Monocellular centrifugal electro-pumps

Similar documents
PV4 - PIV6. Submersible multistage centrifugal electro-pumps. Installation and maintenance. This manual is to be given to the end user

3946 en / a. This manual is to be given to. the end user. HPM x44. A.C. motor. Installation and maintenance

COMPABLOC. Cb Cb Cb 1504 Installation and maintenance. These instructions should be given to the end user GN

Operating Instructions

230V 60Hz LINE FUSES AM CLASS:

VADA - V60-J PRODUCT OVERVIEW CONSTRUCTION MOTOR USAGE LIMITATIONS WARRANTY

VEM motors Thurm GmbH

VADA - V75-S PRODUCT OVERVIEW CONSTRUCTION USAGE LIMITATIONS MOTOR WARRANTY

OPERATION & MAINTENANCE INSTRUCTIONS

Installation guide. Mb 3101, Mb Drive systems. Part number: 2910 en / p

VERTICAL MULTI-STAGES CENTRIFUGAL PUMPS

Heavy duty slurry pumps

VERTICAL MULTI-STAGE CENTRIFUGAL PUMPS

DulcoFlex Peristaltic Pump: DFB13B

Heavy duty slurry pumps

SUBMERSIBLE DIRTY WATER PUMP

HOT WASHER MODEL NO: KING 125 OPERATION & MAINTENANCE INSTRUCTIONS PART NO: LS1009

Operating and Installation Instructions Diaphragm Vacuum Pumps and Compressors

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

Installation and Operating Instructions Electric Vibrators HV/VFL Series

SELF PRIMING CHEMICAL SERVICE PUMPS

230V DIESEL FUEL TRANSFER PUMP MODEL NO: DFT230

INSTALLATION AND OPERATING MANUAL. TM Series Multi-stage Pump

OPERATION & MAINTENANCE INSTRUCTIONS

INSTRUCTION MANUAL FOR THE CLINICAL 50 CENTRIFUGE

77014 / Automatic Users Manual. Carefully read this entire Instruction Manual before using this product

ASYNCHRONOUS MOTORS THREE-PHASE MOTORS SINGLE-PHASE MOTORS BRAKE MOTORS INSTRUCCIONES DE SERVICIO OPERATING INSTRUCTIONS 2016

THREE PHASE AND SINGLE PHASE ASYNCHRONOUS ELECTRIC MOTORS OPERATION AND MAINTENANCE BOOKLET Rev

Matala. VersiFlow Series. Instruction and Maintenance Manual

SERIES PC INSTRUCTION AND OPERATION MANUAL

Single Stage Rotary Vane Vacuum Pump Installation and Operation Manual RX-40 RX-63 RX-100

INSTRUCTION MANUAL INDUSTRIAL PERISTALTIC PUMPS MODEL RBT-70

Single Stage Rotary Vane Vacuum Pump Installation and Operation Manual RX-10 RX-21 RX-25

Compact System NRGS 11-2 NRGS Original Installation Instructions English

Medium and high pressure pumps

6L Oil-less Air Compressor 53103

NEOTECHA NTB-NTC BALL VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS

250W PUDDLE PUMP WITH AUTO SENSOR MODEL NO: PSP105

BAH series Use and Maintenance Manual

VT Oil-Free Range Operators Handbook

TPHK Series Immersible Pump

These installation and maintenance instructions must be read in full and completely understood before the installation!

Instruction for RBP250-3 and RBP300-3

LEAD ACID BATTERY CHARGER

Table 6-1. Problems and solutions with pump operations. No Fluid Delivery

MC3000 OPERATING AND CALIBRATION INSTRUCTIONS

Owners Manual: - Pumps

This manual is to be given to. the end user P.M.G. / ALTERNATORS. Installation and maintenance

User Manual Rittal PMC UPS 6kVA

These operating instructions apply for: NCX 380 NCZ 300 NCX 480 NCZ 370 NCX 580 L NCZ 480 NCX 660 K NCZ 560 NCZ 660 NCZ 800

