DGP-25 MF. 1 / Genset general decription. > Open genset with automatic start-up, control card allows automatic, manual or signal start-up.

Similar documents
1 / Genset general description

1 / Genset general description

1 / Genset general description

DGL 6 MF. 1 / Genset general decription. > Open genset with automatic start-up, control card allows automatic, manual or signal start-up.

Technical specification

Code: KOHLER KDW 1404 ZANARDI ATO 28-1VS/4. VOLTAGE HZ PHASE COS Ø PRP kva/kw LTP kva/kw AMP. (LTP) 400/ ,8 10,0/8,0 11,0/8,8 15,9

VOLTAGE HZ PHASE COS Ø PRP KVA/KW LTP KVA/KW AMPERAGE 415/ ,8 85,0/68,0 93,5/74,8 130,23 400/ ,8 85,0/68,0 93,5/74,8 135,12

VOLTAGE HZ PHASE COS Ø PRP KVA/KW LTP KVA/KW AMPERAGE 415/ ,8 172,9/138,3 190,6/152,5 265,44 400/ ,8 172,9/138,3 190,6/152,5 275,4

Code: VOLVO TAD 734 GE MECC-ALTE ECO 38-1LN. VOLTAGE HZ PHASE COS Ø PRP kva/kw LTP kva/kw AMP. (LTP) 400/ ,8 250,0/200,0 275,0/220,0 397,4

Code: DEUTZ BF4M 1013 FC MECC-ALTE ECP 34-1L/4. VOLTAGE HZ PHASE COS Ø PRP kva/kw LTP kva/kw AMP. (LTP)

Code: VOLVO TAD 731 GE MECC-ALTE ECP 34-2L/4. VOLTAGE HZ PHASE COS Ø PRP kva/kw LTP kva/kw AMP. (LTP) 400/ ,8 150,0/120,0 165,0/132,0 238,44

Code: FPT F32AM1A MECC-ALTE ECP 28-VL / 4. VOLTAGE HZ PHASE COS Ø PRP kva/kw LTP kva/kw AMP. (LTP) 400/ ,8 30,0/24,0 32,5/26,0 46,97 ESPAÑA

Generating Rates WATER-COOLED THREE PHASE 50 HZ DIESEL. ADVANCED with quality certification ISO 9001

VOLTAGE HZ PHASE COS Ø PRP KVA/KW LTP KVA/KW AMPERAGE 415/ ,8 450,0/360,0 495,0/396,0 689,46 400/ ,8 450,0/360,0 495,0/396,0 715,32

Code: KOHLER KDI1903M MECC-ALTE ECP 28-M/4. VOLTAGE HZ PHASE COS Ø PRP kva/kw LTP kva/kw AMP. (LTP) 400/ ,8 18,9/15,2 20,8/16,6 30,07

Industrial Diesel Generator Set KD3500-F 50 Hz Fuel Consumption Optimized

LSC500S3. Powered by Cummins 50HZ. Water-cooled. Three Phase. Diesel KVA 500 KW 400. Standby Power

VOLTAGE HZ PHASE COS Ø PRP KVA/KW LTP KVA/KW AMPERAGE 415/ ,8 102,6/82,1 113,0/90,4 157,32 400/ ,8 102,6/82,1 113,0/90,4 163,22

Power kva 9,3 10 Power kw 9,3 10 Rated Speed r.p.m Standard Voltage V 240 Rated at power factor Cos Phi 1

350 KW / 438 KVA. POWERED by TP-V350-T1-60. kva 438 Standby 3 Phase kw /208, 110/220, 120/240, 277/480. kva 400 Prime Power Factor 0.

