Actuators for Air and Gas Dampers

Similar documents
Actuators for Air and Gas Dampers

Actuators for Air and Gas Dampers

Actuators for air dampers and control valves of oil burners

Actuators for air dampers and control valves of oil burners

Actuators for air dampers and control valves of oil burners

ASZ... Potentiometers. Building Technologies Division. ASZxx.3x

For air dampers and control valves of oil or gas burners

SQN9... Damper Actuators. Building Technologies HVAC Products. SQN9..., front (covers removed) SQN9..., rear (covers fitted)

Actuators for air and gas dampers

For air / gas dampers and control valves of oil or gas burners

VKF41...C. Butterfly Valves. Building Technologies Division Industry Sector

VLF45... Hot Air Valves. Siemens Building Technologies HVAC Products

Electronic Ignition Module

Actuators. Building Technologies Division

Electromotoric Actuators

Connection Accessories for small Burner Controls

Electronic Ignition Equipment

SKPx5... Actuators for Gas Valves. Building Technologies HVAC Products SKP15... SKP25... / SKL25 SKP55... SKP75...

Electromotoric Actuators

VGD20... VGD40... Double Gas Valves. Siemens Building Technologies Landis & Staefa Division

Proportional controlling element

Electromotoric actuators

Electromotoric Actuators

VLF45... Hot Air Valves. Building Technologies Division

Gas Pressure Governors

LKS 160 FOR AIR DAMPERS ON MULTI-STAGE AND MODULATING BURNERS

Electromotoric Actuators

SAV Electronic Valve Actuator

Actuators for Fire Protection Dampers

Electrical data Nominal voltage AC/DC 24V Nominal voltage frequency 50/60Hz

SAX Electronic Valve Actuator

Actuators for Fire and Smoke Protection Dampers

Power consumption Wire/transformer sizing. Motor. Spring return. Motor. Spring return. EMC Low voltage directive

LKS 170 FOR AIR DAMPERS ON SINGLE, DUAL STAGE AND MODULATING BURNERS

Flowrite 599 Series SAX Electronic Valve Actuator Non-spring Return, 24 Vac, 3-Position Control

MF /MS Series

Differential Pressure Sensors

Eclipse Trilogy Actuator

Current consumption Auxiliary switch. Angle of rotation 90 (internal electrical stops) Running time

DA-053 Series. Overview. Applications. Features & Benefits. Datasheet. 53lb-in (6 Nm), Non-Spring Return Damper Actuators

Differential Pressure Sensors

Actuators for Fire and Smoke Protection Dampers

Actuators for Fire and Smoke Protection Dampers

Technical data. Safety notes

Air damper actuators

Air damper actuators

Use. Functions. OpenAir TM. Rotary version, modulating, with spring return, AC 24 V

GDB..3..1A GLB..3..1A

SCC Inc. VA Series. Technical Instructions. Document No. VA-3000 March 15, VA VKF Valve Actuator Assemblies with VKF Butterfly Valves

MA-5200 Series MA-5300 Series

DuraDrive MF /MS Series Non-spring Return Rotary Electronic Damper Actuators 24 Vac Three-position/Modulating

Technical data. Safety notes. Power consumption In operation At rest For wire sizing. 1.5 nominal torque 0.2 W 4 VA Auxiliary switch

Technical data. Safety notes. Power consumption In operation At rest For wire sizing. 1 nominal torque 0.2 W 2 VA Auxiliary switch

A44 W0...W2: Motorised actuator

WARNING WARNING. ECM3000 Control Motor User's Manual CAUTION NOTICE SAFETY PRECAUTIONS

SQL35.00 SQL85.00 SQK angle of rotation

Power Plugs for Proportional Valves (12 volt supply)

OpenAir Electric Damper Actuator GDE/GLB Series Non-spring Return Rotary 24 Vac 3-position Control

Electromotoric actuators

Modulating control valves with magnetic actuators, PN 16

Electromotoric Actuators

OpenAir Electric Damper Actuator GDE/GLB Series Non-spring Return, 24 Vac Floating Control, Rotary

EL5600 Series Electric Actuators for DN15 to DN100 Valves

Temperature Controller (Heat Pumps)

MX4X-6XXX Series MX4X-7XXX Series. Selection Guide. Applications. DuraDrive Series Actuators and Accessories

Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate

GMX On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 100 to 240 VAC

Type 231 ACTUATOR FOR DAMPERS. G R U N E R t h e. f r i e n d l y a l t e r n a t i v e. Actuator with rotation drive. 20 Nm 30 Nm

Commercial Actuator Selection Chart Non-Spring Return

Electric actuators for small valves

OpenAir GBB/GIB Series Electronic Damper Actuators Non-Spring Return, 24 Vac, Modulating Control

OpenAir GBB/GIB Series Electronic Damper Actuators Non-Spring Return, 24 Vac, Modulating Control

Actuators for heating, ventilation, air-conditioning 2. LM-4 -CD. Product Information Damper actuators. i

NFB24, NFB24-S, NFX24, NFX24-S On/Off, Spring Return, 24 V

Power consumption In operation At rest For wire sizing. Functional data Torque Motor Spring return. Rated impulse voltage Control pollution degree 3

ELECTRIC ACTUATOR MOD. VB015 MAINTENANCE AND INSTALLATION INSTRUCTIONS OF VALBIA ELECTRIC ACTUATORS

Non-Spring Return SMU... series

Electrical data Nominal voltage AC 230 V Nominal voltage frequency

Power consumption In operation At rest For wire sizing

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Power consumption In operation At rest For wire sizing. Connection Motor. Auxiliary switch

Electrical data Nominal voltage AC V / DC V Nominal voltage frequency

Technical data sheet. Technical data. Safety notes

Overview of types. Technical data. Safety notes

TZIM. Electropneumatic Analog Positioner 10/ EN

OpenAir Electric Damper Actuators GDE/GLB Series Non-spring Return Rotary 24 Vac - Modulating Control 0 to 10 Vdc

Technical data. Safety notes

OpenAir Electric Damper Actuators GDE/GLB Series Non-spring Return Rotary 24 Vac - Modulating Control 0 to 10 Vdc

Current consumption Auxiliary switch. Angle of rotation 90 (internal electrical stops) Running time

Actuators LKS Series. Combustion Solutions Burner & Boiler Control Europe

AKM 105, 115: Rotary actuator for ball valve

Electrical data Nominal voltage AC 24 V, 50/60 Hz DC 24 V

2-position electric actuators with Ball valves VBZ ½...11/4

Flowrite EA 599 Series SKD Electronic Valve Actuator 24 Vac 3-Position (Floating) Control

Electro-hydraulic actuators for valves

Differential pressure sensor

Boiler Management Unit (BMU)

2. A E LM Form-fit versions Linear adapter ZH-LM

LMB24-3 (-S)(-T) On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 24 V

Mounting and operating instructions EB 5801 EN. Electric Actuators Type 5801 (Rotary Actuator) Type 5802 (Linear Actuator)

Transcription:

7 815 SQM5..., gear train side with drive shaft no. 7 SQM5..., rear, version without second drive shaft end SQM5..., rear, version with 2 drive shaft ends Actuators for Air and Gas Dampers with electronic modules SQM5... Reversible electromotive actuators up to 40 Nm Running times from 10 to 90 seconds With 1 or 2 drive shaft ends; drive shafts can be exchanged or available as separate items Can be equipped with electronic modules for control and position feedback signal via steady signals Internal and external position indication Drive shaft and cam shaft can be separately disengaged Choice of UL-listed types for use in the U.S. and Canada Supplementary Data Sheets, refer to N7921 and N7922 The SQM5... and this Data Sheet are intended for use by OEMs which integrate the SQM5... in their products! Use The SQM5... actuators are used to drive air and gas dampers of oil and gas burners of medium to large capacity. They are used primarily for load-dependent control of the amounts of gas, oil and combustion air: In connection with 3-position or modulating controllers (e.g. 4...20 ma), or Directly by burner controls 06.10.2008 HVAC Products

