Research on Transient Stability of Large Scale Onshore Wind Power Transmission via LCC HVDC

Similar documents
Experience on Technical Solutions for Grid Integration of Offshore Windfarms

Wind Power Plants with VSC Based STATCOM in PSCAD/EMTDC Environment

CHAPTER 3 TRANSIENT STABILITY ENHANCEMENT IN A REAL TIME SYSTEM USING STATCOM

FAULT ANALYSIS OF AN ISLANDED MICRO-GRID WITH DOUBLY FED INDUCTION GENERATOR BASED WIND TURBINE

Integration of Large Wind Farms into Electric Grids

Analysis of Grid Connected Solar Farm in ETAP Software

CIGRE US National Committee 2013 Grid of the Future Symposium. Facilitating Bulk Wind Power Integration Using LCC HVDC

POWER TRANSMISSION OF LOW FREQUENCY WIND FIRMS

Grid code Compliance and Renewable Energy Projects. Mick Barlow, Business Development Director, S&C Electric, United Kingdom

Statcom Operation for Wind Power Generator with Improved Transient Stability

Evaluation of the Performance of Back-to-Back HVDC Converter and Variable Frequency Transformer for Power Flow Control in a Weak Interconnection

Experiences with Wind Power Plants with Low SCR

(by authors Jouko Niiranen, Slavomir Seman, Jari-Pekka Matsinen, Reijo Virtanen, and Antti Vilhunen)

ECEN 667 Power System Stability Lecture 19: Load Models

CHAPTER 5 FAULT AND HARMONIC ANALYSIS USING PV ARRAY BASED STATCOM

Fuzzy based STATCOM Controller for Grid connected wind Farms with Fixed Speed Induction Generators

Shunt Capacitor Bank Protection in UHV Pilot Project. Qing Tian

Implementation of FC-TCR for Reactive Power Control

Journal of American Science 2015;11(11) Integration of wind Power Plant on Electrical grid based on PSS/E

TRANSMISSION LOSS MINIMIZATION USING ADVANCED UNIFIED POWER FLOW CONTROLLER (UPFC)

ABB FACTS Grid connection of Wind Farms

INSTALLATION OF CAPACITOR BANK IN 132/11 KV SUBSTATION FOR PARING DOWN OF LOAD CURRENT

COMPARISON OF DIFFERENT METHODS FOR EXCITATION OF SYNCHRONOUS MACHINES

The Application of Power Electronics to the Alberta Grid

ABB POWER SYSTEMS CONSULTING

Comparative Analysis of Integrating WECS with PMSG and DFIG Models connected to Power Grid Pertaining to Different Faults

Simulated Switching Transients in the External Grid of Walney Offshore Wind Farm

International Journal Of Global Innovations -Vol.2, Issue.I Paper Id: SP-V2-I1-048 ISSN Online:

Battery Energy Storage System addressing the Power Quality Issue in Grid Connected Wind Energy Conversion System 9/15/2017 1

ABB Wind Power Solution

ELG4125: Flexible AC Transmission Systems (FACTS)

Voltage Sag Mitigation in IEEE 6 Bus System by using STATCOM and UPFC

Simulation of real and reactive power flow Assessment with UPFC connected to a Single/double transmission line

Accidental Islanding of Distribution Systems with Multiple Distributed Generation Units of Various Technologies

Enhancement of Power Quality in Transmission Line Using Flexible Ac Transmission System

Use of STATCOM for Improving Dynamic Performance of Wind Farms Connected in Power Grid

Low-Frequency AC Transmission for Offshore Wind Power

Design and Implementation of an 11-Level Inverter with FACTS Capability for Distributed Energy Systems

Squirrel cage induction generator based wind farm connected with a single power converter to a HVDC grid. Lluís Trilla PhD student

Integrating Large Supplies of Wind Power - System Performance and Maintaining Quality of Supply in the Transmission Network

Supercapacitor Based Power Conditioning System for Power Quality Improvement in Industries

Wind Farm Evaluation and Control

Georgia Transmission Corporation Georgia Systems Operations Corporation

CHAPTER 6 POWER QUALITY IMPROVEMENT OF SCIG IN WIND FARM USING STATCOM WITH SUPERCAPACITOR

Stability Study of Grid Connected to Multiple Speed Wind Farms with and without FACTS Integration

