Technical ata 6001 Supersedes ecember 2015 Features and benefits escription: Indoor/enclosure, R-Rated medium voltage, current-limiting fuses for motor circuit protection. urrent-limiting R-Rated fuses will safely interrupt all currents between their minimum and maximum interrupting ratings and will melt in a range of 15 to 35 seconds at a value of 100 times the R number per NSI 37.46. R-Rated fuses are physically dimensioned for easy installation in existing hardware. vailable in standard, MPGR Hookeye and hermetically sealed, and bolt-on mounting styles to meet application needs. 4.8kV Limitamp bolt-on constructions available in ratings from 2R to 24R. 2.4kV and 4.8kV MPGR hermetically sealed constructions are suitable for lass I, Group, iv. 2 hazardous locations. Open fuse indicator on all mounting styles speeds troubleshooting. Optional remote contact signaling microswitch available. lassified as backup fuses for current-limiting protection of medium voltage motor controllers (short-circuit performance only). These fuses are in a self-contained, non-venting package for installation indoors or outdoors in an enclosure. Typical applications: Medium voltage motors and controllers ontents escription Page escription Page 2.4kV R-Rated fuses... 2-7 Introduction...2 atalog numbers...3 urves... 4-7 4.8kV R-Rated fuses... 8-16 Introduction...8 atalog numbers...9 urves... 10-16 7.2kV R-Rated fuses... 17-21 Introduction...17 atalog numbers...18 urves... 19-21
Technical ata 6001 2.4kV R-Rated fuses atalog symbols: ode-(amps)r onstruction 2LS-25 Standard (25 only) 2LS-25 MPGR Hookeye (25 only) JK-_R Standard (2R-24R) JK--_R MPGR Hookeye* (2R-24R) 2HLS-_R Hermetically sealed MPGR Hookeye* (25/2R-24R) 2LS-_R olt-on (25/2R-24R) * For use in 400 amp MPGR motor starters. Ratings: Volts 2.4kV (nominal) 2.54kV (max design) mps 25-450 Interrupting ratings 50k Sym 80k sym gency information: UL Recognized: Guide #MSSS2, File #96676 Recommended fuse holders for standard constructions: mp range escription at. No. Fuseclips 25-230 3 nclosed fuseclip* 3354730 25-450 Fuse holders 25-230 Single barrel 390-450 ouble barrel 3 Open fuseclip 10065 3 Spring loaded open fuseclip 907867G04 Non-disconnect holder, porcelain Non-disconnect holder, glass polyester isconnect holder, porcelain isconnect holder, glass polyester Non-disconnect holder, porcelain Non-disconnect holder, glass polyester isconnect holder, porcelain isconnect holder, glass polyester * Single barrel only, not sold in pairs. 2L-PNM- 2L-GNM- 2L-PM- 2L-GM- 2L-PNM- 2L-GNM- 2L-PM- 2L-GM- imensions - in [mm] onstruction Standard - short MPGR Hookeye* olt-on mp imension range 25-230 10.8 (274) 3 (76) 3 (76) 390-450 10.8 (274) 3 (76) 3 (76) 3.3 (84) 70-230 10.8 (274) 3 (76) 3 (76. 