RC-DO. Room controllers with display and manual forced ventilation function

Similar documents
STRA-24 for chilled beams

ROOM CONTROLLER STRA-04 TECHNICAL CATALOGUE AND INSTALLATION

ROOM CONTROLLER STRA-24 TECHNICAL CATALOUGE AND INSTALLATION

HERZ Electronic room thermostat analog and digital

SE8300 Series Installation Guide 24 Vac Low Voltage

Commissioning manual. - Simplified VAV solution with full potential... Rev. Pascal-Comm RM-ver / RC-ver 1.

ELECTRIC POWER REGULATION TEMPERATURE CONTROLLERS. room C

PGK Rectangular duct coolers for cooled water

CWK Circular duct coolers for cooled water

ADAPTTM. Extract. Extract air diffuser for the WISE system. Quick Selection

CWW Circular duct heaters for hot water

CWK Circular duct coolers for cooled water

Description. functions including single duct pressure dependent or pressure independent systems.

Digital Room Thermostats with Touch Screen LCD

Version 11 Controls for natural ventilation. NV Comfort Standard / Plus KNX control

Carbon Dioxide (CO2) + Humidity (rh) + Temperature (T) transmitter with Display for room mounting. Features

lindab comfort Regula Control er

MiG2 TIME SWITCHES. 1, 2 & 4 Channel, 365 Day, Energy Saving Time Switches

Commerical Comfort System (CCS) Variable Air Volume (VAV) Zone Pressure Independent Damper Controller

LK Control v.3 & LK Control v.3 - RA

ADAPTTM. Sphere. Active communicative, supply air diffuser for the WISE system. Quick Selection

DS DC1100 Energy Controller SELF CONFIGURING OPTIMISER/COMPENSATOR WITH BOILER SEQUENCE AND HWS CONTROL

Power consumption Wire/transformer sizing. Motor. Spring return. Motor. Spring return. EMC Low voltage directive

PGV Rectangular duct heaters for hot water

ADAPTTM. Free. Active communicative, supply air diffuser for the WISE system, ADAPT F

HGM1770 Automatic Generator Control Module OPERATING MANUAL Smartgen Electronic

SMT-AZC INSTALLATION / OPERATION MANUAL

APPLICATION GUIDE. Simplicity LINC GATEWAY OVERVIEW. 24 must be grounded close to the Simplicity LINC

HGM1780 AUTOMATIC GENERATOR MODULE CONTENT 1. SUMMARY PERFORMANCE AND CHARACTERISTICS SPECIFICATION OPERATION...

Two temperature sensors to protect against freezing and high head pressure in both the indoor evaporator and the outdoor condenser

Metasys Zoning Package Installation

ELIOS 25 DIGITAL CONTROL UNIT WITH LCD DISPLAY FOR THERMAL SOLAR SYSTEMS TDS 006 M00 0SE A

Actuators for modulating control AME 110 NL, AME 120 NL

Room product for Swegon s WISE System for demand-controlled ventilation

Technote. Frese OPTIMIZER - pressure independent 4-pipe coil control unit. Application. Benefits. Features.

Digital Fan Coil Thermostats with 0(2)-10 VDC Fan Output

22 POINT FULLY PROGRAMMABLE HVAC CONTROLLER

Control Solutions Biofloor

Chilled beam for ceiling installation

WSTH/WPTH. Woltmann type combined energy meter. Woltmann flow meters for large nominal flows combined with calculator and temperature sensors.

DCV-RC DCV-RC. DCV-RC Room climate control unit. Room climate control SMART DAMPERS & MEASURING UNITS. Product description.

VTZ variable speed Reciprocating compressors

BACnet Lab and Pressurized Room Controllers with Off-board Air Modules

Ventilation Control. Ventilation Control 12

42GW. Hydronic Cassette Fan Coil Units PRODUCT SELECTION DATA INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS EASY INSTALLATION

l The Battery Tester is designed for measuring the l AC four-terminal method to measure the internal

Time scale: from 0.05 s to 100 h Multi-function Plug-in for use with 96 series sockets. Relay + socket. Wiring diagram (without control signal)

QUOTATION BLADE 7 LX. Product code GEAL6S2BAA

Current Automation Catalogue

HGM1750 Genset Security Module USER MANUAL Smartgen Technology

BAPI-Com, Two Wire Multifunction Sensor BA/BS4SCOM Temperature/Humidity Sensor Installation and Operating Instructions

US-S/FFL. Ultrasonic energy meters. Function. Flexible design. Connection. Mounting. High reliability

SE8300 Series Installation Guide 24 Vac Low Voltage

LDX-U20 is a microprocessor controlled DC-UPS rated 20 A usable in 12 V or 24 V systems.