Power Quality Improvement Using Statcom in Ieee 30 Bus System

Transient reactive power characteristics of HVDC during commutation failure and impact of HVDC control parameters

Faults Mitigation Control Design for Grid Integration of Offshore Wind Farms and Oil & Gas Installations Using VSC HVDC

Paper ID: EE19 SIMULATION OF REAL AND REACTIVE POWER FLOW ASSESSMENT WITH FACTS CONNECTED TO A SINGLE TRANSMISSION LINE

Targeted Application of STATCOM Technology in the Distribution Zone

ABB November 16, 2016 Slide 1

THE IMPORTANCE OF INTEGRATING SYNCHRONOUS COMPENSATOR STATCOM IN WIND POWER PLANT CONNECTED INTO THE MEDIUM VOLTAGE GRID

The Effect Of Distributed Generation On Voltage Profile and Electrical Power Losses Muhammad Waqas 1, Zmarrak Wali Khan 2

APPLICATION OF STATCOM FOR STABILITY ENHANCEMENT OF FSIG BASED GRID CONNECTED WIND FARM

Dynamic Study of Bonaire Island Power System: Model Validation and Project Experience

The 1,400-MW Kii-Channel HVDC System

Lab Validation of PV Solar Inverter Control as STATCOM (PV-STATCOM) Rajiv K. Varma and Ehsan Siavashi

Review paper on Fault analysis and its Limiting Techniques.

International Journal of Scientific & Engineering Research, Volume 6, Issue 10, October ISSN

Question Question 1.2-8

Hamdy S. K. El-Goharey, Walid A. Omran, Adel T. M. Taha

Power Flow Simulation of a 6-Bus Wind Connected System and Voltage Stability Analysis by Using STATCOM

Introduction CONTENT Future of offshore wind energy in Europe Offshore wind energy in Spain Alternatives to the transmission system to the grid Compar

A novel synthetic test system for thyristor level in the converter valve of HVDC power transmission

REDUCING VULNERABILITY OF AN ELECTRICITY INTENSIVE PROCESS THROUGH AN ASYNCHRONOUS INTERCONNECTION

High Voltage Direct Current and Alternating Current Transmission Systems Conference. August Nari Hingorani

Workshop on Grid Integration of Variable Renewable Energy: Part 1

Transient Stability Improvement of Squirrel Cage Induction Wind Turbine Generator using Plugging Mode

Examples of Electric Drive Solutions and Applied Technologies

Enhancement of Transient Stability Using Fault Current Limiter and Thyristor Controlled Braking Resistor

Dynamic Reactive Power Control for Wind Power Plants

COMPARISON BETWEEN ISOLATED AND GRID CONNECTED DFIG WIND TURBINE

World Scientific Research Journal (WSRJ) ISSN: Multifunctional Controllable and Detachable Bicycle Power Generation /

An Alternative to Reduce Medium-Voltage Transient Recovery Voltage Peaks

China. Fig. 1 Chain SVG Electrical Diagram

Cascading Fault in AC/DC Hybrid Power Grid Xinzhou Dong

A Case Study on Aggregate Load Modeling in Transient Stability Studies

DYNAMIC BEHAVIOUR OF SINGLE-PHASE INDUCTION GENERATORS DURING DISCONNECTION AND RECONNECTION TO THE GRID

Electric Power System Under-Voltage Load Shedding Protection Can Become a Trap

POWER QUALITY IMPROVEMENT BASED UPQC FOR WIND POWER GENERATION

Cost Benefit Analysis of Faster Transmission System Protection Systems

Fuzzy Based Unified Power Flow Controller to Control Reactive Power and Voltage for a Utility System in India

Power Transmission Solutions Grid Access

Rural electrification using overhead HVDC transmission lines

Experimental Resultsofa Wind Energy Conversion Systemwith STATCOM Using Fuzzy Logic Controller

Aggregation of plug-in electric vehicles in electric power systems for primary frequency control

A Cost Benefit Analysis of Faster Transmission System Protection Schemes and Ground Grid Design

ENHANCEMENT OF ROTOR ANGLE STABILITY OF POWER SYSTEM BY CONTROLLING RSC OF DFIG

Next Generation of UHVDC System. R. Montaño, D Wu, L. Arevalo, B. Jacobson ABB - HVDC Sweden

