Solid Dielectric Load Break Switch SPECIFICATION. 25kV, 630A, 4 WAYS, 4 WAYS SWITCHED PADMOUNTED VACUUM LOAD INTERRUPTER

Similar documents
SERIES 802 / 812 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTERS AND FUSE ASSEMBLIES

100 / 110 DRYWELL FUSE SPECIFICATION

SERIES G100 / G110 SPECIFICATION 15KV & 25KV SUBMERSIBLE & VAULT MOUNTED SF 6 -INSULATED VACUUM LOAD INTERRUPTING SWITCHES

Guide Specification. Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break

Underground Distribution Switchgear

Submersible Vacuum Fault Interrupters

OPERATION AND MAINTENANCE OF TRAYER 4000 SERIES PADMOUNTED VACUUM FAULT INTERRUPTER

Typical Specification

Molded Current-Limiting Fuse

Underground Distribution Switchgear

OPERATION AND MAINTENANCE OF TRAYER 3000 SERIES PADMOUNTED VACUUM FAULT INTERRUPTER

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

35-kV Safefront SuperWell Mini-Switch Source Isolated Pad-Mounted Switchgear 50 Amp (Max) Clip-Mounted Current Limiting Fuses

Elastimold. Cable Accessories. Underground Distribution Switchgear. Molded Vacuum Switches and Fault Interrupters

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS

Underground Distribution Switchgear

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-115

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS

A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system.

Solid Dielectric, Triple Option Reclosers Catalog O-vst14

FEBRUARY 14, 2017 Elastimold Solid dielectric switchgear customer presentation

15-kV Wall-Mount Switchgear Three-Phase Indoor/Outdoor 600 Amp S&C Mini-Rupter Switch

Solid Dielectric, Single Phase Reclosers

solutions RUS accepted

SPECIFICATION FOR THREE-PHASE PAD MOUNT TRANSFORMERS. D. Dead Front, loop feed design shall be employed.

Product Specifications for Phase Over Phase GOABS(r)

C1000 Series Automatic Cap Bank

GENERAL INFORMATION POLE MOUNT TRANSFORMER SINGLE PHASE PAD MOUNT TRANSFORMER SINGLE PHASE POLE MOUNT TRANSFORMER THREE PHASE 17

CPG.1 Gas insulated, single busbar cubicle range Up to 27 kv / 2000 A / 31.5 ka Up to 38 kv / 2000 A / 31.5 ka IEEE Standards

9. Non-Residential Services (Commercial, Industrial, and Agricultural)

Solid Dielectric, Single Phase Recloser

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

NEW Solutions for Underground System Growth

Padmount Solid Dielectric Switchgear Catalog

Product Specification Guide. Title: Southern States 362 kv RLSwitcher Vertical Interrupter Style Reactor Switcher

STANDARD SPECIFICATION FOR TYPE PLD LIVE-FRONT/DEAD-FRONT PAD-MOUNTED SWITCHGEAR 15kV 25kV A. General

Technical Specification For Outdoor Substation Harmonic Filter Banks

SECTION PADMOUNT TRANSFORMER - OIL FILLED

Publication No.: PSG

Technical Specification for Pole Mounted Capacitor Rack

Solar Power Switchgear & Energy Storage Renewable Energy Systems

Medium Voltage Metal-Enclosed Switches

15-kV Live Terminal 600 Amp Group Operated Pad-Mounted Metal-Enclosed Outdoor Switchgear 140 Amp (Max) Clip Mount Current-Limiting Fuses

Elastimold & Hi-Tech Fuse Products

Product Specifications for Aluminum Vertical Break Switches

Fixed, Medium-Voltage, Pad-Mounted, Three-Phase Power Capacitor Bank Guide Form Specification

SWITCHGEAR DIVISION PRODUCT PROFILES

Medium Voltage Metal-Enclosed Switches

Product Specification Guide. Title: Southern States 72 kv RLSwitcher Vertical Interrupter Style Reactor Switcher

Contents. PG6 Single Side Access Padmount PufferPak Switch. SG6 Subsurface PufferPak Switch. PT6 Pole Top PufferPak Switch

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14

Three-Phase Pole Mounted Recloser

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)

MEDIUM VOLTAGE AIR INSULATED ARC-RESISTANT LOAD BREAK AND DISCONNECT SWITCHES

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14

34-SDMS-01 SPECIFICATIONS FOR

16.13 Unit Substation to 15kV Construction Standards Page 1 of 7

CATALOG. Hi-Tech Fuse Products

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents

CENTER BREAK GROUP OPERATED AIR BREAK SWITCHES RATED 15.5kV THROUGH 170kV EFFECTIVE DATE: 10/25/16 REV B

Automatic, Medium-Voltage, Pad-Mounted, Three-Phase Power Capacitor Bank Guide Form Specification

