Load break switches sircopv_058_a cat SIRCO PV UL98 new sircopv_059_a cat The solution for > Combiner box > Recombiner box > Inverter Function SIRCO PV UL98 non fusible disconnect switches are heavy duty switches that break and make DC photovoltaic circuits on and off load. They are suitable for use in accordance with NEC rt. 690 Photovoltaic Installations. These switches are extremely durable and are tested and approved for use in the most demanding applications. dvantages Optimise your investment High switching performances means less poles in series to reach the operating voltage, consequently: Less bridging bars required, limiting installation costs and time. Less heat dissipation, making it possible to be installed in a smaller enclosure. Guarantee safety over time SIRCO PV are extremely robust products, with all casings made from fiber glass reinforced polyester materials that allows: High mechanical withstand. High stability to temperatures (RTI of 30 C). High dielectric performance (high CTI / tested according to STM D 2303). They are available in 2, 3, 4, 6 and 8 poles for all configurations from one to 4 circuits and can be used in all types of earthing systems (floating or grounded systems, single or double switching), in order to suit all your requirements. Take advantage of an innovative design The SIRCO PV are able to operate on and off load up to 500 VDC per poles, providing extremely compact solution: 000 VDC (UL 98) on a 2 poles switch. 500 VDC (IEC 609473) on a 3 poles switch. Up to 4 circuits each at 000 VDC on an 8 poles switch. Reliability and performance Our range of SIRCO PV load break switches is compliant with UL98 and IEC 609473 standards and have been tested above standards expectation, ensuring no critical current. They are as well able to withstand 0 k, 50 ms, allowing the use of any overcurrent protection device for line protection. Strong points > Patented switching technology > Positive break indication > Up to 000 VDC as per UL98 > Up to 500 VDC as per IEC 609473 > Suitable for use in accordance with NEC rt. 690 Conformity to standards > UL98 Guide WHV, file E34648 > CS C22.2#4, Class 46502, file 2964 > NEC rt 690 > IEC 609473 pprovals and certifications () () Product reference on request. 58 Catalogue 204
Typical PV architecture The SIRCO PV range provides safe disconnection and isolation at all levels of your PV installation. SIRCOPV 054 The SOCOMEC solutions Combiner box LEVEL OF INSTLLTION SOCOMEC SOLUTIONS SIRCO PV One circuit up to 500 at 500 VDC Recombiner box SIRCO PV 4 circuits up to 500 at 000 VDC 2 circuits up to 500 at 500 VDC Inverter SIRCO PV One circuit up to 2000 at 000 VDC up to 2000 at 500 VDC Catalogue 204 59
