LIQUID DIELECTRIC TEST SET MODEL NUMBER LD60 VERSION 3.2

Similar documents
VACUUM INTERRUPTER TEST SET

PORTABLE POWER SUPPLY MODEL NUMBER VMS-1 VERSION 1.0

OPERATIONS AND APPLICATIONS MANUAL MODEL NUMBER PM6. 6 KV DC HIGH POTENTIAL TESTER WITH MEGOHMMETER Version 2.0

Phenix Technologies Inc. 75 Speicher Drive Accident, Maryland 21520

AC DIELECTRIC TEST SET 600P SERIES

Phenix Technologies, Inc. 75 Speicher Drive Accident, Maryland 21520

DC DIELECTRIC TEST SET - 400P

PORTABLE PRODUCTS for Field Testing High Voltage High Current High Power Test Systems and Components

AC DIELECTRIC TEST SET 600P SERIES

AC DIELECTRIC TEST SET 600P Series

Hand Held Pull Tester Instruction Manual Order No

POWER AMPLIFIER SERVICE MANUAL CONTENTS

POWER SUPPLY MODEL XP-800. TWO AC VARIABLE VOLTAGES; 0-120V and 7A, PLUS UP TO 10A. Instruction Manual. Elenco Electronics, Inc.

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

Illustrated Parts List for GPU-400

LB LOAD BANK MANUAL CONTAINS OPERATING INSTRUCTIONS PARTS LIST WIRING DIAGRAMS SERVICE INSTRUCTIONS

Abbeon Cal, Inc. Model BD-50E HIGH FREQUENCY GENERATOR OPERATING MANUAL

Solstice Electric Fryers SE Series Service Manual

200 Shadylane Drive Philipsburg, PA Phone: (814) Fax: (814) Service Manual. Model 642E Centrifuge

MPT-250B SPECIFICATIONS AND OPERATING INSTRUCTIONS

200 Shadylane Drive Philipsburg, PA Phone: (814) Fax: (814) Service Manual

MegaPulse 1.2x50-8 PV

VACUUM CONTROL SPI-MODULE INSTRUCTION MANUAL

Maintenance Manual 13 AMPERE POWER SUPPLY 19A704647P1-P3. Mobile Communications LBI-31801C

PHASE CONVERTERS OPERATING & MAINTENANCE INSTRUCTIONS. MODEL NO: PC40 and PC60. PART Nos:

MODEL ELC-12/40-CVM-D BATTERY CHARGER

KV4-300 mk2. KV5-200 mk2. KV5-100T mk2. KV3-250 mk2

Dielectric Withstand Tester

Instruction Manual AVTM for. Strip Chart Recorder Catalog Nos and

Metrohm E3640 FLASH TESTER INSTRUCTION MANUAL. Martindale Electric Co Ltd.

Phenix Technologies, Inc. 75 Speicher Drive Accident, Maryland 21520

OPERATING AND MAINTENANCE MANUAL. Primary Current Injection Test Set. 750ADM-H mk2

Parts Manual. Transfer Switch. OTPCB (Spec A) 150/225/260 Amps. English Original Instructions (Issue 4)

HLS Watt Halogen Illuminator Service Manual

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

HI-POT/CONTINUITY TESTER Model PLEP01

MegaPulse. Antenna Surge PF 65

SUREPOWR TM SERIES -SURE 24/25 FIELD INSTALLATION INSTRUCTIONS

Phenix Technologies, Inc. 75 Speicher Drive Accident, Maryland 21520

800PL Series DC Hipot Testers

MegaPulse. IMPULSE TESTER Implantable Test 1. Instruction Manual

Service Manual. Microwave Oven. Model: KOR-6L35. S/M No. : OR6L353S001. Caution

TS-E TURBO STEAM ELECTRIC COUNTERTOP CONVECTION STEAMER PARTS AND SERVICE MANUAL

PORTABLE CURRENT SOURCE FOR CIRCUIT BREAKER AND MOTOR OVERLOAD TESTING INSTRUCTION MANUAL PI-250B. Release 1.0 April 5, 2013

Model G14SD Vapor Management System

Optimal Series. Automatic Transfer Switch. Installation and User Manual for the OPT2225 Automatic Transfer Switch. Full Version

