C&D VRLA Batteries Extended Run Time for Small UPS Machines

Similar documents
TECHNICAL BULLETIN Fig #1 - VRLA Battery Components. Intercell Welded Connection Strap joining neg. plates in parallel.

PURE LEAD PLUS UPS APPLICATIONS Valve Regulated Lead Acid Battery Designed for UPS Standby Power Applications Watts per Cell

FEATURES & benefits. Constant Power Discharge Ratings - Watts per 77 F (25 F) Operating Time (in minutes) to 1.

FEATURES & BENEFITS. 10 year design 25 C

ENGINEERED RACK SOLUTIONS

Switchgear Utility specific gravity nominal sulfuric acid. 10 years, full float service at 77 F (25 C)

LIBERTY SERIES 1000 VALVE REGULATED LEAD-CALCIUM BATTERY For standby applications Capacities from 25 to 600 Ampere-hours

UPS FEATURES & BENEFITS C&D Technologies flooded batteries are engineered to provide superior performance

Installation and Operating Procedures For C&D Technologies TRUE Front Access TEL Series Batteries

UPS FEATURES & BENEFITS TECHNICAL DATA Valve Regulated Lead Acid Battery Designed for UPS Standby Power Applications.

LIBERTY 2000 SuperMAX For standby applications Capacities from 295 to 2000 Ampere-hours

The Birth of a Powerful Idea

Battery Back-up BBM Owner's Manual. Please read this manual BEFORE installing your inverter

Powerterm L120C Single Output PSU/Battery Chargers Model C2199A-1 (12V/8A) or Model C2199A-2 (24V/6A)

Installation and Operating Procedures For C&D Technologies TRUE Front Access TEL Series Batteries

Gay E. Canough. OFF-GRID Design. Dr. Gay E. Canough, Master trainer. Living Off the Grid

TOTALFLOW Technical Bulletin 59 Lead Acid Battery Inspection and Maintenance Procedures

Models DP10 & DP20 Series Low Voltage Disconnects User s Manual Rev. 1.1 October 31, 2007

STANDBY BATTERY LI TEL48-170C INSTALLATION AND OPERATING MANUAL

Battery Back-up Model: BBM-1225

OFF GRID Solar system

PURE LEAD PLUS UPS APPLICATIONS. Valve Regulated Lead Acid Battery Designed for UPS Standby Power Applications Watts per Cell

Power your day-to-day when others are power-less. Humless Sentinel User s Guide.

EV Power - Battery Control Unit Instructions. 8 Cell 24V

TROJAN BATTERY COMPANY Renewable Energy Warranty Claim Form

1RECHARGEABLE APPLIANCES

Coleman Air C440-HVM 440 Amp Diversion Controller Version 3.2

Coleman Air Diversion Controller Model C40

Reference: Photovoltaic Systems, p References: Photovoltaic Systems, Chap. 7 National Electrical Code (NEC), Articles 110,

IEEE IAS Atlanta Chapter

VRLA Batteries. Battery Installation And Start up Guide

Reference Number PDS 18 - (RIC Standard: EP SP)

Valve Regulated Lead Acid (VRLA) Battery Series Designed for UPS Standby Power Applications FEATURES & BENEFITS

High Efficiency Battery Charger using Power Components [1]

Battery Bank for Wind Turbine. Project Proposal Prash Ramani, Marcos Rived TA: Katherine O Kane

SimpliPhi Power PHI Battery

EV Power - A-Series 8 Cell, 16 Cell and 24Cell Chargers Installation & Usage Instructions.

Hillstone PowerBank HPB54 Series ( 400A 700A )

Super PWRgate PG40S Spring City Drive Waukesha, WI

SITE PLANNING DATA LIEBERT EXM 3-PHASE UPS: KVA/KW, 60HZ, VAC, SINGLE INPUT

SMT. Installation and Operation Manual. Model:SMT WITH MPPT TECHNOLOGY

PSIM Tutorial. How to Use Lithium-Ion Battery Model

Technical Note. Management of Sealed Lead Acid Batteries in Reliable Small DC Standby Power Supply Systems