390-450 10.8 (274) 3 (76) 3 (76) 3.3 (84) 25-230 19.2 (488) 17.9 (455) 3 (76) 390-450 19.2 (488) 17.9 (455) 3 (76) 3.3 (84) * Includes hermetically sealed versions. Standard and MPGR Hookeye olt-on 3.0 [76.2] = 3 [76.2] F = 2.5 [63.5] G = 2.04 [51.81 H = 0.96 [24.4] I= 0.5 [12.7] 3.0 [76.2] F G H I Indicator 2.12 [53.8] Gripping tab for Hookeye constructions R 0.23 [5.81] Typ. Indicator 2
Technical ata 6001 2.4kV R-Rated fuse catalog numbers mp rating R esignation Standard Mounting style (minimum interrupting rating in amps) MPGR Hookeye Regular Hermetically sealed olt-on 25 2LS-25* (90) 2LS-25* (90) 2HLS-25* (90) 2LS-25* (90) 1 70 2R JK-2R (165) JK--2R (165) 2HLS-2R (170) 2LS-2R (170) 1 100 3R JK-3R (220) JK--3R (220) 2HLS-3R (245) 2LS-3R (245) 1 130 4R JK-4R (320) JK--4R (320) 2HLS-4R (340) 2LS-4R (340) 1 150 5R JK-5R (410) JK--5R (410) 2HLS-5R (430) 2LS-5R (430) 1 170 6R JK-6R (480) JK--6R (480) 2HLS-6R (500) 2LS-6R (500) 1 200 9R JK-9R (720) JK--9R (720) 2HLS-200* (1000) 2LS-9R (1000) 1 230 12R JK-12R (970) JK--12R (970) 2HLS-230* (1250) 2LS-12R (1250) 1 390 18R JK-18R** (1430) JK--18R** (1430) 2HLS-390* (1700) 2LS-18R (1700) 2 450 24R JK-24R** (1880) JK--24R** (1880) 2HLS-24R (2100) 2LS-24R (2100) 2 * oes not comply with NSI 37.46 for R rating. ** Not UL Recognized JK and 2HLS Type mountings -in (mm) atalog Hole centers number isconnect single barrel Overall length Hole Inset Hole centers ontact height F G Overall height 2L-GM- 8.24 (209.3) 6 (152.4) 18 (457.2) 0.62 (15.7) 1.75 (44.4) 4.5 (114.3) 11.72 (297.7) 60 2L-PM- 8.24 (209.3) 6 (152.4) 18 (457.2) 0.62 (15.7) 1.75 (44.4) 4.5 (114.3) 11.72 (297.7) 60 isconnect double barrel 2L-GM- 8.24 (209.3) 6 (152.4) 18 (457.2) 0.62 (15.7) 1.75 (44.4) 4.5 (114.3) 15.28 (388.1) 60 2L-PM- 8.24 (209.3) 6 (152.4) 18 (457.2) 0.62 (15.7) 1.75 (44.4) 4.5 (114.3) 15.28 (388.1) 60 Non-disconnect single barrel 2L-GNM- 8.24 (209.3) 6 (152.4) 18 (457.2) 0.62 (15.7) 1.75 (44.4) 4.5 (114.3) 8.79 (223.3) 60 2L-PNM- 8.24 (209.3) 6 (152.4) 18 (457.2) 0.62 (15.7) 1.75 (44.4) 4.5 (114.3) 8.79 (223.3) 60 Non-disconnect double barrel 2L-GNM- 8.24 (209.3) 6 (152.4) 18 (457.2) 0.62 (15.7) 1.75 (44.4) 4.5 (114.3) 12.48 (317.0) 60 2L-PNM- 8.24 (209.3) 6 (152.4) 18 (457.2) 0.62 (15.7) 1.75 (44.4) 4.5 (114.3) 12.48 (317.0) 60 Number of barrels IL rating (kv) 2.4kV disconnect mounting 2.4kV non-disconnect mounting G F G F isconnect mountings provide a means for fuse extraction only. o not use a disconnect mounting for load switching or fuse removal while energized. 3