HGM1780. Automatic Genset Controller USER MANUAL. Smartgen Technology

V200 V200. Control on water, proportional integral. Simplified Master / Slave operation GENERAL DESCRIPTION

RWBa. ROOM CONTROL EQUIPMENT Electronic control of cooling and heating. RWBa

The S Series unit is a ceiling mounted unit that comes in 3 sizes S1500, S1200 and S1000.

PCT-3000 plus DIGITAL PRESSURE CONTROLLER FOR COOLING PLANTS

ASSEMBLY INSTRUCTIONS ZONE MODULE 2 1 THERMOSTAT DESCRIPTION POWER SUPPLY AIRZONE CONTROLLER

Index. To contact Regin Company information News Lon-News. Electronic Electro mechanical. 1-phase 230 V, 2-phase 400 V, 3-phase 400 V Step controllers

RDG160TU Commercial Thermostat

ST Wiring diagram. Product description. Temperature controller. Order number

Appendix A: Inputs, Outputs, and Parameters

SE7000 Series Room Controllers

DCV-LC DCV-LC. DCV-LC Lab climate control unit. Lab climate control SMART DAMPERS & MEASURING UNITS. Product description. Occupancy AIN AOUT DCV-LC

GVL 8301-K CNV control panel

INFRESCO 2KW VARIABLE CONTROLLER Issue 3

Swegon PACIFIC. Integrated climate beam

HML - Airflow Unit for Large Volumes. HML Airflow Unit for Large Volumes. with Centralized Airflow Heating

HMR DUAL DUCT CABIN UNIT CABIN UNITS HMR. For passenger and crew cabins

Product Data. SYSTXBBUIZ01 -D Evolutiont Zone Control. EVOLUTION t ZONE CONTROL

Pressure Boosting Systems Multiple-Pump Units

Section 3 Technical Information

Ducted medium static pressure monosplit DC Inverter

Technical Specificaions. kwh Energy Meter

PART MATERIAL PART MATERIAL. Casing Hot galvanized steel / Option: stainless steel EN (AISI316L) Reheat coil EN 1.

Low voltage AC drives. ABB component drives ACS to 2.2 kw / 0.25 to 3 hp Catalog

START-UP CHECKLIST. Date: Job Name: Customer Name: Address: City: State: Zip: Model Number: Serial Number: Qualified Start-up Technician:

Digital Time Switches

Modbus Integration Integration for Modbus Functionality for VT8600 Series

ECL Apex 10. User Guide. ECL Apex 10 *087R9745* Installation and configuration. *vijem102*

Product Data. SYSTXCCITC01---B Infinityr System Control INDUSTRY LEADING FEATURES/BENEFITS INFINITYR SYSTEM CONTROL

InBin-P Pressure switches 5 Pa Pa

Hardware Installation. Tracer AH541 Version 2 Air-Handler Controller CNT-SVN02B-EN

Product Data. SYSTXBBECC01-B Evolutionr Connext Control INDUSTRY LEADING FEATURES/BENEFITS. EVOLUTION r CONNEX t CONTROL

Halton Rex 600 RE6 - Adaptable active chilled beam

Product Data. SYSTXCCUIZ01-- V Infinityt Zone Control. INFINITY t ZONE CONTROL

Cooling mode. Temperature adjustment button. Override button. 24 VAC COM AN1 COM OPEN CLOSED T2/AN2 T2/COM T3 T3 COM SENSOR COM C-Over COM NSB

Temperature Controller (Heat Pumps)

ALC-PRM-VFC. Ceiling Mounted Photocell. Product Guide. Overview. Features

Pressure Independent Control Valve

SMT-150 Installer Manual

Swegon PACIFIC. Integrated climate beam

Accessories STRA Room Controller

Metasys Zoning Package

PH120. Rooftop Packaged. R410a Refrigerant PERFORMANCE DATA OUTDOOR COIL ENTERING TEMPERATURE 0 C