RU BMS Power Supply and Battery Management System Owners Guide

Testing Lead-acid fire panel batteries

4.0 OPERATION Type ITH-T Relay

Coleman Air Diversion Controller Model C40

INDUSTRIAL CHARGER AUTOMATIC BATTERY CHARGER SERIES 150 KUSSMAUL ELECTRONICS CO., INC. MODEL # XX YEAR WARRANTY INSTRUCTION MANUAL

TECHNICAL MANUAL RS02061

Pure Lead-Tin Technology

User Manual 123electric Battery Management System 123\BMS Revision 1.4 Augusts 2015

Chek-A-Cell TM. Instruction Manual Rev A 8/12

Christopher LaForge. IREC Certified Master Trainer. NABCEP Certified Photovoltaic Installation Professional - Emeritus

Using Inverter Input Modes for Smart Grid Management

POWER+ PREMIUM CBS. BS-EN Emergency electrical installations Electric power systems Emergency lighting Escape lighting

Ride On Locomotive. Installation Guide

TUTORIAL Lithium Ion Battery Model

NorthStar Battery Company DCN: SES DCR: 1548-S09 Date:

Flywheel Energy Storage

Onesource. Onecompany. The only. solution. The Integrated Rack System

Model NTX7 Series Automatic Battery Charger User s Manual Rev. 1.0 October 17, 2006

OPERATING MANUAL: FLAGGER STATION & WORK AREA LIGHTING SYSTEM 12 VOLT LED

Maintenance Manual 13 AMPERE POWER SUPPLY 19A704647P1-P3. Mobile Communications LBI-31801C

A Brief Look at Batteries

Introduction: Supplied to 360 Test Labs... Battery packs as follows:

Solid-State Relays. Solid-State Relays. Features. Description. Overview

Charging with AC (wall) Charger

Solid-State Relays. Solid-State Relays. Features. Description. Overview

Circuits-Circuit Analysis

SSC Sensor Replacement Board for the SSC Evaluation Kit. Features. Benefits

Illuminator Series CM. GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION. 500W, 1000W, 1500W and 2000W Single-Phase Emergency Power System

User Manual. BMS123 Smart

EnergyCell FLA Series. Owner s Manual

Schedule GS-2 INTERMEDIATE GENERAL SERVICE

American Traction Systems

Using Inverter Input Modes for Smart Grid Management

Contacts The moveable contact, which is the one affected by the armature is sometimes referred to as the hinge contact.

CARDINAL COMPONENTS. Standby supply

MGL Avionics AvioGuard. Fault protected, wide input range, isolated, DC to DC converter for avionics applications

Standby Power Systems

Application Note. Common Bussing AC Drives. For 650 and 690+ series drives APP-AC-03

Smart Battery Charger GPC-35-MAX GPC-45-MAX GPC-55-MAX GPC-75-MAX GPC-100-MAX. Owner s Manual

American Power Design, Inc.

Features and Benefits

Battery Storage Systems

XLR Energy Storage Module

INSTALLATION & OPERATION MANUAL

AUTO CHARGE D2 MODEL #: AUTOMATIC TRIPLE OUTPUT BATTERY CHARGER INSTRUCTION MANUAL

ENTRANCE EQUIPMENT ER D PAGE 1 OF 5

Digital echo-charge. Owner s Manual. Xantrex Digital echo-charge Battery Charger

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

FLEXnet DC Programming & Guidelines

Model HPX60 Series Automatic Battery Charger User s Manual Rev. 1.0 October 17, 2006

Chapter 6. Batteries. Types and Characteristics Functions and Features Specifications and Ratings Jim Dunlop Solar

PRODUCT GUIDE Publication No: EN-SBS-PG-001 February 2003

Northeastern Rural Electric Membership Corporation Columbia City, Indiana

AUTO CHARGE D PUMP PLUS

Emergency Power. Are you prepared? Rev 2.0

AUTOMATIC BATTERY CHARGER WITH CONSTANT VOLTAGE AND CURRENT

INTELEPOWER CXS SWITCHING SYSTEMS

Transcription:

TECHNICAL BULLETIN 41-7954 C&D VRLA Batteries Extended Run Time for Small UPS Machines 41-7954/0112/CD www.cdtechno.com