Technical ata 6001 2.4kV Time-current curves minimum melting for 2HLS-_R and 2LS-_R (25, 2R-24R @25 ) URRNT IN MPS 2HLS-_R and 2LS-_R 4
Technical ata 6001 2.4kV Time-current curves total clearing for 2HLS-_R and 2LS-_R (25, 2R-24R @25 ) URRNT IN MPS 2HLS-_R and 2LS-_R 5
Technical ata 6001 2.4kV Peak let-through curves for 2HLS-_R and 2LS-_R (25, 2R-24R @25 ) PROSPTIV SHORT-IRUIT URRNT IN MPS 2HLS-_R and 2LS-_R 6
Technical ata 6001 2.4kV Time-current curves minimum melting for JK-_R and JK--_R (2R-24R @25 ) 2.4kV Time-current curves total clearing for JK-_R and JK--_R (2R-24R @25 ) 2.4kV Peak let-through curves for JK-_R and JK--_R (2R- 24R @25 ) 7
Technical ata 6001 4.8kV R-Rated fuses atalog symbols: ode-(amps)r onstruction 5LS-30 Standard - short (30) JL-_R Standard - short (2R - 24R) 5LLS-_R Standard - long (2R - 24R) JL--_R MPGR Hookeye* (2R - 24R) 5LS-30 MPGR Hookeye* (30) 5HLS-30 Hermetically sealed MPGR Hookeye* (30) 5HLS-_R Hermetically sealed MPGR Hookeye* (2R - 24R) 5LS-30 olt-on (30) 5LS-_R olt-on (2R - 44R) 5MLS-_R-_ olt-on (2R- 24R) Limitamp fuses * For use in 400 amp MPGR motor starters. Ratings: Volts 4.8kV (nominal) 5.08kV (max design) mps 30-450 Interrupting ratings 50k Sym 80k sym gency information: UL Recognized: Guide #MSSS2, File #96676 (JL-_R [2R-12R] and JL--_R [2R-12R]) Recommended fuse holders for standard constructions: mp range escription IL (kv) at. No. Fuseclips 30-230 3 nclosed fuseclip* 3354730 30-450 3 Open fuseclip 10065 3 Spring loaded open fuseclip 907867G04 Fuse holders for LS / JL / 5HLS Non-disconnect holder, porcelain 60 5HL-PNM- 30-230 Non-disconnect holder, glass polyester 60 5HL-GNM- Single barrel isconnect holder, porcelain 60 5HL-PM- isconnect holder, glass polyester 60 5HL-GM- Non-disconnect holder, porcelain 60 5HL-PNM- 390-450 Non-disconnect holder, glass polyester 60 5HL-GNM- ouble barrel isconnect holder, porcelain 60 5HL-PM- isconnect holder, glass polyester 60 5HL-GM- Fuse holders for 5LLS Non-disconnect holder, porcelain 60 5L-PNM- Non-disconnect holder, glass polyester 60 5L-GNM- 70-230 isconnect holder, porcelain 60 5L-PM- Single barrel isconnect holder, glass polyester 60 5L-GM- isconnect holder, porcelain 75 8L-PM- isconnect holder, glass polyester 75 8L-GM- 390-450 isconnect holder, porcelain 60 5L-PM- ouble arrel isconnect holder, glass polyester 60 5L-GM- * Single barrel only, not sold in pairs. ** Not available for standard - long constructions Not available for 390 to 450 amp ratings. imensions - in [mm] onstruction Standard - short Standard - long MPGR Hookeye* olt-on Limitamp (-) Limitamp (-) mp imension range 30-230 15.9 (404) 3 (76) 3 (76) 390-450 15.9 (404) 3 (76) 3 (76) 