Warning notes To avoid injury to persons, damage to property or the environment, the following warning notes must be observed! Only qualified staff may open, interfere with or modify the actuators! All activities (mounting, installation and service work, etc.) must be performed by qualified staff Before making any wiring changes in the connection area, completely isolate the plant from mains supply (all-polar disconnection). Ensure that the plant cannot be inadvertently switched on again and that it is indeed dead. If not observed, there is a risk of electric shock hazard Ensure protection against electric shock hazard by providing adequate protection for the connection terminals Protection against electric shock hazard is ensured by folding upwards cover of control unit (made of plastic), allowing safe setting of the cams when mains voltage is present Each time work has been carried out (mounting, installation, service work, etc.), check to ensure that wiring is in an orderly state Fall or shock can adversely affect the safety functions. Such actuators must not be put into operation even if they do not exhibit any damage Mounting notes Ensure that the relevant national safety regulations are complied with Standards and certificates Conformity to EEC directives - Electromagnetic compatibility EMC (immunity) - Low-voltage directive 2004/108/EC 2006/95/EC ISO 9001: 2000 Cert. 00739 ISO 14001: 2004 Cert. 38233 For use in the U.S. / Canada, the actuators carry type suffix «R» (see example) and are UL- and CSA-listed. Example: SQM50.480R1 Disposal notes The actuator contains electrical and electronic components and must not be disposed of together with domestic waste. Local and currently valid legislation must be observed. 2/12

Mechanical design Housing Drive motor Couplings Housing sections made of die-cast aluminium Covers made of impact-proof and heat-resistant plastic Reversible and locking-proof synchronous motor Driven shaft and cam shaft can be adjusted via 2 separately couplers, independent of the gear train Shaft can be disengaged from gear train and motor via manual operation of a coupler (pressure pin «K», refer to «Technical data»). Automatic reengagement Pressure pin «K...» - Disengagement of gear train / cam shaft by pressing pin «K1» 7815z07e/0908 Pressure pin "K1" - Disengagement of cam / gear train by pressing pin «K2» 7815z08e/0908 Pressure pin "K1" Cam shaft drive Adjustment of switching points Position indication Backlash-free gearing With rotating cams Scales beside the cams indicate the angle of the switching point Internally: Scale at the end of the drive shaft Black scale for counterclockwise rotation, single arrow on the cam Red scale for clockwise rotation, double arrow on the cam Externally: Scale in viewing window 3/12

Mechanical design (cont d) Electrical connections Gear train Drive shaft Actuator fixing Blade terminal on micro switch Screw terminals for «N» and «PE» Subassembly and fixing of wiring by means of removable Pg plastic insert possible Easy introduction of cables through large openings in the housing Fixing of Pg insert with all cables by means of a screw Maintenance-free gearwheels and bearings Secured with a removable circlip Easily exchangeable With corresponding shaft both sides transmission possible Fixing holes on the front of the housing and at the bottom Front fixing also possible from inside the housing Variable mounting height through the use of an extra adapter 4/12

Type summary (other types are available on request) When ordering, please give type reference according to following tables. Accessories are to be ordered separately. Actuators with premounted accessories are only available on request. AC 220 V -15 %...AC 240 V+10 %, 50 60 Hz ±6 % Standard types! (other versions on request) Torque and holding torque 3) Running time at 50 Hz for angular rotation 1) Auxiliary switches incl. 2 end switches Type of shaft Electronic module (integrated ex works) 5) Potentiometer (integrated ex works) 6) Type reference max. Nm 2) 90 130 Piece AGA AGA ASZ SQM50.260A2G4 10 10 s 14 s 4 --- 4 ) 56.41A27 12.33 SQM50.341A2 10 15 s 22 s 4 58.1 --- --- SQM50.341A2G3 10 15 s 22 s 4 58.1 56.41A27 12.30 SQM50.341A2K3 10 15 s 22 s 4 58.1 56.43A27 12.30 SQM50.381A2 10 15 s 22 s 8 58.1 --- --- SQM50.381A2G3 10 15 s 22 s 8 58.1 56.41A27 12.30 SQM50.441A2 10 30 s 43 s 4 58.1 --- --- SQM50.441A2G3 10 30 s 43 s 4 58.1 56.41A27 12.30 SQM50.480A2 15 30 s 43 s 8 --- 4 ) --- --- SQM50.480A2Z3 15 30 s 43 s 8 --- 4 ) 56.9A27 12.30 SQM50.481A2 10 30 s 43 s 8 58.1 --- --- SQM50.481A2G3 10 30 s 43 s 8 58.1 56.41A27 12.30 SQM50.481A2Z3 10 30 s 43 s 8 58.1 56.9A27 12.30 SQM50.482A2 15 30 s 43 s 8 58.2 --- --- SQM50.482A2Z3 15 30 s 43 s 8 58.2 56.9A27 12.30 SQM50.483A2Z3 15 30 s 43 s 8 58.3 56.9A27 12.30 SQM50.681A2 10 60 s 87 s 8 58.1 --- --- SQM53.482A2 20 30 s 43 s 8 58.2 --- --- SQM53.482A2Z3 20 30 s 43 s 8 58.2 56.9A27 12.30 SQM53.489A2 25 30 s 43 s 8 58.9 --- --- SQM54.480A2 25 30 s 43 s 8 --- 4 ) --- --- SQM54.482A2 20 30 s 43 s 8 58.2 --- --- SQM54.580A2Z3 25 45 s 65 s 8 --- 4 ) 56.9A27 12.30 SQM56.680A2 40 60 s 87 s 8 --- 4 ) --- --- SQM56.684A2G4 30 60 s 87 s 8 58.4 56.41A27 12.33 SQM56.684A2Z3 30 60 s 87 s 8 58.4 56.9A27 12.30 SQM56.687A2 40 60 s 87 s 8 58.7 --- --- SQM56.687A2G3 40 60 s 87 s 8 58.7 56.41A27 12.30 SQM56.687A2Z3 40 60 s 87 s 8 58.7 56.9A27 12.30 5/12

