Control & Ditribution Ditribution Board & Motor Control Center SIVACON The Veratile Low-Voltage Switchboard SIVACON A&D CD DM PM, 1004 Power Ditribution Board 1
Control & Ditribution Ditribution Board & Motor Control Center Requirement SIVACON - Low-Voltage Switchboard - Deign Objective Economy Operational and peronal afety Life-time cot, Space, Intallation, Operation Security Availability Quality, Interchangeability Operator friendline Ergonomic Flexibility Meeting requirement, rapid adaptation A&D CD DM PM, 1004 Power Ditribution Board 2
Control & Ditribution Ditribution Board & Motor Control Center Requirement SIVACON The Obviou Solution for Global Challenge Type-teted tandard module (TTA) for building and indutrial ytem Know-how of technological leader SIEMENS Locally manufactured by authorized SIVACON Technology Partner Trade name product of high quality Globally applicable witchgear of SIEMENS A&D CD DM PM, 1004 Power Ditribution Board 3
Control & Ditribution Ditribution Board & Motor Control Center Requirement Power Center I n up to 7400 A I cw up to 150 ka I pk up to375 ka SIVACON For All Application in the Low-Voltage Network Main Ditribution Board I n up to 4000 A I cw up to 100 ka I pk up to 250 ka Unterverteiler I n up to 3200 A I cw up to 80 ka I pk up to 200 ka Motor Control Center I n up to 3200 A I cw up to 80 ka I pk up to 200 ka Load A&D CD DM PM, 1004 Power Ditribution Board 4 M M M M
Control & Ditribution Ditribution Board & Motor Control Center Requirement SIVACON Standard and Specification Standard and Specification Type-teted low-voltage witchgear aemblie (TTA) Teting of repone to internal fault (arcing fault) IEC 60439-1 DIN EN 60439-1 (VDE 0660 Part 500) DIN VDE 0106 Part 100 IEC 61641, VDE 0660 Part 500, Supplement 2 Clearance and creepage ditance Rated inulation voltage (U i ) Rated operational voltage cla (U e ) Rated impule withtand voltage 8 kv 1000 V up to 690 V DIN EN 60439-1 (VDE 0660 Part 500) A&D CD DM PM, 1004 Power Ditribution Board 5
Control & Ditribution Ditribution Board & Motor Control Center SIVACON Modular Product Sytem Cutomer Specification Modular-Sytem SIVACON Functionality Function-Module: 45.000 4711 4712 4713... Deign Module Engineering Rule Deign Modul: 3.600 Market of Low Voltage Switchboard and Sytem A&D CD DM PM, 1004 Power Ditribution Board 6 4.6
Control & Ditribution Ditribution Board & Motor Control Center Modular Technology SIVACON - Modular Technology: Optimal Adaptation to All Requirement 800/1000 600 1000/1200 800 1000/ 1200 800 2200 2600 Device compartment Cro-wiring compartment (optional) Horizontal bubar compartment Cable connection compartment optionally at the ide or bottom (depending on the technology ued) Cable compartment for cable connection rear or cable from above A&D CD DM PM, 1004 Power Ditribution Board 7
Control & Ditribution Ditribution Board & Motor Control Center Frame and Encloure SIVACON - Frame and Encloure: Dimenionally Accurate and Stable All-round perforation row with a 25 mm hole grid for individual intallation Flexible door ytematic for all requirement Door opening angle up to 180 Spring-loaded lock reliably prevent door from opening unintentionally Preure-relief top cover A&D CD DM PM, 1004 Power Ditribution Board 8
Control & Ditribution Ditribution Board & Motor Control Center Frame and Encloure SIVACON Frame and Encloure frame partition heet (inide) 2 mm rear panel 2 mm door 25 mm ide panel 2 mm Cubicle height (mm) Cubicle width (mm) 2200 400, 600, 800, 1000, 1200 2600 400, 600, 800, 1000, 1200 Cubicle depth (mm) 600, 800, 1000, 1200 800, 1000, 1200 Surface treatment: Material: Degree of protection to IEC 60529: optionally powder-coated, wet painted or galvanized heet teel in the following thicknee: Frame: 2.5 mm Encloure: 2.0 mm IP 30, IP 40, IP 42 ventilated IP 40, IP 54 unventilated A&D CD DM PM, 1004 Power Ditribution Board 9
Control & Ditribution Ditribution Board & Motor Control Center Bubar SIVACON - Variable Bubar Sytem: The Anwer to Divere Requirement Standardized bubar poition at top of the cubicle Bubar ytem for rated current up to 7400 A Uer-oriented gradation of rated current Rated peak withtand current (I pk ) up to 375 ka Separation of the bubar compartment from the device compartment Tranport unit joint eaily acceible from above A&D CD DM PM, 1004 Power Ditribution Board 10
