SERIES G100 / G110 SPECIFICATION 15KV & 25KV SUBMERSIBLE & VAULT MOUNTED SF 6 -INSULATED VACUUM LOAD INTERRUPTING SWITCHES

Similar documents
100 / 110 DRYWELL FUSE SPECIFICATION

Solid Dielectric Load Break Switch SPECIFICATION. 25kV, 630A, 4 WAYS, 4 WAYS SWITCHED PADMOUNTED VACUUM LOAD INTERRUPTER

SERIES 802 / 812 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTERS AND FUSE ASSEMBLIES

Submersible Vacuum Fault Interrupters

Guide Specification. Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break

Typical Specification

Underground Distribution Switchgear

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS

Underground Distribution Switchgear

Publication No.: PSG

35-kV Safefront SuperWell Mini-Switch Source Isolated Pad-Mounted Switchgear 50 Amp (Max) Clip-Mounted Current Limiting Fuses

Product Specifications for Phase Over Phase GOABS(r)

Three-Phase Pole Mounted Recloser

CENTER BREAK GROUP OPERATED AIR BREAK SWITCHES RATED 15.5kV THROUGH 170kV EFFECTIVE DATE: 10/25/16 REV B

Underground Distribution Switchgear

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS

Molded Current-Limiting Fuse

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

SWITCHGEAR DIVISION PRODUCT PROFILES

Product Specifications for Aluminum Vertical Break Switches

Product Specification Guide. Title: Southern States 362 kv RLSwitcher Vertical Interrupter Style Reactor Switcher

FEBRUARY 14, 2017 Elastimold Solid dielectric switchgear customer presentation

Product Specification Guide. Title: Southern States 72 kv RLSwitcher Vertical Interrupter Style Reactor Switcher

15-kV Wall-Mount Switchgear Three-Phase Indoor/Outdoor 600 Amp S&C Mini-Rupter Switch

Technical Specification For Outdoor Substation Harmonic Filter Banks

OPERATION AND MAINTENANCE OF TRAYER 4000 SERIES PADMOUNTED VACUUM FAULT INTERRUPTER

Solid Dielectric, Triple Option Reclosers Catalog O-vst14

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008

MEDIUM VOLTAGE AIR INSULATED ARC-RESISTANT LOAD BREAK AND DISCONNECT SWITCHES

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

Medium Voltage Metal-Enclosed Switches

Elastimold. Cable Accessories. Underground Distribution Switchgear. Molded Vacuum Switches and Fault Interrupters

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)

Chapter 6 Generator-Voltage System

Load Break Switch Type LBOR-II, Oil Immersed PTAT-LIR975 IZUA Technical Guide Nut Mount Weld Mount

Specification Guide. for RMVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system.

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14

Descriptive bulletin. Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications

Contents. PG6 Single Side Access Padmount PufferPak Switch. SG6 Subsurface PufferPak Switch. PT6 Pole Top PufferPak Switch

OPERATION AND MAINTENANCE OF TRAYER 3000 SERIES PADMOUNTED VACUUM FAULT INTERRUPTER

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

STANDARD SPECIFICATION FOR TYPE PLD LIVE-FRONT/DEAD-FRONT PAD-MOUNTED SWITCHGEAR 15kV 25kV A. General

Medium Voltage Metal-Enclosed Switches

16.13 Unit Substation to 15kV Construction Standards Page 1 of 7

Detail Bill of Material Page 1 of 1 Project Name: Amphi School - MVS Replacement Negotiation No: TU700213X7K2 General Order

A. Submit manufacturer's literature and technical data before starting work.

9. Non-Residential Services (Commercial, Industrial, and Agricultural)

ELASTIMOLD UNDERGROUND CABLE ACCESSORIES

25 kv Apparatus Bushings

solutions RUS accepted

35-kV Safefront Mini-Switch Source Isolated Pad-Mounted Switchgear 50 Amp (Max) Clip-Mounted Current-Limiting Fuses