JCB DIESEL GENERATOR TECHNICAL SPECIFICATIONS

TECHNICAL SPECIFICATIONS

APD-ULJ250. Standby Power

Industrial Diesel Generator Set KD3300-F 50 Hz Fuel Consumption Optimized

NG904PES SERIES. Power Output Ratings. kva 904 kw 723 kva 808 kw 646. Standby Power (ESP) Prime Power (PRP)

Industrial Diesel Generator Set KD1250-UE 60 Hz - Emission Optimized EPA Tier 2 Certified

70 KW / 90 KVA POWERED by

Industrial Diesel Generator Set KD1750-UF 60 Hz Fuel Consumption Optimized

GMN - 22P 29/07/2016 GMN - 022P (ACP KPR) Main Features Frequency Hz 50 Voltage V 400 Power factor cos ϕ 0.8 Phase and connection 3

GSW500DO. Main Features Frequency Hz 50 Voltage V 400 Power factor cos ϕ 0.8 Phase and connection 3

VOLTAGE HZ PHASE COS Ø PRP KVA/KW LTP KVA/KW AMPERAGE (LTP) 400/ ,8 62,3/49,9 68,6/54,9 99,17

Industrial Diesel Generator Set KD2250-F 50 Hz Fuel Consumption Optimized

Engine Model: 4B3.9-G1 Engine Technical Data No. of Cylinders / Alignment: Cycle: 4 / In Line 4 Stroke Bore / Stroke: mm 102/120 Induction: Cooling Me

ENGINE MAKE MODEL CONTINUOUS POWER PERKINS 2206A-E15TAG2 STAND-BY POWER

Industrial Diesel Generator Set KD1100-F 50 Hz Fuel Consumption Optimized

GMS-015Y. Main Features Frequency Hz 50 Voltage V 400 Power factor cos ϕ 0.8 Phase and connection 3

VOLTAGE HZ PHASE COS PRP KVA/KW LTP KVA/KW AMPERAGE A

HFW-85 T5. Generating Rates SERVICE PRP STANDBY. INDUSTRIAL RANGE Standard soundproofing Powered by FPT_IVECO

18 KW / 18 KVA POWERED by

VOLTAGE HZ PHASE COS Ø PRP KVA/KW LTP KVA/KW AMPERAGE 415/ ,8 41,8/33,4 46,0/36,8 64,02 400/ ,8 41,8/33,4 46,0/36,8 66,42

Subsidiaries: PORTUGAL POLAND GERMANY UK SINGAPORE UAE PANAMA DOMINICAN REPUBLIC ARGENTINA ANGOLA SOUTH AFRICA

This generator set has been designed to meet ISO 8528 regulation. This generator set is manufactured in facilities certified to ISO 9001.

JCB DIESEL GENERATOR TECHNICAL SPECIFICATIONS

Industrial Diesel Generator Set KD1650-E 50 Hz - Emission Optimized EPA Tier 2 Compliant

This generator set has been designed to meet ISO 8528 regulation. Enclosed product is tested according to EU noise legislation 2000/14/EC

Industrial Diesel Generator Set KD2500-F 50 Hz Fuel Consumption Optimized

This generator set has been designed to meet ISO 8528 regulation. This generator set is manufactured in facilities certified to ISO 9001.

Industrial Diesel Generator Set KD1100-F 50 Hz Fuel Consumption Optimized

LSP88S3. Powered by 50HZ. Water-cooled. Three Phase. Diesel KVA 88 KW 70. Standby Power

GSW22P. Main Features Frequency Hz 50 Voltage V 230 Power factor cos ϕ 1 Phase and connection 1

Enclosed product is tested according to EU noise legislation 2000/14/EC. Voltage kva kw kva kw Amp 400/ , , , , ,00

HFW-350 T5. Generating Rates SERVICE PRP STANDBY. INDUSTRIAL RANGE Soundproof Powered by FPT_IVECO

DIESEL GENERATOR DATA SHEET

HDW-200 T5. Generating Rates SERVICE PRP STANDBY. INDUSTRIAL RANGE Soundproof Powered by DOOSAN

APD-NG400. NG Standby Power

This generator set has been designed to meet ISO 8528 regulation. This generator set is manufactured in facilities certified to ISO 9001.