Control & Ditribution Ditribution Board & Motor Control Center SIVACON Variable Bubar Sytem up to 3200 A up to 4000 A up to 7400 A Bubar Rated current at 35 C ambient temperature Phae conductor (L1, L2, L3) Quantity, dimenion [mm] 2 x 100 x 10 + 3 x 100 x 10 + 3 x 100 x 10 + 3 x 100 x 10 + unventilated ventilated [A] I pk / I cw [ka] Cubicle height [mm] Cubicle depth [mm] [A] 2400 3200 200/800 2200 600, 800, 10000 2950 4000 250/100 2200 800, 1000, 1200 5400 7400 375/150 2600 800, 1000, 1200 A&D CD DM PM, 1004 Power Ditribution Board 11
Control & Ditribution Ditribution Board & Motor Control Center Circuit breaker Deign Supply, Feeder and Coupling Cubicle: Compact, Reliable and Uer-Friendly Circuit-Breaker Deign: For circuit-breaker 3W. from 630 A up to 6300 A Up to 3 circuit-breaker per cubicle 3 and 4-pole Fixed-mounted and withdrawable deign Tet and diconnected poition with door cloed Rated peak withtand current I pk up to 250 ka I cw up to 100 ka, 1 up to 80 ka, 3 A&D CD DM PM, 1004 Power Ditribution Board 12
630 0A-320 A 630A-4-630A 20A 0A-25-250A 0 630A-160 60A 60 /80 60-10 0 0 6 80 8 80 0 1 0 10 80 Low Voltage Control & Ditribution Ditribution Board & Motor Control Center Circuit Breaker Deign Supply, Feeder and Coupling Cubicle Circuit-Breaker Deign Circuit Breaker 3WN / 3WL A&D CD DM PM, 1004 Power Ditribution Board 13
Control & Ditribution Ditribution Board & Motor Control Center Circuit Breaker Deign Supply, Feeder and Coupling Cubicle Circuit-Breaker Deign Uer-friendly with 3WN: Free choice of upply direction without any retriction in term of technical data High hort-time current-carrying capacity for time-graded hortcircuit protection up to 500 m Short-time grading control (ZSS) for very brief delay time (50 m) LCD operating current indication in the control conole (without ammeter and current tranformer) Indication and operation when the door i cloed A&D CD DM PM, 1004 Power Ditribution Board 14
Control & Ditribution Ditribution Board & Motor Control Center Circuit Breaker Deign Supply, Feeder and Coupling Cubicle Circuit-Breaker Deign Optimum connection compartment for high afety Cable or bubar connection optionally from above or below A rated current-dependent connection compartment offer optimum termination condition for cable and bubar Aembly time are hortened by optimum connection compartment A&D CD DM PM, 1004 Power Ditribution Board 15
Control & Ditribution Ditribution Board & Motor Control Center Fixed-Mounted Deign Outgoing Feeder Cubicle in Fixed-Mounted Deign: Economical, Reliable and Variable Any combination of modular cable feeder Swift converion by virtue of the lateral univeral cubicle bubar Eay replacement of cable feeder after deenergizing the witchboard A&D CD DM PM, 1004 Power Ditribution Board 16
Control & Ditribution Ditribution Board & Motor Control Center Fixed-Mounted Deign Outgoing Feeder Cubicle in Fixed-Mounted Deign: Vertical Ditribution Bubar Rated current up to 1400 A Rated peak withtand current I pk up to 163 ka I cw up to 65 ka, 1 up to 50 ka, 3 3 and 4-pole Device are connected without the need for drilling or punching Eaily acceible connection for quick modification and expanion Connection are viible and can be connected from the front A&D CD DM PM, 1004 Power Ditribution Board 17
Control & Ditribution Ditribution Board & Motor Control Center Fixed-Mounted Deign Outgoing Feeder Cubicle in Fixed-Mounted Deign: Modular Cable Feeder Moulded cae circuit-breaker or fue-witch-diconnector can be fitted a required Continuouly adjutable mounting plate for a tandard front plane Cable feeder with and without current meaurement A&D CD DM PM, 1004 Power Ditribution Board 18
Control & Ditribution Ditribution Board & Motor Control Center Fixed-Mounted Deign Cable Feeder in Fixed-Mounted Deign: Compartment Technology Individual ub-ection with door with door for each circuit breaker Breaker 3KL, 3RV and 3VL up to 630 A With or without plug-in ocket High form of internal eparation up to Form 4 Type 7 acc. to BS EN 60439 (gland box per functional unit) Optimum connection condition in the front and rear cable connection compart-ment A&D CD DM PM, 1004 Power Ditribution Board 19
Control & Ditribution Ditribution Board & Motor Control Center Fixed-Mounted Deign Cable Feeder in Fixed-Mounted Deign: Compartment Technology Optimum cable connection compartment for high afety Cable connection compartment at the rear with cable gland box High form of internal eparation up to Form 4 Type 7 acc. to BS EN 60439 (gland box per functional unit) A&D CD DM PM, 1004 Power Ditribution Board 20
