MODVAR Low voltage reactive power compensation modules Installation manual

Similar documents
LV Capacitor CLMD03 Power Module Instruction manual

Technical brochure. The Vector series The ABB comprehensive solution for automatic power factor correction

LV Capacitor Bank APC

LCL FILTERS INSTRUCTIONS MANUAL (M A) (c) CIRCUTOR S.A.

AUTOMATIC CAPACITOR BANK WITH CONTACTOR OPERATIONS

LV Capacitor Bank APC

CLMD Low-voltage capacitors for reliable power factor correction

APC03 capacitor bank series The ABB comprehensive solution for automatic power factor correction

LV Capacitor CLMD Reliability for Power Factor Correction

Low voltage capacitors CLMD Improving power factor and enhancing power quality of your network

Chapter 08 Dynamic power factor correction systems (real time PFC) Dynamic power factor correction systems (real time PFC) Optimised, thermal design

PhiCap Capacitors for Power Factor Correction

High Reliable Components for Power Factor Correction and Power Quality

Three Phase Capacitors KNK

CP Automatic capacitor bank

Essential equipment for all your requirements

multicond Power capacitors Data sheet: multicond

EMPAC Metal enclosed capacitor bank for wind applications

HARMONIC FILTER REACTOR

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL

Automatic capacitor banks

POWER CAPACITORS. Cylindrical capacitor standard duty

High Reliable Components for Power Factor Correction and Power Quality

DYNACOMP. The top-class reactive power compensator

Capacitor Switching Contactors Type K3...-A, K3...-K

REFERENCE MANUAL FORM: MX-TRM-E REL REV MTE

FRANKE. Power Factor Correction GMKP ENERGY. GMKPg Low Voltage Capacitors by Gas Technology Save energy and reduce carbon dioxide emission!

RSC09 RSC16 RSC22 RSC38 RSC43 RSC63 RSC-AUX

NEW. Heavy Duty Capacitors. Power Factor Correction Capacitors Type LKT. It s all about saving your money! Features that matter:

PhaseCap Premium PFC Capacitors Gas-impregnated n Dry type n Concentric winding n Wavy cut n Triple safety system

Appendix: Safety and application notes for... 15

www. ElectricalPartManuals. com Instruction Bulletin ALTIVAR FLEX58 TRX Adjustable Speed Chassis Drive Controllers Installation Guide

INSTRUCTION MANUAL (M A)

MADE IN GERMANY. Components for reactive power compensation. Components for reactive power compensation. Power Quality. Reactive power controllers

Power Factor Correction Equipment

OWNER S MANUAL Please read this manual before operating your power supply

Power Factor Correction Capacitors Type LKT

FIXED POWER FACTOR CORRECTION EQUIPMENT 5KV CLASS MEDIUM VOLTAGE SECTION Z

Installation and Start-up Guide. ACS-BRK Brake Units

43-SDMS-04 REV. 00 SPECIFICATIONS FOR

VD4 Installation and service instructions kv A ka

Resin Impregnated Paper Bushing, Oil to SF 6. , Type GSBK

Model Number Structure

Power Factor Correction Capacitors Type LKT

LV CAPACITOR BANKS WITH STATIC SWITCHING EMK SERIES

AF series contactors (9 2650)

1ZSC AAA EN, REV. 7. Transformer bushings type GSBK Technical guide

Power Factor Correction Capacitors Type LKT

TeSys contactors. Use in category DC-1 (resistive loads; time constant L/R y 1 ms) Rated operational current Ie. to be wired in series

C1000 Series Automatic Cap Bank

Switch Disconnectors. SENTRON 3NP5 Fuse Switch Disconnectors up to 630 A. Introduction. 7/106 Siemens LV

Instruction Manual. Harmonic Filter AHF 005/010. Drives Solutions

Automatic COSYS PFC. Automatic power factor correction system NEW

1ZSC AAA en, Rev. 6. Resin impregnated paper bushing, oil to SF 6., type GSBK Technical guide

1ZSE EN, REV. 7. Oil SF 6. bushings type GOEK Technical guide

Manual for Inverter system type PCI05

DNX 3 MCB 4500 A / 6 ka Phase + Neutral, neutral on left side

Power Factor Correction Capacitors in sheet steel cases

(with Class-1 AC resistive load) 3. G3PB-215B-2N-VD kW max. (25 A) G3PB-225B-3N-VD 2. G3PB-225B-2N-VD kw max. (35 A) G3PB-235B-3N-VD 2