LSC220S3. Powered by Cummins 50HZ. Water-cooled. Three Phase. Diesel KVA 220 KW 176. Standby Power

This generator set has been designed to meet ISO 8528 regulation. Enclosed product is tested according to EU noise legislation 2000/14/EC

TPD2250H6.3 TECHNICAL DATA

28 KW / 28 KVA POWERED by

GSL30D. Main Features Frequency Hz 50 Voltage V 230 Power factor cos ϕ 0.8 Phase and connection 3

This generator set has been designed to meet ISO 8528 regulation. This generator set is manufactured in facilities certified to ISO 9001.

Voltage kva kw kva kw Amp 400/ ,00 388,00 425,00 340,00 613,00 OTHER ACCESSORIES

13,000 Watt Diesel Generator AGi13P E

GMS - 560V 06/05/2016 GMS - 560V (ACP) Main Features Frequency Hz 50 Voltage V 400 Power factor cos ϕ 0.8 Phase and connection 3

GKP 550KVA. GKP Series. Generator Set Specification. Ultra Silent, Extended Life!

45 KW / 55 KVA POWERED by

AP59-6. Model Name AP59-6 Frequency / PF 60Hz, 1800 rpm, 0.8pf. Engine Make & Model Perkins 1103A-33TG1 Alternator Make Stamford

This generator set has been designed to meet ISO 8528 regulation. This generator set is manufactured in facilities certified to ISO 9001.

80 KW / 100 KVA POWERED by

60 KW / 75 KVA. POWERED by. kva 75 Standby 3 Phase kw /208, 110/220, 120/240, 277/480. kva 70 Prime Power Factor 0.8 kw 55

Enclosed product is tested according to EU noise legislation 2000/14/EC. Voltage kva kw kva kw Amp 400/ ,00 880, ,00 824, ,00

275 KW / 344 KVA. POWERED by TP-JD275-T3F-60. kva 313 Standby 3 Phase kw /208, 110/220, 120/240, 277/480. kva 224 Prime Power Factor 0.

16 KW / 20 KVA POWERED by

APD-ULM2000. Engine Alternator Voltage Standby Power Power Factor. PI734E (Wnd-312) 480 / 277V 2000kW A N.A.

ANG50P-6. Voltage Stand-by Power Stand-by Current Prime Power Prime Current. 480 / 277V 50kVA / 40kW 60.1 A 40kVA / 32kW 48.1 A

This generator set has been designed to meet ISO 8528 regulation. This generator set is manufactured in facilities certified to ISO 9001.

10,000 Watt Diesel Generator AGi9P E

30 KW / 40 KVA POWERED by

WPS60/S EP Series. Features:

HYW-20 T5. Generating Rates SERVICE PRP STANDBY. INDUSTRIAL RANGE Open Skid Powered by YANMAR

Standby Amper VOLTAGE

kva kw kva Dry Weigt Length Width kg K.U.N.Z. Handels-&Produktions GmbH

1000 KW / 1250 KVA POWERED by

JCB DIESEL GENERATOR TECHNICAL SPECIFICATIONS

WPS100/S EP Series. Features:

WPS20/S EP Series. Features:

SIVASA Doosan Series. SD250 Technical Data

Rating Definitions and Conditions

WPS350/S EP Series. Features:

55 KW / 70 KVA POWERED by

Power (kva) 3 Phase,50 Hz, PF 0.8. STANDBY RATING (ESP) PRIME RATING (PRP) Standby Amper. kw kva kw kva 400/

GKP 660KVA. GKP Series. Generator Set Specification. Ultra Silent, Extended Life!

JCB DIESEL GENERATOR TECHNICAL SPECIFICATIONS

Rental Power Kubota V2403 series engine

Generating Rates SERVICE PRP STANDBY. INDUSTRIAL RANGE Open Skid Powered by SCANIA

600 KW / 750 KVA POWERED by

GE.VO.360/325.SS+0_all

204 KW / 254 KVA POWERED by

WPS150/S EP Series. Features:

Transcription:

Measures: L : 1500 mm H : 1275 mm W: 800 mm H Weight: 550 Kg W L Hz 50 Hz V 230 V Water cooled Diesel illustrative image. 1500 r.p.m Opened CE Conformity 1 / Genset general decription Engine Alternator STAMFORD PI 144H > Open genset with automatic start-up, control card allows automatic, manual or signal start-up. GENERAL TECHNICAL DATA Performance class Frequency Voltage G2 50Hz 230 V Control panel DSE 6020 Fuel tank (L) 160 POWER 1 PRP (kva / KW) 20 / 16 ESP (kva / KW) 22 / 17,6 Voltage PRP (KVA/KW) ESP (KVA/KW) Amperage (A) 230 20/16 22/17,6 95 1. PRP: Continuous power ( Prime Power ) ISO 8528-1 standard. ESP: Emergency power ( Emergency Standby Power ) ISO8528-1 standard.