3.3 (84) 70-230 17.9 (455) 3 (76) 3 (76) 390-450 17.9 (455) 3 (76) 3 (76) 3.3 (84) 30-230 15.9 (404) 3 (76) 3 (76) 390-450 15.9 (404) 3 (76) 3 (76) 3.3 (84) 30-230 19.2 (488) 17.9 (455) 3 (76) 390-450 19.2 (488) 17.9 (455) 3 (76) 3.3 (84) 600-800 19.2 (488) 17.9 (455) 4 (101) 9 (229) 70-230 18.3 (465) 18.8 (478) 1.4 (36) 4.8 (122) 390-450 18.3 (465) 18.8 (478) 1.4 (36) 7.4 (188) 70-230 18.3 (465) 18.8 (478) 1.4 (36) 3.0 (76) 390-450 18.3 (465) 18.8 (478) 1.4 (36) 2.4 (61) * Includes hermetically sealed versions. Standard (short and long) and MPGR Hookeye 3.0 [76.2] olt-on 5LS-_ = 3 [76.2] F = 2.5 [63.5] G = 2.04 [51.81 H = 0.96 [24.4] I= 0.5 [12.7] 3.0 [76.2] F G H I Indicator 2.12 [53.8] olt-on 5MLS-_R- 0.25 olt-on 5MLS-_R- 3.00 RF 2 SLOTS (0.38X0.5) 2.250 3.0 (RF) 0.25 0.25 7.75 Gripping tab for Hookeye constructions R 0.23 [5.81] Typ. 17.7 16.5 (STRIKR NOT XTN) (STRIKR NOT XTN) 17.7 16.5 0.25 0.25 7.01 7.75 0.25 3.1 2.25 Indicator 3.1 2.25 2 SLOTS (.343 X.875) 0.38 2.25 2 SLOTS (0.38X0.5) 2 SLOTS (0.343X0.875) 8
Technical ata 6001 4.8kV R-Rated fuse catalog numbers mp Rating Mounting style (minimum interrupting rating in amps) MPGR Hookeye R esignation Standard - short Standard - long Regular Hermetically sealed olt-on - 5LS-_ olt-on - 5MLS-_-R- olt-on - 5MLS-_-R- 30 5LS-30* (95) 5LS-30* (95) 5HLS-30* (95) 5LS-30* (95) 1 70 2R JL-2R (165) 5LLS-2R (165) JL--2R (165) 5HLS-2R (180) 5LS-2R (180) 5MLS-2R- (180) 5MLS-2R- (180) 1 100 3R JL-3R (220) 5LLS-3R (220) JL--3R (220) 5HLS-3R (270) 5LS-3R (270) 5MLS-3R- (270) 5MLS-3R- (270) 1 Number of barrels 130 4R JL-4R (320) 5LLS-4R (320) JL--4R (320) 5HLS-4R (350) 5LS-4R (350) 5MLS-4R- (360) 5MLS-4R- (360) 1 150 5R JL-5R (410) 5LLS-5R (410) JL--5R (410) 5HLS-5R (450) 5LS-5R (450) 5MLS-5R- (450) 5MLS-5R- (450) 1 170 6R JL-6R (480) 5LLS-6R (480) JL--6R (480) 5HLS-6R (540) 5LS-6R (540) 5MLS-6R- (540) 5MLS-6R- (540) 1 200 9R JL-9R (720) 5LLS-9R (720) JL--9R (720) 5HLS-9R (700) 5LS-9R (700) 5MLS-9R- (850) 5MLS-9R- (850) 1 230 12R JL-12R (970) 5LLS-12R (970) JL--12R (970) 5HLS-12R (1000) 5LS-12R (1000) 5MLS-12R- (1150) 5MLS-12R- (1150) 1 390 18R JL-18R** (1430) 5LLS-18R (1430) JL--18R** (1430) 5HLS-18R (1450) 5LS-18R (1450) 5MLS-18R- (1725) 5MLS-18R- (1725) 2 450 24R JL-24R** (1880) 5LLS-24R (1880) JL--24R** (1880) 5HLS-24R (2000) 5LS-24R (2000) 5MLS-24R- (2350) 5MLS-24R- (2350) 2 600 32R 5LS-32R (2600) 2 650 36R 5LS-36R (3000) 2 800 44R 5LS-44R (3250) 2 * oes not comply with NSI 37.46 for R rating. ** Not UL Recognized. 