R.4. Automatic capacitor banks with static system. Power factor correction and harmonic filtering. Homepage :

Appendix: Safety and application notes for 19

SOLSTART Instruction Manual

Approved Standards. Ordering Information. Thermal Overload Relay J7TKN. Model Number Legend. Thermal Overload Relay. Accessories

Power Factor Correction

DESIGN CONSIDERATIONS FOR APPLICATION OF SHUNT CAPACITORS IN HEAVY HATER PLANT (TUTICORIN)

Power System Solutions (PSS)

PF Guard Power Factor Capacitor Bank Installation, Operation, and Maintenance Manual

AF series contactors (9 2650)

LV Capacitors QCap-L series Capacitors for power factor correction

THE PROTECTION OF INDUSTRIAL CAPACITOR BANKS BY CURRENT LIMITING FUSES. By M.J. Smart and B. Wadcock

Sr. No. Details Page No. 1 MV Capacitor Unit Drawings 3. 2 Technical Perticular for Capacitor Unit 4. 3 MV Surge Capacitor Unit Drawings 6

3 - Protection components Motor circuit-breakers

Latch for Contactors 4-pole see page 36. Ratings Rated Aux. Contacts Type Coil voltage 2) AC2 Current Built-in Additional 24 24V= DC 5

Medium Voltage Capacitors

dv Sentry TM 208V 600V INSTALLATION GUIDE Quick Reference ❶ How to Install Pages 6 14 ❷ Startup/Troubleshooting Pages WARNING

BellMega BM-510. Operation Manual Ver: 1.0 Rev: 1

Medium Voltage. Power Factor Correction Reactive Compensation Harmonic Filters. Electrical Power Quality Management at its best.

Model Number Legend. Motor Contactor J7KN. Motor Contactor J7KN 1

GB60S 60W Single Output General Purpose Series

CTX 3 Control relays Cat. N (s) : /06/09..14/16/19..24/26/29

NH fuse-links gg 500VAC size 000, 00, 0, 1, 2, 3

1 Low-voltage Power-factor Correction capacitors KNK APPLICATION DESIGN

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL MTE Corporation

SPECTRA ENGINEERING PTY LTD. MXPS15 Series Technical Manual

CTU 02. Thyristor switching module for fast PF compensation. User manual

Transforming Energy.. For Advanced Technology

LINEAR LED DRIVERS. ComfortLine Selectable Current (Output Terminal) ComfortLine SELECTABLE CURRENT (OUTPUT TERMINAL)

High Speed Fuse Applications Module 5

Presentation Soft starters 0 Altistart 48 soft start - soft stop units

CALTRAP INSTALLATION AND OPERATIONS MANUAL

COOPER POWER SERIES. Metal-enclosed, pad-mounted capacitor banks installation instructions. Power Capacitors MN230009EN

DX³ 4-pole RCBO 6000 A/10 ka

Innovation in soft start technology HFE-2 USER MANUAL. MAN-HFE-002. Version 01

Domae. The right solution for distribution boards

FLÄKTGROUP PM-MOTOR WITH INTEGRATED FC 106 FREQUENCY CONVERTER

tests Partial discharge level from day 1 10 pc Insulation 24 kv : impulse tested at 125 kv Insulation 36 kv : impulse tested at 170 kv, 200 kv indeed.

Film Capacitors Power Factor Correction

ARTECHE LOW VOLTAGE CAPACITOR BANKS. smartbat LV.

Medium Voltage Distribution PIX. Air Insulated Switchgear up to 24 kv PARS TABLEAU

System pro E power Capacitor Bank

Transcription:

MODVAR Low voltage reactive power compensation modules Installation manual

MODVAR Low voltage reactive power compensation modules Before installation, read this manual carefully and keep at the disposal of personnel in charge of installation, maintenance and operation. 1.0 Safety For the safe use of MODVAR modules, please ensure: Installation and maintenance is undertaken only by authorised and qualified personnel, in accordance with current local regulations Failure to follow the safety rules may lead to bodily injury, premature failure of the capacitors, or other material damage to installations. Isolation of the equipment from the supply before working Wait 5 minutes after isolating supply before handling After 5 minutes short-circuit the capacitor terminals with a piece of insulated cable to confirm discharge 2.0 Inspection on receipt Inspect the packing and immediately report any damages. Unpack the MODVAR module and check that: Data on the label correspond to those of your purchase order. MODVAR module is not damaged. Any loss or damage should be notified immediately to your nearest ABB agent. 2.1 Storage-transportation-handling Store indoors, in dry, dust free and non-corrosive environments, protected from vibrations or shocks. Storage in initial packing is recommended. Storage temperature: Minimum: -40 C / -40 F Maximum: 75 C / 167 F 3 ABB Instruction manual MODVAR Low voltage reactive power