Operator's Manual. Storage System. Ultrasound Probe Cabinet. Manufactured by:

MOdel No: MM19.V3 WARNING CAUTION 1. SAFETY INSTRUCTIONS

ABB ! CAUTION. Type KRV Directional Overcurrent Relay E 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION. Instruction Leaflet

GFM-40ac COMPLIANCE WESTUSA. Ground Circuit Tester. Instruction Manual

Phenix Technologies, Inc. 75 Speicher Drive Accident, Maryland 21520

NE-1027 NE Microwave Oven. BTQ (U.K.) ETG (Continental Europe) ORDER NO.PHAMOS C2

50 Hz Mini/Micro Computer Regulator (MCR) Series Installation and Operation Manual

Phenix Technologies, Inc. 75 Speicher Drive Accident, Maryland 21520

MODEL ELC-12/60-D BATTERY CHARGER

BATTERY SAVER LOW RIPPLE HO

CBC-300 Series & CBC-300C Series Dual Channel Adjust Clutch/Brake Controls

90W DC Power Supply. User Manual. 99 Washington Street Melrose, MA Phone Toll Free

XENON POWER SUPPLY 4000 Watt Gladiator IV

Digitrip Retrofit System for the Federal Pioneer 25-H(L)-2, 30-H(L)-2, 30-H(L)-3, and 30-3 Breakers

Users Manual. Phase Rotation Indicator

5. Alignment and Adjustments

MODUL-CONNECT 1.2. Owner s Manual. Modular, digital wiring and control system. Document Part Number MSMC Rev 9 (04/18)

BENCHTOP INSTRUMENT. Single Channel DC Power Supply SL Series Operation Manual V1.0

3 Phase Smart Controller

1ZSE en, Rev. 4. On-load tap-changers, type UC User s manual

Order Number MOP C2. Microwave Oven

Fan Coil Unit (FCU) Fan Motor Control

BENCHTOP INSTRUMENT. Multi-channel DC Power Supply TP2000N/TP2000PU/TP4000N Series Operation Manual V1.0

SIGNAL WORDS QUALIFIED PERSON

Parts Manual. Transfer Switch. OTPCC (Spec A) 300/400/600 Amps. English Original Instructions (Issue 4)

Electronic Service Manuals

PITNEY BOWES FLEXIBLE INK JET TRANSPORT 36 FIT BASE: FIT-36. Parts Manual. (BOM: FIT36rev1.0) FIT-36parts_rev0 1

B BASIC HEAT TREATMENT CONSOLE

Reproduction or other use of this Manual, without the express written consent of Vulcan, is prohibited.

AC DIELECTRIC TEST SET 600 Series

ISO1000R Service Manual SALES: CUSTOMER SERVICE:

Parts Information. Commercial Microwave Oven

Product Overview. Product Identification. Amps One CT Two CTs Three CTs

AC DIELECTRIC TEST SET 600 SERIES

AUTO CHARGE 4000 MODEL #: LOW PROFILE CHARGER AUTOMATIC DUAL OUTPUT BATTERY CHARGER INSTRUCTION MANUAL

AUTO CHARGE 4000 MODEL #: AUTOMATIC DUAL OUTPUT BATTERY CHARGER INSTRUCTION MANUAL. Ph: Fax:

The EFL 2000/1 & 2 User Guide Test Sieve Shaker. Contents

GFM-200A. Instruction Manual

Installation Instructions

Mini Multimeter with Non-Contact Voltage Detector (NCV)

802C System Controller Original and SMD Version

Phenix Technologies, Inc. 75 Speicher Drive Accident, Maryland 21520

3 Slot Payphone Controller

Automatic Burnout Furnaces 115 to 230-volt Models OPERATOR S MANUAL

POWERLINE 2000 Energy Management System TM

PART NO CP-DOOR FRONT PANEL WINDOW PART NO CP-DOOR FRONT PANEL SECOND WINDOW PART NO CP-DOOR LOCK PART NO. 5026

CONTROLLER DIAGNOSTIC GUIDE

Table of Contents Title Page No.

KD1E Range Potential Indicators

DC POWER SUPPLY ALIMENTATION C.C.