Type summary (other types are available on request) [cont d] AC 100 V -15 %...AC 110 V+10 %, 50 60 Hz ±6 % Standard types! (other versions on request) Torque and holding torque 3) Running time at 50 Hz for angular rotation 1) Auxiliary switches incl. 2 end switches Type of shaft Electronic module (integrated ex works) 5) Potentiometer (integrated ex works) 6) Type reference max. Nm 2) 90 130 Piece AGA AGA ASZ SQM50.480A1 15 30 s 43 s 8 --- 4 ) --- --- SQM50.480A1Z3 15 30 s 43 s 8 --- 4 ) 56.9A17 12.30 SQM50.483A1Z3 15 30 s 43 s 8 58.3 56.9A17 12.30 SQM53.480A1 25 30 s 43 s 8 --- 4 ) --- --- SQM53.482A1Z3 20 30 s 43 s 8 58.2 56.9A17 12.30 SQM56.687A1 40 60 s 87 s 8 58.7 --- --- SQM56.687A1Z3 40 60 s 87 s 8 58.7 56.9A17 12.30 AC 24 V -15 / +10 %, 50 60 Hz ±6 % Standard types! (other versions on request) Torque and holding torque 3) Running time at 50 Hz for angular rotation 1) Auxiliary switches incl. 2 end switches Type of shaft Electronic module (integrated ex works) 5) Potentiometer (integrated ex works) 6) Type reference max. Nm 2) 90 130 Piece AGA AGA ASZ SQM50.380A8 10 15 s 22 s 8 --- 4 ) --- --- SQM50.443A8 15 30 s 43 s 4 58.3 --- --- SQM50.444A8 15 30 s 43 s 4 58.4 --- --- SQM50.444A8Z3 15 30 s 43 s 4 58.4 56.9A87 12.30 SQM50.454A8 15 30 s 43 s 5 58.4 --- --- SQM50.483A8 15 30 s 43 s 8 58.3 --- --- SQM50.483A8Z3 15 30 s 43 s 8 58.3 56.9A87 12.30 1) At 60 Hz frequency, running times are about 17 % shorter 2) Based on 250,000 position changes 3) Refer to «Drive shafts» and «Torques», depending on voltage 4) Drive shaft to be ordered separately 5) For details, refer to Data Sheet N7922 6) For details, refer to Data Sheet N7921 6/12