3.0 MODVAR modules layout There are two types of MODVAR modules: 1 MODVAR complete in one tray MODVAR segregated 4 3 2 MODVAR complete in one tray 5 1. Discharge resistor 2. Capacitor 3. Reactor 4. Fuse and fuse base 5. Contactor 6. Mounting plate 6 Figure 3.1: MODVAR all in one power modules MODVAR segregated 1. Reactor 4. Mounting plate 2. Fuse and fuse base (not shown) 3. Contactor 5. Cables 6. Discharge resistors 7. Capacitors 3 1 4 5 6 7 Figure 3.2: MODVAR segregated (reactor and capacitors are mounted on separate trays to reduce thermal stress on capacitors) MODVAR Low voltage reactive power ABB Instruction manual 4

MODVAR Low voltage reactive power compensation modules 3.1 MODVAR dimensions 300mm 575mm 455mm Figure 3.3: MODVAR dimensions 472mm R W B B W R 575mm R W B 8mm fixing holes 455mm Figure 3.4: MODVAR dimensions 5 ABB Instruction manual MODVAR Low voltage reactive power

4.0 Mechanical installation MODVAR modules must be fixed horizontally so as to allow airflow circulation (see blue arrows in the figure below). MODVAR modules must be fixed on a rigid frame with two M6 screws (not provided). Make sure that the rigidity of the support and the screws are sufficient to bear the weight (about 50 kg) of the MODVAR module(s). Air clearances: 25 mm to walls and flange to flange between modules. Figure 4.1: MODVAR air flow direction MODVAR Low voltage reactive power ABB Instruction manual 6

MODVAR Low voltage reactive power compensation modules 4.1 Airflow and cooling requirement The service conditions specified in the IEC 60831 1 section 4 are applicable. As per IEC 60831-1 section 3.21, the ambient temperature for capacitors is the air temperature around the capacitors itself and not around the cubicle. The cross-section of air inlet and outlet must be adapted to the air flow. Air should flow from the bottom to the top of the cubicle as illustrated on the opposite picture. One fan per 6 MODVAR columns blowing a minimum air flow of 525 m³/h is necessary. Design guideline The difference between ambient temperature outside the cubicle and measured temperature must be lower than 10 C. To meet that requirement, the temperature probe must be located on top of the air duct. Note: An over temperature protection device must be fitted and set to 55 C to protect the capacitors against thermal stress. Figure 4.2: MODVAR air flow direction 7 ABB Instruction manual MODVAR Low voltage reactive power

4.2 Electrical installation Electrical connection overview 1. Fuses 2. Cable from fuses to contactor 3. Contactor 4. Cable from contactor to reactor 5. Reactor 6. Cable from reactor to capacitor 7. Discharge resistors 8. Capacitors 2 1 3 Supply cable sizing The cables must be sized for a current of 1.5 times nominal current (In) minimum. The nominal current can be calculated with the following formula: 4 In= Qn 415V 3 [1] 5 Formula abbreviations Qn - reactive power output in kvar Vn - line voltage, phase-to-phase The temperature around the cables must also be considered according to cable manufacturer. 6 7 8 Figure 4.3: MODVAR electrical connection diagram MODVAR Low voltage reactive power ABB Instruction manual 8

MODVAR Low voltage reactive power compensation modules Contactor for capacitor switching Capacitor switching leads to transient operating conditions. Therefore, the use of standard contactors is not acceptable and can be dangerous for the safety of people as well as the installations. The ABB UA75 contactors are specially designed to switch capacitors where inrush current peaks are less than or equal to 100 times nominal rms current. Earthing Earthing is achieved through fixing points of the MODVAR mounting tray. Fuses and fuse base The fuses are made with non-isolated gripping lugs, double indicator and contact blades compliant to DIN VDE 0636 Part 201 and IEC 60269-2-1. Figure 4.4: ABB UA75 contactor Figure 4.5: HRC fuse Please refer to the ABB contactors for capacitor switching application guide for the contactor s dimensions as well as the additional inductance in case of inrush current peak. Fuses fit into a three phase bus mounting fuse base (provided). Suitable for use with up to 30 x 10mm bus bar. 9 ABB Instruction manual MODVAR Low voltage reactive power