2 /Engine specifications Engine general data Manufacturer / Model r.p.m. 1500 Max. Power ESP (kva) 22,3 Power PRP (kva) 20,3 Fuel Diesel Number of cylinders 4 > diesel engine, inline 4-cylinders, 4-stroke, natural suction, mechanically regulated power through fuel pump. Complying TIER 0 and EU Stage 0 emissions. Engine capacity 2200 Compression ratio 23,3:1 Cooling system Regulation type Engine type / injection / suction type Liquid Mechanic Diesel / indirect / natural Fuel Fuel type Diesel Fuel tank capacity (L) 160 2.1 / Fuel feed system > Indirect injection system, filter that prevents the passage of particles, original parts from the engine manufacturer. Fuel consumption table % Load Consumption PRP Consumption ESP L/h Autonomy (h) L/h Autonomy (h) 50% 2,9 55,2 3,3 48,5 75% 4 40 4,6 34,8 100% 5,3 30,2 6,1 26,2 Cooling system Fan airflow (m 3 /min) 29,4 Fan power consumption (kw) 0,125 Engine + radiator capacity (L) 7 2.2 / Cooling system > Cooling by fully distributed coolant in a closed circuit driven by a pump activated by the engine. Tropicalized radiator. Original parts from the engine manufacturer. Lubrication system Total oil capacity (L) 10,6 2.3 / Lubrication system > Lubrication system driven by the crankshaft driven pump. Filter on top with full flow cartridge inserted, front crankcase. Original parts from the engine manufacturer. Air intake system Combustion air flow (m³/min) 1,45 2.4 / Air intake system > Natural air intake system including twostage filter. Original parts from the engine manufacturer.

Electrical start system Number of batteries 1 Battery features 12V 60Ah Starting voltage (V) 12V 2.5 / Start system > Start system by electric motor, battery (without maintenance) with disconnector and charging alternator driven by the starter motor (1,1kW, 12V), original parts from the engine manufacturer. Exhaust system Exhaust gas flow (m³/min) 2,7 Exhaust gas temperature (ºC) 445 2.6 / Exhaust system > Attenuation level -15dB(A). Complying TIER 0 and EU Stage 0 emissions. Exhaust external diameter (mm) 42 Max. exhaust backpressure (kpa) 10,2 3 / Alternator specifications Alternator General Data Manufacturer/model STAMFORD PI 144H No. poles 4 Insulation class H number of wires 12 Mechanical protection degree IP23 Voltage regulator AVR AS480 Voltage regulator ±1% ESP power rating 27ºC (kva) 24,9 PRP power rating 40ºC (kva) 22,7 number of phases 1 Power factor (cos φ) 1 Efficiency at 100% Load η (%) 85,2 Efficiency at 110% Load η (%) 84,8 Low wave distortion: > Alternator STAMFORD 4-poles, brushless, robust mechanical structure with easy access to connections and components, insulation class H, 12-wires, winding with 2/3 pitch and autoexcited AVR. Protection with Premium epoxy resins, high voltage parts are impregnated under vacuum allowing always an excellent insulation. The alternator complies with the following standards: - AS 1359 - IEC 34-1 - BS EN 60034-1 - VDE 0530 - BS 5000 - CAN/CSA-C22.2-100 - NEMA MG1-32 - THD (100% load) = 2% - THF < 2% - Complying with EN61000-6-3, EN61000-6-2 standards on radio interference.