Small UPS machines, in the range of 400 to 2500 VA, are typically used to provide standby power for one or more personal computers in the event of a commercial power outage. These UPS machines will typically have an internal battery with a 3 to 5 year life expectancy and which is sized to provide from 5 to 45 minutes of standby operating time. The user may operate at a location that experiences frequent commercial power outages of long duration, perhaps even daily, and they may want to use the UPS as an alternative power source since there is no backup generator. The solution? Add a battery of the same voltage in parallel. Naturally, the additional parallel battery will be external to the UPS machine and the most obvious solution is as shown in Figure 1. When adding an external battery there are several issues to be considered when determining the actual configuration. These would include: 1. The capability of the UPS electronics to operate for extended periods without overheating. 2. The capability of the UPS charging circuit to recharge the additional battery in the desired recharge time. 3. Isolation of the additional battery from the UPS internal battery to prevent a shorted cell in one string from affecting the other string. 4. Battery to UPS connector and wire size as related to the anticipated discharge and recharge current of the additional battery. 5. Appropriate ventilation of the additional battery in the external enclosure. 41-7954/0112/CD 2 www.cdtechno.com

The configuration as shown in Figure 1 is certainly the easiest to implement, however, it does assume that the UPS rectifier has the ampere output capability to power the inverter, recharge the internal battery and in addition, recharge the auxiliary battery. For this configuration and that of Figure 2, the UPS rectifier should have a minimum reserve current of 2 amperes per 100 ampere-hours of capacity of the auxiliary battery. This minimum reserve current should provide for recharge of the auxiliary battery within a 72-hour period. If the current capability of the UPS internal rectifier is marginal, the recharge current to the batteries can be limited with resistors (R1 & R2) as noted in Figure 2. For example, assume a UPS rectifier had only 2 amperes available for charging a self contained 10 ampere-hour capacity battery and that a 40 ampere-hour battery were being added in parallel as an external battery. In this case the limited available charging current should be divided between the two batteries in proportion to their capacities. In this case, 1/5 of the recharge current (0.4 amperes) should be supplied to the internal 10 ampere-hour battery and 4/5 or the recharge current (1.6 amperes) to the external 40 ampere-hour battery. The current limiting resistor values would be calculated as that required to limit the inrush current to the desired value when the full charging voltage is applied to the discharged battery while at it's open circuit value. The value of the resistors heat dissipation capability (wattage) would be simply the product of the voltage drop multiplied by the maximum current (V*I) or the maximum current squared multiplied by the resistance (I 2 R). For example, assume the charging voltage is 2.3 volts per cell for a 24-cell system or 55.2 VDC. The worse case is when the discharged battery open circuit voltage would be 1.96 volts per cell or 47 VDC for a 24-cell system. The internal 10 ampere-hour battery current limiting resistor values would be calculated as: R1 = (55.2-47) VDC/0.4 amperes R1 = 20.5 Ohms 41-7954/0112/CD 3 www.cdtechno.com

W R1 = (55.2-47) VDC x 0.4 amperes W R1 = 3.25 watts minimum The external 40 ampere-hour battery current limiting resistor values would be calculated as: R2 = (55.2-47) VDC/1.6 amperes R2 = 5.1 Ohms W R2 = (55.2-47) VDC x 1.6 amperes W R2 = 13.1 watts minimum During discharge the batteries will supply power through the diodes D1 and D2 thus eliminating the voltage drop that would otherwise have occurred through R1 and R2. While other approaches to the current limiting feature are possible, use of the resistor is perhaps the simplest and least expensive, however, it will increase the recharge time. Also, if resistive current limiting is employed, the heat-producing resistor should not be mounted near the battery. Although the configuration of Figure 1 and 2 will work, they have one significant common deficiency: they do not provide for mutual isolation of the two battery systems. As a result, if there should be a shorted cell in one battery it will discharge the other battery connected in parallel. This can be a significant problem especially when the two-battery systems have different life expectancies or use histories. This deficiency can be corrected as shown in Figure 3. In this configuration the resistors R1 and R2 limit the charging current to each of the two batteries as they did in Figure 2 however the action of D1, D2 and D4 prevent a short in either battery from discharging the other battery. 41-7954/0112/CD 4 www.cdtechno.com