TT /17 INSTALLATION INSTRUCTIONS. Introduction. Required Tools and Equipment

5.2 PRE-OPERATION PROCEDURE WARRANTY

Service and Parts Manual. NO LONGER IN PRODUCTION Some service parts may not be available for this product. Otolaryngology Chair.

Installation Instructions For Motor Control Center (MCC) Units

Transcription:

Users Manual Phenix Technologies Inc. LIQUID DIELECTRIC TEST SET MODEL NUMBER LD60 VERSION 3.2

TABLE OF CONTENTS Section Number DANGER DESCRIPTION 1 SPECIFICATIONS 2 INSTALLATION AND GROUNDING INSTRUCTIONS 3 OPERATING INSTRUCTIONS 4 RECALIBRATION 5 ELECTRICAL SCHEMATICS 6 MAINTENANCE AND TROUBLESHOOTING 7 PARTS LIST 8 PARTS ORDERING INFORMATION 9 RETURNED MATERIAL 10

GENERAL SAFETY PRECAUTIONS! CAUTION HIGH VOLTAGE This equipment is capable of providing POTENTIALLY LETHAL VOLTAGES! Improper operation or test practices may result in injury or death to the operator or surrounding personnel. The operation of High Voltage test equipment should only be performed by personnel familiar with HIGH VOLTAGE testing and safety procedures. The operator of this equipment must be aware of all hazards associated with High Voltage testing. The operator is responsible for himself and others in close proximity of the testing area. Some General Safety Practices for working with High Voltage Test Equipment have been listed below for your reference. Become familiar with your instrument before performing an actual test Know your work area, check that all circuits are de-energized and locked out. Never work alone; always work with another qualified worker. Mark off entire work area with barriers and warning tape. Make all personnel aware of your testing activities. Be aware of dangerous conditions that may arise from energizing a test specimen. Never modify test equipment, modifications to equipment could introduce an unknown hazard or hinder a designed-in safety feature. DO NOT operate damaged equipment. Remove power, and do not use the equipment until safe operation can be verified by service-trained personnel. Phenix Technologies, Inc. assumes no liability for unsafe or improper use of test equipment.

DESCRIPTION 1-1 The Liquid Dielectric Test Set, Model LD60, is designed to test and measure the dielectric breakdown of insulating oil used in transformers, capacitors, bushings, etc. in accordance to ASTM D877 and ASTM D1816. The standard test set also satisfies the requirements of IEC, VDE, and BS standards. The test set is of portable type built into a rugged carrying case. Below and protected by the cover is the control panel with the voltmeter as well as the high voltage test compartment. The test compartment is provided with a see through lid interlocked to the test circuit with a limit switch to ensure full safety for the operation. As options, the test set can be supplied with two different kinds of test cells, either TC/VDE test cell with VDE electrodes according to ASTM D1816, or TC/DE test cell with 1-inch flat electrodes according to ASTM D877. Other cells are available upon request. The test set is fully automatic. Just put the prepared test cell in the test compartment, set voltage rate of rise switch to correct position, close test chamber lid and switch to start position. It will automatically raise the voltage to the breakdown level, indicate failure and the breakdown level can be read on the voltmeter. SAFETY FEATURES Center tapped high voltage transformer. The test cell is isolated from the supply when the protective lid is raised. Fast acting relay in series with the high voltage winding and the test cell ensures immediate cutout at flashover above specified current levels. Control lamp indicating AC power on. Control lamp indicating failure. Fast acting fuses are located both in the input to the test set and in the primary of the high voltage transformer. OTHER FEATURES Input switch, fuse, and power indicator lamp. Motorized output voltage control from 0 to 60,000 volts with three selectable speeds of 500, 2000 and 3000 volts per second. Single range memory voltmeter connected across transformer primary calibrated to output voltage level records breakdown voltage for the test sample. The test compartment is provided with a 115 volt outlet for convenient plug-in of motor driven stirrer when testing to ASTM D1816 standards.