Centrifugal Pumps (Part Nos. PS2SS PS73SS) PS2SS

US - UP2/OIL 12V US - UP2/OIL 24V

Installation and Operational Instructions for ROBATIC -clutch Type and Type Sizes 3 9

Professional Séries. Professional Séries. Model T03828 SUBMERSIBLE SUMP DUPLEX SYSTEM SUBMERSIBLE SUMP DUPLEX SYSTEM. 1/3HP 2400 GPH Head of 20 (6 m)

UNPACKING SAFETY GUIDELINES GENERAL SAFETY INFORMATION. Operating Instructions & Maintenance Manual

ESE Series Cast Iron Sewage Pumps

GD series Submersible Grinder Pump

This manual presents installation, servicing, troubleshooting, and maintenance for M PUMPS CM MAG-M SERIES Information that may be required regarding

Crispin Valves Operating Guide. Crispin

AIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST

Service Handbook HD /97

SUBMERSIBLE PUMP HSE RANGE

Installation Vertical Pump: Installation 'CM' and 'CDM' Style: Operation:

SUBMERSIBLE PUMP HSE RANGE

PRECISION UK Ltd DUPLEX AGSS PLANT

END SUCTION CENTRIFUGAL PUMPS

Internet For latest information, PDF catalogs and operation manuals

Zebra ZVac Vacuum System Operator s Manual

Hydraulic Immediate Need Power Pack

GeyserMax-Flow Series

APT14 Automatic Pump Trap Installation and Maintenance Instructions

KEYSTONE SERIES 320 BUTTERFLY VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS

Clamping and drive module

Thank you for selecting the GD submersible grinder pump.

INSTRUCTION MANUAL. CAT Place Table Top Centrifuge

Instruction manual. Installation requirements. Power Take-Off. Pump mounting: Spline shaft DIN 5462 / ISO 14. Mounting flange ISO 7653-D.

OWNERS MANUAL ECODIVER

Model and Series 115 VAC INDUSTRIAL DIAPHRAGM PUMPS. PumpAgents.com - buy pumps and parts online INDUSTRIAL DIAPHRAGM PUMPS

Instruction and Maintenance Manual

Horizontal And Vertical Centrifugal Pumps

PACKING, HANDLING, TRANSPORTING AND STORING MOTORS

Operating manual Separator

INSTALLATION, OPERATION AND MAINTENANCE MANUAL (IOM)

X-JET (Counter current system)

Installation, Operating, Maintenance and Safety Instructions for CW332 Pressurised water system for boats 24 volt d.c.

Keystone Figure 85/86 Check valves Installation and Maintenance Instructions

Series Base mounted pump. Installation and operating instructions

SUBMERSIBLE WATER PUMPS

NDR Series Rotor Pack

F O R M. Installation and Maintenance Manual for FCR Equipped Motors and Gearmotors. 9055E Revised October 2015

Installation, Operation and Maintenance Manual Stancor SSD & SL Series Pumps

M Series Condensate Recovery Unit

CFT24 &CFT230 PART NOS:

Eurovacuum Installations and Operating manual EVD Series Vacuum pumps Models: EVD-6 to EVD-90. Double Stage Oil Lubricated Rotary Vane Vacuum Pump

Instruction and Maintenance Manual

H.S. MACHINERY RING COMPRESSORS

R231 A.V.R. Installation and maintenance R 231. This manual is to be given to. the end user. Armature 6- Field. Slow-blow fuse 250V 8 A

Maintenance Guide COMPABLOC Reference: 5060 en / c

Quick guide. Plug-in fans GPPM with FC101_106 August 2014

Variable Vane Pump, Direct Controlled PV7...A Series 1X / 2X

Transcription:

Réf. 2100 - O33 / a - 5.95 This manual must be given to the end user LS Monocellular centrifugal electro-pumps Installation and maintenance