Accessories Potentiometers ASZ... refer to Data Sheet N7921 - ASZxx.3x refer to Mounting Instruction M7921 (4 319 9604 0) - ASZxx.7xx refer to Mounting Instruction M7806 / M7808 / M7812 (4 319 2263 0) - ASZxx.8xx refer to Mounting Instruction M7806 / M7808 / M7812 (4 319 2263 0) - ASZxx.9xx refer to Mounting Instruction M7806 / M7808 / M7812 (4 319 2263 0) Mounting kit ASK33.9 - For fitting the SQM5... to butterfly valves VKF41..., always with drive shaft AGA58.1 - Refer to Mounting Instruction M7815.4 (4 319 9535 0) Pg insert - Inclusive sealing and screw, for SQM5... AGA55.2 Kit for shaft seal AGA55.5 - For sealing the shaft feedthrough and therewith for perfecting the degree of protection - On both sides shaft seals for actuator SQM5... - Packed as kit together with O-rings inclusive mounting screws - Refer to Mounting Instruction M7815.5 (74 319 0577 0) Spacer - Adapter for SQM10... / SQM20... - Refer to Mounting Instructions M7815.1 (4 319 9529 0) Adapter for actuator ME8 - Refer to Mounting Instruction M7815.2 (4 319 9536 0) Adapter for Honeywell Mod. III actuator - Refer to Mounting Instruction M7815.2 (4 319 9536 0) AGA57.1 AGA57.2 AGA57.3 Electronic modules AGA56... - For control of the actuator - Modular installable, complete with mounting frame and fixing screws - Refer for AGA56.1... Data Sheet N7922 and Mounting Instruction M7922.3 (4 319 9602 0) - Refer for AGA56.4... Data Sheet N7922 and Mounting Instruction M7922.2 (4 319 9542 0) - Refer for AGA56.9... Data Sheet N7922 and Mounting Instruction M7922.1 (4 319 9532 0) Drive shafts: Type of drive shaft Max. torque Type no. Order no. 10 mm dia., single-sided, Woodruff key to DIN 6888, equivalent to drive shaft of 10 Nm 1 AGA58.1 SQM10... 10 mm dia., single-sided, Woodruff key to DIN 6888, equivalent to drive shaft of SQM10..., packs of 10 pieces 10 Nm 1 AGA58.1(10) 12 mm dia., single-sided, Woodruff key to DIN 6888, equivalent to drive shaft of 20 Nm 2 AGA58.2 SQM20... 9 mm square, double-sided, equivalent to drive shaft of ME8 25 Nm 3 AGA58.3 9.5 mm square, double-sided, equivalent to drive shaft of Honeywell Mod. III 30 Nm 4 AGA58.4 9.5 mm square, double-sided, equivalent to drive shaft of Honeywell Mod. III, packs of 10 pieces 30 Nm 4 AGA58.4(10) 10 mm dia. gear train side, 9,5 square rear, Woodruff key to DIN 6888, equivalent to drive shaft of Honeywell Mod. SQM10... 10 6 AGA58.6 14 mm dia., single-sided with parallel key to DIN 6885, mandatory with SQM56... 40 Nm 7 AGA58.7 14 mm dia., single-sided with parallel key to DIN 6885, mandatory with SQM56..., packs of 10 pieces 40 Nm 7 AGA58.7(10) 12 mm square, single-sided 30 Nm 9 AGA58.9 Refer to Mounting Instruction M7815.3 (4 319 9534 0) 7/12

Technical data General unit data Environmental conditions Kind of current AC Operating voltage and frequency refer to «Type summary» Drive motor synchronous motor Power consumption 20 VA Angular rotation adjustable between 0! and max. 160 (scale range) Mounting position optional Degree of protection IP 54 (provided knockout holes remain closed for mounting or are closed off, with adequate cable entries) Cable entry 4 x Pg13.5 with thread Direction of rotation facing the gear train side: counterclockwise or clockwise (selectable), delivery: counterclockwise Torque refer to torque charts and drive shafts Holding torque max. torque Running time 10...90 s (refer to «Type summary») End and auxiliary switches - Type - Switching voltage - Switching capacity to DIN 41636 AC 24...250 V to CEE 24 / VDE 0630 7.5 (3) A, AC 250 V Number of end switches 2 Number of auxiliary switches max. 6 Drive shaft exchangeable Weight approx. 3.3 kg Storage DIN EN 60 721-3-1 Climatic conditions class 1K2 Mechanical conditions class 1M2 Temperature range without integrated -50...+60 C AGA56... Humidity < 95 % r.h. Transport DIN EN 60 721-3-2 Climatic conditions class 2K2 Mechanical conditions class 2M2 Temperature range without integrated -50...+60 C AGA56... Humidity < 95 % r.h. Operation DIN EN 60 721-3-3 Climatic conditions class 3K3 Mechanical conditions class 3M3 Temperature range without integrated -20...+60 C AGA56... Humidity < 95 % r.h. Condensation, formation of ice and ingress of water are not permitted! 8/12