Control & Ditribution Ditribution Board & Motor Control Center Fixed-Mounted Deign Cable Feeder in Fixed-Mounted Deign: Cubicle Dimenion / Cubicle Structure Modular cable feeder Cable connection front, right-hand ide Compartment technology Cable connection rear 600/800/1000 800 1000/1200 A&D CD DM PM, 1004 Power Ditribution Board 21
Control & Ditribution Ditribution Board & Motor Control Center Fixed-Mounted Deign Outgoing Feeder Cubicle in Fixed-Mounted Deign Switchable Fue-Switch-Diconnector 3NJ4 Cable feeder up to 630 A with/without current metering 25 feeder can be intalled in each cubicle Dead-tate fue replacement A&D CD DM PM, 1004 Power Ditribution Board 22
Control & Ditribution Ditribution Board & Motor Control Center Outgoing Feeder Cubicle in Fixed-Mounted Deign Switchable Fue-Switch-Diconnector 3NJ4 Cable connection lateral Cable connection below Fixed-Mounted Deign 800 600/800/1000 up to 160 A / feeder up to 630 A / feeder A&D CD DM PM, 1004 Power Ditribution Board 23
Control & Ditribution Ditribution Board & Motor Control Center In-Line Plug-In Deign Outgoing Feeder Cubicle in In-line Plug-in Deign: 3NJ6 Plugged in Swiftly, Alway Safe In-line type witching device for cable feeder up to 630 A High packing denity up to 34 feeder per cubicle Dead-tate fue replacement 400 mm or 600 mm wide cable connection compartment Degree of protection up to IP 40 Supply-ide plug-in contact enable quick replacement Poible to replace a feeder without having to hut down the ytem A&D CD DM PM, 1004 Power Ditribution Board 24
Control & Ditribution Ditribution Board & Motor Control Center Ditribution Bubar Outgoing Feeder Cubicle in In-line Plug-in Deign Vertical Ditribution Bubar Rated current up to 2100 A Rated peak withtand current I pk up to 125 ka up to 50 ka, 1 I cw Protection againt electric hock from plug-on bu ytem A&D CD DM PM, 1004 Power Ditribution Board 25
Control & Ditribution Ditribution Board & Motor Control Center Reactive Power Compenation Reactive Power Compenation Lower Cot with Increaed Safety Non-choked up to 500 kvar Choked up to 350 kvar Capacitor module up to 100 kvar Controller module with electronic power factor controller for fluh door mounting Cubicle width 800 mm A&D CD DM PM, 1004 Power Ditribution Board 26
Control & Ditribution Ditribution Board & Motor Control Center Cubicle for Cutomied Solution Cubicle for Cutomied Solution Plenty of Space for Flexibility Variou intallation component Cubicle-high door or compartment door Compartmentalization Vertical ditribution bubar 3 and 4 pole Rated current up to 1200 A Rated peak withtand current I pk up to 163 ka up to 65 ka I cw A&D CD DM PM, 1004 Power Ditribution Board 27
Control & Ditribution Ditribution Board & Motor Control Center Cubicle for Cutomied Solution Cubicle for Cutomied Solution Cubicle Dimenion / Cubicle Structure Cable connection front, right-hand ide 600-1000 1000 A&D CD DM PM, 1004 Power Ditribution Board 28
Control & Ditribution Ditribution Board & Motor Control Center SIVACON- Motor-Control-Center in Withdrawable Unit Deign SIVACON 8PT A&D CD DM PM, 1004 Power Ditribution Board 29
Control & Ditribution Ditribution Board & Motor Control Center SIVACON 8PT Motor and Cable Feeder Cubicle in Withdrawable Unit Deign: Highly available, Alway Safe Motor and cable feeder up to 630 A (fued and non-fued) Space-aving ize of withdrawable unit from 100 mm module height (up to 17 feeder per cubicle) Clearly viible withdrawable unit poition Standard operator interface for all withdrawable unit Iolating gap on the upply and feeder ide Cable connection compartment at front or rear Alteration of compartment ize poible without having to hutdown the witchboard A&D CD DM PM, 1004 Power Ditribution Board 30
Control & Ditribution Ditribution Board & Motor Control Center SIVACON 8PT Motor and Cable Feeder Cubicle in Withdrawable Unit Deign: Highly available, Alway afe Cable connection front Cubicle width 1000 mm Cubicle depth 600-1200 mm Cable connection rear Cubicle width 600 mm Cubicle depth 1000 / 1200 mm A&D CD DM PM, 1004 Power Ditribution Board 31