References 000 VDC ack plate mounting Rating () No. of poles Switch body External handle PV circuit S2 type 00 4 27PV 2009 lack, 3R, 2 42F 2 () 200 4 27PV 209 Red/Yellow, 3R, 2 250 4 2P 27PV 2024 42G 2 () 325 5 27PV 2032 400 5 27PV 2039 600 6 27PV 4060 4 P 800 7 27DC 408 200 7 27DC 42 2000 7 DS 8 P 27DC 420 00 4 DS 2 PV circuits 27PV 5009 200 4 DS 27PV 5024 325 5 27PV 4032 4 P 400 5 27PV 4039 600 6 DS 27PV 8060 800 7 DS 8 P 27DC 808 000 7 DS 27DC 80 lack 42D 2 () Red/Yellow 42E 2 () S3 type lack 43D 3 () Red/Yellow 43E 3 () S4 type lack 44D 3 () Red/Yellow 44E 3 () V type lack 3R, 2 2799 745 S2 type lack, 3R, 2 42F 2 () Red/Yellow, 3R, 2 42G 2 () lack 42D 2 () Red/Yellow 42E 2 () V type lack 3R, 2 2799 745 Shaft for external handle 200 mm 7.9 inches 400 020 320 mm 2.6 inches 400 032 400 mm 5.7 inches 400 040 (2) 200 mm 7.9 inches 40 520 320 mm 2.6 inches 40 532 400 mm 5.7 inches 40 540 (2) 320 mm 2.6 inches 499 308 200 mm 7.9 inches 400 020 320 mm 2.6 inches 400 032 400 mm 5.7 inches 400 040 (2) 320 mm 2.6 inches 499 308 ridging bar x 2709 020 x 2709 04 2x 2709 04 2x 2709 0062 2x 2709 008 2x 2709 02 2x 2709 020 4x 2709 020 2x 2709 0027 2x 2709 0045 (2 units) 4x 2709 0062 4x 2709 02 4 PV circuits 350 5 DS 8 P 27PV 8039 S3 type lack 43D 3 () Red/Yellow 43E 3 () 200 mm 7.9 inches 40 520 320 mm 2.6 inches 40 532 400 mm 5.7 inches 40 540 (2) 4x 2709 0045 () Defeatable handle. (2) Shaft guide reference 429 0000 is required for shaft length over 5.7 inches (400mm). 60 Catalogue 204
500 VDC ack plate mounting Due to UL98 voltage limitation at 000 VDC, these switches are certified per UL at 000 VDC and selfcertified at 500 VDC. Rating () No. of poles Switch body External handle PV circuit Shaft for external handle ridging bar 275 5 27PV 3026 325 5 3 P 27PV 3032 400 5 27PV 3039 S2 type lack, 3R, 2 42F 2 () Red/Yellow, 3R, 2 42G 2 () lack 42D 2 () Red/Yellow 42E 2 () 200 mm 7.9 inches 400 020 320 mm 2.6 inches 400 032 400 mm 5.7 inches 400 040 (2) 2x 2709 0027 ( unit) 2x 2709 0045 (3 units) 600 6 DS 27PV 8060 4x 2709 0062 (3 units) 800 7 DS 8 P 27DC 808 V type lack 3R, 2 2799 745 320 mm 2.6 inches 499 308 4x 2709 02 (2 units) 000 7 DS 27DC 80 2 PV circuits 275 5 DS 6 P 27PV 6026 350 5 DS 27PV 6039 S3 type lack 43D 3 () Red/Yellow 43E 3 () 200 mm 7.9 inches 40 520 320 mm 2.6 inches 40 532 400 mm 5.7 inches 40 540 (2) 4x 2709 0027 ( unit) 4x 2709 0045 (2 units) () Defeatable handle. (2) Shaft guide reference 429 0000 is required for shaft length over 5.7 inches (400mm). Catalogue 204 6
ccessories External operation Use In a combiner box, located close to the solar cell strings, or located close to the inverter, we recommend to use a door interlocked external handle for its safety features. Door interlocked external operation handles include an escutcheon, are padlockable and must be utilised with an extension shaft. Example The locking function of the enclosure in the "ON" position will force the operator to safely disconnect and isolate the solar cell strings prior to any intervention. Opening the door when the switch is on "ON" position is possible by defeating the locking function using a tool (authorized persons only). The interlocking function is restored when the door is closed back. acces_50_a_2_cat S2 type handle acces_236_a_2_cat Reinforced S2 type handle Handle type Handle colour Nema degree of protection Reference lack 42F 2, 3R, 2 4 5 