SPECIFICATIONS 2-1 Input Voltage/Current Output Voltage/Power Rate of Rise Memory Voltmeter Dimensions Weight Single Phase, 120 Volts at 60 Hz, 5 Amps or 220 Volts at 50 Hz, 2.5 Amps (Check Specification Tag) 0-60,000 Volts at 500 VA (momentary), Maximum Voltage to Earth is 30,000 Volts Selectable 500/2000/3000 Volts/Second Scale of 0-60,000 Volts, Accuracy 1% of Full Scale 21 1/4 W x 16 3/4 D x 13 3/4 H (540 mm W x 426 mm D x 350 mm H) 50.5 lbs. (22.9 kg) - 120 V 53.5 lbs. (24.26 kg) - 220 V

INSTALLATION AND GROUNDING INSTRUCTIONS 3-1 1. Place the test set on a table or similar flat surface. 2. Make sure that the test set is level. 3. Open the cover. 4. Check that your input voltage corresponds with the input of the test set. 5. Check that your supply outlet provides a ground. 6. Connect the power cord to the outlet. 7. The test set is now installed and ready for operation.

OPERATING INSTRUCTIONS 4-1 Operation with TC/DE Test Cell (ASTM D877 Standard) 1. Adjust the test cell electrode by the use of the measuring rod located on the test cell in the following manner. a. Remove the measuring rod by unscrewing it from its threaded holder. b. Release the setscrew, which holds the adjustable electrode in place on the test cell. c. Place the measuring rod between the electrodes. d. Move the adjustable electrode in until snugly against the measuring rod. e. Moderately tighten setscrew to secure this position. f. Remove the measuring rod and place it in the holder for safekeeping. (Distance between the electrodes should be 0.100 of an inch if measuring rod is not used.) 2. Fill the test cell with test sample of oil according to standards procedure. 3. Place the test cell in the test chamber of the unit and close chamber lid. 4. Turn on AC power switch. 5. Select 3000 volts per second rate of rise. 6. Move the start switch to start position when stand time requirements have been met. 7. High voltage will come on; the unit will automatically raise the voltage to the desired rate per second until failure occurs. 8. If a failure occurs, the voltage will shut off, the failure light will illuminate, and the breakdown voltage will be indicated on the kilovolt meter. 9. To return to zero, switch the stop-reset switch to stop/reset. 10. Continue test as per ASTM D877. 11. Remove the test sample of oil and repeat the above procedure for other samples. NOTICE: The voltmeter may continue to rise slightly after the failure indicator is tripped. This meter response delay should be ignored. The final voltage reading is the breakdown point.

OPERATING INSTRUCTIONS 4-2 Operation with TC/VDE Test Cell (ASTM D1816) 1. Adjust the test cell electrode gap using the double end gauge rod in the following manner. a. Remove the gauge rod and hex key from the storage block on the side of the cell. b. Loosen the setscrew that holds the moveable electrode in place. c. Place the desired end of the gauge, either.080 or.040 diameter, between the electrodes. d. Hold the movable electrode snugly against the gauge rod while moderately tightening the setscrew. e. Remove the gauge rod and replace it and the hex key back into storage. 2. Fill the test cell with test sample of oil according to standards procedure. 3. Place the test cell in the test chamber of the unit. 4. Plug cord of stirrer into chamber receptacle. 5. Close chamber cover. 6. Turn on AC power switch. 7. Set the rate of rise to 500 volts per second. 8. Move the start switch to start position when stand time requirements have been met. 9. High voltage will come on; the unit will automatically raise the voltage at the desired rate per second until failure occurs. 10. If a failure occurs, the voltage will shut off, the failure light will illuminate, and the breakdown voltage will be indicated on the kilovolt meter. 11. To return to zero, switch the stop-reset switch down as labeled. 12. Continue test as per ASTM D1816. 13. Remove the test sample of oil and repeat the above procedure for other samples.

4-3 OPERATING INSTRUCTIONS Operation with optional LDCU (Liquid Dielectric Comparison Unit) 1. Make sure power to LD set being checked is turned off. 2. Place the comparison cell in the test chamber of the unit. Plug LDCU ground lead into ground jack. Close transparent cover. 3. Turn on Input Power switch. 4. Set the Rate of Rise to the slowest speed. 5. Move the Start/Stop switch to the Start position. 6. High voltage will come on; the unit will automatically raise the voltage at the selected rate per second. 7. Allow voltage to rise on the LDCU until it reaches 60 KV. 8. Move the Start/Stop switch to the Stop position at this time. 9. Unit under test and comparison cell should be in agreement. If a discrepancy is found, LD unit being checked should be sent for recalibration. 10. Turn Input Power switch off and back on to shut off high voltage and reset unit. 11. Check 15 KV, 30 KV, and 45 KV settings. Calibration of LDCU LDCU unit should be sent to OEM factory for recalibration at periodic intervals, not to exceed 12 months.

