Load Break Switches 20 to 1600 A Easy mounting and safety Load break switches with visual breaking from 20 to 125A, 100 to 400A and 125 to 1600A, are easy to mount directly on DIN rail. The advantages for you: Technical data: Lorperiu Easy to install scillam in eratio consectet praessi. Lore Quick, vullum easy zzrit, and safety commy mounting nis nos adiat of accessories la feugiam etummodo do Dolobor Range of si breaking tis accumsandre capacities exer iril inci blamcon ulpute modolor perostis amconulla ad del ut ulputem vero odigna amcor iriliqu Lockable in off position ismodiamet, sismolore dui et illumsan ent utat, si. Main or modular breaking Lorperiu Complies scillam with NF in EN eratio 60 consectet 947-3 praessi. Lore Visual vullum breaking zzrit, commy nis nos adiat la feugiam etummodo do Dolobor Breaking si capacity: tis accumsandre 20-125A, exer 100 iril to inci 400A blamcon and 125 ulpute to 1600A modolor perostis amconulla ad del ut ulputem vero odigna amcor iriliqu ismodiamet, sismolore dui et illumsan ent utat, si.
Quick tips 1 Modular design Units up to 200A can be DIN-rail mounted 4 Flexible operation All switches can be fitted with internal or external handles 2 Insulated terminals IP2 finger protection 5 Convenient mounting Univers kits for 125-1600A switches 3 Lockable handles Operational handle can be safely locked in off position 6 Accessories Auxiliary blocks and terminal covers for all switches
Load Break Switches with Visual Breaking 20 to 125A Load break switches with visual breaking, 20 to 125A modular design, to mount directly on DIN rail, lockable in OFF position. Complies with NF EN 60 947-3. Connection with collar terminals copper conductors compatible. Connection capacity HAB 20 to 63A: 16 mm 2 lexible or rigid cables HAC 60 to 100A: 35 mm 2 lexible or rigid cables HAD 100 and 125A: 70 mm 2 lexible or rigid cables Description Characteristics In/A Width in z Cat. ref. 3P 4P 3P 4P Load break switches disconnector 20A 2,6 3,5 HAB302 HAB402 visual breaking modular design IP20 32A 2,6 3,5 HAB303 HAB403 In=Ith, AC23 40A 2,6 3,5 HAB304 HAB404 63A 2,6 3,5 HAB306 HAB406 63A 3 4,5 HAC306 HAC406 HAB406 80A 3 4,5 HAC308 HAC408 100A 3 4,5 HAC310 HAC410 100A 4,5 6 HAD310 HAD410 125A 4,5 6 HAD312 HAD412 HZC113 External handles for LBS 20 to 100A HZC010 HZC010 IP55 lockable with 3 padlocks for LBS 100 to 125A HZC011 HZC011 Shaft extensions 20 to 125A, 150mm HZC111 HZC111 20 to 125A, 200mm HZC112 HZC112 20 to 125A, 320mm HZC113 HZC113 Terminal shrouds 20 to 63A HZC211 HZC212 top and bottom 2 pieces / packaging 63 to 100A HZC213 HZC214 100 to 125A HZC215 HZC216 HZC212 Auxiliaries contacts 1O + 1F 0,5 0,5 HZC311 HZC311 In = 10A 2F 0,5 0,5 HZC312 HZC312 HZC311 3.112
Load Break Switches with Visible Breaking 100 to 400A Load break switches with visible breaking, 100 to 400A modular design, to mount directly on DIN rail for LBS up to 200A, lockable in OFF position. HA964N and HA966N are with double visible breaking (upstream and downstream). Mounting on plate. Complies with NF EN 60 947-3. Connection HAE: with collar terminals copper conductors compatible HA308, HA408, HA964N and HA966N on terminal. Connection capacity HAE 100 to 160A: 70 mm 2 lexible or rigid cables HA308, HA408: 95 mm 2 end lugs, HA964N: 150 mm 2 end lugs, HA966N: 240 mm 2 end lugs. Description Characteristics In/A Width in z Cat. ref. 3P 4P 3P 4P HAE416 Load break switches disconnector 100A 6,5 8 HAE310 HAE410 visible breaking modular design IP20 125A 6,5 8 HAE312 HAE412 160A 6,5 8 HAE316 HAE416 200A 8,5 8,5 HA308 HA408 250A 11,5 HA964N 400A 19,5 HA966N Main Incomers External handles for LBS 