Red/Yellow 42G 2 S2 4 DS lack 42D 2 Red/Yellow 42E 2 5 DS lack 43D 3 S3 6 Red/Yellow 43E 3 7 S4 lack 44D 3 Red/Yellow 44E 3 6 DS 7 DS V lack, 3R, 2 2799 745 acces_66_a_2_cat acces_52_a_2_cat access_89_a_2_cat S3 type handle S4 type handle V type handle Shaft for external handle Use Standard lengths: 7.9 in / 200 mm, 2.6 in / 320 mm, 5.7 in / 400 mm. Other lengths: please consult us. acces_44_b cat 4 5 6 7 4 DS 5 DS 6 DS Handle type S2 S3 S4 S2 S3, S4 Dimension (inches) Dimension X (mm) Length (inches) Length (mm) Reference 6.6 50 295 7.9 200 400 020 6 6.3 50 45 2.6 320 400 032 6 9.4 50 495 5.7 400 400 040 8 2.9 203 328 7.9 200 400 020 8 7.6 203 448 2.6 320 400 032 8 20.7 203 525 5.7 400 400 040 8.70 3.50 220 343 7.9 200 40 520 8.70 8.23 220 463 2.6 320 40 532 8.70 2.38 220 543 5.7 400 40 540 2 4.4 305 366 7.9 200 40 520 2 9. 305 485 2.6 320 40 532 2 22.2 305 564 5.7 400 40 540 2 4.3 305 363 7.9 200 400 020 2 9 305 483 2.6 320 400 032 2 22.0 305 56 5.7 400 400 040 6 8.4 406 467 7.9 200 40 520 6 23. 406 589 2.6 320 40 532 6 26.3 406 668 5.7 400 40 540 20 28. 508 74 2.6 320 499 308 20 3.3 508 795 5.7 400 499 309 V 20 28. 508 74 2.6 320 499 308 7 DS 20 39.4 508 795 5.7 400 499 309 X acces_369_a cat acces_202_a x_cat 62 Catalogue 204
Stype handle adapter Use For handles S2, S3 and S4. Dimensions Increases the distance between the handle grip and the door by 2 mm, for better handling. To be ordered Colour Nema degree of protection in multiples of Reference lack, 3R, 2 0 493 0000 acces_87_a_3_cat lternative Stype handle cover colours Use For handles S2, S3 and S4. Handle colour Other colours: please consult us. To be ordered in multiples of Handle type Reference Light grey S2, S3 50 40 000 Dark grey S2, S3 50 40 00 Light grey S4 50 40 003 Dark grey S4 50 40 004 acces_98_a_3_cat uxiliary contact Use Prebreak and signalling of positions 0 and I: to 2 NO/NC auxiliary contacts, to 2 low level NO/NC auxiliary contacts. Electrical characteristics 300. NO/NC contact Position C Type Reference 4 7 contact 2799 002 2 contacts NO/NC 2799 0022 4 DS 7 DS contact 459 002 Low level NO/NC auxiliary contacts Position C Type Reference contact 2799 02 4 7 2 contacts NO/NC 2799 022 4 DS 7 DS contact 499 0022 acces_076_a cat Terminal screen Use Top or bottom protection against direct contact with terminals or connection parts. No. of poles Position Pack Reference 4 2 P top or bottom unit 2798 302 5 3 P top or bottom unit 2798 304 5 4 P top or bottom unit 2798 404 6 4 P top or bottom 2798 406 7 4 P top or bottom unit 2798 42 4 DS 2 P top or bottom unit 458 302 6 P top or bottom unit 458 304 5 DS 8 P top or bottom unit 458 404 6 DS 8 P top and bottom 2 units 2798 806 7 DS 8 P top or bottom unit 2798 42 acces_079_a cat Catalogue 204 63