16kA Solid Dielectric, Triple Option Reclosers Catalog VLT12

VersaRupter 5-38 kv Load Interrupter Switch. Technical Guide

FIXED POWER FACTOR CORRECTION EQUIPMENT 5KV CLASS MEDIUM VOLTAGE SECTION Z

Power/Vac Vacuum Replacement Breakers for GE Magne-Blast Type AM & AMH Breakers

Technical Specification for Pole Mounted Capacitor Rack

CPG.1 Gas insulated, single busbar cubicle range Up to 27 kv / 2000 A / 31.5 ka Up to 38 kv / 2000 A / 31.5 ka IEEE Standards

Padmount Solid Dielectric Switchgear Catalog

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

15-kV Safefront Mini-Switch Source Isolated Pad-Mounted Switchgear 140 Amp (Max) Clip-Mounted Current-Limiting Fuses

C1000 Series Automatic Cap Bank

35-kV 200-kV BIL Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-115

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

35-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

Specification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS

TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS

Medium Voltage Equipment 5-15 kv GM-SG and 38 kv GM38 Metal-Clad Switchgear General

SECTION III SF6 GAS CIRCUIT BREAKER TECHNICAL SPECIFICATIONS TABLE OF CONTENTS

Solar Power Switchgear & Energy Storage Renewable Energy Systems

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE_107_R1

34-SDMS-01 SPECIFICATIONS FOR

Horizontal Circuit Switchers

Elastimold & Hi-Tech Fuse Products

7. SERVICES OVER 600 VOLTS

35-kV Safefront 200 Amp SuperWell Primary Metering Station Pad-Mounted Outdoor

Extensible Unit - VCE2a

Solid Dielectric, Three Phase Reclosers Catalog O-vs18

15-kV Live Terminal 600 Amp Group Operated Pad-Mounted Metal-Enclosed Outdoor Switchgear 140 Amp (Max) Clip Mount Current-Limiting Fuses

S&C Manual PME Pad-Mounted Gear

A. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified.

SPECIFICATION FOR THREE-PHASE PAD MOUNT TRANSFORMERS. D. Dead Front, loop feed design shall be employed.

15 kv and 25 kv Thru-Bushings

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

43-SDMS-01 SPECIFICATIONS FOR

Cobra-S. Catalog Cobra-S

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Dead Tank Circuit Breaker 145PM40-C Compact design with enhanced reliability

Fixed, Medium-Voltage, Pad-Mounted, Three-Phase Power Capacitor Bank Guide Form Specification

25-kV Apparatus Bushings A Series (clamp-in) for Elbow to Air-Insulated Service 200 Amp and 600 Amp

Automatic, Medium-Voltage, Pad-Mounted, Three-Phase Power Capacitor Bank Guide Form Specification

045 : 2000 CEB STANDARD

35-kV Thru-Bushings F Series (bolt-in) for Air-Insulated to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

Transcription:

SERIES G100 / G110 SPECIFICATION 15KV & 25KV SUBMERSIBLE & VAULT MOUNTED SF 6 -INSULATED VACUUM LOAD INTERRUPTING SWITCHES MANUALLY OPERATED / REMOTELY OPERATED DEAD FRONT SUBMERSIBLE AND VAULT MOUNTED SWITCHGEAR WITH VACUUM LOAD-INTERRUPTING SWITCHES FOR USE WITH SEPARABLE CONNECTORS FOR 15 KV / 95KV BIL AND 25 KV / 125KV BIL THREE-PHASE ALTERNATING-CURRENT SYSTEMS

TABLE OF CONTENTS TABLE OF CONTENTS. 2 1 Scope. 3 2 Definitions.. 3 3 Construction Requirements 3 3.1 Electrical. 3 3.2 Bussing... 3 3.3 Grounding Provision. 3 3.4 Ratings....... 4 3.5 Tank Construction.... 4 3.6 Mounting Stand. 5 4 Dielectric 5 5 Manual Operating Provisions. 5 6 Switch Operating Mechanism.... 5 7 Position Indicators 5 8 Motor Operating Provisions 5 9 Terminations. 5 10 Bushing Designation. 6 11 Nameplate... 6 12 Testing Requirements... 6 12.1 Tank.. 6 12.2 Electrical.. 6 13 Shipping Requirements. 7 14 Documentation... 7 15 Standards 7 2