NXPLUS C Single busbar. Maintenance-free for lifetime

Chapter 6 Generator-Voltage System

DEAD-FRONT PAD-MOUNTED SWITCHGEAR 15kV 25kV

35-kV Safefront 200 Amp SuperWell Primary Capacitor Station Pad-Mounted Outdoor

Dead Tank Circuit Breaker 145PM40-C Compact design with enhanced reliability

35-kV Safefront Mini-Switch Source Isolated Pad-Mounted Switchgear 50 Amp (Max) Clip-Mounted Current-Limiting Fuses

Edison modular fuse, vault application products

Single-phase pad-mounted step voltage regulator

15-kV Safefront 200 Amp Primary Capacitor Station Pad-Mounted Outdoor

16kA Solid Dielectric, Triple Option Reclosers Catalog VLT12

Type MOST oil switch

045 : 2000 CEB STANDARD

35-kV Safefront 200 Amp SuperWell Primary Metering Station Pad-Mounted Outdoor

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS

MDS Dead-front Padmount Switchgear Style Guide 1VAM SG May 2010 Revision D

S&C Manual PME Pad-Mounted Gear

Figure 1. Single-phase pad-mounted voltage regulator. STANDARD FEATURES

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

Specification Guide. for RMVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

Solid Dielectric, Three Phase Reclosers Catalog O-vs18

ACCESSORIES FOR LPOF, HPPT AND XLPE HIGH VOLTAGE CABLE SYSTEMS PRODUCT CATALOGUE

A. Submit manufacturer's literature and technical data before starting work.

15 kv and 25 kv Thru-Bushings

FIXED POWER FACTOR CORRECTION EQUIPMENT 5KV CLASS MEDIUM VOLTAGE SECTION Z

Cobra-S. Catalog Cobra-S

Gas Insulated Metal-clad Switchgear, HMGS!

35-kV Thru-Bushings F Series (bolt-in) for Air-Insulated to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

ELASTIMOLD UNDERGROUND CABLE ACCESSORIES

25 kv Apparatus Bushings

Design Standard. Electric Motors. Detailed specifications follow. PART 1 - GENERAL

C. System Design and Performance Requirements

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

SWITCHGEAR FOR SERVICE UP TO 36kV (CABLE AND OVERHEAD CONDUCTOR CONNECTED)

35-kV 200-kV BIL Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

RUS accepted Catalog O-vst18

Transcription:

Solid Dielectric Load Break Switch SPECIFICATION 25kV, 630A, 4 WAYS, 4 WAYS SWITCHED PADMOUNTED VACUUM LOAD INTERRUPTER MANUALLY OPERATED / REMOTELY OPERATED DEAD FRONT PADMOUNTED VACUUM LOAD INTERRUPTING SWITCHGEAR FOR USE WITH SEPARABLE CONNECTORS FOR 25kV / 125KV BIL THREE-PHASE ALTERNATING-CURRENT SYSTEMS Document: SP-00102-R2 4/7/2018 Page 1 of 9

CONTENTS 1. Scope... 3 2. Applicable Standards... 3 3. Definitions... 4 4. Electrical Ratings... 5 5. Construction Requirements... 6 6. Manual Operating Provisions... 8 7. Load Break Switch Operating Mechanism... 7 8. Position Indicators... 7 9. Motor Operating Provisions... 7 10. Terminations... 7 11. Bushing Designation... 7 12. Main Nameplate... 9 13. Routine Testing Requirements... 8 14. Shipping Requirements... 8 15. Documentation...10 Page 2 of 9

1. Scope This specification applies to solid dielectric insulated 25kV 60Hz class three-phase gangoperated pad mounted vacuum load interrupting assemblies with continuous ratings of 630 Amps for use on underground distribution systems utilizing dead front equipment. 2. Applicable Standards The applicable standards for the equipment are: IEEE Std C37.74-2014 IEEE Standard Requirements for Subsurface, Vault, and Pad-Mounted Load-Interrupter Switchgear and Fused Load-Interrupter Switchgear for Alternating Current Systems Up to 38 kv IEEE Std C37.100.1-2007 IEEE Standard of Common Requirements for High Voltage Power Switchgear Rated Above 1000V IEC 62271-103, Ed. 1.0 2011-06 High-voltage switchgear and controlgear - Part 103: Switches for rated voltages above 1 kv up to and including 52 kv IEC 62271-1, Ed. 1.0, 2007-10 High-voltage switchgear and controlgear - Part 1: Common specifications IEC 60059 Ed. 2.1, 2009-08 IEC standard current ratings IEC 60529, Edition 2.1, 2001-02 Degrees of protection provided by enclosures (IP Code) IEEE Std 386-2006 IEEE Standard for Separable Insulated Connector Systems for Power Distribution Systems Above 600 V IEEE Std C37.301-2009 IEEE Standard for High-Voltage Switchgear (Above 1000V) Test Techniques Partial Discharge Measurements Page 3 of 9