ccessories (continued) ridging bars for connecting poles in series Use The bridging bars will make easy the connection of the poles in series, allowing the following configurations (). () Other connections: refer to mounting instructions. 000 VDC Rating () Quantity to be ordered Fig. Reference PV circuit 4 00 2709 020 4 200 2709 020 4 250 2709 020 5 325 2709 04 5 400 2 2 2709 04 6 600 2 3 2709 0062 7 800 2 3 2709 008 7 200 2 3 2709 02 7 DS 2000 2 3 2709 02 2 PV circuits 4 DS 00 2 2709 020 4 DS 200 4 4 2709 020 5 325 2 5 2709 0027 5 400 2 6 2709 0045 5 400 2 6 2709 0045 6 DS 600 4 3 2709 0062 7 DS 800 4 3 2709 02 7 DS 200 4 3 2709 02 4 PV circuits 5 DS 350 2 6 2709 0045 500 VDC Rating () Quantity to be ordered Fig. Reference PV circuit 5 275 2 5 2709 0027 5 325 2 5 2709 0027 5 400 2 6 2709 0045 6 DS 600 4 3 2709 0062 7 DS 800 4 3 2709 02 7 DS 000 4 3 2709 02 2 PV circuits 5 DS 275 4 5 2709 0027 5 DS 350 4 6 2709 0045 64 Catalogue 204
ridging bars for connecting poles in series (continued) acces_38_a x_cat Fig. acces_382_a x_cat Fig. 2 acces_374_a x_cat Fig.4 acces_383_a x_cat Fig. 3 acces_386_a x_cat acces_378_a x_cat Fig. 5 Fig. 6 Catalogue 204 65
ccessories (continued) Cage terminals Use Connection of bare copper cables onto the terminals (without lugs). Optional fan out kit for ratings of 800 to 200 for connecting several cables to the switch. Rating max () Numbrer and of cables Max. number of connections per terminal Type of cable Quantity Reference 4 4 DS 00 200 conductor (#6300MCM) Cu / l 2 lugs 3954 2020 2 conductors (#42/0) Cu / l 2 lugs 3954 2025 4 4 DS 325 400 conductor (#2600MCM) Cu / l 2 lugs 3954 2040 2 conductors (#6350MCM) Cu / l 2 lugs 3954 204 6 6 DS 600 2 conductors (#2600MCM) Cu / l 2 lugs 3954 2060 7 800 200 2 conductors (#2600MCM) 2 Cu / l 2 lugs 3954 2060 2 conductors (#2600MCM) 3 () Cu / l 3 lugs 3954 3060 7 DS 2000 2 conductors (#2600MCM) 2 (2) Cu / l 2 lugs 3954 2060 2 conductors (#2600MCM) 3 (3) Cu / l 3 lugs 3954 3060 () Order a fan out kit reference 2709 203 for connecting 3 connectors per terminal (6 in total for the switch). (2) 2 connectors per terminal with the connection kit 2729 200. (3) 3 connectors per terminal with the connection kits 2729 20 and 2709 202. ul_032_a Copper bar connection kits Use To allow connection between the two power terminals from a same pole for 2000 ratings. (Fig., Fig. 2 and Fig. 3) Fig. Top or bottom flat connection Quantity to Rating () Figure order per pole terminals Reference 7 DS 800 000 2 2729 200 2 3 2729 202 2000 2 2729 200 2 3 2729 202 acces_32_b x_cat Fig. 2 Fig. 3 Top or bottom edgewise connection Quantity to Rating () Figure order per pole terminals Reference 7 DS 800 2000 3 3 2729 20 acces_33_b x_cat acces_34_b x_cat 66 Catalogue 204
Characteristics SIRCO PV UL98 switches have dual UL98 and IEC 609473 approval. Due to the difference in the standard test conditions, an identical product can have 2 different ratings: a "rating" as per UL98 a "rated current" as per IEC 609473 as per standard UL98 Rating () 00 200 circuits Rated voltage () () circuit 000 VDC 00 2 P 2 P 4 200 2 P 2 P 4 2 circuits 600 VDC 00 P 2 P 4 30 P 2 P 4 2 circuits 000 VDC 00 2 P 4 P 4 DS 200 2 P 4 P 4 DS 4 circuits 600 VDC 00 P 4 P 4 DS 30 P 4 P 4 DS Shortcircuit capacity at 000 VDC (any circuit breaker) Prospective shortcircuit current (k rms DC) 0 () 0 () Connection terminals Min. connection wire range/ WG #6 #6 Max. connection wire range/ WG 300MCM 300MCM Mechanical characteristics Durability (number of operating cycles) 0 000 0 000 Tightening torque (lbs.in/nm) 88.5/0 88.5/0 uxiliary contact Electrical characteristics 300 300 as per standard IEC 609473 Rated current 60 250 Thermal current at 40 C () 60 250 Thermal current at 50 C () 60 250 Thermal current at 60 C () 60 250 Rated insulation voltage U i (V) 500 500 Rated impulse withstand voltage U imp (kv) 2 2 circuits Rated voltage Utilisation category () () circuit 000 VDC DC2 60 2 P 2 P 4 250 2 P 2 P 4 circuit 500 VDC DC2 60 4 P 4 P 4 DS 250 4 P 4 P 4 DS 2 circuits 000 VDC DC2 60 2 P 4 P 4 DS 250 2 P 4 P 4 DS 4 circuits 600 VDC DC2 25 P 4 P 4 DS 60 P 4 P 4 DS () Without fuse during 50 ms. Catalogue 204 67
Characteristics (continued) as per standard UL98 Rating 250 275 circuits Rated voltage () () circuit 000 VDC 250 2 P 2 P 4 275 2 P 2 P 5 2 circuits 600 VDC 30 P 2 P 4 25 P 2 P 5 2 circuits 000 VDC 250 2 P 4 P 4 DS 275 2 P 4 P 5 4 circuits 600 VDC 30 P 4 P 4 DS 25 P 4 P 5 4 circuits 000 VDC 25 2 P 8 P 5 DS 6 circuits 600 VDC 25 P 6 P 5 DS 8 circuits 600 VDC 25 P 8 P 5 DS Shortcircuit capacity at 000 VDC (any circuit breaker) Prospective shortcircuit current (k rms DC) 0 () 0 () Connection terminals Min. connection wire range/ WG #6 2x#6 Max. connection wire range/ WG 300MCM 600MCM Mechanical characteristics Durability (number of operating cycles) 0 000 6 000 Tightening torque (lbs.in/nm) 88.5/0 28.3/4.5 uxiliary contact Electrical characteristics 300 300 as per standard IEC 609473 Rated current 35 275 Thermal current at 40 C () 35 275 Thermal current at 50 C () 35 275 Thermal current at 60 C () 35 275 Rated insulation voltage U i (V) 500 500 Rated impulse withstand voltage U imp (kv) 2 2 Rated Utilisation circuits voltage category () () circuit 000 VDC DC2 35 2 P 2 P 4 275 2 P 2 P 5 circuit 500 VDC DC2 35 4 P 4 P 4 DS 275 2 P 3 P 5 2 circuits 000 VDC DC2 35 2 P 4 P 4 DS 275 2 P 4 P 5 4 circuits 600 VDC DC2 60 P 4 P 4 DS 275 P 4 P 5 4 circuits 000 VDC DC2 275 2 P 8 P 5 DS 6 circuits 600 VDC DC2 275 P 6 P 5 DS 8 circuits 600 VDC DC2 275 P 8 P 5 DS () Without fuse during 50 ms. 68 Catalogue 204
as per standard UL98 Rating 325 350 circuits Rated voltage () () circuit 000 VDC 325 2 P 2 P 5 2 circuits 600 VDC 25 P 2 P 5 2 circuits 000 VDC 325 2 P 4 P 5 350 3 P 6 P 5 DS 4 circuits 600 VDC 25 P 4 P 5 4 circuits 000 VDC 325 2 P 8 P 5 DS 350 2 P 8 P 5 DS 6 circuits 600 VDC 25 P 6 P 5 DS 25 P 6 P 5 DS 8 circuits 600 VDC 25 P 8 P 5 DS 25 P 8 P 5 DS Shortcircuit capacity at 000 VDC (any circuit breaker) Prospective shortcircuit current (k rms DC) 0 () 0 () Connection terminals Min. connection wire range/ WG 2x#6 2x#6 Max. connection wire range/ WG 600MCM 600MCM Mechanical characteristics Durability (number of operating cycles) 6 000 6 000 Tightening torque (lbs.in/nm) 28.3/4.5 28.3/4.5 uxiliary contact Electrical characteristics 300 300 as per standard IEC 609473 Rated current 400 500 Thermal current at 40 C () 400 500 Thermal current at 50 C () 400 500 Thermal current at 60 C () 400 500 Rated insulation voltage U i (V) 500 500 Rated impulse withstand voltage U imp (kv) 2 2 Rated Utilisation circuits voltage category () () circuit 000 VDC DC2 400 2 P 2 P 5 2 circuits 000 VDC DC2 400 2 P 4 P 5 500 3 P 6 P 5 DS 4 circuits 600 VDC DC2 275 P 4 P 5 4 circuits 000 VDC DC2 400 2 P 8 P 5 DS 500 2 P 8 P 5 DS 6 circuits 600 VDC DC2 275 P 6 P 5 DS 275 P 6 P 5 DS 8 circuits 600 VDC DC2 275 P 8 P 5 DS 275 P 8 P 5 DS () Without fuse during 50 ms. Catalogue 204 69
Characteristics (continued) as per standard UL98 Rating 400 600 circuits Rated voltage () () circuit 000 VDC 400 2 P 2 P 5 600 4 P 4 P 6 2 circuits 600 VDC 25 P 2 P 5 600 3 P 6 P 6 DS 2 circuits 000 VDC 400 2 P 4 P 5 600 4 P 8 P 6 DS 4 circuits 600 VDC 25 P 4 P 5 Shortcircuit capacity at 000 VDC (any circuit breaker) Prospective shortcircuit current (k rms DC) 0 () 0 () Connection terminals Min. connection wire range/ WG 2x#6 2x #2 Max. connection wire range/ WG 600MCM 2 x 600MCM Mechanical characteristics Durability (number of operating cycles) 6 000 6 000 Tightening torque (lbs.in/nm) 28.3/4.5 327.5/37 uxiliary contact Electrical characteristics 300 300 as per standard IEC 609473 Rated current 500 800 Thermal current at 40 C () 500 800 Thermal current at 50 C () 500 800 Thermal current at 60 C () 500 800 Rated insulation voltage U i (V) 500 200 Rated impulse withstand voltage U imp (kv) 2 2 circuits Rated voltage Utilisation category () () circuit 000 VDC DC2 500 2 P 2 P 5 800 4 P 4 P 6 circuit 500 VDC DC2 500 2 P 3 P 5 800 8 P 8 P 6 DS 2 circuits 000 VDC DC2 275 P 4 P 5 800 4 P 8 P 6 DS 4 circuits 600 VDC DC2 275 P 4 P 5 () Without fuse during 50 ms. 70 Catalogue 204
as per standard UL98 Rating 800 200 circuits Rated voltage () () circuit 000 VDC 800 4 P 4 P 7 200 4 P 4 P 7 2 circuits 600 VDC 800 3 P 6 P 7 DS 200 3 P 6 P 7 DS 2 circuits 000 VDC 800 4 P 8 P 7 DS 200 4 P 8 P 7 DS Shortcircuit capacity at 000 VDC (any circuit breaker) Prospective shortcircuit current (k rms DC) 0 () 0 () Connection terminals Min. connection wire range/ WG 4x#2 4x#2 Max. connection wire range/ WG 6x 600MCM (2) 6x 600MCM (2) Mechanical characteristics Durability (number of operating cycles) 3 500 3 500 Tightening torque (lbs.in/nm) 495.7/56 663.9/75 uxiliary contact Electrical characteristics 300 300 as per standard IEC 609473 Rated current 000 400 Thermal current at 40 C () 000 400 Thermal current at 50 C () 000 400 Thermal current at 60 C () 000 400 Rated insulation voltage U i (V) 200 200 Rated impulse withstand voltage U imp (kv) 2 2 circuits Rated voltage Utilisation category () () circuit 000 VDC DC2 000 4 P 4 P 7 400 4 P 4 P 7 DS circuit 500 VDC DC2 000 8 P 8 P 7 DS 000 8 P 8 P 7 DS 2 circuits 000 VDC DC2 000 4 P 8 P 7 DS 000 4 P 8 P 7 DS () Without fuse during 50 ms. (2) Maximum 6 x 600MCM with fan out kit 2729 203. Catalogue 204 7