1 - GENERAL The LS range of monobloc electro-pump units should be installed in accordance with the instructions in this manual. They must not be used in duty conditions other than those indicated in this document. Should these instructions not be adhered to, or the equipment be modified in any way without LEROY- SOMER's approval, the guarantee is immediately rendered null and void. LEROY-SOMER cannot be held responsible if the instructions contained in this document have not been followed. This manual does not take account of existing safety recommendations and regulations which may be in force where the equipment is installed. It is the responsibility of the user to ensure that these are applied and adhered to. 3.2 - Electrical characteristics Mot 3 ~ DL 2,2 / 2 N 343566DG001 kg IP 55 cl F C 40 S S 1 V Hz min -1 kw cos ϕ A Δ 220 50 2845 2.2 0.87 8.50 Y 380 2845 0.87 4.90 Δ 230 50 2860 2.2 0.82 8.70 Y 400 2860 0.82 5.00 Δ 240 50 2870 2.2 0.77 9.00 Y 415 2870 0.77 5.20 Rated current Power factor Rated power Type of motor Electro-pump serial number Speed of rotation Frequency 2 - USE The LS range of centrifugal, mono-cellular, monobloc electro-pump units is designed to carry water, and any other clear liquid which is non-contaminated, nonabrasive, non-corrosive, non-explosive and compatible with the material of which the pump is made. For any other pumped liquid : please consult LEROY- SOMER. Maximum content of solid particles in suspension: 50 g/m 3 Maximum temperature of pumped liquid: 110 C Minimum temperature of pumped liquid: - 10 C Maximum ambient temperature: 40 C Maximum duty pressure of the pump (on lift) : 16 bar Maximum pressure at intake : 10 bar Density of pumped liquid: 1 Viscosity of pumped liquid: 1 mm 2 /s Supply voltage Connection 4 - HANDLING Electro-pump units should be handled and unpacked with care. We recommend the unit is handled as shown in the sketch below. 3 - CHARACTERISTICS The dimensions of the pump body, intake and outlet openings and foot mountings conform to DIN 24255 and NFE 44111 standards. Each electro-pump unit has two identification plates; one which defines the hydraulics, and the other the motor. 3.1 - Hydraulic characteristics The hydraulic characteristics are guaranteed to conform to international standard ISO 2548 class C for massproduced pumps. CC typ LS 50-32 - 160/2,2-2 Q m3/ h 21 Hm 11 Type of electro-pump Total manometric lift in metres Rated flow in m 3 /h 5 - STORAGE In good storage conditions, our electro-pump units are not at risk of deterioration. They should be stored in dry, enclosed areas, away from inclement weather conditions, dust, vibration, and shocks. If there is a risk of freezing temperatures in the storage area, ensure that the pump has been drained. Do not place units leaning against the motor fan cover. Before commissioning or re-commissioning an electropump unit, always read the instructions contained in this manual, and follow them carefully. 3

6 - INSTALLATION Electro-pump units must be installed by personnel suitably qualified to undertake this type of work. Install the unit as close as possible to the water supply in an easily accessible location. The suction and delivery pipes must be fitted in such a way that they do not create any mechanical force on the body of the pump. We recommend fixing the unit on a concrete pillar. If necessary, wedge it in position. In some cases, the motor flange comes into contact with the mating surface before the foot mountings. It must then be wedged beneath both the pump and the motor. The unit can be installed in a number of positions, but not with the motor under the pump (see sketch below). If the pump is working on load, the bottom valve is replaced by an isolation valve on the pump. If the diameter of the suction pipe is greater than the nominal diameter of the pump intake, use a reducer to connect them. Suction On load Well immersed 1 - INLET FILTER 2 - VALVE 3 - NON-RETURN VALVE 4 - PUMP 6.2 - Delivery pipe The diameter of this pipe should be chosen after first carefully calculating the installation pressure losses. Place a flow-control valve on the pipe and a non-return valve upstream of this valve. The unit should be installed in a well-ventilated location, sheltered from inclement weather conditions. 6.1 - Suction pipe This pipe must be large enough in diameter to avoid significant loss of pressure. It must be absolutely watertight, capable of resisting depressurization and should not have any high points. A watertight inlet filter valve must be fitted at the bottom end. An incline of 2% rising towards the pump is advisable to ensure that no liquid remains in the pipe. The inlet filter should not allow the passage of particles larger than 2 mm. It should be placed at a depth below the lowest water level so that outside air cannot be siphoned in, and kept away from the walls and the bottom of the well. 6.3 - Before commissioning - Make sure that the electro-pump rotates freely without sticking. - Fill the suction pipe and the pump, taking care not to let any air get in, by unscrewing the filler cap : part no. 90 - Check that the bottom inlet filter valve is watertight and the water level has not dropped near to the opening : part no. 90 - Screw the filler cap back on : part no. 90 7 - ELECTRICAL CONNECTION Electrical connection must be performed by a qualified electrician taking any existing regulations into account. If the electro-pump unit has been stored in damp conditions, check the motor insulation resistance before commencing any electrical connection. This must be a minimum of 10 megohms in cold state at 500 volts for a period of 60 seconds. 7.1 - Power supply Make sure that the supply voltage indicated on the motor identification plate corresponds to the actual electricity supply. Check that the diameter of the meter incoming and outgoing conductors is adequate to supply the unit with the correct power. 7.2 - Connections The motors are delivered with the following connections : - Δ 230 / Y 400 V up to 2.2 kw inclusive at 50Hz - Δ 400 V from 3 kw at 50 Hz 4