1. Scope This specification applies to three-phase group operated 60 Hz subsurface load interrupting vacuum switches, SF 6 -insulated with maximum ratings of 600A and 15.5kV or 27kV and utilizing separable insulated connectors. 2. Definitions The definitions of terms contained in this specification, or in other standards referred to in this document, are not intended to embrace all the legitimate meanings of the terms. They are applicable only to the subject treated in this specification. 2.1 ANSI American National Standards Institute 2.2 IEEE Institute of Electrical and Electronic Engineers 2.3 AISI American Iron and Steel Institute 2.4 Bus (As used in this specification) A three-phase junction common to two or more ways 2.5 Subsurface Switch A submersible switching assembly suitable for application in a below-grade enclosure that does not allow space for personnel access and is subject to flooding. 2.6 Surface Operable A term indicating that the switch and its accessories are operable from above grade. 2.7 Vault Mounted A term indicating the switch and its accessories are operable from floor level with all handles and elbows facing the operator. 2.8 Way A three-phase circuit entrance to a switching assembly. 2.9 Switched Way A way connected to the bus through a three-pole, gang operated switch. 2.10 Solid Tapped Way A way solidly connected to the bus. 3. Construction Requirements 3.1 Electrical The switch shall utilize vacuum interrupters having load and emergency fault break capabilities and shall have minimum life of 3,000 600A interruptions without changing insulation or replacing parts. 3.2 Bussing All internal switch bussing shall be copper. 3

3.3 Grounding Provision One stainless steel grounding pad with a 1/2 13 NC hole, 7/16 (11.1 mm) deep, shall be provided for each way and shall be located near the center bushing of each way. 3.4 Ratings Ratings for the Unit / System Voltage Load interruption arcing shall take place in a vacuum to keep insulation clean and system switching transients to a minimum. Nominal Voltage (Series) 15kV 25kV Maximum Design Voltage 15.5kV 27kV Device Load Break Switch Load Break Switch BIL Phase-to-Phase, Phase-to-Ground 125kV 125kV BIL Across Open Contacts 95kV 125kV One Minute Withstand (60Hz) 34kV 40kV Continuous Current 600A 600A Load Switching 600A 600A Load Switching Operations at Full Load Maximum Interrupting Current (Symmetrical) Number of Fault Interruptions (12.5kA) Maximum Emergency 3-Time Interrupting (Symmetrical) Momentary & Make and Latch (Asymmetrical) = Not Applicable 3,000 3,000 2,000A 2,000A 20,000A 20,000A 3.5 Tank Construction 3.5.1 The switch tank shall be made of AISI 304 Stainless steel completely welded using AISI 308 filler to maintain corrosion resistance properties. 3.5.2 All bushings and bushing wells to be welded to make them an integral part of the tank. 3.5.3 All tank penetrations shall be double o-ring sealed. 3.5.4 No external portion of the tank or accessories shall trap water. 3.5.5 Switch tanks shall be equipped with mounting provisions (such as feet or support rails) and shall include provision for anchoring the tank to the mounting stand. 3.5.6 Lifting provisions of AISI 304 stainless steel shall be welded to the tank so that the switch will remain level when being lifted. The provisions shall be designed and located to avoid interference between lifting slings and any attachments (bushings, switch handles, etc.). 4