Fifteenth National Power Systems Conference (NPSC), IIT Bombay, December 2008

Electrical grid stability with high wind energy penetration

Induction Generator: Excitation & Voltage Regulation

Full-Scale Medium-Voltage Converters for Wind Power Generators up to 7 MVA

Protective firing in LCC HVDC: Purposes and present principles. Settings and behaviour. V. F. LESCALE* P. KARLSSON

Benefits of HVDC and FACTS Devices Applied in Power Systems

Reactive power support of smart distribution grids using optimal management of charging parking of PHEV

Published by: PIONEER RESEARCH & DEVELOPMENT GROUP ( 201

Islanding of 24-bus IEEE Reliability Test System

NEWFOUNDLAND AND LABRADOR HYDRO GULL ISLAND TO SOLDIERS POND HVDC INTERCONNECTION DC SYSTEM STUDIES VOLUME 1

ABB Inc. Public Service Company of New Mexico Broadview Full Buildout Affected PSLF Study

Transcription:

Research on Transient Stability of Large Scale Onshore Wind Power Transmission via LCC HVDC Rong Cai, Mats Andersson, Hailian Xie Corporate Research, Power and Control ABB (China) Ltd. Beijing, China rong.cai@cn.abb.com, mats.andersson@cn.abb.com, hailian.xie@cn.abb.com Abstract Wind power has a booming development in the world in recent years. In some countries, large scale and long distance are two prominent characteristics of the wind power integration and transmission market, e.g. China and US etc. LCC HVDC hence becomes one of the attractive wind power transmission solutions. A transient stability research was done under different operation conditions for a large scale onshore wind power LCC HVDC transmission system. The results are presented in this paper. It indicates the key features and factors that needs attention during the design of a large scale wind power LCC HVDC transmission system. Keywords-large scale, wind power, LCC HVDC transmission, transient stability I. INTRODUCTION To reduce the emission level of CO 2 and improve the global environment, the utilization of clean energy is greatly encouraged by many countries. Wind power, as one type of clean energy, has had a booming development in the world in recent years. In some countries, large scale and long distance are two prominent characteristics of wind power integration and transmission market, e.g. China and US etc. LCC HVDC hence becomes one of the attractive wind power transmission solutions. Based on a 8 W large scale onshore wind power LCC HVDC transmission system, research of transient stability was done under different operation conditions, and time domain simulation results are presented in this paper. This will indicate the key features and factors that needs attention during the design of a large scale onshore wind power LCC HVDC transmission system. The configuration of the studied system is introduced in section II. Transient stability research under different operation conditions are presented in section III. In section IV, the influence of wind converter parameters on the system transient stability is discussed. The conclusions are presented in section V. II. CONFIURATION OF THE STUDIED SYSTEM This research is carried out in an 8 W wind power LCC HVDC transmission system, which is simulated in PSCAD/EMTDC. The configuration of the studied system is showed in Fig. WT5 (.568W) R5 WT2 (.568W) WT4 (.568W) B5/2 L5 Pi equivalent parameters of WT connection lines and (.568W) transformers In the wind farm.568w wind farm R2 B2/2 R B/2 L2 B2/2 L B/2 WFB2 FC2 & STATCOM2 WFB WF WFC TR 35/33 kv (5 km) FC & STATCOM TR2 WF2 WT3 (.568W) WFB3 WF3 WFC2 TR3 L3 R3 (5 km) B3/2 B3/2 B5/2 R4 B4/2 L4 B4/2 FC5 & STATCOM5 WT6 (.568W) WFB6 WF6 R6 B6/2 L6 B6/2 WFB4 WFB5 WF5 WFC3 TR5 (5 km) TR6 FC6 & STATCOM6 WT7 (.568W) WFB7 WF7 WFC4 R7 B7/2 L7 B7/2 FC7 & STATCOM7 WT8 (.568W) WFB8 WF8 R8 B8/2 L8 B8/2 FC8 & STATCOM8 TR8 TR7 FC4 & STATCOM4 ( km) ( km) (5 km) FC3 & STATCOM3 TR4 TR TR2 WF4 B2 ( km) ( km) B TR9 33/75 kv Fig. Overview diagram of the studied system In the studied system, a 2.5 W (installation capacity) wind farm cluster is composed of eight.568 W wind farm sub clusters. Each.568 W wind farm sub cluster consists of seven 224 MW (2 x 2 MW PMS or DFI type WT) wind farms, in which % PMS or % DFI type WTs are used. Each wind turbine is connected to a 35 kv bus via a.69/35 kv transformer and AC cable. Then the wind farm is connected to a 33 kv bus via a 35/33 kv transformer. Limited by the simulation capability of PSCAD/EMTDC, the.568 W wind farm sub cluster is represented by a single machine based aggregation model and equivalent π line (equivalent to the transformer and 35 kv AC grid in the wind farms) with a length of m. A detailed description about aggregation methods used for.568 W wind farm sub cluster model is presented in []. The terminal voltage of this.568 W wind farm aggregation model is 35 kv. TR (22 km) (6 km) B3 B4 Equivalent AC grid Ls (2 km) AC FC&STATCOM B5 Equivalent AC grid 2 Ls2 AC2