MB A 12V/24V DC PROGRAMMABLE DUAL BATTERY ISOLATOR

Swegon PACIFIC. Integrated climate beam QUICK FACTS KEY FIGURES

VAV TERMINAL UNIT KYODO-ALLIED TECHNOLOGY PTE LTD

Transcription:

revision 10 2017 RC-DO Room controllers with display and manual forced ventilation function RC-DO is a room controller from the Regio Mini series intended to control heating and cooling in a single zone. RC-DO is a room controller in the Regio series. The controller does not have a communication port. Regio Regio is an extensive range of controllers for control of heating and cooling. The controllers are divided into three different series; Mini, Midi and Maxi. The Midi range consists of pre-programmed controllers with communication. Maxi consists of freely programmable controllers with communication. The Mini controller range, of which RC-DO is a part, consists of pre-programmed, stand-alone controllers. Applications The Regio controllers are suitable for use in buildings requiring optimum comfort and reduced energy consumption, such as offices, schools, shopping centres, airports, hotels and hospitals. See application example on page 3. Sensor The controller has a built-in room temperature sensor. An external sensor for room temperature or change-over can also be connected (PT1000). Short facts about RC-DO Easy installation Built-in function for forced ventilation On/Off or 0...10 V control Input for occupancy detector, window contact, condensation detector and change-over function Easy to install The modular design, featuring a separate bottom plate for wiring, makes the entire Regio range of controllers easy to install and commission. The bottom plate can be put into place before the electronics are installed. Mounting takes place directly on the wall or on an electrical connection box. Actuators RC-DO can control 0...10 V DC valve actuators and/or 24 V AC thermal actuators.

Display handling The display has the following indications: Setpoint Indoor / outdoor temp. OFF: Unoccupied (also shows temperature) or Off indication (only OFF) STANDBY: Standby indication SERVICE: Setting parameters The buttons on the controller enables easy setting of parameter values using a parameter menu shown in the display. The parameter values are changed with the INCREASE and DECREASE buttons and changes confirmed with the occupancy button. Occupancy button Changeable value INCREASE DECREASE Occupancy indication Current room temperature in C to one decimal point Open window COOL/HEAT: Shows if the unit controls according to the heating or cooling setpoint Control modes RC-DO can be configured for different control modes/ control sequences: Heating Heating or Cooling via change-over function Heating/Heating Heating/Cooling Heating/Cooling with VAV-control and forced supply air function Heating/Cooling with VAV-control Cooling Cooling/Cooling Operating modes There are five different operating modes: Off, Unoccupied, Stand-by, Occupied and Bypass. Occupied is the preset operating mode. It can be set to Stand-by using the parameter menu in the display. The operating modes can be activated via an occupancy detector or the occupancy button. Off: Heating and cooling are disconnected. However, frost protection is still active (factory setting (FS) = 8 C). This mode is activated if a window is opened. Unoccupied: The room in which the controller is placed is not used for a extended time period, such as during holidays or long weekends. Both heating and cooling are kept within a temperature interval with configurable min/ max temperatures (FS min=15 C, max=30 C). Stand-by: The room is in an energy saving mode and is not used at the moment. This can, for instance, be during nights, weekends and evenings. The controller stands by to change operating mode to Occupied if presence is detected. Both heating and cooling are disconnected within a temperature interval surrounding the current setpoint (FS heating setpoint=-3 C, cooling setpoint=+3 C). Occupied: The room is in use and a comfort mode is activated. The controller maintains the temperature around a heating setpoint (FS=22 C) and a cooling setpoint (FS=24 C). Bypass: The temperature in the room is controlled in the same way as in the Occupied operating mode. The output for forced ventilation is also active. This operating mode is useful for instance in conference rooms, where many people are present at the same time for a certain period of time. When Bypass has been activated by pressing the occupancy button, the controller will automatically return to its preset operating mode (Occupied or Stand-by) after a configurable time has elapsed (FS=2 hours). If an occupancy detector is used, the controller will automatically return to its preset operating mode if no occupancy is detected for 10 minutes. Occupancy detector By connecting an occupancy detector, RC-DO can switch between the Bypass operating mode and its preset operating mode (Occupied or Stand-by). This way, the temperature is controlled from requirement, making it possible to save energy while maintaining the temperature at a comfortable level. The occupancy button Pressing the occupancy button for less than 5 seconds when the controller is in its preset operating mode will cause it to change to operating mode Bypass. A short press of the button when the controller is in Bypass mode will cause it to revert to the preset operating mode. If the occupancy button is pressed for more than 5 seconds will change the controller s operating mode to Shutdown (Off/Unoccupied) regardless of its current operating mode. The display enables selecting which operating mode, Off or Unoccupied, should be activated on Shutdown (FS=Unoccupied). A short press when in Shutdown mode will return the controller to Bypass. 2