Make absolutely sure that this type of connection corresponds to the mains supply voltage. It must be connected as shown in the diagram below, which appears on the terminal box lid. W2 U1 U2 V1 L1 L2 L3 Δ connection V2 W1 W2 U2 V2 Y connection 7.3 - Protection Connect to earth as required by current regulations. In order to benefit from the guarantee, it is essential to protect the motor electrically by placing a thermal magnetic circuit-breaker between the isolator and the motor. This circuit-breaker may also be fused. Before starting up the unit, the circuit-breaker should be set provisionally to the correct current (shown on the identification plate) for the corresponding mains supply voltage. Definitive setting should be performed as instructed in paragraph 8. So as not to subject the unit to excessive temperature rises, a maximum number of starts per hour as shown below should not be exceeded. Motor Max number of power starts / hour 1.2 kw 35 1.5 to 3.3 kw 30 4 to 6.5 kw 20 8.2 to 16 kw 15 > 16 kw 10 This number of starts should be spread over the hour. 8 - STARTING THE PUMP UNIT An electro-pump unit must never be run on empty. This is very important to ensure the mechanical seal remains watertight. - Open the suction valve (for an on load pump). - Fill the pump and suction pipe with the liquid to be pumped. - Close the outlet flow-control valve. - Make sure that the the direction of rotation is that indicated by the arrow on the unit (flange or fan cover) by running the motor for a couple of turns. - If the direction of rotation is reversed, modify the connection to the motor terminal block by reversing 2 power supply wires. - After starting, once the motor has reached its operating speed, make sure that the back pressure is normal, and not subject to significant fluctuations. If this is not the case, stop the pump and re-fill it. If the problem persists, U1 V1 W1 L1 L2 L3 look for air getting into the suction pipe. - If the motor is not running fast enough, check the connection. - Gradually open the pressure valve until the desired flow or pressure if achieved. - Take care not to leave the pressure valve closed for more than 5 minutes. - With the unit operating normally, measure the maximum current drawn on each phase. Set the circuitbreaker definitively, for a slightly higher current than the maximum measured. The latter must never exceed the current indicated on the motor identification plate. - Check that the voltage between phases at the motor terminals is correct. - Any disruption to operation indicates abnormal pump unit operating conditions (voltage drop, broken phase, incorrect setting, foreign body in the pump, sludge, etc). - The unit should turn smoothly without vibrating. - Never run the unit with a closed valve (whether the intake or the pressure valve). Running the pump unit on empty is absolutely prohibited - The pump must not operate at a flow rate of less than 30 % of the rated flow shown on the unit identification plate. Motor - Drain holes : For draining condensates produced when the machine is cooling, holes have been made at the base of the housings or motor flanges according to their operating position. These holes are stopped up with plastic plugs, and should be periodically unplugged and replugged. 9 - STOPPING THE PUMP UNIT - If the unit is not fitted with a non-return valve, close the pressure control valve to avoid water hammer. - Switch off the electrical supply to the motor. - In the event of prolonged stoppage and/or risk of freezing, drain the suction and delivery pipes as well as the pump itself, or take precautions against freezing by appropriate methods. To drain the pump, unscrew the special cap, part no. 89 10 - SERVICING - Practically no servicing is required. - All motors, except 18.5 kw, 22 kw, 30 kw and 37 kw 2-pole motors (2900 min -1 ) are fitted with bearings, which are greased for life and do not therefore require any attention. 5