5LS, JL, JL-, 5LS, 5HLS and 5LLS Type mountings - in (mm) Hole centers Overall length Hole Inset Hole centers ontact height Overall height atalog number F G IL rating (kv) isconnect single barrel 5L-GM- 15.24 (387.1) 6 (152.4) 25 (647.7) 0.62 (15.7) 1.75 (44.4) 4.5 (114.3) 11.72 (297.7) 60 5L-PM- 15.24 (387.1) 6 (152.4) 25 (647.7) 0.62 (15.7) 1.75 (44.4) 4.5 (114.3) 11.72 (297.7) 60 5HL-PM- 16.25 (412.8) 6 (152.4) 23 (584.2) 0.62 (15.7) 1.75 (44.4) 4.5 (114.3) 11.72 (297.7) 60 5HL-GM- 16.25 (412.8) 6 (152.4) 23 (584.2) 0.62 (15.7) 1.75 (44.4) 4.5 (114.3) 11.72 (297.7) 60 isconnect double barrel 5L-GM- 15.24 (387.1) 6 (152.4) 25 (647.7) 0.62 (15.7) 1.75 (44.4) 4.5 (114.3) 15.28 (388.1) 60 5L-PM- 15.24 (387.1) 6 (152.4) 25 (647.7) 0.62 (15.7) 1.75 (44.4) 4.5 (114.3) 15.28 (388.1) 60 5HL-GM- 16.25 (412.8) 6 (152.4) 23 (584.2) 0.62 (15.7) 1.75 (44.4) 4.5 (114.3) 15.28 (388.1) 60 5HL-PM- 16.25 (412.8) 6 (152.4) 23 (584.2) 0.62 (15.7) 1.75 (44.4) 4.5 (114.3) 15.28 (388.1) 60 Non-disconnect single barrel 5L-GNM- 15.24 (387.1) 6 (152.4) 25 (635.0) 0.62 (15.7) 1.75 (44.4) 4.5 (114.3) 8.79 (223.3) 60 5L-PNM- 15.24 (387.1) 6 (152.4) 25 (635.0) 0.62 (15.7) 1.75 (44.4) 4.5 (114.3) 8.79 (223.3) 60 5HL-GNM- 16.25 (412.7) 6 (152.4) 23 (584.2) 0.62 (15.7) 1.75 (44.4) 4.5 (114.3) 8.79 (223.3) 60 5HL-PNM- 16.25 (412.7) 6 (152.4) 23 (584.2) 0.62 (15.7) 1.75 (44.4) 4.5 (114.3) 8.79 (223.3) 60 Non-disconnect double barrel 5HL-PNM- 16.25 (412.7) 6 (152.4) 25 (635.0) 0.62 (15.7) 1.75 (44.4) 4.5 (114.3) 12.48 (317.0) 60 5HL-GNM- 16.25 (412.7) 6 (152.4) 25 (635.0) 0.62 (15.7) 1.75 (44.4) 4.5 (114.3) 12.48 (317.0) 60 4.8kV disconnect mounting 4.8kV non-disconnect mounting G F G F isconnect mountings provide a means for fuse extraction only. o not use a disconnect mounting for load switching or fuse removal while energized. 9
Technical ata 6001 4.8kV Time-current curves minimum melting for 5LS-30, 5LS-30, 5HLS-_R, 5LS-30, 5LS-_R, 5MLS-_R- and 5MLS-_R- (30, 2R-24R @ 25 ) URRNT IN MPS 5LS-30, 5LS-30, 5HLS-_R, 5LS-30, 5LS-_R, 5MLS-_R-, 5MLS-_R- 10
Technical ata 6001 4.8kV Time-current curves total clearing for 5LS-30, 5LS-30, 5HLS-_R, 5LS-30, 5LS-_R, 5MLS-_R- and 5MLS-_R- (30, 2R-24R @ 25 ) URRNT IN MPS 5LS-30, 5LS-30, 5HLS-_R, 5LS-30, 5LS-_R, 5MLS-_R-, 5MLS-_R- 11
Technical ata 6001 4.8kV Peak let-through curves for 5LS-30, 5LS-30, 5HLS-_R, 5LS-30, 5LS-_R, 5MLS-_R- and 5MLS-_R- (30, 2R-24R @ 25 ) PROSPTIV SHORT-IRUIT URRNT IN MPS 5LS-30, 5LS-30, 5HLS-_R, 5LS-30, 5LS-_R, 5MLS-_R-, 5MLS-_R- 12
Technical ata 6001 4.8kV Time-current curves minimum melting for JL-_R and JL--_R (2R-24R @25 ) 4.8kV Time-current curves total clearing for JL-_R and JL--_R (2R-24R @25 ) 4.8kV Peak let-through curves for JL-_R and JL--_R (2R-24R @25 ) 13
Technical ata 6001 4.8kV Time-current curves minimum melting for 5LLS-_R (2R-24R @ 25 ) URRNT IN MPS 5LLS-_R 14