RECALIBRATION 5-1 Recalibration of this test set is normally not necessary. For any internal changes, modifications, or calibrations found necessary, please return to the factory.

ELECTRICAL SCHEMATICS 6-1 Drawing Number Description 1. 9101060 LIQUID DIELECTRIC TEST SET PCB1019 E 2. 31114000 LD60 VM Circuit

MAINTENANCE AND TROUBLESHOOTING 7-1 Maintenance No maintenance is required besides the control of fuses and control lamps located on the front panel. Ratings of these are described in the parts list. No solution or chemical stronger than ordinary mild soap and water solution should be applied to the cabinet area of this unit. Care must be used when cleaning the meter faces and console panel. Abrasives may remove printing and descriptive titles and scratch meter faces. When cleaning, always have unit disconnected from power source. Never attempt to clean inside the unit as the cleaning solution may cause damage to the electronic components. In the event it becomes necessary to replace any parts, a description can be found with the supplied parts list. Troubleshooting No power on. Have you plugged in the power cord? Is voltage available in the wall outlet? Check fuse F1. Check the control lamp for Input power. The test procedure does not start. Is Input power turned on? Is the compartment lid closed? Check that the micro switch is clicking when closing the lid. Have you turned the toggle switch to start position? Have you reset the test set before start-up? The voltmeter does not show any reading. Check test procedure start as above. Check fuse F2.

PARTS LIST ITEM DESCRIPTION QTY PART NO. ASSY NO. 8131060, LD60 (120V/240V) FRONT PANEL A1 PC1140 METERING ASSEMBLY 1 31114000 F1, 2 FUSE HOLDER, 3AGHKP 2 1603920 F1, 2 FUSE, 3AG-5A 2 1603605 F1 (220v) 3AG-3A 1 1603603 PL1 PILOT LAMP, YELLOW LED 1 1420138 PL2 PILOT LAMP, RED LED 1 1420137 KNOB, (PLEXIGLASS COVER) 1 1350050 M1 METER, 3 ½ DIGIT LCD 1 1506400 MOV6 (120V) MOVISTOR 130V, V130LA10A 1 1606100 SW1 SWITCH, CH7565K7 TGL2PDT 1 1865005 SW2 RATE OF RISE SWITCH 1 1863037 SW2 KNOB PKAP 50B 1 1355310 SW3 SWITCH, 8832KT TGL SPRING 1 1865025 HINGE PIANO HINGE 1 40500060 COVER PLEXIGLASS (SMOKED GRAY) 1 40500070 CAL HOLE PLUG-1/4 1 1359925 CORD LINE CORD 18/3 8 1 1077183 PANEL FRONT PANEL 1 42000024 CHASSIS T1 (220 V) N2X 230/115 STEP DOWN AUTO XFMR-100 VA 1 1894427 CAM CAM ALUM BORED ½ 3 41000002 MOT1 MOTOR, 744KC1-22T5 BODINE WITH CAP. 1 1560715 PCB ASSY PCB1019E - LD60 ASSY 1 31101900 RECPT RECEPTACLE 15 A, 125 V 1 1159900 SPACER SPACER 3/4X 4-40 2 1350123 SW4-7 SWITCH, U3L-121-DB LIMIT 4 1866015 T3 TRANSFORMER 221 VARIABLE STACO 1 1890105 MOTOR SHAFT 1 40500030 MOTOR - VARIAC BRACKET 1 40500020 CHASSIS 1 40500040 HV XFMR T2 TRANSFORMER, EPOXY CAST 1 38322205 C-CORE C-CORE 1 1900130 BRKT TRANSFORMER MOUNTING BRACKET 1 46000067 CASE CASE WITH HANDLES 1 2100508 CABLE BRACKET 1 40500050 8-1

