring of motor is allowed ON/OFF function when Δ or Y can be chosen with Δ Y switch 3

Ordering key Ordering key: IRB 315 2SM/accessories Current M mono phase motor T 3-phase motor Version S standard power at nominal dimension H high power at nominal dimension Number of poles 2-2 poles 4-4 poles 6-6 poles Nominal height 15 (15 mm) 2 (2 mm) 25 (25 mm) 3 (3 mm) 35 (35 mm) 4 ( mm) 5 (5 mm) Nominal width 3 (3 mm) 4 ( mm) 5 (5 mm) 6 (6 mm) 7 (7 mm) 8 (8 mm) 1 (1 mm) IRBS sound attenuated housing IRB basic housing Ordering key: SRK 2,5 M FR 1,5 M RS 3 P Current M mono phase inlet/outlet T three phase inlet/outlet Maximal allowed current at outlet (A) Motor overload protection K inlet for thermal contact TK Type of regulation SR 5-step transformer BR stepless thyristor regulation ZS motor protection switch Current M mono phase inlet three phase outlet T three phase inlet three phase outlet Maximal allowed power at outlet (kw) Type of regulation FR frequency controller Number of pole 3 P - 3 pole 5 P - 3 pole 6 P - 3 pole 9 P - 3 pole Revision ON/OFF switch Ordering key: Ordering key: RŽ-1 315/G/3/R JNŽ-4 315 Regulation of volume control dampers /R manual control /B power driven but without actuator /B7 or /J7 actuator SM 24 or DA 1 /B8 or /J8 actuator SM 23 or DA 2 /B9 or /J9 actuator SM 24 SR (continuous regulation) or DM 1.1 /B1 or /J1 actuator SM 22 SR (continuous regulation) or DM 2.2 3 installation frame / without installation frame G heaters built in blades Nominal height 15 (15 mm) 2 (2 mm) 25 (25 mm) 3 (3 mm) 35 (35 mm) 4 ( mm) 5 (5 mm) Nominal width 3 (3 mm) 4 ( mm) 5 (5 mm) 6 (6 mm) 7 (7 mm) 8 (8 mm) 1 (1 mm) RŽ-1 Volume control damper Nominal height 15 (15 mm) 2 (2 mm) 25 (25 mm) 3 (3 mm) 35 (35 mm) 4 ( mm) 5 (5 mm) Nominal width 3 (3 mm) 4 ( mm) 5 (5 mm) 6 (6 mm) 7 (7 mm) 8 (8 mm) 1 (1 mm) JNŽ-4, JNŽ-6 Steel overpressure damper without installation frame JNŽ-4/3, JNŽ-6/3 Steel overpressure damper with installation frame ZM Protection grill FS Fleksible connector DZ Sound attenuator 31

Installation and maintenance Very important information IRB/IRBS fan can be installed in outer wall only from inside in opening made before installing the fan. IRB/IRBS must be protected against atmosphere by steel overpressure dampers JNŽ-4, JNŽ-4/3, JNŽ-6 in JNŽ-6/3 or by steel overpressure dampers with the same characteristics. It can be installed in outer wall only from inside when it is completely protected against atmosphere (direct sun, rain, snow, hail etc.) and against consequences of human activity (radiation, flammable and explosive substances and vapours). IRB/IRBS fan must be used with protection grill ZM according to EN 294 if operates for direct air supply or for direct air exhaust. Several fans can be controlled by regulators parallel as long as the current or power limit of all fans together is not exceeded. Current and power limits for all regulators are given in this catalogue. IRB/IRBS with thermal connection leads (TK) must be connected to the external overload protection (motor protection switch ZSK 25 T or regulator with inlet for TK). Only regulators in this catalogue can be used for speed regulation. Also regulators with the same characteristics as original can be used. Pay attention on the device between transportation, storing and handling. If anybody find any sign of damage, deformation, malfunction or a missing part, do not install this device and claim it at its seller The fan must be stored in original package in dry place protected against rain or snow, direct sunshine and dust. IRB and IRBS fan must be transported carefully. Do not lift fan by the swing out door, impeller, motor, inlet cone, connection box and connecting wire. IRB and IRBS fan can be used indoor only. IRB/IRBS can not be immured into a wall or fixed with any kind of polyurethane foams. IRB and IRBS fan must not be used before they are installed into the duct systems or before its moving parts are protected according to EN 294. Device for switching off all pole of IRB/IRBS must be installed into the installation in accordance with regulations and standards applicable in the country of use. Duct fan IRB/IRBS must be completely switched off from power supply with all it s pole before and during the checking, cleaning, service, maintenance, opening the connection box, removal connection box, opening swing out door, changing connection wires etc. IRB and IRBS must not be used for duct systems with explosive gases and they must not be installed in explosive atmosphere. The maximum ambient temperature must not be higher then maximum temperature of transported air. IRB and IRBS fans can be used up to the maximum temperature of the transported air, which is determinated for each IRB/IRBS in this catalogue. After stop using the product it is possible to demount and recycle. The person who executes the installation is responsible for correct and safe installation of this device. IRB/IRBS can be moved from its original package only before montage. Please recycle the package after removing fans from original packaged in accordance with regulations and standards applicable in the country of use. IRB/IRBS must be installed into the duct system in right direction of the air stream in duct (see the arrow on housing). The connection flanges can be used for installation into duct system. Position of the fan in duct work must allow swinging out the door to provide free and safe service access. Do not forget any tool, screws or any other thing in the fan after installation. Too long screws can prevent rotation of the impeller and they can damage the motor or rotor. IRB/IRBS must be stably mounted into the duct work. Check up if all electrical connections are completely unplugged from power supply and impeller has stopped running than rotate the impeller by hand to check that it rotates freely. The electrical installation of the fan and other electrical accessories must be connected according to wiring diagrams in this catalogue or in Installing, operating, maintenance and removal instructions and in accordance with regulations and standards applicable in the country of use. Electrical connection can be done only by a person with an adequate electrical qualification who is accredited for this work and is informed about this manual. Wires for power supply must be fastened with cable gland which is placed on connection box. Cable gland must fasten the wire so much that the cable can not displace from its position under a force 1N and a torque,35nm. Speed regulator needs the cable with the same characteristics like an IRB/IRBS for power supply when only one fan is controlled. Speed regulator must have wire in accordance with regulations and standards applicable in the country of use when it regulates two or more fans parallel. Three phase fan must be wired only to connection (Δ or Y) which is allowed in the wiring scheme, any other connection is prohibited because it can damage the motor! Connection box must be closed and screwed carefully after wiring the IRB/IRBS. All regulators from this catalogue must not be installed directly in the sunshine or at any source of heat. They can be used indoor only. Before cleaning, service, maintenance and removal make absolutely sure that: fan is completely disconnected from the power supply and prevent any risk of the fan start rotating; the impeller has stopped rotating, surface of the fan, inside of the fan, impeller and motor are not too hot to prevent the risk of burning. The fan must be checked regularly and cleaned when necessary or according to national standards and directives. It must be checked and cleaned at least once per year to prevent imbalance and other damage inside the fan. Motor, impeller and inside must be cleaned carefully to avoid damage to the fan, motor and impeller. High pressure cleaner must not be used for inside and outside cleaning. Clean motor only when is necessary with non electrolyte or explosive detergents. The right for technical changes reserved. 32