Technical ata 6001 4.8kV Time-current curves total clearing for 5LLS-_R (2R-24R @ 25 ) URRNT IN MPS 5LLS-_R 15
Technical ata 6001 4.8kV Peak let-through curves for 5LLS-_R (2R-24R @ 25 ) PROSPTIV SHORT-IRUIT URRNT IN MPS 5LLS-_R 16
Technical ata 6001 7.2kV R-Rated fuses atalog symbols: ode-(amps)r onstruction 8LS-_R Standard (2R - 6R) 7LS-_R Standard (9R - 24R) 8LS-_R MPGR Hookeye* (2R - 6R) 7LS-_R MPGR Hookeye* (9R - 24R) 7LS-_R olt-on (2R - 44R) * For use in 400 amp MPGR motor starters. Ratings: Volts 7.2kV (nominal) 8.3kV (max design 70-170 standard and MPGR Hookeye) 7.2kV (max design 200-450 standard and MPGR Hookeye) 7.2kV (max design 70-800 bolt-on) mps 25-450 Interrupting ratings 50k Sym 80k sym Recommended fuse holders for standard constructions: imensions - in [mm] onstruction Standard MPGR Hookeye olt-on mp imension range 70-230 15.8 (401) 3 (76) 3 (76) 390-450 15.8 (401) 3 (76) 3 (76) 3.3 (84) 70-230 15.8 (401) 3 (76) 3 (76) 390-450 15.8 (401) 3 (76) 3 (76) 3.3 (84) 70-230 19.2 (488) 17.9 (455) 3 (76) 390-650 19.2 (488) 17.9 (455) 3 (76) 3.3 (84) 800 19.2 (488) 17.9 (455) 4 (102) 9 (229) Standard and MPGR Hookeye Gripping tab for Hookeye constructions Indicator mp range escription IL (kv) at. No. Fuseclips 70-230 3 nclosed fuseclip* 3354730 70-450 3 Open fuseclip 10065 3 Spring loaded open fuseclip 907867G04 Fuse holders for 7LS and 8LS Non-disconnect holder, porcelain 75 8HL-PNM- 70-230 Non-disconnect holder, glass polyester 75 8HL-GNM- Single barrel isconnect holder, porcelain 75 8HL-PM- isconnect holder, glass polyester 75 8HL-GM- Non-disconnect holder, porcelain 75 8HL-PNM- 390-450 Non-disconnect holder, glass polyester 75 8HL-GNM- ouble barrel isconnect holder, porcelain 75 8HL-PM- isconnect holder, glass polyester 75 8HL-GM- olt-on 3.0 [76.2] = 3 [76.2] F = 2.5 [63.5] G = 2.04 [51.81 H = 0.96 [24.4] I= 0.5 [12.7] 3.0 [76.2] F G H I Indicator 2.12 [53.8] R 0.23 [5.81] Typ. * Single barrel only, not sold in pairs. 17
Technical ata 6001 7.2kV R-Rated fuse catalog numbers mp rating R esignation Mounting style (minimum interrupting rating in amps) Standard MPGR Hookeye olt-on 70 2R 8LS-2R (160) 8LS-2R (160) 7LS-2R (160) 1 100 3R 8LS-3R (250) 8LS-3R (250) 7LS-3R (250) 1 130 4R 8LS-4R (325) 8LS-4R (325) 7LS-4R (325) 1 150 5R 8LS-5R (390) 8LS-5R (390) 7LS-5R (390) 1 170 6R 8LS-6R (500) 8LS-6R (500) 7LS-6R (500) 1 200 9R 7LS-9R (750) 7LS-9R (750) 7LS-9R (750) 1 230 12R 7LS-12R (1000) 7LS-12R (1000) 7LS-12R (1000) 1 390 18R 7LS-18R (1450) 7LS-18R (1450) 7LS-18R (1450) 2 450 24R 7LS-24R (2500) 7LS-24R (2500) 7LS-24R (2500) 2 800 44R 7LS-44R (3250) 2 Number of