PARTS LIST 8-2 ITEM DESCRIPTION QTY PART NO. ASSY NO. 3111941, LD60, PCB 1019 REV. E C2 CAPACITOR 1 uf 250 V 1 1094130 C1 CAPACITOR.01 uf 1kV 1 1092050 PC BOARD PCB1019 REV E 1 1110195 X5 3 PIN PHOENIX CONN. & PLUG 1 1152603 X2, X6 4 PIN PHOENIX CONN. & PLUG 2 1152604 X1 5 PIN PHOENIX CONN. & PLUG 1 1152605 X4 8 PIN PHOENIX CONN. & PLUG 1 1152608 X3 16 PIN PHOENIX CONN. & PLUG 1 1152616 K1 KU SERIES RELAY SOCKET 1 1157600 SPACERS STANDOFF 8-32 X 1 ½ 4 1350116 SG1,2 SPARK GAP 90 V 2 1605110 MOV1-3 MOVISTOR 130 V, V130LA10A 3 1606100 MOV4,5 V56Z MOVISTOR 2 1606130 K1 RELAY KUP14A153P, 120V, 3 POLE 1 1700610 K3 AROMAT D52E-S-DC48V, 2 POLE 1 1700820 K4 RELAY 1310P-4C-120A, 4 POLE 1 1701305 K2 RELAY 5A, 120V, 2 POLE 1 1701316 R1, 2 RHEOSTAT 1.5 K OHM 25 W 2 1761010 D1-9 DIODE 1N4007 9 1780025 ASSY NO. 31114000, LD60, PCB 1140.01 UF 1 KV 18F2727 1 1092050 4 UF 350 V 1 1094655 10 UF 20 V 47F386 TAN 1 1095800 100 UF 35 V 14F3253 1 1098050 PCB 1140 LD60 METER BD REV A 1 1111401 1-640454-0 HDR 10 CKT.1 1 1152211 1-640440-0 CONN 10 CKT.1 2 1152210 4 POS MINI PCTERMINAL BLOCK 44F2705 1 1155040 8254 SPCR 1X6-32, M/F 4 1350110 3 ½ DIGIT LCD METER DISPLAY 1 1506400.175 AMP 3AG FUSE 2 1603595 1A1119-10 FUSE CLIP 4 1603925 MOVISTOR V130LA10A 2 1606100 NE-2 NEON 1 1609990.5 W 1 K 10% 1 1711960.5 W 5 K 1% 1 1722100.5 W 1 MEG 1% 1 1725950 10 K TYPE 43P 12F4409 1 1761096 1N4007 (1000 VR, 1.0 A) 4 1780025 UA7805C, VR +5 V REG 1 1794000 XFMR DPC 120-8 1 1894314 XFMR PC16-55 1 1894317 1N4734A 56V ZENER 1 1780034 1N6267A 5V TRANSORB 1 1780060

PARTS ORDERING INFORMATION 9-1 Replacement parts are available from Phenix Technologies, Inc. Changes to Phenix Technologies' products are sometimes made to accommodate improved components as they become available, and to give you the benefit of the latest technical improvements developed in our Engineering Department. It is, therefore, important when ordering parts to include the serial number of the unit as well as the part number of the replacement part. When your purchase order is received at our office, a representative of Phenix Technologies will contact you to confirm the current price of the part being ordered. If a part you order has been replaced with a new or improved part, an Applications Engineer will contact you concerning any change in part number. Your order for replacement parts should be sent to: Replacement Parts Department Phenix Technologies, Inc. 75 Speicher Drive Accident, Maryland 21520

RETURNED MATERIAL 10-1 If for any reason it should become necessary to return this equipment to the factory, the Service Department of Phenix Technologies, Inc. must be given the following information: Name Plate Information Model Number Serial Number Reason for Return Cause of Defect If Phenix Technologies, Inc. deems return of the part appropriate, it will then issue an "Authorization for Return". If return is not deemed advisable, other inspection arrangements will be made. NOTE: Material received at this plant without the proper authorization shall be held as "Customer's Property" with no service until such time as the proper steps have been taken. Your cooperation is requested in order to ensure prompt service.