The supporting AC system connected to rectifier and inverter AC bus of the HVDC system (see AC grid and 2 in Fig.) are simulated as an ideal voltage source in series with equivalent impedance for corresponding short circuit power level. A bipolar LCC HVDC transmission system with rated voltage of ± 8 kv and rated power of 8 W, which includes two 2 pulse converter groups per pole, is used to transmit wind power. According to Chinese standard [2], a STATCOM is connected at the terminal of each.568 W wind farm sub cluster to provide dynamic reactive power compensation. Similar to realistic situation, a fixed capacitor (FC) is also shunt connected at the wind farm sub cluster terminal to work together with the STATCOM for reactive power compensation, as showed in Fig. (bus WFB WFB8). For bus WFB, WFB3, WFB5 and WFB7, the capacity of STATCOM and FC are ± 25 Mvar and 65 Mvar respectively. For bus WFB2, WFB4, WFB6 and WFB8, the capacity of STATCOM and FC are ±5 Mvar and 45 Mvar respectively. These capacities are designed according to load flow calculation. More detailed parameters of the studied system are presented in [3]. By considering different operation conditions with different WT types and variable power sources at the sending end of HVDC system, the following four scenarios have been used for the research discussed in later sections: - Scenario : % FPC type WTs, 8 W wind power - Scenario 2: % FPC type WTs, 6 W wind power and 2 W coal power - Scenario 3: 75% DFI type WTs and 25% FPC type WTs, 8 W wind power (WF 6 are DFI type WT; WF7 and 8 are FPC type WT) - Scenario 4: 75% DFI WTs and 25% FPC type WTs, 6 W wind power (WF 6 are DFI type WT; WF7 and 8 are FPC type WT) and 2 W coal power Except for sub-section C of section III and section IV, a SCR (Short Circuit Ratio) of 3 is used for AC grid, and SCR of 5 is used for AC grid 2 (see Fig.) in this research. III. TRANSIENT STABILITY UNDER DIFFERENT OPERATION CONDITIONS In this section, the typical simulation results of transient stability under different operation conditions are presented and discussed. A. Different fault locations To evaluate the system performance when faults occurs at different locations, a three-phase-to-ground fault was applied at both rectifier and inverter station in Scenario. The RMS voltage at the terminal of all wind farms, rectifier AC voltage and of the HVDC system are presented in Fig. 2. Comparing RMS voltage at the terminal of all wind farms, the transient AC overvoltage caused by inverter AC fault is higher than the one caused by rectifier AC fault. This is due to the following reasons: For a rectifier AC fault, it shows as voltage dip in rectifier AC system and the voltage at wind farm terminal is decreased during the fault. If the controller response of wind converter adapts to the strength of rectifier AC network (i.e. slow enough), the transient AC overvoltage only occurs at the terminal of wind farms after fault release. For inverter AC fault, AC overvoltage will occur quickly after fault occurrence (around 22 ms in our simulations, depending on the controller response speed of wind converter) and occurs after fault release. This is due to the fact that too much excessive reactive power flows from HVDC system to AC system, which is caused by the rectifier of the HVDC system cannot consume the reactive power provided by AC filter and shunt capacitor banks because of no DC power transmission from rectifier to inverter AC network. The AC overvoltage is higher if the supporting rectifier AC network is weaker. Thus, this is the most serious fault in the system. WF - 6 RMS WF - 6 RMS 4 3 2.5.5 2 4 3 2.5.5 2 8 6 4 2.5.5 2.5.5.5 2 4 3 2 Fig. 2 Three-phase-to-ground fault (start at.2 s and release at.3 s) applied at rectifier and inverter station in Scenario B. Different types of wind turbine generator (WT) It is also interesting to check the system transient behavior with different type of WTs under the same fault condition. A three-phase-to-ground fault was applied at both rectifier.5.5 2 4 3 2.5.5 2 8 6 4 2.5.5 2 -.5.5 2