barrels 8LS, 8LS, 7LS, 7LS Type mountings - in (mm) atalog Hole centers number isconnect single barrel Overall length Hole inset Hole centers ontact height Overall height F G 8HL-GM- 16.25 (412.8) 6 (152.4) 23 (584.2) 0.62 (15.7) 1.75 (44.4) 7 (177.8) 11.72 (297.7) 75 8HL-PM- 16.25 (412.8) 6 (152.4) 23 (584.2) 0.62 (15.7) 1.75 (44.4) 7 (177.8) 11.72 (297.7) 75 isconnect double barrel 8HL-GM- 16.25 (412.8) 6 (152.4) 23 (584.2) 0.62 (15.7) 1.75 (44.4) 7 (177.8) 17.78 (451.6) 75 8HL-PM- 16.25 (412.8) 6 (152.4) 23 (584.2) 0.62 (15.7) 1.75 (44.4) 7 (177.8) 17.78 (451.6) 75 Non-disconnect single barrel 8HL-GNM- 16.25 (412.7) 6 (152.4) 23 (584.2) 0.62 (15.7) 1.75 (44.4) 7 (177.8) 11.29 (286.7) 75 8HL-PNM- 16.25 (412.7) 6 (152.4) 23 (584.2) 0.62 (15.7) 1.75 (44.4) 7 (177.8) 11.29 (286.7) 75 Non-disconnect double barrel 8HL-GNM- 16.25 (412.7) 6 (152.4) 23 (584.2) 0.62 (15.7) 1.75 (44.4) 7 (177.8) 14.98 (380.5) 75 8HL-PNM- 16.25 (412.7) 6 (152.4) 23 (584.2) 0.62 (15.7) 1.75 (44.4) 7 (177.8) 14.98 (380.5) 75 IL rating (kv) 7.2kV disconnect mounting G F 7.2kV non-disconnect mounting G F isconnect mountings provide a means for fuse extraction only. o not use a disconnect mounting for load switching or fuse removal while energized. 18
Technical ata 6001 7.2kV Time-current curves minimum melting for 8LS-_R, 7LS-_R, 8LS-_R, 7LS-_R and 7LS-_R (2R-44R @ 25) URRNT IN MPS 8LS-_R, 7LS-_R, 8LS-_R, 7LS-_R and 7LS-_R 19
Technical ata 6001 7.2kV Time-current curves total clearing for 8LS-_R, 7LS-_R, 8LS-_R, 7LS-_R and 7LS-_R (2R-44R @ 25) URRNT IN MPS 8LS-_R, 7LS-_R, 8LS-_R, 7LS-_R and 7LS-_R 20
Technical ata 6001 7.2kV Peak let-through curves for 8LS-_R, 7LS-_R, 8LS-_R, 7LS-_R and 7LS-_R (2R-44R @ 25) VILL URRNT IN MPS 8LS-_R, 7LS-_R, 8LS-_R, 7LS-_R and 7LS-_R 21
Technical ata 6001 The only controlled copy of this ata Sheet is the electronic read-only version located on the ussmann Network rive. ll other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. ussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. ussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications. aton 1000 aton oulevard leveland, OH 44122 aton.com ussmann ivision 114 Old State Road llisville, MO 63021 United States 2016 aton ll Rights Reserved Publication No. 6001 - U-S15148 February 2016 aton, ussmann and MPGR are valuable trademarks of aton in the U.S. and other countries. You are not permitted to use the aton trademarks without prior written consent of aton. Limitamp is a registered trademark of General lectric. UL is a registered trademark of Underwriters Laboratories, Inc. Follow us on social media to get the latest product and support information. 22