3.5.7 Optional parking stands shall be provided and located to allow each way to be parked with a minimum elbow and cable movement distance. Some designs do not allow for a parking stand to be provided for every bushing or bushing well. 3.6 Mounting Stand An optional mounting stand shall be made available to which the switch shall be bolted. The stand shall elevate the switch to a convenient operating height and shall be of hot-dip galvanized carbon steel or stainless steel. 4. Dielectric SF 6 shall be provided as insulation. A color coded pressure gauge shall be provided with colors to indicate safe and unsafe operating pressures. A Dilo valve shall be provided to add SF 6 if required. A chart of temperature versus correct tank pressure for the temperature shall be provided near the pressure gauge. 5. Manual Operating Provisions 5.1 Manual operating handles shall move in to close and out to open. The direction of operation shall be apparent. 5.2 Manual operating handles shall be located where they can be operated either to open or to closed positions from the surface with standard live line tools and/or a lanyard. The force required to operate the handle shall be such that one man in a standing position can readily operate it without standing directly over the switch. 5.3 The switch mechanism shall be designed so that operation does not require any special skills, and the closing and opening speeds of the contacts are independent of the speed at which the operating handle is operated. 5.4 Manual operating handles shall be capable of being padlocked in both the open and closed positions. 6. Switch Operating Mechanism 6.1 The switch shall be equipped with an internal operating mechanism design so that speed of opening and closing of the interrupter contacts will be independent of the external operator. All contacts shall open or close simultaneously. 6.2 The switch shall be quick-make, quick-break type. Contacts shall be stable in open and closed positions without use of mechanical latches, sear pins, or detents. 7. Position Indicators 7.1 Switches shall be provided with position indicators or other suitable means that clearly and positively indicate the open and closed positions of the contacts. 7.2 The indicators shall be visible from the operating location. 8. Motor Operating Provisions Provisions for motor operators shall be made available as an optional feature. 9. Terminations The switch bushings shall accommodate cable terminations in accordance with ANSI/IEEE std 386-1977[3]. 5

10. Bushing Designation The switch bushings shall be identified and legibly marked adjacent to each bushing with the appropriate phase designation, using a nameplate of stainless steel or other corrosion resistant material. 11. Nameplate 11.1 A nameplate of stainless steel shall be provided. 11.2 The nameplate shall be tack welded securely to the top of the tank by means of AISI 308 stainless steel filler. 11.3 All letters, schematics, and numbers shall be photo engraved or stamped on the nameplate. 11.4 The nameplate shall contain at least the following information: 11.4.1 The word switch 11.4.2 Name of manufacturer 11.4.3 Date of manufacture (month and year, for example, 1-90) 11.4.4 Serial number 11.4.5 Model or style number 11.4.6 Rated maximum voltage 11.4.7 Rated impulse withstand voltage 11.4.8 Rated continuous current 11.4.9 Rated load interrupting current 11.4.10 Rated momentary current 11.4.11 Rated making current 11.4.12 A three-line bushing-oriented schematic diagram, using standard symbols (may be put on a separate nameplate) 11.4.13 Total weight (including insulating medium) 11.4.14 Type and quantity of insulating medium 12. Testing Requirements 12.1 Tank The finished tank will be pressurized to 15 pounds per square inch and tested for leaks using suitable leak detection methodology. 12.2 Electrical 12.2.1 34kVAC hi-pot for 1 minute phase-to-phase, phase-to-ground, and across open contacts on all ways. Use 40kV on 27kV rated switches. 12.2.2 Continuity test all circuits. 12.2.3 Resistance test all circuits. 12.2.4 Test reports certifying the vacuum switch conforms to ANSI C37.71 Test Sequence Paragraph 5.1.5 shall be submitted. 13. Shipping Requirements 13.1 The switch shall be completely assembled, including the correct amount of insulating medium. 6

13.2 Switches shall be properly packaged and braced to prevent damage during shipment. 14. Documentation Instructions and checklists for the inspection, installation, and maintenance of the switch shall be provided. 15. Standards When the standards referred to in this document are superseded by a revision, the latest revision shall apply. 15.1 C37.71-1984 ANSI Requirements for Three-Phase Manually Operated Subsurface Load- Interrupting Switches for Alternating-Current Systems, or latest revision. 15.2 ANSI/IEEE std 386-1977, Separable Insulated Connectors for Power Distribution Systems above 600V, or latest revision. 7