and inverter station in the system of Scenario and Scenario 3. The results are presented in Fig. 2 and 3. WF - 6 RMS WF - 6 RMS 4 3 2 2 3 4 5 6 7 4 3 2 2 3 4 5 6 7 8 6 4 2 2 3 4 5 6 7.5 2 3 4 5 6 7 4 3 2 2 3 4 5 6 7 4 3 2 2 3 4 5 6 7 8 6 4 2 2 3 4 5 6 7-2 3 4 5 6 7 Fig. 3 Three-phase-to-ground fault (start at.2 s and release at.3 s) applied at rectifier and inverter station in Scenario 3 Comparing Fig. 2 with Fig. 3, it is found that the transient AC overvoltage at all wind farm terminals in the system of Scenario 3 is lower than the corresponding ones in the system of Scenario. One possible reason is that the DFI consumes more reactive power than FPC during fault recovery. Thus, overvoltage is avoided. However, it causes a longer recovery time. C. Different strengths of rectifier AC supporting networks In reality, the system strength might be quite different. Particularly, the rectifier AC supporting network is quite weak in some cases. Thus, it s worth to check the system performance with different strengths of rectifier AC supporting network. The simulations were done for Scenario and 3 by varying the strength of the rectifier AC supporting network. To guarantee the system get successful fault recovery, the simulation results showed that the minimum requirement on the strength of rectifier AC supporting network in our studied system is: For Scenario, SCR at rectifier station is 2 (SCR_rec = 2). Typical results are presented in Fig. 4. For Scenario 3, SCR at rectifier station is 3 (SCR_rec = 3). WF RMS (SP) (pu) WF RMS (SP) (pu) 4 3 2.5.5 2 4 3 2.5.5 2 8 6 4 2.5.5 2.5.5.5 2 5 4 3 2 5.5.5 4 3 2.5.5 8 6 4 2.5.5 -.5.5 Fig. 4 Three-phase-to-ground fault (start at.2 s and release at.3 s) applied at rectifier station and inverter station in Scenario, blue line: SCR at rectifier station is 3; green line: SCR at rectifier station is 2 In our studied system, the system cannot get recovery from the fault if a weaker rectifier AC supporting network is connected. As expected, the results presented in Fig. 4 showed that the transient AC overvoltage is higher (especially for the inverter AC fault) in the system with weaker rectifier AC supporting network (see the green lines in of Fig. 4). D. Different configurations of wind power AC collection grid According to N- security criteria, a system should operate successfully after tripping any single component in the system. As a typical N- criteria test, a permanent fault applied at bus B2 (see Fig. ) followed by a trip of one line between bus B2 and B3 (see Fig. ) after ms was tested. In the system showed in Fig., two 22 km 75 kv lines are connected in parallel between bus B2 and B3. If a permanent fault occurred at bus B2/B3, one line will be tripped after ms. In the simulations, it was found that the system cannot get recovery from the fault after tripping one line (see of Fig. 5). This is due to the fact that the WT connection at bus B2 becomes very weak if only one line is