4 / Bench specifications Genset mounted over an electro-welded bench made of high-strength steel, painted with electrostatic epoxy polyester powder paint. Union assembly to the bench by anti-vibration shock absorbers. Fuel tank located on the bench, provided with measuring gauge and fuel installation to the engine. Tested in saline mist chamber according to the ASTM B-117-09, 500h resistance. 5 / Control panel Including protection devices, distribution with DSE 6020 control card, that allows to operate in automatic, manual or by signal starting modes. 5.1 / Main elements of the control panel: - EMERGENCY STOP BUTTON. - DEEP SEA BATTERY CHARGER: Designed to be permanently connected to the battery and keep 100% of the load. The charger switches to float mode when the load is complete. - PROTECTIONS: 4-pole magnetothermic protection against overloads and shortcircuits. Protection fuses for the control assembly. Interruptor protección Marca/Modelo Schneider Easypact CVS100B + TM-G 100 4P 5.2 / Control card DSE 6020 DEEP SEA control card, with mains grid monitor. The genset will automatically start up when detecting a fault in the electric power network and it will turn off automatically as well, when the electrical supply is re-established. It can also work in manual mode and by signal. It allows you to monitor a wide range of generator parameters and display information alerts, status and alarms. The module includes USB communication ports, 4 configurable digital inputs, 3 analog inputs, 6 configurable outputs, emergency stop button, 8-35 V battery charger. It has 132x64p illuminated LCD display with 4 lines of text, 5-key navigation through menus, programmable clocks and alarms, reading and displaying parameter values, including RMS values. > The control card complies with the following environmental tests: - BS EN 61000-6-2 (electromagnetic compatibility) - BS EN 61000-6-4 (electromagnetic compatibility) - BS EN 60950 (electrical safety) - BS EN 61000-6-2 (Temperature) - BS EN 60068-2-6 (Vibration) - BS EN 60068-2-30 (Humidity) - BS EN 60068--2-27 (Shock) The entire module is easily configurable via PC using the DSE specific software configuration. Different operating modes: AUTOMATIC mode, MANUAL mode, SIGNAL mode and TEST mode. Other alternative configurations are available upon request to extend the capabilities of the operation modes.

Menu navigations Main status an instrumentation display Alarm indicator Transfer to mains (Manual mode only) Transfer to generator (Manual model only) Start engine (manual mode only) Stop genset Mute alarm Manual mode Test on load mode Select Auto mode 5.2.1 / Allowing reading Engine Mains Alarm detected Turning speed Mains Voltage (L-N) Start-up failure Low fuel level Oil pressure Mains Voltage (L-L) High coolant temperature High/Low generator frequency Battery Voltage Mains Frequency Low oil pressure Overload Hours counter Over/low speed engine Charging alternator failure Coolant temperature High/low generator voltage Maintenance interval External emergency stop Generator Voltage generator (L-N) Generator frequency Power factor Voltage generator (L-L) Generator intensity Generator load (kw, kva, kwh, kvah) > Genset reponse to a fully configurable alarm via DSE software.

5.3 / ATS The genset can be provided with an automatic transfer, as an optional device Investor table IV poles (A) 10 kva 25 > The table below shows the different amperage rating of the magneto thermal switches and investors cabinets. 15 kva 25 25 kva 32 35 kva 50 45 kva 60 50 kva 100 GENSET POWER 65 kva 100 90 kva 135 110 kva 160 165 kva 250 220 kva 400 275 kva 400 400 kva 630 450 kva 630 550 kva 800 Regulations ENVIRONMENTAL CONDITIONS ISO 8528-1:2005 standard: 25ºC, 100kPa and 30% relative humidity: PRIME POWER (PRP): Electrical power data available at variable load for unlimited hours per year. A 10% overload is permissible for 1 hour every 12 hours according to ISO 8528-1:2005. EMERGENCY STANDBY POWER (ESP): Electrical power data available at variable load in an emergency according to ISO 8528-1:2005. The DAGARTECH genset has CE marking which includes the following directives: - 2006/42 Machinery safety - 2006/95/CE Electrical Safety - 2004/95/CE Electromagnetic compatibility - 2005/88/CE Noise emissions in the environment outdoors