When the UPS internal charger does not have sufficient ampere capability to recharge the auxiliary battery in a reasonable time it will be necessary to include an auxiliary charger in the external package. This configuration would be similar to that shown in Figure 4. As shown, using the normally closed contacts of the commercial power relay (or a solid state switch), the auxiliary battery and charger are completely isolated from the UPS until such time as there is a commercial power failure. Upon the commercial power failure the relay K1 will deenergize and the normally closed (NC) contacts will close placing the auxiliary battery in parallel with the UPS internal battery. The commercial power relay K1 can be omitted if the UPS internal battery charging voltage is adjusted to a value slightly higher (e.g. 2.3 v/c) than that used on the auxiliary battery (e.g. 2.25 v/c). In this situation diode D2 would be reverse biased until such time that there was a commercial power failure when it would be forward biased and route it's share of the load current to the UPS inverter. The arrangement of diodes D1 and D2 also isolate the two battery systems preventing a shorted cell in one string from affecting the other string. This is perhaps the most simple of all the configurations however, the relative settings of the chargers output voltages is critical. Table 1 identifies the approximate 20 hour rated ampere hour capacity of the battery required to provide the noted operating time for UPS systems of the noted VA rating, power factor (pf), DC-AC inverter efficiency and DC buss voltage. 41-7954/0112/CD 5 www.cdtechno.com

When adding parallel strings of batteries of the same voltage, each of the strings should be separately cabled to the common tie point and should include individual string overcurrent protection. UPS-VA Assumed DC Buss Rating AC-DC Voltage @ 0.8 p.f. Efficiency Battery Watts Battery Watts per Cell Approxomate Hours Operation Per Rated Battery Ampere-Hour Capacity 1 Hour 2 Hours 3 Hours 4 Hours 500 12 65% 615.4 102.6 85 150 200 250 24 65% 615.4 51.3 43 75 100 125 36 70% 571.4 31.7 26 46 62 77 48 75% 533.3 22.2 18 33 43 54 72 75% 533.3 14.8 12 22 29 36 120 80% 500.0 8.3 7 12 16 20 1000 12 65% 1230.8 205.1 170 300 400 500 24 65% 1230.8 102.6 85 150 200 250 36 70% 1142.9 63.5 53 93 124 155 48 75% 1066.7 44.4 37 65 87 108 72 75% 1066.7 29.6 25 43 58 72 120 80% 1000.0 16.7 14 24 33 41 1500 12 65% 1846.2 307.7 255 450 600 750 24 65% 1846.2 153.8 128 225 300 375 36 70% 1714.3 95.2 79 139 186 232 48 75% 1600.0 66.7 55 98 130 163 72 75% 1600.0 44.4 37 65 87 108 120 80% 1500.0 25.0 21 37 49 61 2000 12 65% 2461.5 410.3 340 600 800 1000 24 65% 2461.5 205.1 170 300 400 500 36 70% 2285.7 127.0 105 186 248 310 48 75% 2133.3 88.9 74 130 173 217 72 75% 2133.3 59.3 49 87 116 144 120 80% 2000.0 33.3 28 49 65 81 144 85% 1882.4 26.1 22 38 51 64 2500 12 65% 3076.9 512.8 425 750 1000 1250 24 65% 3076.9 256.4 213 375 500 625 36 70% 2857.1 158.7 132 232 310 387 48 75% 2666.7 111.1 92 163 217 271 72 75% 2666.7 74.1 61 108 144 181 120 80% 2500.0 41.7 35 61 81 102 144 85% 2352.9 32.7 27 48 64 80 Table 1 - Ah Battery Capacity for Specified Run Time 1400 Union Meeting Road P.O. Box 3053 Blue Bell, PA 19422-0858 (215) 619-2700 Fax (215) 619-7899 (800) 543-8630 customersvc@cdtechno.com www.cdtechno.com Any data, descriptions or specifications presented herein are subject to revision by C&D Technologies, Inc. without notice. While such information is believed to be accurate as indicated herein, C&D Technologies, Inc. makes no warranty and hereby disclaims all warranties, express or implied, with regard to the accuracy or completeness of such information. Further, because the product(s) featured herein may be used under conditions beyond its control, C&D Technologies, Inc. hereby disclaims all warranties, either express or implied, concerning the fitness or suitability of such product(s) for any particular use or in any specific application or arising from any course of dealing or usage of trade. The user is solely responsible for determining the suitability of the product(s) featured herein for user s intended purpose and in user s specific application. Copyright 2012 C&D TECHNOLOGIES, INC. Printed in U.S.A. 41-7954 0112/CD