connected between bus B2 and B3, even though the transmission capacity of single line is enough (i.e. theoretically, single line could transmit such amount of power). Another case with three 22 km 75 kv lines in parallel connected between bus B2 and B3 was also tested. The system can get successful fault recovery after tripping one line between B2 and B3 (see of Fig. 5) WF - 6 RMS WF - 6 RMS 4 3 2.5.5 2 2.5 3 3.5 4 4.5 4 3 2.5.5 2 2.5 3 3.5 4 4.5 8 6 4 2.5.5 2 2.5 3 3.5 4 4.5 -.5.5 2 2.5 3 3.5 4 4.5 4 3 2.5.5 2 2.5 3 3.5 4 4.5 4 3 2.5.5 2 2.5 3 3.5 4 4.5 8 6 4 2.5.5 2 2.5 3 3.5 4 4.5 -.5.5 2 2.5 3 3.5 4 4.5 Fig. 5 A permanent three-phase-to-ground fault (start at.2 s and one line between bus B2 and B3 was tripped at.3 s) applied at bus B2 in the system of Scenario (: two lines connected between B2 and B3 before fault; : three lines connected between B2 and B3 before fault) The phase angle difference, which can indicate the impedance of connected lines, was measured between bus B and B3 (Phdiff_BB3, two 6 km 75 kv lines in parallel connected) and between bus B2 and B3 (Phdiff_B2B3). The results are presented in Fig. 6. The phase angle difference between bus B and B3 is around 3.4 before and after fault in both cases. In the system with two lines connected in parallel, the phase angle difference between B2 and B3 jumped from 2.4 before fault, to 27.2 after fault. If three lines are connected in parallel between B2 and B3, the phase angle difference jumped from 7.9 before fault, to 2.7 after fault (see Fig. 7). Comparing the phase angle difference between B2 and B3 in these two cases (Fig. 6 and 7), it is clearly observed that the B2 to B3 link is too weak to handle the power flow with only one line in combination with the performance of the WT control even though the transmission capacity of a single line is enough. Phdiff_BB3 Phdiff_B2B3 5 5.5.5 2 2.5 3 3.5 4 4.5 6 4 2-2.5.5 2 2.5 3 3.5 4 4.5 Fig. 6 A permanent three-phase-to-ground fault (start at.2 s and one line between bus B2 and B3 was tripped at.3 s) applied at bus B2 in the system of Scenario with two lines connected between B2 and B3 before fault Phdiff_BB3 Phdiff_B2B3 5 5.5.5 2 2.5 3 3.5 4 4.5 6 4 2-2.5.5 2 2.5 3 3.5 4 4.5 Fig. 7 A permanent three-phase-to-ground fault (start at.2 s and one line between bus B2 and B3 was tripped at.3 s) applied at bus B2 in the system of Scenario with three lines connected between B2 and B3 before fault E. Impact of a thermal power plant connected to the rectifier AC network In this research, a 2 W thermal power plant is used in Scenario 2 and 4, and is simulated as a synchronous generator. To check the influence of thermal power plant on the system transient performance, a comparison was made between the system with and without thermal power plant for the same type of fault. The simulation results of the system with % FPC type WT and with 75% DFI type WT are presented in Fig. 8 and 9 respectively. The following information can be observed from the results showed in the figures: For the system with % FPC type WT, there is no big difference between the system with and without thermal power plant for a three-phase-to-ground fault occurred at rectifier station. However, the AC voltage at wind farm terminal during the fault is easier to get stable in the system of Scenario 2 (with 2 W thermal power plant) because of the stronger rectifier AC network (the thermal power plant increased the strength of rectifier AC network). For a three-phaseto-ground inverter ac fault, the AC overvoltage occurred at wind farm terminals (WF5 WF8) is higher in the system of Scenario 2 (with 2 W thermal power plant). These results are obtained by using the same controller parameters of wind converters in the system with and without thermal power plant.