Torques SQM50... Nm 30 25 MaxB - 22 20 MaxN - 15 10 5 50 Hz 1) > 60 s / 87 s > 45 s / 65 s 45 s / 65 s > 45 s / 65 s > 15 s / 22 s 34 s / 49 s 15 s / 22 s 7815z02/0102 AC 220...240 V -15 / +10 % AC 24 V -15 / +10 % 0 187 200 220 240 264 20 22 24 26,4 Volt Volt SQM53... / SQM54... Nm MaxB - 30 MaxN - 25 20 15 50 Hz 1) > 45 s / 65 s > 45 s / 65 s 30 s / 43 s 15 s / 22 s > 30 s / 43 s > 30 s / 43 s 7815z03/0102 10 5 AC 220...240 V -15 / +10 % AC 24 V -15 / +10 % 0 187 200 220 240 264 20 22 24 26,4 Volt Volt SQM56... Nm MaxB - 60 50 MaxN - 40 30 50 Hz 1) > 60 s / 87 s 45 s / 65 s 30 s / 43 s 60 s / 87 s > 45 s / 65 s 7815z04/0102 20 15 s / 22 s 10 AC 220...240 V -15 / +10 % AC 24 V -15 / +10 % 0 187 200 220 240 264 20 22 24 26,4 Volt Volt Legend 1) At 60 Hz frequency, running times are about 17 % shorter and torques are proportionally lower Each drive side is capable of delivering the maximum torque, but the total torque of both sides must not exceed the maximum permissible torque of actuator. With appropriate running time for 90 / 130 : Torque in continuous operation ------- Release or starting torque = short-time torque MaxN Max. permissible torque in continuous operation for all running times MaxB Max. permissible release or starting torque for all running times 9/12

Connection terminals Diagram shows the maximum number of switches (2 end and 6 auxiliary switches). On versions with fewer than 6 auxiliary switches, the higher numbers are not used. For example, the actuator version with 2 end and 2 auxiliary switches does not use switches V, VI, VII and VIII. Direction of rotation By exchanging the 2 motor connecting cables, the actuator s direction of rotation can be changed from counterclockwise to clockwise. Counterclockwise rotation Clockwise rotation Note When changing the direction of rotation from counterclockwise to clockwise, the cams must be readjusted. Clockwise rotation: Red scales on the cam shaft, double arrow on the cams. Counterclockwise rotation: Black scales on the cam shaft, single arrow on the cams. 10/12

Dimensions SQM5... Dimensions in mm 180 1) Identical with fixing points SQM1... / SQM2... 1 M6 3.5 113 80 132 Example: AGA58.4 8.5 164 7.5 Pg13.5 M6 52.5 52.5 M6 Pg13.5 M8 44.5 55.5 36 25 M6 M51) 41.5 55.5 44.5 M6 133 67 30 10 7815m06e/0908 25 25 52.5 52.5 58 4.6 dia. for self-tapping screws M5 180 25.5 8 20 9 10 3 AGA58.1 11.2 25.5 20 9 12 3 AGA58.2 13.2 20.5 21.5 9 9 11 9 AGA58.3 #8-32UNC-2Bx14 9.5 M5 x 9 2,5 1.3 17 10.6 AGA58.4 19,8 10.6 2,5 1,3 43.5 28 5 M5 x 9 #8-32UNC-2Bx14 9.5 14 5 AGA58.7 15.1 7815m07/0202 AGA58.9 25,5 12 15 M4 x 14 11/12

Dimensions (cont d) Dimensions in mm AGA57.1 4 mm 7815z05/0602 AGA57.2 44,5 86,5 124,5 164 10 (6x) 40 80 130 113 7 (4x) 7815m08/0102 17 3 AGA57.3 7 (4x) 7 (4x) 3 123,8 80 113 7815m05/0202 14,5 103,3 164 18 12/12 2008 Siemens HVAC Products GmbH Subject to change!