For 18.5 kw to 37 kw 2-pole motors (2900 min -1 ), greasing intervals and the quantity of grease to be used are shown on the motor identification plate. They are as follows : 2900 min -1 motor P ( kw ) Greasing frequency in hours Quantity of grease per grease nipple in grams DL - 18.5-2 18,5 3750 15 DL - 22-2 22 3750 15 DL - 30-2 30 3750 15 DL - 37-2 37 3750 15 Recommended grease : ESSO UNIMEX N3 or similar - The mechanical seal will have been adjusted during assembly of the pump. It will remain watertight until noticeably worn and should then be changed. - Pump units installed as backup equipment should be run for a short time once a week, to ensure that they are working properly. 11 - DISMANTLING - REASSEMBLY Dismantling and reassembly of an electro-pump unit must be performed by personnel qualified to carry out this type of work. Where one or more components of an electro-pump unit are replaced (spare parts), it is essential that only parts supplied by LEROY-SOMER are used. Failure to comply with this instruction invalidates the guarantee, and relieves the manufacturer of responsibility for any malfunction. Any person who tampers with an electropump unit is responsible for the consequences. 11.1 - Dismantling Before commencing work on the unit : Disconnect the motor from the electrical supply. Close the intake and outlet valves. Check that the pump body is not under pressure. Drain the pump. Wait until the pump body has reached the ambient temperature. - The electro-pump unit is designed such that the moving part can be removed with the motor, without detaching the pump body from the pipes. To do this, unscrew the screws, part no. 83 - Remove the key, part no. 54 - Take off the revolving joint, part no. 71 - Unscrew the screws, part no. 86 and remove the base, part no. 11 For units with a motor power rating greater than or equal to 18.5 kw (at 2900 min -1 ) and 15 kw (at 1450 min -1 ) : remove screw, part no. 2-24 and take out the pump shaft, part no. 24 11.2 - Dismantling and reassembling the mechanical seal - Take out the spacer ring, part no. 72 from the base, part no. 11 using a mandrel. The housing for the spacer ring must be clean. Clean it and put in a new spacer ring, lubricating both the rubber ring and its housing with a solution of 10 % Teepol in clean water. - Slip the spacer ring into its housing by exerting pressure with a plastic tubular mandrel. - Make sure that the friction surface is dry and clean, and also that the part of the shaft against which the revolving joint, part no. 71 will slide. - After refitting the base, part no. 11 onto the motor, tighten the machine bolts, part no. 86 and fit a revolving joint, part no. 71, using a clean removable taper shaft lubricated with the same solution, and a propulsion tube to position it. Taper shaft - When performing these various operations, take care not to damage the friction surfaces of the mechanical seal. WARNING : For LS 80-65 - 125 and 100-80 - 160 electro-pumps, fit screws, part no. 83 with a sealing compound. Note : - Never use oil or grease when assembling the unit. - Never oil or grease friction surfaces. - Before locking the turbine onto the shaft, make sure that the mechanical seal is perfectly positioned. 11.3 - Reassembly - To reassemble, carry out the dismantling procedure in reverse. - Clean all parts carefully and change the gasket, part no. 75,which may have deteriorated. The unit should be dismantled as follows: - Unscrew the pump body fixing screws, part no. 83 and remove the entire moving part-motor assembly. - Loosen the turbine locking nut, part no. 79 - Remove the washer, part no. 85 - Take out the turbine, part no. 28 12 - SPARE PARTS To order spare parts, please specify : - the type of electro-pump. - the serial number of the motor. - the description of the part with its part number, as shown on the diagram and on the parts list in this document. 6