5.0 Commissioning With the equipment isolated from the supply, check: Cabling is properly connected (including earth) Ambient ventilation is adequate Correct tightness of the connections 7.0 Maintenance Ensure safety procedures are completed (see paragraph 1.0 Safety ). Maintenance frequency depends on working conditions. As minimum annual maintenance should include: Removal of dust deposits, cleaning of all parts. Check of tightness of all electrical connections. Check of ambient temperature. 6.0 Operation The MODVAR module capacitor unit is delivered with factoryinstalled discharge resistors to comply with IEC 60831 and allow a decrease of the residual voltage to less than 50V after 1 min. disconnection from supply. Check condition of discharge resistors. Check for capacitance of CLMD capacitors. During operation, make sure the delay before the MODVAR is re-energised is not shorter than 40 sec. Failure to follow this rule may cause damage to and reduce the lifetime of the capacitor. MODVAR module discharge devices are not suitable for use with rapid switching. (Minimum off time: 40 sec) Harmonics Installation of capacitors on networks disturbed by harmonics may require special precautions especially when there is a risk of resonance phenomena. Please ensure that your installation is as per the over current rating according IEC 60831 standards. Contact ABB for technical support. MODVAR Low voltage reactive power ABB Instruction manual 10

MODVAR Low voltage reactive power compensation modules 8.0 Technical specifications Voltage range 415V, 50Hz For other voltages please consult ABB Connection Three phase Net output power Q at 415V 12.5kvar, 25kvar, 50kvar Discharge resistors Included Discharge time: less than 50V in 1 minute System connection Fuse base mounted on busbar (max 30x10mm) Earth Earth the mounting plate Fixing Two M6 screws to the supporting rail (M8 holes on mounting plate) Protection degree(according to IEC 60529) IP00 Installation Indoor Weight 12.5kvar 25kg 25kvar 35kg 50kvar 50kg Maximum ambient temperature Class D according to IEC60831: Maximum average over 1 year: 35 C Maximum average over 24h: 45 C Minimum ambient temperature -25 C Fuse ABB gg or gl 50, 63, 100 and 125 A Contactor ABB UA75 Control voltage: 230/240V at 50Hz Required clearance 25 mm minimum to walls Capacitor losses Less than 0.5 W/kvar (discharge resistor losses included) Contactor and fuses losses With UA75 contactor: 0.82 W/kvar Tolerance on capacitance 0% +10 % Capacitor voltage test Between terminals: 2.15xUn for 10 seconds Between terminals and earth: 3kV for 10 sec: Un 450V Lightning impulse voltage: 8 kv: Un 690V Overload capability (according to IEC 60831) Overvoltage tolerance: 10% for maximum 8h in every 24h and 30% for maximum 1min Maximum permissible current: 1.3x In. Altitude Up to 1000m Compliance IEC 60831 part 1 & 2 CE marked Cooling Forced air cooling:120cm 3 /h 11 ABB Instruction manual MODVAR Low voltage reactive power

CE Un (V) F (Hz) Qn (kvar) L (%) Ui: 3kV Cat: -25ºC Self-healing,dry Connection D IEC60831-1 (2002) / IEC60831-2 (1995) Resistance (phase/phase): Ω Capacity (phase/phase): μf Warning: After disconnecting from supply, wait 2 min and check for absence of residual voltage before handling the parts S/N: PN: Made in Australia Figure 8.1: Typical label of a MODVAR module MODVAR Low voltage reactive power ABB Instruction manual 12

Contact us ABB Australia Pty Limited Power Products Division 88 Beresford Road Lilydale VIC 3140 Phone: +61 3 9735 7333 Fax: +61 3 9735 3863 E-mail: lv.powerquality@au.abb.com www.abbaustralia.com.au Copyright 2013 ABB. All rights reserved. ABB is working continuously to improve our products. We therefore reserve the right to change designs, dimensions and data without prior notice. DPD 3034 MODVAR manual ABB Rev 01 OCT 2013