3. Definitions The definitions of terms contained in this specification, or in other standards referred to in this document, are not intended to embrace all the legitimate meanings of the terms. They are applicable only to the subject treated in this specification. ASTM American Society for Testing and Materials ANSI American National Standards Institute AISI American Iron and Steel Institute Bus (As used in this specification) A three-phase junction common to two or more ways Dead Front Switchgear An assembly in which all energized parts are insulated and completely enclosed within a grounded shield system when separable connectors are in place IEC International Electrotechnical Commission NEMA National Electrical Manufacturers Association Solid Dielectric Switch A switchgear assembly which is mainly insulated with solid dielectric material such as plastic, rubber, ceramic, paper, composites, mica, etc. and uses no liquid or SF6 insulation to electrically insulate the various points of potential within the device Switched Way A way connected to the bus through a three-pole gang-operated switch Tapped Way A way solidly connected to the bus Way A three-phase circuit entrance to a switching assembly Page 4 of 9

4. Electrical Ratings Nominal Voltage (Series) 25 kv Maximum Design Voltage 27 kv Device Load Break Switch BIL Phase-to-Phase, Phase-to-Ground 125 kv BIL Across Open Contacts 125 kv One Minute Withstand Voltage (60Hz) 60 kv One Minute Withstand Routine Test Voltage (60Hz) 40 kv Continuous Current 630 A Load Switching 630 A Mechanical Switch Operations 10,000 Peak Current 41.6 ka Maximum Emergency 3-Time Interrupting 2000A Momentary (1 s) & Make and Latch 630A ways (Symmetrical) 630A ways (Asymmetrical) 16 ka 25.6 ka Note: These ratings are applicable for altitudes not exceeding 1000 m and ambient air temperatures in the range of -30 C to +40 C. 5. Construction Requirements 5.1. Electrical 5.1.1. The switchgear shall be of total dead front design. All energized parts shall be sealed behind a metal ground plane to avoid the possibility of exposure to electrical shock when separable connectors are in place. 5.1.2. The vacuum load interrupter switch shall be a three-phase gang-operated device of a quick-make, quick-break design that operates at a speed independent of the speed of the external operating handle and shall utilize vacuum contacts rated at 630A continuous and 25,600A asymmetrical momentary. The mechanism shall have a minimum life of 10,000 operations at a full 630 Amp load without the need for servicing or adjustments. 5.1.3. All internal bus shall be of copper bar, copper ribbon, or copper braid. No aluminum shall be used. 5.2. Tank Construction 5.2.1. The entire assembly shall be constructed of AISI type 304 stainless steel and shall be fully welded using AISI type 308 filler material to maintain the corrosion resistant properties. Bolted/gasketed tank assemblies will not be allowed. 5.2.2. The tank body shall be constructed with a minimum material thickness of AISI 11 ga. 5.2.3. The tank body and cabinetry shall be similar in size and cable connection geometry to a PMH 10 configuration. Page 5 of 9

5.2.4. All line-side bushings and bushing wells to be welded to make them an integral part of the tank. No bolted/gasketed bushing wells shall be allowed. 5.2.5. Bushings shall accept cable terminations as per IEEE 386-2006. They shall be arranged to allow for easy cable training while maintaining a minimum 6 spacing between the 600A bushings. 5.2.6. The entire switch tank shall be hermetically sealed and be fully submersible with all tank bushings welded. 5.2.7. No external horizontal portion of the switch tank or its accessories shall trap water. 5.2.8. Lifting lugs shall be welded to the tank so that the switch will remain level when being lifted. Lifting lugs shall have a rounded contour to limit damage to lifting slings. 5.2.9. Parking stands shall be provided and located to allow each way to be parked with a minimum elbow and cable movement distance. (For parking stand dimensions see ANSI C57.12.26-1993). 5.2.10. One grounding provision with a ½ 13 NC stainless steel nut, 7/16 (11.1mm) deep, shall be provided for each way and shall be located allowing easy access for grounding each way. The grounding provision shall be welded to the switch tank. 5.2.11. The unit shall be fitted with a sealed port, pressure gauge and shielding system for the visual indication of tank sealing integrity. 5.3. Enclosure Construction 5.3.1. The entire enclosure consisting of a base and cabinet shall be constructed of AISI type 304 stainless steel and shall be welded using AISI type 308 filler material to maintain the corrosion resistant properties. 5.3.2. The enclosure shall be constructed of a minimum material thickness of AISI 11ga. 5.3.3. If the enclosure includes a lift up hood, then it shall be constructed of a minimum material thickness of AISI 14ga. 5.3.4. The enclosure(s) shall have double doors. Both doors shall have provisions to latch the doors in the open position to prevent unintentional closing. The right-hand door shall have a three-point locking system with padlock provisions on the operating handle as per IEEE C57.12.29. 5.3.5. The enclosure doors shall include a fully encased and padlockable Pentahead security bolt. 5.3.6. No external portion of the cabinet or its accessories shall trap water. 5.4. Paint 5.4.1. Paint processes shall meet or exceed ANSI standard C57.12.29. Color shall be Munsell 7GY 3.29/1.5 Padmount Green unless otherwise specified. 5.5. Dielectric 5.5.1. Unit shall utilize solid dielectric material to insulate all internal components. The solid dielectric materials in combination with spacing internal to the Page 6 of 9