100 to 160A HZC014 HZC014 IP55 lockable with 3 padlocks for HA308, HA408, HA964N and HA966N HZC001 HZC001 HZC014 Shaft extensions 200 mm, for HA308 and HA408 HZC103 HZC103 300 mm, for HA308 and HA408 HZC104 HZC104 for HAE 100 to 160A, 150mm HZC114 HZC114 for HAE 100 to 160A, 200mm HZC115 HZC115 for HAE 100 to 160A, 320mm HZC116 HZC116 Terminal shrouds 100 to 160A HZC217 HZC218 top and bottom for HA408 HZ062 for HA964N HZ095 HZ095 for HA966N HZ096 HZ096 HZC218 Collar terminals for HA308 and HA408 HZ082 HZ082 copper, 95mm2 for HA964 HZ093 HZ093 aluminium/copper, 185mm2 Auxiliaries contacts 1NC + 1NO 0,5 0,5 HZ022 HZ022 for HA308 and HA408 HZ022 3.113
Load Break Switches 20 to 400A HAB, HAC, HAE switches HAB402, HAB403, HAB404, HAB406, HAC408 HAE410, HAE412, HAE416 A C A C B E B E D D Dimensions (in mm) with visual breaking HAB302, HAB303, HAB304, HAB306 HAB402, HAB403, HAB404, HAB406 HAC306, HAC308, HAC310 HAC406, HAC408, HAC410 A 45 60 54 71.5 135 B 68 68 76 76 124.5 C 48,5 48.5 48,5 48.5 50.5 D 75 75 75 75 76 E 110 110 110 110 189 with visible breaking HAE410, HAE412, HAE416 Technical characteristics HAB302 HAB303 HAB304 HAB306 HAC306 HAC308 HAC310 HAD310 HAD312 HAE310 HAB402 HAB403 HAB404 HAB406 HAC406 HAC408 HAC410 HAD410 HAD412 HAE410 HAE312 HAE412 In 20 A 32 A 40 A 63 A 63 A 80 A 100 A 100 A 125A 100 A 125 A 160 A rated insulation voltage Ui (V) 800 800 800 800 800 800 800 800 800 800 800 800 rated impulse withstand voltage Uimp (kv) 8 8 8 8 8 8 8 8 8 8 8 8 AC 22 at 400 V (A) 20 32 40 63 63 80 100 100 125 100 125 160 AC 23 at 400 V (A) 20 32 40 63 63 80 100 100 100 100 125 125 motor power AC 23A à 400 VM (kw) 9 15 18.5 30 30 37 45 45 55 45 55 75 rated short-circuit breaking capacity in association with gg DIN fuse (ka) 50 50 50 50 50 50 50 50 50 100 65 50 current rated range (A) 20 32 40 63 63 80 100 100 125 100 125 160 short-circuit making capacity Icc (A peak) 6 000 6 000 6 000 9 000 9 000 9 000 9 000 12 000 12 000 12 000 12 000 12 000 HAE316 HAE416 rated short-time withstand current (ka eff) for 1s Icw 2.5 2.5 2.5 2.5 3 3 3 5 5 7 7 7 mechanical endurance (nr of operations) 100 000 100 000 100 000 100 000 100 000 100 000 100 000 100 000 100 000 50 000 50 000 50 000 connection (mm²) 16 16 16 16 35 35 35 70 70 70 70 70 3.114
Load Break Switches 20 to 400A HA switches HA964N - HA966N Main Incomers Technical characteristics Dimensions (in mm) HA964N HA966N HA964N HA966N electrical characteristics rated current 250 A 400 A rated insulation voltage Ui (V) 800 800 rated impulse withstand voltage U imp (kv) 8 8 AC 22A at 400 V (A) 250 400 AC 23A at 400 V (A) 250 400 rated short-circuit breaking capacity (A) dynamic effect (peak) 11 900 15 300 thermal effect (eff. 1 s) 7 000 9 000 rated short-circuit current (ka) 80 50 with gl - gg fuses 250 A 400 A mechanical endurance (nr of operations) 10 000 10 000 electrical connection cage terminal (mm²) 185 - bolt terminal (Ø mm) M 8 M 8 lugs (mm²) 150 240 A 201 344 B 162 214 C 85 80 E 140 135 F 145 145 G 72 132 H 130 172 J 36 66 K 18 45 L 20 20 M 268 360 3.115
Load Break Switches with Rotary Handle 125 to 1600A Load break switches with rotary handle Ith (40 ): 125 to 1600A Un 400 / 690V AC For main and/or modular breaking, to use in commercial premises. Characteristics: 3P and 4P switches with visible breaking, with sudden double breaking, positive action opening, breaking or engagement visualisation, self cleaning silver plated copper contacts. Options: extended handle; auxiliary contact. Note: Handle and shaft must be ordered separately. Fiberglass reinforced polyester case, self extinguishable, resists to creepage distance and