Characteristics (continued) as per standard UL98 Rating circuits Rated voltage () 2000 circuit 000 VDC 2000 8 P 8 P 7 DS Shortcircuit capacity at 000 VDC (any circuit breaker) Prospective shortcircuit current (k rms DC) 0 () Connection terminals Min. connection wire range/ WG 4x#2 Max. connection wire range/ WG 6x 600MCM (2) Mechanical characteristics Durability (number of operating cycles) 3 500 Tightening torque (lbs.in/nm) 663.9/75 uxiliary contact Electrical characteristics 300 as per standard IEC 609473 Rated current 2200 Thermal current at 40 C () 2200 Thermal current at 50 C () 850 Thermal current at 60 C () 600 Rated insulation voltage U i (V) 200 Rated impulse withstand voltage U imp (kv) 2 circuits Rated voltage Utilisation category () circuit 000 VDC DC2 2200 8 P 8 P 7 DS () Without fuse during 50 ms. (2) Maximum 6 x 600MCM with fan out kit 2729 203. 72 Catalogue 204
Pole connections in series PV circuit 000 VDC 45 2P 67 4P Grounded Ungrounded Grounded Ungrounded Ungrounded () () sirco_084_a x_cat sirco_075_a x_cat () sirco_085_a x_cat sirco_086_a x_cat () sirco_076_a x_cat () () 7 DS 8P Grounded Ungrounded sirco_087_a x_cat sirco_088_a x_cat PV circuit 500 VDC 45 2P Grounded sirco_077_a x_cat Ungrounded () () sirco_087_a x_cat sirco_078_a x_cat 6 DS 7 DS 8P Grounded () () sirco_078_a x_cat. Front switch.. Rear switch.. Circuit. Ungrounded () (). Front switch.. Rear switch.. Circuit. Catalogue 204 73
Pole connections in series (continued) 2 PV circuits 000 VDC 4 DS 4P Grounded Ungrounded () () 5 4P Grounded Ungrounded 2 () () () sirco_092_a x_cat sirco_078_a x_cat sirco_089_a x_cat 2 PV circuits 500 VDC 5 DS 7 DS 8P Grounded 5 DS 6P Grounded () 2 2 () 4 PV circuits 000 VDC sirco_079_a x_cat sirco_09_a x_cat sirco_082_a x_cat () Ungrounded Ungrounded () () () () 2 2 () 2 () () () sirco_080_a x_cat sirco_08_a x_cat sirco_080_a x_cat () 2 2. Front switch.. Rear switch.. Circuit. 2. Circuit 2. () () 2 () () (). Front switch.. Rear switch.. Circuit. 2. Circuit 2. 5 DS 8P Grounded Ungrounded () () () () sirco_093_a x_cat 2 3 4 sirco_083_a x_cat () () 2 () 3 4 (). Front switch.. Rear switch.. Circuit. 2. Circuit 2. 3. Circuit 3. 4. Circuit 4. 74 Catalogue 204
Dimensions (in / mm) 45 J J 0.29 7.5 Ø 0.35 Ø 9 Ø 0.27 Ø 7 Y 0.53 3.3 4 0.98 25 Ø 0.43 Ø K K H.8 30 5 0.79 20.77 45 H H Ø 0.5 Ø 3 sircoul_054_a x_cat J2 J3 C.96 50 4 5 5 5 No. of poles Unit C H H max. J J J2 J3 K K Y 2 P inches 7.08 6.30 3.74 5.2 4.2 6.30 2.6 3.94 5.3.89.5 mm 80 60 95 32.5 07 60 55 00 35 48 38.5 2 P inches 9.05 0.23 5.04 8 6.53 8.26 2.95 5.2 7.67 2.65 2.08 mm 230 260 28 203 66 20 75 30 95 67.5 53 3 P inches 9.05 0.23 4.98 8 6.53 8.26 2.95 2.56 7.67 2.65 2.02 mm 230 260 26.5 203 66 20 75 65 95 67.5 5.5 4 P inches.4 0.23 4.98 8 6.53 0.63 5.3 2.56 7.67 2.65 2.02 mm 290 260 26.5 203 66 270 35 65 95 67.5 5.5 4 DS 5 DS J J 0.29 7.5 Ø 0.35 Ø 9 Ø 0.27 Ø 7 Y C Y 0.53 3.3 4 DS 0.98 25 Ø 0.43 Ø K H.8 30 5 DS K 0.79 20.77 45 H H2 Ø 0.5 Ø 3 sircoul_055_a x_cat J3 J2 H.96 50 4 DS 5 DS 5 DS No. of poles Unit C H H H max. J J J2 J3 K K Y Y 4 P inches 9.60 6.30 6.37 5.08 6.93 4.2 6.30.37 3.93 5.3 2.65.5 5.2 mm 244 60 62 29 76 07 60 35 00 35 67.5 38.5 32.5 6 P inches.85 0.23 9.39 8 6.5 6.53 6.26.37 2.56 7.67 2.70 2.02 7.44 mm 30 260 238.5 203 65.5 66 20 35 65 95 68.5 5.5 89 8 P inches 4.2 0.23 9.39 8 6.5 6.53 0.63.37 2.56 7.67 2.70 2.02 7.44 mm 36 260 238.5 203 65.5 66 270 35 65 95 68.5 5.5 89 Catalogue 204 75