sealed tank shall withstand the normal and abnormal service conditions as specified in IEEE 37.74 2014 and IEC 62271-103, 2011-06. 5.5.2. Load interruption shall take place in sealed vacuum contacts. 5.5.3. The unit is a sealed system and requires no servicing of the dielectric. 6. Manual Operating Provisions 6.1. Manual operating handles shall move in to close and out to open. The direction of operation shall be apparent. 6.2. Load break switch operating handles shall be designed to be easily operated with standard live line tools. The handles shall be of a channel shape and formed from AISI type 304 stainless steel, with the lower edge of sufficient width to support the hook end of standard live line tools, and assist in guiding the hook into the handle opening for live line tool operation. They shall be located where they can be operated either to open or to closed positions with standard live-line tools. The force required to operate the handle shall be such that one average strength person in a standing position can readily operate it. 6.3. Load break switch operating handles shall be capable of being padlocked in both the open and closed positions and shall be labeled to clearly indicate switch position. 7. Load Break Switch Operating Mechanism 7.1. The load break switch mechanism shall be designed so that operation does not require any special skills, and the closing and opening speeds of the contacts are independent of the speed at which the operating handle is operated. 7.2. The load break switch shall be of a gang-operated three-phase design so that all contacts of the three phase mechanism shall be operated simultaneously, with no possibility of single phasing due to teasing of switch handle. 7.3. The load break switch shall be quick-make, quick-break type. Contacts shall be stable in open and closed positions without use of mechanical latches, sear pins or detents. 8. Position Indicators The switch handles of the load break switch shall act as position indicators that clearly and positively indicate the open and closed positions of the switch mechanism. A stainless steel nameplate shall be affixed to the switch tank adjacent to the operating handle to assist in identifying the switch position. 9. Motor Operating Provisions Provisions for motor operators shall be available as an optional feature. 10. Terminations The switch bushings shall accommodate cable terminations in accordance with ANSI/IEEE 386 2006. 11. Bushing Designation The switch bushings shall be identified and legibly marked adjacent to each bushing with the appropriate phase designation using a stainless steel nameplate. Page 7 of 9

12. Main Nameplate 12.1. A nameplate of stainless steel shall be provided. 12.2. The nameplate shall be securely welded to the tank. 12.3. All letters, schematics and numbers shall be photo engraved or stamped on the nameplate. 12.4. The nameplate shall contain at minimum the following information: 12.4.1. Name of manufacturer 12.4.2. Date of manufacture (month and year, for example, 1-90) 12.4.3. Serial number 12.4.4. Model number or style number 12.4.5. Rated maximum voltage 12.4.6. Rated impulse withstand voltage 12.4.7. Rated continuous current 12.4.8. Rated load interrupting current 12.4.9. Rated momentary current 12.4.10. Rated making current 12.4.11. A three-line bushing-oriented schematic diagram, using standard symbols (this may be put on a separate nameplate) 12.4.12. Total weight (including insulating medium) 12.4.13. Type of insulating medium 13. Routine Testing Requirements 13.1. Tank The finished tank will be pressurized to 7 pounds per square inch using dry nitrogen and tested for leaks using suitable leak detection methodology. 13.2. Electrical 13.2.1. AC hi-pot for 1 minute phase-to-phase, phase-to-ground, and across open contacts on all ways at 40kV. 13.2.2. Mechanical switch operational test. 13.2.3. DC resistance test on all main circuits using 100 amps. The measured resistance shall not exceed 1.2*Ru, where Ru is equal to the resistance measured before the design (type) temperature-rise test. 13.2.4. Partial discharge test: 100 pc max for a complete 3 phase assembly; 20 pc max for a phase or module tested alone. Modular testing is permitted in all cases. Partial discharge tests will not be performed across open contacts of the vacuum interrupters. 13.2.5. Test reports certifying the vacuum switch conforms to ANSI C37.74 and IEC 62271-103. 14. Shipping Requirements 14.1. The switch shall be completely assembled. 14.2. Switches shall be properly packaged and braced to prevent damage during shipment. Page 8 of 9

15. Documentation Instructions and checklists for the inspection, installation, and maintenance of the switch shall be provided. Page 9 of 9