Regio has a built-in function for forced ventilation. A closing of the digital occupancy detector input will set the controller to Bypass mode and activate the output for forced ventilation (DO1). This can for instance be used to open a damper. This function is terminated when the settable forcing interval (10 min.) has run out. The function can also be activated at the press of a button. Change-over function RC-DO has an input for change-over that automatically resets output UO1 to operate with heating or cooling function. A PT1000 type sensor can be connected and mounted so that it monitors the supply temperature of the heating coil. The output function is set to Heating when the fluid temperature exceeds 22 C and to Cooling when the temperature falls below 18 C. Alternatively, a potential-free contact can be used. When the contact is open, the controller will operate using the heating function, and when closed using the cooling function. To ensure satisfactory functioning using sensor, the system must have continuous primary circuit circulation. When the change-over function is not used, the input must be left disconnected. Setpoint adjustment When in mode Occupied, the controller operates using a heating setpoint (FS = 22 C) or a cooling setpoint (FS = 24 C) that can be changed locally using the INCREASE and DECREASE buttons. Pressing INCREASE will increase the current setpoint by 0.5 C per press until the maximum offset (FS = +3 C) has been reached. Pressing DECREASE will decrease the current setpoint by 0.5 C per press until the maximum offset (FS = -3 C) has been reached. Switching between heating and cooling setpoints takes place automatically in the controller depending on heating or cooling requirements. Built-in safety functions RC-DO has an input for a condensation detector to detect moisture accumulation. If detected, the cooling circuit will be stopped. The controller also has frost protection. This prevents frost damages by ensuring that the room temperature does not drop below 8 C when the controller is in mode Off. Actuator exercise All actuators are exercised, regardless of type or model. The controller performs this exercise at an interval of 23 hours. An opening signal is sent to the actuator for as long time as its configured run time. A closing signal is then sent for an equal amount of time, after which the exercise is completed. Application example Condensation detector Occupancy detector Window contact Temperature sensor 3

Technical data Supply voltage Power consumption Ambient temperature Storage temperature Ambient humidity Protection class Display Built-in temperature sensor Material, casing Weight Colour 18...30 V AC, 50...60 Hz 2.5 VA 0...50 C -20...+70 C Max 90% RH IP20 Backlit LCD NTC type, range 0...50 C, accuracy ±0.5 C at 15...30 C Polycarbonate, PC 110 g White RAL9003 This product is CE marked. More information is available at www.regincontrols.com Inputs External room sensor Change-over alt. potential free contact Presence detector Condensation detector alt. window contact Outputs Valve actuators alt. thermal actuators Valve actuators Termal actuator Output PT1000 sensor, 0 50 C. Suitable sensors are Regin s TG-R5/PT1000, TG-R5/PT1000,TG-UH/PT1000 and TG-A1/PT1000. PT1000 sensor, 0 100 C. Suitable sensor is Regin s TG-A1/PT1000. Closing, potential-free contact. Suitable occupancy detector is Regin s IR24-P. Regin s condensation detector KG-A/1 resp. potential-free contact 24 V AC actuator, max 0.5 A 2 outputs 0 10 V DC, max. 5 ma 24 V AC, max. 2.0 A Heating or cooling Actuator exercise FS = 23 hours interval Terminal blocks Lift type for max cable cross-section 2.1 mm 2 Setpoint settings via display Basic heating setpoint Basic cooling setpoint Setpoint displacement 5...40 C 5...50 C ±0...10 C (FS = ±3 C) 4

Wiring Terminal Designation Function 10 G Supply voltage 24 V AC 11 G0 Supply voltage 0 V 12 DO1 Output for forced ventilation 13-14 No function 20 GDO 24 V AC out common for DO 21 G0 0 V common for UO (when using 0...10 V actuators) 22 No function 23 UO1 Output for 0...10 V valve actuator alt. thermal actuator. Heating or cooling 24 UO2 Output for 0...10 V valve actuator alt. thermal actuator. Heating or cooling. 30 AI1 Input for an external sensor 31 UI1 Input for change-over sensor, alt. potential-free contact 32 DI1 Input for occupancy detector 33 DI2/CI Input for Regin's condensation detector KG-A/1 alt. window contact 40 +C 24 V DC out common for UI and DI 41 AGnd Analogue ground 42-43 No function Dimensions 60 68 95 28 mm Product documentation Document Instruction Regio RC-DO Product sheet TG-R4/PT1000, TG-R5/PT... Product sheet TG-UH/PT... Product sheet TG-A1/PT... Product sheet IR24-P Instruction IR24-P Product sheet KG-A/1 Type Instruction for RC-DO Information about room sensors, outdoor sensors and strap-on sensors suitable for RC-DO Information about occupancy detectors suitable for RC-DO Instruction for IR24-P Information about condensation sensors for the Regio controllers The product documentation is available for download from Regin's website, www.regincontrols.com. Head Office Sweden Phone: +46 31 720 02 00 Web: www.regincontrols.com Mail: info@regin.se