Dimensions (in / mm) (continued) 6 J C J Y 0.82 2.97 50 Ø 0.4 Ø 0.5 H K2 K K H.95 49.5 sircoul_056_a x_cat 2.75 70 Ø 0,35 Ø 9 3.5 80 H 6 No. of poles Unit C H H J J K K K2 Y 4 P inches 24.80 3.38 5.47 0.63 5.70 3.9 6.59 6.88 2.34.0.83 mm 630 340 39 270 45 335 67.5 75 59.5 28 46.5 6 DS C J J Y Y 0.82 2.97 50 Ø 0.4 Ø 0.5 sircoul_057_a x_cat K K H H.95 49.5 2.75 70 3.5 80 H 6 ds No. of poles Unit C H H J J K K Y Y 8 P inches 8.34 3.38 4.56 0.63 3.66 3.8 2.02 9.84 4.92 2.6 9.98 mm 466 340 370 270 347 335 5.5 250 25 66.5 253.5 76 Catalogue 204
Dimensions (in / mm) (continued) 7 J J.73 44 0.82 20.85 3.54 90 Y C Ø 0.4 Ø 0.5 sircoul_058_a x_cat Taille de boîtier 7 DS C J J.73 44 0.82 20.85 3.54 90 Y Ø 0.4 Ø 0.5 K K 0.35 9 H H H H2 K2 K K H 4.72 20 H 7 sircoul_06_a x_cat No. of poles Unit C H H H2 J J K K K2 Y 4 P inches 20.9.33 7.97.89 8.30 8.0 8.38 9.9 9.84 3.82.0 4.23 mm 53 288 200 302 2 203.5 467 233.5 250 97 28 07.5 4.72 20 H 7 DS No. of poles Unit C H H J J K K Y Y 8 P inches 23.95.33 3..85 5.3 8.38 2.02 9.84 4.92 4.23.55 mm 608.5 288 333 30 389 467 5.5 250 25 07.5 293.5 Catalogue 204 77
Dimensions for external handles (in / mm) 4 4 DS 5 Handle type S2 type Front operation Direction of operation 0 Door drilling 40 Ø 78 90 4 Ø 7 poign_03_a gb_cat 45 25 I Ø 37 28 5 DS 6 Front operation Handle type Direction of operation Door drilling S3 type Ø 78 90 Ø 37 0 40 poign_035_a gb_cat 6 20 28 4 Ø 7 78 Catalogue 204
7 Handle type S4 type Front operation Direction of operation Door drilling I Ø78 90 Ø 37 poign_036_a gb_cat 350 0 28 4 Ø 7 60 40 6 DS 7 DS Handle type V type Front operation Direction of operation I Door drilling 50 4 Ø 6,5 poign_037_a gb_cat 22 545 0 Ø 3 50 Catalogue 204 79
ridging bars (in / mm) 4 4 DS 2709 020 2.5 00 ±0.3 4 4 DS 2709 04 Ø3 sircoul_062_a x_cat 43.5 27 Ø 35 25 7 3 9 ±0.2 22.5 30 ±0.3 75 5 50 sircoul_062_a x_cat 2709 0045 6 6 DS 0 2709 0062 Ø3 R 6 sircoul_047_b x_cat 0.55 3.94 4 00 0.98 3.5 25 80 0.98 25 Ø 0.43 Ø 0.2 5 4 ±0.2 6 0 2709 0027 22.5 46.5 65 ±0,2 7 53 5 5 90 57.06 sircoul_062_a x_cat sircoul_048_b x_cat 3.44 87.5 7 2709 008 Ø 0.4 Ø 0.5.02.49 26 8.27 38 0.35 20 8.69 43 45 26 9 ±0.35 22.5 65 ± 0.3 Ø3 sircoul_062_a x_cat 7 7 DS 2709 02 4.82 22.5 Ø 0.4 Ø 0.5 sircoul_049_b x_cat.02.49 26 8.27 38 0.35 20 8 2.8 7 80 Catalogue 204
Mounting orientation ll frames 4 DS 5 DS 6 DS 7 DS sircoul_028_a x_cat sirco_27_a x_cat sirco_27_a x_cat Terminal lugs (in / mm) 00 to 250 00 to 250 400.52 38.8 25 0.45 Ø.6.26 32.476 0.63 37.5 6 0.27 7.3 35 2.8 7.5 Ø 0.4 Ø 4.7 0.63 5.88 sirco_5_b us_cat.2 28.6 sircoul_038_a us_cat 0.2 5 0.79 20 sircoul_00_a us_cat.8 46 0.44.3 300MCM 2/0 600MCM 400 600 to 2000 2.88 2 73.5 5 0.53 3.46.49 38.94 49.30 0.40 Ø0.2 sircoul_026_b us_cat.9 30.23 0.25 6.35.25 3.75 sirco_6_b us_cat 3.5 80 2.87 73 2 x 350MCM 2 x 600MCM Catalogue 204 8