arc, tropicalised. Complies with EN 60 947-3. Description Characteristics In/A Cat. ref. 3P 4P Load break switches switches with visible breaking 125A HA351 HA451 with handle connection: 160A HA352 HA452 3P 4P In 160A: 95 mm 2 max. In 250A: 150 mm 2 max. 200A HA353 HA453 In 400A: 240 mm 2 max. ou 2 x 150 mm 2 max. 250A HA354 HA454 Insulating voltage Ui: 400A HA357 HA457 from 160 to 400A: 800V AC 630A: 1000V AC 630A HA358 HA458 HA358 Delivered with: 800A HA360 HA460 1 lockable handle, ixing screws and nuts, 1250A HA362 HA462 tightening programming segments 1600A HA364 HA464 Auxiliaries contacts 1NO + 1NC 125 to HZ023 HZ023 for HA load break switches AC1, 5A, 250V 1600A HZ023 Rotary handles for extended shaft 125 to 630A HZC002 HZC002 800 to 1600A HZC003 HZC003 Shaft extensions 63 to 630A, 200mm HZC101 HZC101 160 to 630A, 320mm HZC102 HZC102 HZC101 800 to 1600A, 200mm HZC105 HZC105 800 to 1600A, 320mm HZC106 HZC106 Terminal shields for switches: top and bottom HA351, HA352 HZ033 HA451, HA452 HA354, HA357 HZ034 HA454, HA457 HA358 HZ035 HA458 HA360 HZ036 HA460 HA362, HA364 HZ037 HA462, HA464 HZ043 HZ044 HZ045 HZ046 HZ047 Terminal shrouds for switches: HA351, HA352 HA451, HA452 HA354, HA357 HA454, HA457 HA358 HA458 HZC201 HZC203 HZC205 HZC202 HZC204 HZC206 3.116
Load break Switches with Rotary Handle 125 to 1600A HA351, HA451, HA352, HA452, HA454, HA454, HA357, HA457, HA358, HA458 switches Main Incomers Mounting Extended rotary handle Transparent terminal cover Shaft extension holes Direct rotary handle Extended rotary handle Terminal shield IP2 auxiliary contact Direct rotary handle Extended rotary handle Dimensions fo switches from 125A to 630A (rotary handle) Ref. In(A) A B B1 C D E F G H H1 J K L M N O P R Rr1 S T U V W X Y Z HA351 125A 140 135 93 120 124/354 65 50 80 50 40 120 65 5,5 15 75 75 36 20 20,5 25 3,5 115 22 20 9 20,5 10 HA451 125A 170 135 93 120 124/354 65 50 80 50 40 150 65 5,5 15 75 75 36 20 20,5 25 3,5 115 22 20 9 20,5 10 HA352 160A 140 135 93 120 124/354 65 50 80 50 40 120 65 5,5 15 75 75 36 20 20,5 25 3,5 115 22 20 9 20,5 10 HA452 160A 170 135 93 120 124/354 65 50 80 50 40 150 65 5,5 15 75 75 36 20 20,5 25 3,5 115 22 20 9 20,5 10 HA354 250A 190 160 108 130 135/365 75 60 115 60 50 160 80 5,5 20 105 105 50 25 25,5 30 3,5 130 33 27 11 22,5 15 HA454 250A 230 160 108 130 135/365 75 60 115 60 50 210 80 5,5 20 105 105 50 25 25,5 30 3,5 130 33 27 11 22,5 15 HA357 400A 190 170 108 130 135/365 75 60 115 60 50 160 80 5,5 20 105 105 50 25 25,5 30 3,5 130 33 27 11 22,5 15 HA457 400A 230 170 108 130 135/365 75 60 115 60 50 210 80 5,5 20 105 105 50 25 25,5 30 3,5 130 33 27 11 22,5 15 HA358 630A 230 260 170 165 167/397 110 89 115 70 75 210 140 7 30 135 135 65 45 45,5 50 5 220 37,5 37,5 13 36 20 HA458 630A 290 260 170 165 167/397 110 89 115 70 75 270 140 7 30 135 135 65 45 45,5 50 5 220 37,5 37,5 13 36 20 3.117
Load Break Switches with Rotary Handle 125 to 1600A HA360, HA362, HA364, HA460, HA462, HA464 switches with rotary handle terminal shield Connection terminals 800A 1250-1600A Rotary handle min. length with shaft extension: 262 ± 1 without shaft extension:212 ± 1 Switches with rotary handle from 800A to 1600A Ref. In(A) A B C H J N O P R S T V W Y HA360 800 280 320 214 50 255 127,5 127,5 80 50 60,5 7 47,5 47,5 46,5 HA460 800 360 320 214 50 335 167,5 167,5 80 50 60,5 7 47,5 47,5 46,5 HA362 1250 372 288 215 66,5 347 173,5 173,5 120 90 44 8 53,5 53,5 47,5 HA462 1250 492 288 215 66,5 467 233,5 233,5 120 90 44 8 53,5 53,5 47,5 HA364 1600 372 288 215 66,5 347 173,5 173,5 120 90 44 8 53,5 53,5 47,5 HA464 1600 492 288 215 66,5 467 233,5 233,5 120 90 44 8 53,5 53,5 47,5 3.118