Fault Cause Remedy The motor will not start. - Circuit-breaker faulty or incorrectly set. - Check the circuit-breaker. - The supply voltage is correct but the voltage at the motor terminals is too low. - Redo the unit power supply line, increasing the diameter of the wires. - The motor is not properly connected. - Comply with the wiring diagram (connection to the motor). The pump will not start. - Pump body not filled sufficiently. - Fill up the pump. - The inlet filter valve is not sufficiently - Check the depth of immersion. immersed. - Direction of rotation reversed (3-phase motor). - Reverse 2 cables on the motor terminal block. - Intake manometric lift too great. - Reduce the lift (minimize pressure losses). - The suction pipe is not watertight or has - Check the suction pipe. a counter-slope where an air pocket forms. - The valve is stuck. - Check the valve. Inadequate performance. - Direction of rotation reversed (3-phase motor). - Reverse 2 cables on the motor terminal block. - Total manometric lift is greater than expected. - Use a more sophisticated pump or minimize the pressure losses. - Intake manometric lift too high. - Reduce the geometric intake lift. - Minimize the pressure losses on the suction pipe. - The pump, intake valve or inlet filter valve - Clean them and remedy the problem. are partially obstructed. - Counter-slope on intake where an air pocket forms. The circuit-breaker trips. - Make sure the suction pipe has a minimum upward slope of 2 cm per metre. - Air entering on intake. - Check that the suction pipe is airtight. - Check the depth of immersion of the inlet filter valve. - Permanent overload due to inadequate HMV, resulting in too high a flow. - Permanent overload due to excessive viscosity or density of the liquid being pumped. - Fit a control valve on the pump discharge pipe to slow down the flow. - Please consult LEROY-SOMER. - Excessive voltage drop. - Increase the voltage or the cable diameter. - Operation with 2 phases (3-phase motor). - Inspect the supply cables and connection terminals. Leaking mechanical seal. - Faulty mechanical seal. - Check and replace all the components of the mechanical seal (never run on empty). Unit vibration. - Conformity of the various points - Check these points. indicated above. - Abnormal restriction on the flanges. - Check the connection of the pipes to the pump flanges and remove any restrictions (reposition pipes or fit flexible collars). - Faulty motor bearings. - Check and change the bearings (with same size and type). 7

IP 55 motor - Power up to 16 kw with 2 poles (2900 min -1 ) and up to 12 kw with 4 poles (1450 min -1 ) Part no. Description Part no. Description 01 Pump body 86 Base fixing screw 11 Base 89 Drain plug 15 Front motor flange 3-89 Plug seal 25 Rotor 90 Filler cap 28 Turbine 3-90 Cap seal 54 Key 101 Full stator 60 Deflector 103 Fan 63 Spacer part 104 Fan cover 71 Revolving joint 105 Bearing on pump end 72 Spacer ring 107 Bearing on fan end 75 Gasket 108 Flexible washer 79 Turbine locking nut 110 Terminal box 83 Body fixing screw 111 Terminal block 85 Turbine washer 120 Identification plate 8

IP 23 motor - Power of 18.5 kw or higher with 2 poles (2900 min -1 ) and 15 kw or higher with 4 poles (1450 min -1 ) Part no. Description Part no. Description 01 Pump body 72 Spacer ring 11 Base 75 Gasket 15 Spacer flange 79 Turbine locking nut 2-15 Screw 83 Body fixing screw 3-15 Nut 85 Turbine washer 24 Pump shaft 86 Base fixing screw 2-24 Roundheaded screw 89 Drain plug 28 Turbine 3-89 Plug seal 54 Pump key 90 Filler cap 54/1 Motor key 3-90 Cap seal 71 Revolving joint 101 Motor 9

Notes

MOTEURS LEROY-SOMER 16015 ANGOULÊME CEDEX - FRANCE RCS ANGOULÊME N B 671 820 223 S.A. au capital de 131 910 700 F