For the system with 75% DFI type WT, the transient AC overvoltage at the wind farm terminal is lower and the system stabilizes faster after fault release in the system of Scenario 4 (with 2 W thermal power plant) (see green line in of Fig. 9). This is due to the strength of rectifier AC network is increased because of adding thermal power plant and reducing the wind power output. Comparing the results obtained in the system with 75% DFI type WT with the results obtained in the system with % FPC type WT, the following observations are made: From the transient AC overvoltage level (at wind farm terminals) point of view, the controller response speed of FPC is more sensitive to the strength of rectifier AC network. From the fault recovery point of view, the system with FPC type WT is faster to get fault recovery. WF RMS (SP) (pu) WF RMS (SP) (pu) Fig. 8 Three-phase-to-ground fault (start at.2 s and release at.3 s) applied at rectifier and inverter station, blue line: Scenario ; green line: Scenario 2 IV. 4 3 2.5.5 2 4 3 2.5.5 2 8 6 4 2.5.5 2.5.5.5 2 4 3 2.5.5 2 4 3 2.5.5 2 8 6 4 2.5.5 2 -.5.5 2 INFLUENCE OF WIND CONVERTER PARAMETERS ON TRANSIENT STABILITY In a large scale onshore wind power transmission system, the AC overvoltage level is one of the sensitive factors for transient stability. This is due to the fact that the wind converters are more sensitive to overvoltage than other conventional equipment, e.g. transformer etc. According to Chinese grid code [2], the wind converter will trip if the AC voltage is higher than.2 p.u. WF RMS (SP) (pu) WF RMS (SP) (pu) 4 3 2 2 3 4 5 6 7 4 3 2 2 3 4 5 6 7 8 6 4 2 2 3 4 5 6 7.5 2 3 4 5 6 7 4 3 2 2 3 4 5 6 7 4 3 2 2 3 4 5 6 7 8 6 4 2 2 3 4 5 6 7-2 3 4 5 6 7 Fig. 9 Three-phase-to-ground fault (start at.2 s and release at.3 s) applied at rectifier and inverter station, blue line: Scenario 3; green line: Scenario 4 Looking at the RMS voltage at WF and 8 terminal showed in of Fig. 4, the AC overvoltage of green lines (rectifier AC system with SCR of 2) caused by fault is higher than.2 p.u. To explore ways to limit the AC overvoltage at wind farm terminal, the following two simulation cases were made and compared in the system of Scenario (SCR of rectifier AC system is 2). Case : Wind converter with fast controller response Case 2: wind converter with slow controller response The detailed controller parameters used in these two cases are presented in table. A three-phase-to-ground fault was applied at the inverter station in these two cases. The simulation results are presented in Fig.. Comparing the results obtained from these two cases, it is found that the transient AC overvoltage at wind farm terminal could be limited by slowing down the controller response speed of wind converter.

By testing more cases in our research, it is proved that the AC overvoltage at wind farm terminal could be limited if the controller response speed of wind converter could adapt well enough to rectifier ac system strength. The controller response of wind converter should be slower if the rectifier ac system is weaker, which is similar finding as [4]. More methods to limit the AC overvoltage at wind farm terminal are discussed in [3]. Table The controller parameters used in FPC for the tested two cases Controller parameters of wind converter (FPC) PLL Current controller of SC controller of SC Reactive power controller of SC WF RMS (SP) (pu) Case Case 2 WF-4 WF5-8 WF-4 WF5-8 Kp.. Ti 5 5 Kp 2 2.5. Ti.. 5 Kp.3.3.. Ti Kp.3.5 2 5 Ti.4 5 4 3 2 5.5.5 4 3 2.5.5 8 6 4 2.5.5 -.5.5 Fig. Three-phase-to-ground fault (start at.2 s and release at.3 s) applied at inverter station in the system of Scenario, blue line: case ; red line: case 2 V. CONCLUSIONS An evaluation of the transient stability of a large scale onshore wind power LCC HVDC transmission system was done, and the results are presented in this paper. Based on the time domain simulations, the main conclusions could be drawn as below: The rectifier AC system strength, the configuration of wind power collection AC grid and the controller response speed of wind converters are important factors to significantly affect the transient stability of this type of system. Comparing with AC fault occurred in rectifier AC system, the AC fault occurred in inverter AC system is a more serious fault due to large amount of excessive reactive power in this system. The system cannot get successful fault recovery if the rectifier AC network is too weak (e.g. SCR lower than 2 in our studied system). To limit the AC overvoltage caused by fault at wind farm terminal, the controller response speed of wind converters should adapt to the strength of rectifier AC system. The controller response speed of wind converter should be slow if the rectifier AC network is weak. REFERENCES [] Xiaobo Yang, Chengyan Yue and Hailian Xie, An Aggregation Method of Permanent Magnet Synchronous enerators Wind Farm Model for Electromagnetic Transient Simulation Analysis, Power System Technology, Vol. 35, No.2, Feb. 2 [2] B/T 9963 2, Technical Rule for Connecting Wind Farm to Power System, Dec. 2 [3] Rong Cai, Mats Andersson and Hailian Xie, Methods for Transient AC Overvoltage Reduction at Wind Farm Terminal, Proceeding of 26 China International Conference on Electricity Distribution (CICED 26), 3 Aug. 26, Xi an, China [4] Australian Energy Market Operator, Wind Turbine Plant Capabilities Report 23 wind integration studies, 23