Control & Ditribution Ditribution Board & Motor Control Center SIVACON 8PT Motor and Cable Feeder Cubicle in Withdrawable Unit Deign: Withdrawable Principle Connecting poition I Diconnected poition 0 Tet poition TEST L1 L2 L3 N N L1 L2 L3 L1 L2 L3 N N L1 L2 L3 L1 L2 L3 N N L1 L2 L3 A&D CD DM PM, 1004 Power Ditribution Board 32
Control & Ditribution Ditribution Board & Motor Control Center SIVACON 8PT Motor and Cable Feeder Cubicle in Withdrawable Unit Deign: Plug-on bu ytem Integrated protection againt electric hock, afe-totouch (IP20B) 3- and 4-pole verion Tap opening in a modular grid of 25 mm Rated current up to 1200 A Short-circuit trength I pk up to 163 ka I cw up to 65 ka, 1 up to 50 ka, 3 A&D CD DM PM, 1004 Power Ditribution Board 33
Control & Ditribution Ditribution Board & Motor Control Center Witdraw. unit Motor and Cable Feeder Cubicle in Withdrawable Unit Deign: Withdrawable Unit Standardied deign in 8 module height (100, 150, 200, 300, 400, 500, 600, 700 mm) Motor feeder fue-le up to 11 kw in 100 mm module height only Integrated maloperation protection in all withdrawable unit (main witch locking device) Control plug up to 40-pole with bu contact optionally (PROFIBUS-DP) Plenty of pace for auxiliary equipment by poibility of fitting component at the rear A&D CD DM PM, 1004 Power Ditribution Board 34
Control & Ditribution Ditribution Board & Motor Control Center SIVACON 8PT Motor and Cable Feeder Cubicle in Withdrawable Unit Deign: Withdrawable Unit Inertion upport for eay moving of the withdrawable unit > 250 A Tet and diconnected poition with protection degree IP 30 (outide of the contour of cubicle, therefore clearly viible) Hinged cover of withdrawable unit for adjutment ( module height 200 mm) Control panel for meauring intrument and actuating device directly on the withdrawable unit A&D CD DM PM, 1004 Power Ditribution Board 35
Control & Ditribution Ditribution Board & Motor Control Center SIVACON 8PT Motor and Cable Feeder Cubicle in Withdrawable Unit Deign: Withdrawable Unit Simple converion of withdrawable compartment without hutdown of witchboar Lockable diconnected poition for afe operating at the load A&D CD DM PM, 1004 Power Ditribution Board 36
Control & Ditribution Ditribution Board & Motor Control Center SIVACON 8PT Motor and Cable Feeder Cubicle in Withdrawable Unit Deign: Cable Connection Connection for power and control cable in the eparate cable connection compartment No connection work neceary in the withdrawable unit compartment Cable connection compartment optionally - front = 400 mm wide - rear = 600 mm wide A&D CD DM PM, 1004 Power Ditribution Board 37
Control & Ditribution Ditribution Board & Motor Control Center Buway connection SIVACON Low-voltage witchboard Buway connection Type-teted and tandardied connection to the bubar trunking ytem SIVACON 8PS Type-teted and tandardied Rated-current from 1600 A up to 6300 A Degree of protection IP20 up to IP54 Buway connection to circuit-breaker 3WL For bubar trunking ytem LD (up to 5000 A) and LX (up to 6300 A) A&D CD DM PM, 1004 Power Ditribution Board 38
Control & Ditribution Ditribution Board & Motor Control Center Type tet Alway on the Safe Side: Type-Tet Included Every SIVACON witchgear aembly i verifiably type-teted SIVACON Technology Partner ue innovative IT tool for project planning and manufacture afely and conform to the type-tet SIVACON Technology Partner maintain a quality management ytem SIVACON Technology Partner i audited periodically and certified by Siemen A&D CD DM PM, 1004 Power Ditribution Board 39
Control & Ditribution Ditribution Board & Motor Control Center Highlight SIVACON Highlight Type-teted tandard module (TTA) Standardized bubar poition at the top of the cubicle 3 and 4-pole bubar ytem up to 7400 A Rated peak withtand current I pk up to 375 ka Deep witchgear compartment for univeral intallation Modular tructure of device compartment Single-front and back-to-back intallation Cable lead-in from above or below Cable connection from the front or rear A&D CD DM PM, 1004 Power Ditribution Board 40
Control & Ditribution Ditribution Board & Motor Control Center Partner concept SIVACON-Technology-Partner The Unique Combination High tandard Type tet Know-how Image & reource SIVACON Technology Partner Local Switchboard manufacturer Cloe cutomer contact High flexibility Regional experience Proximity to the cutomer + World trade name A&D CD DM PM, 1004 Power Ditribution Board 41